SALDA RIS 1200 PE 3.0 EKO 3.0, RIS 1200 PE 9.0 EKO 3.0, RIS 700 PE 1.2 EKO 3.0, RIS 2500 PE 9.0 EKO 3.0, RIS 2500 PW EKO 3.0 Datasheet

...
RIS P EKO
EC
Application Ventilation of houses, oces or other heated premises (classrooms, apartments, conference rooms, etc.)
Description
AIR HANDLING UNITS
A1/L2
V [m3/h]
RIS P EKO 3.0 is a range of heat recovery units with high-eciency counter-ow heat exchangers and low height. The units are designed for mounting under ceilings in order to save space. There are 5 sizes (airow interval 420-2500 m3/h) with separate heaters available for dierent climate zones. RIS P EKO 3.0 units have high overall energy savings due to the highly ecient heat recovery (up to 90%), quiet and economical EC fans, eective low-pressure-drop lters, 100% motorized bypass dampers (for the 1900 and 2500 versions) and top-level of air tightness. Energy eciency ensures full thermal comfort for passive houses, without an additional pre-heater at temperatures above -5°C. All the RIS P EKO 3.0 units are fully equipped with automatic controls. Optional external sensors for CO2 and humidity and the event planning feature will help to control automatically your climate (demand-level control). RIS P EKO 3.0 units are service-friendly and are easy to mount. Filter pollution may be identied by timers or contamination controls (RIS 1200-2500 P EKO 3.0). All units are supplied tested and ready to install.
Three remote control options are available:
Remote control
Features
Construction
1. Flex, Stouch or Ptouch remote controllers.
2. Building management system connections.
3. Remote control via PC MB-Gateway.
Ideal for ceiling installations. Ready for Passive House technology: high eciency. Easy and quick mounting. Water/electrical heating options. Fully integrated plug-and-play control system.
Frameless construction from double-skinned panels. Acoustic and thermal wall insulation: RIS 400–2500 P EKO 3.0 – 30/50 mm. RIS 400-700 P EKO 3.0 powder-coated white housing RAL 9016; RIS 1200–2500 P EKO 3.0 powder-coated
grey housing RAL 7040.
Integrated electrical heater or optional duct-based water heater/cooler. Low-pressure-drop lters: F7/M5. Hinged door with locks grants easy access to internal components. Separate compartment on the side of the unit grants quick access to the control board (plug-and-play). Stainless steel condensate tray. Fitted with mounting brackets. Integrated anti-frost pressure switch (RIS 1200-2500 P EKO 3.0).
RIS 400 P E 0.9 EKO 3.0
Equipped with new PRV V2 control board
AHU with EC motors and ecient heat exchanger
Electrical heater power in kW
Heater type (E - integrated electrical heater; W - prepared for water heater)
Housing type (V - vertical, H - horizontal, P - ceiling)
AHU size according to maximum airow range m3/h
AHU with plate heat exchanger
64
The company reserves the right to make changes of technical data without prior notice
H2
H1H
H4
H3
W
F
W1
W2
H1H
W2
H4
G
D
F
W
W1
H2
H3
RIS P EKO
RIS 400P EKO - RIS 700P EKO 3.0 RIS 1200P EKO - RIS 2500P EKO 3.0
Dimensions [mm]
Unit W W1 W2 H H1 H2 H3 H4 F øD G D
RIS 400PE/PW EKO 3.0 1300 1361 650 768 670 158 330 98 31 200 - -
RIS 700PE/PW EKO 3.0 1380 1461 695 1069 970 160 350 99 40 250 - -
RIS 1200PE/PW EKO 3.0 1550 1655 780 1497 1397 172 390 100 52 - 500 250
RIS 1900PE/PW EKO 3.0 1750 1870 710 1955 1850 194 399 105 60 - 700 300
RIS 2500PE/PW EKO 3.0 1850 1970 720 2055 1950 244 499 105 60 - 700 400
AIR HANDLING UNITS
Optional accessories
Flex Stouch Ptouch
Unit
RIS 400PE EKO 3.0 + + - 81 CM230-1-F-L CM230-1-F-L - - - - 200 200 -
RIS 400PW EKO 3.0 + + 61 81 TF230 CM230-1-F-L - - + + 200 200 -
RIS 700PE EKO 3.0 + + - 81 CM230-1-F-L CM230-1-F-L - - - - 250 250 -
RIS 700PW EKO 3.0 + + 61 81 TF230 CM230-1-F-L - - + + 250 250 -
RIS 1200PE EKO 3.0 + + - - LM230A-TP LM230A-TP - 500x250 - - - - 500x250
RIS 1200PW EKO 3.0 + + 61 - NFA LM230A-TP 500x250 500x250 + + - - 500x250
RIS 1900PE EKO 3.0 + + - - LM230A-TP LM230A-TP - 700x400* - - - - 700x400*
RIS 1900PW EKO 3.0 + + 61 - NFA LM230A-TP 700x400* 700x400* + + - - 700x400*
RIS 2500PE EKO 3.0 + + - - LM230A-TP LM230A-TP - 700x400 - - - - 700x400
RIS 2500PW EKO 3.0 + + 61 - NFA LM230A-TP 700x400 700x400 + + - - 700x400
MB-
Gateway
Accessories
Network Module
MB­Gateway
Humidity sensor
Ptouch Stouch p. 177 p. 175 p. 176
p. 178
Thermic water valve actuator
S-1141
S-RC02-F2
S-KFF-U
SSB
Heating
Control panelRemote controller
FLEX
Actuator for dampers
SSB
CoolingSPSupply
Remote controller
Water heater coil
SP
Exhaust
Pressure transmitter
S-1141
p. 179
Damper for rectangular duct
SVS
SSK SKS
*necessary to order ange adapter STP 700x400-700x300
CO2 sensor
S-RC02-F2
Rectangular duct silencer
p. 180
RMG
Shut-o damper
VVP/
VXP
SKG AKS
AP
AVS AVA
EKA NV
PH
Circular duct silencer
EKS NV PH
S-KFF-U
Mounting clamps
AP
p. 181
p. 219
SSB p. 195
Heating coil Mixing point
AVS RMG
p. 185 p. 196
The company reserves the right to make changes of technical data without prior notice
SP p. 210
Circular duct water cooler
AVA VVP/VXP STP
p. 193 p. 197 p. 220
SVS
p. 190
Electrical duct pre-heater
EKS NV PH
SSK p. 215 p. 212 p. 216
Electrical duct pre-heater
EKA NV PH
SKS SKG AKS
p. 213
p.201 p. 203
2 and 3 way valves Flange adapter
65
RIS P EKO
50%
50%
RIS 400PE EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
RIS 400PE EKO 3.0
AIR HANDLING UNITS
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
Temperature eciency
η [%]
air ow m3/h
x 3600
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version
GAGRIS1747_0017A 400PE 0.9 EKO 3.0 Integrated electrical heater GAGRIS1746_0017A 400PE 1.6 EKO 3.0 Integrated electrical heater GAGRIS1692_0016A 400PE 3.0 EKO 3.0 Integrated electrical heater
V [m3/h]
V [l/s]
Electrical heater
EC fans
exhaust
supply
Thermal eciency up to* 90% Motorized by-pass + Max power consumption Control board PRV V2 Filter class Housing insulation, mineral wool Colour Weight (net, without packing) Comply with ERP 2016; 2018 Operation indoors Fresh air temperature limits** Housing protection class IP
phase/voltage [50Hz/VAC]
phase/voltage [50Hz/VAC]
power/current [kW/A]
fan speed [min-1]
power/current [kW/A]
fan speed [min-1]
exhaust/supply
RAL white
0.9 EKO 3.0 1.6 EKO 3.0 3.0 EKO 3.0
~1, 230 ~1, 230 ~1, 230
[kW]
[kW/A]
[mm]
[kg]
°C
0,9 1,6 3,0
0,085/0,73
0,085/0,73
1,07/5,50 1,77/8,50 3,17/14,50
* Calculated according EN 13141-7. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
V [m3/h]
V [l/s]
~1, 230
3200
3200
M5/F7
30
9016
74
-5 - +40 34
66
Temperature eciency (balanced mass ow) EN 13141-7:
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
V [m3/h]
RIS 400PE EKO 3.0
Supply 67 54 59 64 58 57 54 47 Extract 58 48 50 53 51 48 46 41 Surrounding 51 40 43 46 45 40 39 36 Measured at 395 m3/h, 100 Pa
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
RIS P EKO
50%
50%
RIS 400PW EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
AIR HANDLING UNITS
RIS 400PW EKO 3.0
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
air ow m3/h
Temperature eciency
η [%]
x 3600
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version GAGRIS1748_0019A 400PW EKO 3.0 Optional water heater
V [m3/h]
Water heater (optional) AVS 200
V [l/s]
Fans phase/voltage [50Hz/VAC] ~1, 230 exhaust power/current [kW/A] 0,085/0,73
fan speed [min-1] 3200
supply power/current [kW/A] 0,085/0,73
fan speed [min-1] 3200 Thermal eciency up to* 90% Motorized by-pass + Max power consumption [kW/A] 0,17/1,50 Control board PRV V2 Filter class exhaust/supply M5/F7 Housing insulation, mineral wool [mm] 30 Colour RAL white 9016 Weight (net, without packing) [kg] 73 Comply with ERP 2016; 2018 Operation indoors Fresh air temperature limits** °C -5 - +40 Housing protection class IP 34
* Calculated according EN 13141-7. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
V [m3/h]
V [l/s]
400PW EKO 3.0
Temperature eciency (balanced mass ow) EN 13141-7:
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
V [m3/h]
RIS 400PW EKO 3.0
Supply 67 54 59 64 58 57 54 47 Extract 58 48 50 53 51 48 46 41 Surrounding 51 40 43 46 45 40 39 36 Measured at 395 m3/h, 100 Pa
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
67
RIS P EKO
200
180
160
140
120
100
80
60
40
20
0
200
180
160
140
120
100
80
60
40
20
0
RIS 700PE EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
RIS 700PE EKO 3.0
AIR HANDLING UNITS
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
Temperature eciency
η [%]
68
Extract airExhaust air Outdoor air Supply air
Article No. Version
GAGRIS1737_0008A 700PE 1.2 EKO 3.0 Integrated electrical heater GAGRIS1736_0007A 700PE 3.0 EKO 3.0 Integrated electrical heater
GAGRIS1693_0005B 700PE 4.5 EKO 3.0 Integrated electrical heater
V [m3/h]
V [l/s]
Electrical heater
EC fans
exhaust
supply
Thermal eciency up to* 90% Motorized by-pass + Max power consumption Control board PRV V2 Filter class Housing insulation, mineral wool Colour Weight (net, without packing) Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** Housing protection class IP
phase/voltage [50Hz/VAC]
phase/voltage [50Hz/VAC]
power/current [kW/A]
fan speed [min-1]
power/current [kW/A]
fan speed [min-1]
exhaust/supply
RAL white
* Calculated according EN 13141-7. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
air ow m3/h
The company reserves the right to make changes of technical data without prior notice
x 3600
V [m3/h]
V [l/s]
V [m3/h]
Temperature eciency (balanced mass ow) EN 13141-7:
RIS 700PE EKO 3.0
Supply 75 64 66 68 70 66 60 59 Extract 62 53 55 57 56 52 49 45 Surrounding 56 45 47 50 50 47 43 42 Measured at 700 m3/h, 100 Pa
Lwa total,
dB(A)
View from inspection side
1.2 EKO 3.0 3.0 EKO 3.0 4.5 EKO 3.0
~1, 230 ~1, 230 ~3, 400
[kW]
[kW/A]
[mm]
[kg]
°C
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
1,2 3,0 4,5
~1, 230
0,168/1,4
3230
0,168/1,4
3230
1,54/8,34 3,34/15,84 4,84/9,3
M5/F7
30
9016
103,5 104 104,5
-5 - +40 34
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
RIS P EKO
200
180
160
140
120
100
80
60
40
20
0
200
180
160
140
120
100
80
60
40
20
0
RIS 700PW EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
AIR HANDLING UNITS
RIS 700PW EKO 3.0
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
air ow m3/h
Temperature eciency
η [%]
View from inspection side
Outdoor air
V [m3/h]
V [l/s]
Extract airExhaust air
Article No. Version
GAGRIS1738_0009A 700PW EKO 3.0 Optional water heater
Water heater (optional) AVS 250
Fans phase/voltage [50Hz/VAC] ~1,230 exhaust power/current [kW/A] 0,168/1,4
fan speed [min-1] 3230
supply power/current [kW/A] 0,168/1,4
fan speed [min-1] 3230 Thermal eciency up to* 90% Motorized by-pass + Max power consumption [kW/A] 0,34/2,84 Control board PRV V2 Filter class exhaust/supply M5/F7 Housing insulation, mineral wool [mm] 30 Colour RAL white 9016 Weight (net, without packing) [kg] 103 Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** °C -5 - +40 Housing protection class IP 34
* Calculated according EN 13141-7. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
x 3600
The company reserves the right to make changes of technical data without prior notice
V [m3/h]
V [l/s]
V [m3/h]
Temperature eciency (balanced mass ow) EN 13141-7:
Outdoor air = -7°C / 2°C / 7°C
RIS 700PW EKO 3.0
Supply 75 64 66 68 70 66 60 59 Extract 62 53 55 57 56 52 49 45 Surrounding 56 45 47 50 50 47 43 42 Measured at 700 m3/h, 100 Pa
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
LWA, dB(A)
Supply air
700PW EKO 3.0
Extract air = 20°C/60%RH
69
RIS P EKO
RIS 1200PE EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
RIS 1200PE EKO 3.0
AIR HANDLING UNITS
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
Temperature eciency
η [%]
air ow m3/h
x 3600
View from inspection side
Outdoor air
3.0 EKO 3.0 6.0 EKO 3.0 9.0 EKO 3.0
~1, 230 ~3, 400 ~3, 400
3,0 6,0 9,0
0,450/2,95
3,82/18,49 6,82/14,19 9,82/18,49
V [m3/h]
V [l/s]
Extract airExhaust air
Article No. Version
GAGRIS1744_0022A 1200PE 3.0 EKO 3.0 Integrated electrical heater GAGRIS1745_0021B 1200PE 6.0 EKO 3.0 Integrated electrical heater GAGRIS1701_0020B 1200PE 9.0 EKO 3.0 Integrated electrical heater
Electrical heater
EC fans
exhaust
supply
Thermal eciency up to* 90% Motorized by-pass + Max power consumption Control board PRV V2 Filter class Housing insulation, mineral wool Colour Weight (net, without packing) Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** Housing protection class IP
phase/voltage [50Hz/VAC]
[kW]
phase/voltage [50Hz/VAC]
power/current [kW/A]
fan speed [min-1]
power/current [kW/A]
fan speed [min-1]
[kW/A]
exhaust/supply
[mm]
RAL grey
[kg]
°C
* Calculated wet eciency. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
V [m3/h]
V [l/s]
Supply air
~1,230
3400
0,370/2,5
3400
M5/F7
50
7040
170
-5 - +40 34
70
Temperature eciency (balanced mass ow) :
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
V [m3/h]
RIS 1200PE EKO 3.0
Supply 76 58 69 71 69 67 64 56 Extract 64 52 56 61 56 50 45 42 Surrounding 56 42 48 50 49 48 46 40 Measured at 1298 m3/h, 100 Pa
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
RIS P EKO
RIS 1200PW EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
RIS 1200PW EKO 3.0
AIR HANDLING UNITS
AIR HANDLING UNITS
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
air ow m3/h
Temperature eciency
η [%]
x 3600
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version GAGRIS1721_0023A 1200PW EKO 3.0 Optional water heater
V [m3/h]
Water heater (optional) SVS 500x250
V [l/s]
Fans phase/voltage [50Hz/VAC] ~1,230 exhaust power/current [kW/A] 0,450/2,95
fan speed [min-1] 3400
supply power/current [kW/A] 0,370/2,5
fan speed [min-1] 3400 Thermal eciency up to* 90% Motorized by-pass + Max power consumption [kW/A] 0,82/5,49 Control board PRV V2 Filter class exhaust/supply M5/F7 Housing insulation, mineral wool [mm] 50 Colour RAL grey 7040 Weight (net, without packing) [kg] 170 Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** °C -5 - +40 Housing protection class IP 34
* * Calculated wet eciency. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
V [m3/h]
V [l/s]
1200PW EKO 3.0
Temperature eciency (balanced mass ow) EN :
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
V [m3/h]
RIS 1200PE EKO 3.0
Supply 76 58 69 71 69 67 64 56 Extract 64 52 56 61 56 50 45 42 Surrounding 56 42 48 50 49 48 46 40 Measured at 1298 m3/h, 100 Pa
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
71
RIS P EKO
600
500
400
300
200
100
0
600
500
400
300
200
100
0
RIS 1900PE EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
RIS 1900PE EKO 3.0
AIR HANDLING UNITS
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
Temperature eciency
η [%]
air ow m3/h
x 3600
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version
GAGRIS1751_0025A 1900PE 3.0 EKO 3.0 Integrated electrical heater GAGRIS1752_0024B 1900PE 6.0 EKO 3.0 Integrated electrical heater GAGRIS1706_0001B 1900PE 12.0 EKO 3.0 Integrated electrical heater
V [m3/h]
V [l/s]
Electrical heater
EC fans
exhaust
supply
Thermal eciency up to* 90% Motorized by-pass + Max power consumption Control board PRV V2 Filter class Housing insulation, mineral wool Colour Weight (net, without packing) Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** Housing protection class IP
phase/voltage [50Hz/VAC]
phase/voltage [50Hz/VAC]
power/current [kW/A]
fan speed [min-1]
power/current [kW/A]
fan speed [min-1]
exhaust/supply
RAL grey
3.0 EKO 3.0 6.0 EKO 3.0 12.0 EKO 3.0
~1, 230 ~3, 400 ~3, 400
[kW]
[kW/A]
[mm]
[kg]
°C
3,0 6,0 12,0
0,485/3,12
0,488/3,16
3,97 /20,32 6,97 /14,92 12,97 /24,32
269 270 272
* Calculated wet eciency. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
V [m3/h]
V [l/s]
~1, 230
2540
2540
M5/F7
50
7040
-5 - +40 34
72
The company reserves the right to make changes of technical data without prior notice
V [m3/h]
RIS 1900PE EKO 3.0
Supply 77 53 64 69 73 70 65 61 Extract 68 42 58 64 62 61 58 55 Surrounding 60 50 52 54 54 50 48 41 Measured at 1938 m3/h, 100 Pa
Lwa total,
dB(A)
Temperature eciency (balanced mass ow) :
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
RIS P EKO
600
500
400
300
200
100
0
600
500
400
300
200
100
0
RIS 1900PW EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
AIR HANDLING UNITS
RIS 1900PW EKO 3.0
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
air ow m3/h
Temperature eciency
η [%]
x 3600
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version GAGRIS1753_0026A 1900PW EKO 3.0 Optional water heater
V [m3/h]
Water heater (optional) SVS 700x400
V [l/s]
Fans phase/voltage [50Hz/VAC] ~1, 230 exhaust power/current [kW/A] 0,485/3,12
fan speed [min-1] 2540
supply power/current [kW/A] 0,488/3,16
fan speed [min-1] 2540 Thermal eciency up to* 90% Motorized by-pass + Max power consumption [kW/A] 0,97 /6,32 Control board PRV V2 Filter class exhaust/supply M5/F7 Housing insulation, mineral wool [mm] 50 Colour RAL grey 7040 Weight (net, without packing) [kg] 269 Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** °C -5 - +40 Housing protection class IP 34
* Calculated wet eciency. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
V [m3/h]
V [l/s]
1900PW EKO 3.0
The company reserves the right to make changes of technical data without prior notice
V [m3/h]
RIS 1900PW EKO 3.0
Supply 77 53 64 69 73 70 65 61 Extract 68 42 58 64 62 61 58 55 Surrounding 60 50 52 54 54 50 48 41 Measured at 1938 m3/h, 100 Pa
Lwa total,
dB(A)
Temperature eciency (balanced mass ow) :
Outdoor air = -7°C / 2°C / 7°C
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
LWA, dB(A)
Extract air = 20°C/60%RH
73
RIS P EKO
RIS 2500PE EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
RIS 2500PE EKO 3.0
AIR HANDLING UNITS
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
Temperature eciency
η [%]
air ow m3/h
x 3600
V [m3/h]
V [l/s]
V [m3/h]
V [l/s]
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version
GAGRIS1754_0027B 2500PE 4.5 EKO 3.0 Integrated electrical heater GAGRIS1755_0028B 2500PE 9.0 EKO 3.0 Integrated electrical heater GAGRIS1707_0015B 2500PE 18.0 EKO 3.0 Integrated electrical heater
Electrical heater
EC fans
exhaust
supply
Thermal eciency up to* 90% Motorized by-pass + Max power consumption Control board PRV V2 Filter class Housing insulation, mineral wool Colour Weight (net, without packing) Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** Housing protection class IP
phase/voltage [50Hz/VAC]
phase/voltage [50Hz/VAC]
power/current [kW/A]
fan speed [min-1]
power/current [kW/A]
fan speed [min-1]
exhaust/supply
RAL grey
4.5 EKO 3.0 9.0 EKO 3.0 18.0 EKO 3.0
~3, 400 ~3, 400 ~3, 400
[kW]
[kW/A]
[mm]
[kg]
°C
4,5 9,0 18,0
~1,230
0,725/3,24
2800
0,675/3
2800
5,90 /12,78 10,40 /19,28 19,40 /32,28
M5/F7
50
7040
322
-5 - +40 34
* Calculated wet eciency. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
74
Temperature eciency (balanced mass ow) :
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
V [m3/h]
RIS 2500PE EKO 3.0
Supply 80 60 68 72 75 74 71 65 Extract 69 56 60 64 63 60 58 41 Surrounding 62 46 54 56 57 54 50 45 Measured at 2548 m3/h, 102 Pa
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
RIS P EKO
RIS 2500PW EKO 3.0
Supply air
Δ Pstat [Pa]Δ Pstat [Pa]
Exhaust air
Performance
Power consumption
V [l/s]
V [m3/h]
V [l/s]
P [W]
P [W]
AIR HANDLING UNITS
RIS 2500PW EKO 3.0
Specic fan power
Δ Pstat [Pa]
total power for supply & exhaust fans kW
SFP=
air ow m3/h
Temperature eciency
η [%]
x 3600
V [m3/h]
V [l/s]
V [m3/h]
V [l/s]
View from inspection side
Extract airExhaust air Outdoor air Supply air
Article No. Version GAGRIS1756_0029A 2500PW EKO 3.0 Optional water heater
2500PW EKO 3.0
Water heater (optional) phase/voltage [50Hz/VAC] SVS 700x400
Fans phase/voltage [50Hz/VAC] ~1, 230 exhaust power/current [kW/A] 0,725/3,24
fan speed [min-1] 2800
supply power/current [kW/A] 0,675/3
fan speed [min-1] 2800 Thermal eciency up to* 90% Motorized by-pass + Max power consumption [kW/A] 1,40 /6,28 Control board PRV V2 Filter class exhaust/supply M5/F7 Housing insulation, mineral wool [mm] 50 Colour RAL grey 7040 Weight (net, without packing) [kg] 322 Comply with ERP 2016;2018 Operation indoors Fresh air temperature limits** °C -5 - +40 Housing protection class IP 34
* Calculated wet eciency. **For temperatures lower than recommended, use electrical pre-heater to ensure balanced operation.
Temperature eciency (balanced mass ow) :
Outdoor air = -7°C / 2°C / 7°C
LWA, dB(A)
V [m3/h]
RIS 2500PW EKO 3.0
Supply 80 60 68 72 75 74 71 65 Extract 69 56 60 64 63 60 58 41 Surrounding 62 46 54 56 57 54 50 45 Measured at 2548 m3/h, 102 Pa
Lwa total,
dB(A)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
The company reserves the right to make changes of technical data without prior notice
Extract air = 20°C/60%RH
75
EKS NV
PH
RIS P EKORIS P EKO
RIS 400PE EKO 3.0 / RIS 700PE EKO 3.0 (ceiling mounted) versions with electrical heater
IV - exhaust air fan PV - supply air fan PR - plate heat exchanger PF - lter for supply air (class F7) IF - lter for extract air (class M5) KE - electrical heater M1 - actuator of by-pass damper
TL - fresh air temperature sensor TJ - supply air temperature sensor TE - exhaust air temperature sensor DTJ 100.1- humidity + temperature sensor AVA - optionally supplied water cooler EKA NV PH - optional fresh air pre-heater
AVA
AIR HANDLING UNITS
RIS 1200PE EKO 3.0 / 1900PE EKO 3.0 / 2500PE EKO 3.0 (ceiling mounted) versions with electrical heater
IV - exhaust air fan PV - supply air fan PR - plate heat exchanger KE - electrical heater PF - lter for supply air (class F7) IF - lter for extract air (class M5) TE - temperature sensor for exhaust air TL - temperature sensor for fresh air
76
EKS NV PH - optional fresh air pre-heater DTJ 100.1 - humidity + temperature sensor TJ - temperature sensor for supply air M1 - actuator of by-pass damper PS1 - supply air dierential pressure switch PS2 - extract air dierential pressure switch PS3 - heat exchanger antifrost pressure switch
The company reserves the right to make changes of technical data without prior notice
RIS 400PW EKO 3.0 / RIS 700PW EKO 3.0 (ceiling mounted) versions with water heater
PH
EKANV
RIS P EKORIS P EKO
AVA
T1
DTJ
100.1
M4 - water heater circulation pump IV - exhaust air fan PV - supply air fan PR - plate heat exchanger PF - lter for supply air (class F7) IF - lter for extract air (class M5) TV - antifrost sensor M1 - actuator of by-pass damper AVA - optionally supplied water cooler
M6 - optionally supplied mixing valve and motor
TL - fresh air temperature sensor
TJ - supply air temperature sensor
TE - exhaust air temperature sensor
T1 - antifrost thermostat
DTJ 100.1 - humidity + temperature sensor
AVS - optionally supplied water heater
EKA NV PH - optional fresh air pre-heater
RIS 1200PW EKO 3.0 / RIS 1900PW EKO 3.0 / 2500PW EKO 3.0 (ceiling mounted) versions with water heater
PH
EKS NV
AIR HANDLING UNITS
DTJ
100.1
IV - exhaust air fan PV - supply air fan PR - plate heat exchanger PF - lter for supply air (class F7) IF - lter for extract air (class M5) TE - temperature sensor for exhaust air TL - temperature sensor for fresh air TJ - temperature sensor for supply air T1 - antifrost thermostat
The company reserves the right to make changes of technical data without prior notice
TV - antifrost sensor DTJ 100.1 - humidity + temperature sensor M1 - actuator of by-pass damper M4 - water heater circulation pump M6 - optionally supplied mixing valve and motor PS1 - supply air dierential pressure switch PS2 - extract air dierential pressure switch PS3 - heat exchanger antifrost pressure switch SVS - optionally supplied water heater EKS NV PH - optional fresh air heater
77
RIS P EKO
Description of the functions
4 speeds for easy and user-friendly control (“Stop” – the unit is stopped; “Low”, medium”, and “High”. Service menu allows adjusting each
Fans
Electric heater
AIR HANDLING UNITS
Water heater
DX cooler
Water cooler
Bypass damper
Filter pollution monitoring
Sensors
FUNCTIONS
PRV V2
RIS EKO 3.0
E W
Functions
Date and time settings
speed individually)
BOOST function (Fans operate at highest speed)
Comfortable air temperature function
Cold/heat recovery
Fire place function
Dryness protection
Weekly schedule
Holiday schedule
User and service control levels
Manual air ow balancing
CO2 level indication and reduction function
Night cooling function
Relative humidity (RH) level indication and reduction function
Software and conguration update possibility
Supply air temperature control according to the extract air sensor
Monitoring function (all sensors and I/O) 2 2
Mode switch (start/stop)
Extracted air relative humidity converter
Manual components control 1 1
Functional units
Soft start and stop
Fan failure protection
Speed synchronous/asynchronous 0-10V control
On/O / PWM control
Manual protection
Overheat protection (additional protection software)
Pulse-width modulation (PWM) valve actuator control
Protection using temperature sensor
Protection using termostat (NC)
Circulation pump control
Return water temperature sensor
Control On/O
Pulse-width modulation (PWM) valve actuator control
Control with three-positional valve actuator
3-position actuator control
By pressure switch (NC)
By lter timer
Supply air temperature sensor
Fresh air temperature sensor
Exhaust air temperature sensor
Extract air temperature sensor
Emergency signals and inputs/outputs
Fire protection input
Working indication output
Alarm indication output
Remote controllers
Stouch
Flex
Ptouch
MB-Gateway
78
1 With FLEX TEST remote controler 2 Only sensors
The company reserves the right to make changes of technical data without prior notice