17.1. RECOMMENDATIONS BEFORE THE START OF THE UNIT (BEFORE THE FINAL USER) 11
17.2. POSSIBLE FAULTS AND TROUBLESHOOTING 11
18. MAINTENANCE 11
18.1. FILTERS 11
18.2. FAN 11
18.3. HEAT EXCHANGER 12
18.4. ELECTRICAL HEATER 13
19. AUTOMATIC CONTROL 13
19.1. SYSTEM PROTECTION 14
19.2. USING THE UNIT IN BMS NETWORK 14
19.3. MODBUS ADRESSES 15
19.4. ELECTRICAL CONNECTION OF THE HVAC UNIT 16
19.5. SYSTEM ADJUSTMENT GUIDELINES 16
20. CONTROL BOARD RG1 18
20.1. LABELING, CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS 19
20.2. REGULAR SYSTEM CHECK-UP 21
21. ELECTRICAL CONNECTION DIAGRAM 22
21.1. RIRS 1200 HE EKO 3.0 22
21.2. RIRS 1900 HE EKO 3.0 23
21.3. RIRS 1200-1900 HW EKO 3.0 24
21.4. RIRS 2500 HE EKO 3.0 25
21.5. RIRS 2500 HW EKO 3.0 26
21.6. RIRS 3500 HE EKO 3.0 27
21.7. RIRS 3500 HW EKO 3.0 28
21.8. RIRS 5500 HE EKO 3.0 32
21.9. RIRS 5500 HW EKO 3.0 33
22. ECODESIGN DATA TABLE 34
24. DECLARATION OF CONFIMITY 35
25. WARRANTY 36
25.1. LIMITED WARRANTY COUPON 36
2 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
2. SYMBOLS AND MARKING
SERIAL
2514523357
XXX GAMINIO PAVADINIMAS
Nominal voltage frequency
Max.current
Max.power consumption
Protection class
Weight
/ xxx/xx VAC/Hz
x.xxA
x.xx kW
IPxx
xx kg
Made inŠiauliai, Lithuania
AHU000000
BN:xxxxxx
2019/01/01
SERIAL
2514523357
XXX GAMINIO PAVADINIMAS
Nominal voltage frequencyMax.currentMax.power consumptionProtection classWeight
/xxx/xx VAC/Hz
x.xxAx.xx kWIPxxxx kg
Made inŠiauliai, Lithuania
AHU000000
BN:xxxxxx2019/01/01
SERIAL
2514523357
XXX GAMINIO PAVADINIMAS
Nominal voltage frequency
Max.current
Max.power consumption
Protection class
Weight
/ xxx/xx VAC/Hz
x.xxA
x.xx kW
IPxx
xx kg
Made inŠiauliai, Lithuania
AHU000000
BN:xxxxxx
2019/01/01
SERIAL
2514523357
XXX GAMINIO PAVADINIMAS
Nominal voltage frequencyMax.currentMax.power consumptionProtection classWeight
/xxx/xx VAC/Hz
x.xxAx.xx kWIPxxxx kg
Made inŠiauliai, Lithuania
AHU000000
BN:xxxxxx2019/01/01
LN: XX000000
2019.01.01
Figure. 2.1. Technical label
1 - Logo; 2 - Product code (SKU); 3 - Product name; 4 - Technical data; 5 - Production place; 6 - Lot number and production date; 7 - Serial
number.
Figure. 2.2. Technical label place
Figure. 2.3. Indication for duct connection.
ODA - outdoor air; SUP - supply air; ETA - extract air; EHA - exhaust air.
3. SAFETY INSTRUCTIONS AND PRECAUTIONS
Read this instruction very carefully before installing and using this equipment. Installation, connection and maintenance should be carried out by
a qualifed technician and in accordance with the local rules and legal acts.
The company shall take no responsibility for the injuries suered by the people or for the damaged property, if the safety requirements are not
followed or the device is modifed without the permission of the manufacturer.
Warning – pay attentionAdditional information
Main safety rules
Danger
• Before performing any electricity or maintenance tasks make sure, that the device is disconnected from the mains, that all moving parts
of the device have stopped.
• Make sure that the fans can not be entered through air ducts or branch openings.
• Do not plug the device into the mains, that diers from the one indicated on the label or on the housing.
• Voltage of the mains should comply with the electrotechnical parameters indicated on the label.
• The device should be earthed in accordance with the rules of installation of electric appliances. It is forbidden to turn on and use unearthed device. Follow the requirements of the device’s labels that indicate Danger.
• If you notice liquids on electric parts or connections that bear voltage, stop the operation of the appliance.
EN | 3RIRS 1200-5500 H EKO 3.0 v2019.06
Warnings
L
W
H
D*
W1
H1
L1
H
H2*
W2*
H3*
L
W
H
D*
W1
L2*
H2
H1
H4*
H3
L1
d*
W2*
H
W2*
H5*
W3*
• Connection of electricity and maintenance of the device should be performed only by a qualied personnel, in accordance with the
manufacturer’s instructions and valid safety requirements.
• In order to reduce the risk during installation and maintenance, suitable protective clothes should be worn.
• Beware of sharp angles while performing installation and maintenance tasks.
• Do not touch heating elements until they haven’t cooled down.
• Some devices are heavy, thus one should be very careful while transporting and installing. Use suitable lifting equipment.
• While connecting electricity to the mains a circuit breaker of suitable size is necessary.
Warning!
• If the device is installed in a cold environment, make sure that all connections and tubes are properly isolated. Intake and discharge air
ducts should be isolated in all cases.
• Openings of the ducts should be covered during transportation and installation.
• Make sure not to damage the heater when connecting the piping of the water heater. For tightening up, use a wrench/spanner.
Before starting the equipment
• make sure, that there are no strange objects inside;
• manually check whether fans are not stuck or blocked;
• if rotary heat exchanger is installed in the device, make sure that it is not stuck or blocked;
• check the grounding;
• make sure that all components and accessories are connected in accordance with the project or provided instructions.
Danger: Fumes
Salda Antifrost system uses dis-balancing of the air ow and it may cause negative pressure in premises. Great care should be taken
when using at the same time in premises as another heating appliance what depend on the air in premises. Such appliances include
gas, oil, wood or coal-red boilers and heaters, replaces, continuous ow or other water heaters, gas hobs, cookers or ovens which
draw air in from the room and duct exhaust gases out through a chimney or extraction ducting. The heating appliance can be starved
of oxygen, impairing combustion. In exceptional cases harmful gases could be drawn out of the chimney or extraction ducting back
into the room. In this case we strictly recommend to turn o Salda Antifrost and use an external preheater for heat exchanger anti-frost
protection (see Salda Antifrost function on the Remote controller manual).
Only a product placed on a pallet may be lifted in order to prevent damage to the casing.
10. UNPACKING
Figure. 9.1. Lifting with forklift.
Figure. 9.2. Lifting
Accessories may be packed together with the product. Prior to transporting the unit, rst unpack the accessories.
• Remove the lm from the unit.
• Remove the bracing packaging tape which keeps the protective proles.
• Remove the protective proles.
•After unpacking the unit, examine it to make sure that it it has not been damaged during transportation. The installation of damaged units is
prohibited!
• Verify that all ordered equipment are delivered before starting the installation. Any deviation from the ordered equipment must be reported to the
supplier of products.
EN | 7RIRS 1200-5500 H EKO 3.0 v2019.06
11. STANDART PACKAGE OF COMPONENTS
α
α
RIRS EKO 3.0
HANDLES SETSUPPORT LEG WITH EXTENDABLE
1200 HE 1-
1200 HW1-
1900 HE1-
1900 HW1-
2500 HE212
2500 HW212
3500 HE212
3500 HW212
5500 HE312
5500 HW312
12. PLACE REQUIREMENTS
L
1,5xL
RODS
H
13. MOUNTING
The protective lm is intended to protect the unit during transportation. It is recommended to remove the lm because otherwise oxidation signs may occur.
Before every heating season the condensate tube shall be lled with water as indicated during the rst startup!
Min. distance to open the door - 1,5xL; Min. distance to open control box door - H > 400 mm.
α
W
Figure. 13.1. Mounting positions on oor horizontal (α>1o)
8 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
Figure. 13.2. Floor mounting
PS
PS
PS
PS
2
2
2
2
14. CONNECTION OF THE AIR DUCT
15. CONNECTION DIAGRAM
Figure. 14.1. Circular air duct conection
Figure. 14.2. Rectangular air duct conection
2
PS
Figure. 15.1. RIRS 1200-1900 HE EKO 3.0 (* Placement of the component depends on model)
PS
Figure. 15.2. RIRS 1200-1900 HW EKO 3.0
EN | 9RIRS 1200-5500 H EKO 3.0 v2019.06
PS
PS
M
CO
2
Figure. 15.3. RIRS 2500-5500 HE EKO 3.0
PS
Figure. 15.4. RIRS 2500-5500 HW EKO 3.0
Figure. 15.5. Indication for duct connection.Figure. 15.6. Ventilated premises
ODA - outdoor air; SUP - supply air; ETA - extract air; EHA - exhaust air.
LIST OF COMPONENTS
CPlate heat exchangerA1Fire alarm damper actuator I
PVSupply air fanA2Fire alarm damper actuator II
IFExtract air lterTJSupply air temperature sensor
PFSupply air lterTLOutdoor air temperature sensor
IVExhaust fanTEExhaust air temperature sensor
KE1Electric heaterDTJExtract air temperature and RH sensor
PE1Electric pre-heaterT2Cooler changeover thermostat
KV2Water pre-heaterTV2Water preheater temperature sensor
KV3Water coolerTV3Water cooler temperature sensor
DXDX coolerU3PV pressure transmitter
M1By-pass damperU4IV pressure transmitter
M2Outdoor air damper actuatorCO
System mode switch (START/STOP)Fans speed switch (BOOST)
* Component/posibility to connect it depends on model. For more information please, check the manual
16. CONNECTION OF THE UNIT TO ELECTRIC NETWORK
10 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
• Supply voltage to the unit must be connected by a qualied specialist following the manufacturer’s instructions and eective safety instructions.
• The unit’s power network voltage must correspond to electrotechnical parameters of the unit indicated in the technical decal.
• The unit’s voltage, power and other technical parameters are provided in the unit’s technical decal (on the unit casing). The unit must be connect-
ed to the voltage plug socket of the grounded power network in compliance with the eective requirements.
• The unit must be earthed according to the rules on installing electrical equipment.
• It is prohibited to use extension wires (cables) and power network plug socket distribution devices.
• Prior to carrying out any ventilation unit installation and connection activities (until its hand-over to the customer), the unit must be disconnected
from the power network.
• After installation of the ventilation unit, the power network plug socket must be accessible at any time and disconnection from the power network
is performed through the two-pole circuit breaker (by disconnecting phase pole and neutral).
• The unit must be thoroughly checked against damages (execution, control, measurement nodes) during transportation before it is connected to
the power network.
• The power cable can be replaced only by a qualied specialist upon the evaluation of the rated power and current.
The manufacturer does not assume any liability for personal injuries and property damage due to nonconformance with the
provided instructions.
17. START-UP RECOMMENDATIONS
17.1. RECOMMENDATIONS BEFORE THE START OF THE UNIT (BEFORE THE FINAL USER)
Prior to start-up the system must be thoroughly cleaned. Check whether:
• operation systems and unit elements as well as automation and automation devices were not damaged during installation,
• all electrical devices are connected to power supply and t for service,
• all necessary automation elements are installed and connected to power supply and terminal blocks,
• cable connection to terminal blocks comply with the existing power connection diagrams,
• all electrical equipment protection elements are properly connected (if they are additionally used),
• cables and wires correspond to all applicable safety and functional requirements, diameters, etc.,
• earthing and protection systems are properly installed,
• condition of all seals and sealing surfaces are proper.
17.2. POSSIBLE FAULTS AND TROUBLESHOOTING
FAILURECAUSEEXPLANATION / CORRECTIVE ACTIONS
No supply voltage
Unit is not operating
Air supply heater or pre-heater is not operating or malfunctioning (if installed)
Too low air ow at rated fan speedClogged supply and/or extract air lter(s)Filter replacement needed
Filters are clogged and no message is shown
on the remote control
Protection device is o or a current
leakage relay is active (if installed by the
installer)
Too low air ow in air ducts activates automatic
protection
Manual protection is activated
Wrong time in lter timers or their switch is
broken, or its pressure is set improperly.
Check whether the device is connected to the
power network
Switch on only if the unit condition has been
evaluated by a qualied electrician. If the system failed, the failure MUST BE rectied prior
to switching it on.
Check if air lters are not clogged
Check if fans are rotating
Possible heater or unit failure. MUST contact
the servicing sta for failure detection and its
elimination.
Shorten lter timer time till the message of
clogged lters or replace the pressure switch
of the lters, or set their proper pressure.
18. MAINTENANCE
Unplug unit from mains rst and wait for 2 minutes (till fans fully stop) before opening the covers.
18.1. FILTERS
Dirt increases air resistance in the lter, therefore less air is supplied into the premises.
- It is advisable to change the lters every 3-4 months, or in accordance with the readings of lter contamination sensor. (Sensor PS 600 is inte-
grated in the unit).
18.2. FAN
- Maintenance and repair should only be performed by experienced and trained sta.
- The fan should be inspected and cleaned if needed at least once a year.
- Be sure the fan is disconnected from power source before performing any maintenance or repair.
- Proceed to maintenance and repair after any rotation in the fan stopped.
- Observe sta safety regulations during maintenance and repair.
EN | 11RIRS 1200-5500 H EKO 3.0 v2019.06
- The motor is of heavy duty ball bearing construction. The motor is completely sealed and requires no lubrication for the life of the motor.
- Detach fan from the unit.
- Impeller should be specially checked for buil-up material or dirt which may cause an imbalance. Excessive imbalance can lead to accelerated
wear on motor bearings and vibration.
- Clean impeller and inside housing with mild detergent, water and damp, soft cloth.
- Do not use high pressure cleaner, abrasives, sharp instruments or caustic solvents that may scratch or damage housing and impeller.
- Do not plunge impeller into any uid.
- Make sure, that impeller’s balance weights are not moved.
- Make sure the impeller is not hindered.
- Mount the fan back into the unit. Replace fan guards and connect the fan to power supply source.
- If after maintenance or repair the fan does not start either thermal protection contact activates automatically, contact the manufacturer.
- During the maintenance do not hold the fan by the impeller, it might cause disbalance of impeller or damage it. Hold the fan by the casing.
Figure. 18.1. RIRS 1200-1900 H EKO 3.0
Figure. 18.2. RIRS 2500-5500 H EKO 3.0
18.3. HEAT EXCHANGER
• Be sure the unit is disconnected from power source before performing any maintenance or repair.
• Proceed to maintenance and repair after any rotation in the fan stopped.
• Clean it once a year.
• The maintenance works for the rotor heat exchanger shall be carried out once a year.
• Ensure that the gaps of the heat exchanger are not contaminated, the seal brushes are not worn, the belt drive is not worn and the clamp assemblies are tight.
• The rotor heat exchanger can be easily removed from the unit by disconnecting the power supply cable of the heat exchanger motor (Pic. 1-2).
• The heat exchanger is cleaned using the solution of warm water and non-corrosive toward aluminum alkaline agent or the air stream. It is not
recommended to apply direct stream of liquid as it can harm the heat exchanger.
• It is NECESSARY to protect the motor of the heat exchanger from the moisture and liquid while cleaning the heat exchanger.
• CAUTION! It is forbidden to use the heat exchanger if the lters are removed!
Figure. 18.1. RIRS 1200-1900 H EKO 3.0Figure. 18.2. RIRS 2500-5500 H EKO 3.0
12 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
18.4. ELECTRICAL HEATER
Electrical heater does not need to be serviced additionally. It is compulsory to change lters as described above.
Heaters have 2 thermal protections: automatically self-resetting, which activates at +50°C and the manually restored, which activates at +100°C.
After the activation of the manually restored protection, the unit must be disconnected from the power supply. Wait until the heating elements cool
down and the fans stop rotating. After identifying and removing the reason of failure, to start the unit, press the “reset” button. The failure can be
identied only by a qualied professional.
If necessary, the electrical heater can be removed. Disconnect the electrical connector from the heater and remove the heater (Pic. a-b).
Figure. 18.1. RIRS 1200-1900 H EKO 3.0Figure. 18.2. RIRS 2500-5500 H EKO 3.0
19. AUTOMATIC CONTROL
Supply air temperature can be adjusted according to the temperature measured by the supply or extracted air temperature sensor and the temperature which is set by the user on the remote control panel. User selected supply air temperature is maintained by the plate (or rotor) heat
exchanger and additional electric and/or water heater (optional). When the supply air temperature is under the set temperature, by-pass valve is
closed (fresh ambient air passes through the plate heat exchanger). If the device has the rotor heat exchanger, then rotation starts. In case the
set temperature is not reached, the heater (electric or water) is switched on and operates (heater valve is opened/closed if water heater is used)
until the set temperature is reached. When supply air temperature exceeds the set temperature, the heater is switched o in the rst place. If the
temperature is still greater than the set temperature, the by-pass valve is opened or rotation is stopped if the device has rotor heat exchanger.
In the remote controller, temperatures (the set and the measured) are displayed as degrees Celsius (°C).
Room air temperature can be adjusted not only according to the supplied air temperature sensor, but also according to the extracted air sensor
(see FLEX panel description II.6.5.3 for details on selecting this feature).
When control algorithm of the extracted air sensor is selected, then supply air temperature is adjusted based on estimated additional received
heat (heat emitted by the sun, electric heaters, etc.). Thus the energy for excessive heating of the supply air is saved. The room is heated based
on the estimated room temperature to provide the desired room temperature microclimate.
Supply air electric heater (resistance heating elements if the electric heater is used) is controlled by the ESKM controller using the PWM signal. If
the water supply air heater is used, then the actuator is controlled using RG1 controller with analogous 0-10V DC signal.
“BOOST” feature
Fans are started at maximum speed and “BOOST” is displayed in the remote control panel (FLEX). “BOOST” feature is inactive if the heat exchanger protection is triggered. When triggering signal for this function disappears, the desired operation period for this feature can be selected in
the control panel (FLEX) (see FLEX panel description II.6.6 for details on selecting this feature).
There is boost time setting in minutes (factory setting: O) in the user menu item Add.Func. For example, if 5min is set, then in case the signal
is lost for boost controlled with the external control signal, the boost will be active for 5 minutes. For boost controlled with the fast button (FLEX
control panel), boost is activated for 5 minutes if the button is pressed once, and boost will deactivated immediately if the button is pressed second
time. Maximum setting is 255min.
START/STOP feature
The operation of the recuperator is started or stoped using the START/STOP feature. “STOP” is displayed at the remote control panel (FLEX). In
START mode, the recuperator operates based on the latest settings of the panel.
FanFail and FanRun features
It provides option to connect the external fan state indication such as the indication lamp which would visualize the state of the device.
Continuous control of the heater
The new feature is installed: continuous keeping of the supply air temperature (accuracy up to 0,5 °C) by using two-way thyristor module – ESKM...
(these modules are installed only in heaters connected to the three-phase mains).
Cooling by ventilation:
Two types of cooling exist: using halocarbon or water cooler. Cooling is based on the algorithm of the PI regulator and is activated when there
is need for cooling. Conditions for activation and deactivation of halocarbon cooler can be set and changed using the menu of the FLEX remote
control panel (see section II.6.4. of the FLEX description). Actuator position of the water cooler is set accordingly to the PI regulator in the range
between 0% and 100%. The halocarbon cooler is switched on when PI regulator value exceeds the value set in the menu (see section II.6.4.2. of
the FLEX description). The halocarbon cooler is switched o when PI regulator value is less than the set value (see section II.6.4.3. of the FLEX
description).
Ventilation:
Three types of ventilation are possible (see section II.6.3. of the FLEX description): based on the supply air (Supply), based on the extracted air
(Room) and automatic (ByOutdoor). When operation is based on the supply air, the supply air temperature is maintained as set on the PI regulator.
When operation is based on the extracted air, the set extracted air temperature is maintained to keep the supplied air temperature between the
EN | 13RIRS 1200-5500 H EKO 3.0 v2019.06
minimum and the maximum set temperatures (see sections II.6.3.2. and II.6.3.3. of the FLEX description) based on the algorithm of the PI regulator. When operation is automatic (ByOutdoor), both mentioned cooling types are used (supply and extracted air): cooling based on the supply
air is used when ambient air temperature is less than the set temperature (see section II.6.3.3. of the FLEX description). This is so called “winter
mode”. Cooling based on the extracted air is used when ambient air temperature is greater than the set temperature (see section II.6.3.3. of the
FLEX description). This is so called “summer mode”.
Using the remote control panel, the user can adjust fan motor speed as three steps (values of steps are speed set in the window of the remote
control panel, see sections II.6.7 and II.6.8 of the FLEX description). Analogous 0–10 VDC control signal for motors is generated by the controller
RG1. Speed of the supply and extracted air fans can be adjusted synchronously or asynchronously (see sections II.6.7 and II.6.8 of the FLEX
description). If water supply air heater is used and after HVAC unit is switched on, fans are switched on after 20 seconds. During this period, water
valve actuator is being opened to allow water heater to reach the optimum temperature.
Two pressure converters should be used to control both fans while maintaining constant pressure at the system.
Also, CO2 (extract air) converter can be connected (if no pressure converters are connected).
19.1. SYSTEM PROTECTION
a) Several steps of protection are provided for protection of the water heater.
First: if during cold periods the temperature of the outward water ow drops below +10 °C (as measured by the TV sensor), then the water heater
valve actuator M6 is forced to open regardless the need for heat.
Second: if the water temperature does not reach +10 °C after fully opening the hater valve and the air temperature after heating drops below
+7/+10 °C (as set on the protection thermostat T1), then the air supply device is stopped. To protect water heater from freezing (when the unit is
stopped), tow outputs operate: circulatory pump M4 and water heater valve actuator M6. Supply air valve actuator with the return spring is (should
be) used for the protection of the water heater. During voltage loss, supply air valve is closed immediately. It does not automatically reset and
should be reset (restarted) from the control panel.
b) When the device has the electric heater, then two levels of overheat protection are used. Two types of the capillary thermal protections are used
for the overheat protection of the electrical heater: manual and automatic. Automatic thermal protection is activated when air temperature exceeds
+50 °C and manual protection is activated when air temperature exceeds +100 °C. Automatic thermal protection +50 °C is used to disconnect the
electric heater if the temperature of the heating elements exceeds +50 °C which could cause consumption of the oxygen.
Capillary thermal protections are dierent only with respect to construction to allow automatic thermal protection to reset to the operation state.
Manual thermal protection does not reset and should be reset to the operation state by pressing RESET button on the service cover of the heater.
When manual thermal protection is triggered, fans operate in maximum capacity until the manual heater protection is reset (by pressing the reset
button) and the device is restarted. When heater fault is registered, manual heater protection can be restored only after estimation of the fault
cause and only if it is safe to do so regardless of the temperature setting on the control panel. Also it should be inspected if other automation and
installation elements are not damaged.
Antifreeze protection of the dierential pressure heat exchanger (dierential pressure relay PS600) is used only in more ecient devices (from
1200 m3/h).
Triggering of the automatic thermal protection mostly occur due to low fan speed (faulty fan, stuck/faulty air inlet valve/actuator).
19.2. USING THE UNIT IN BMS NETWORK
The recuperator can be connected to the BMS network by using the ModBus protocol.
The device can be controlled using FLEX panel and BMS network simultaneously: the device will work based on the latest changes of settings.
As set in the factory, the device will operate (if no faults are present) based on the latest panel settings in case the panel or BMS network (or even
both) is disconnected. This setting can be changed, please see Flex_meniu_montuotojas section 14 “Misc” for details.
ModBus type: RTU
RS485_2 port is used for connecting the ModBus (Fig. 3);
Settings (see section II.6.2. of the FLEX installer description):
Figure. 19.1. RS485_1 and RS485_2. RS485_1: remote control panel socked; RS485_2: ModBus port
Stouch control panel must be connected to RS485_2 (ModBus) connection
RJ10 socket contacts reference:
1 – COM
2 – A
3 – B
4 - +24V
Microswitches 1 and 2 (Fig. 4) are mounted in the control board for selecting of resistances during network adjustment. Adjustment depends on
the connection method. If the ring type connection is used, up to 30 units could be connected. If other method is used, approximately 7 units could
be connected. The resistance between the rst and the last unit should be 120...150 Ω.
14 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
Resistance Ω
180
470ONOFF
330OFFON
ONON
Figure 19.2.2. Microswitches 1 and 2
Switch 1Switch 2
19.3. MODBUS ADRESSES
Nr. NameModBus func.
1Antifrost01h_Read_Coils01Plate heat exchanger frost protection function
2Fire01h_Read_Coils11Fire alarm
3Filter01h_Read_Coils21Dirty lter alarm
4Fan01h_Read_Coils31Fans alarm
5LowPower01h_Read_Coils51Low voltage
6Textract01h_Read_Coils61DTJ(100) temperature sensor alarm
7Texhaust01h_Read_Coils71Exhaust air temperature sensor alarm
8Tlimit01h_Read_Coils81Supply air temperature sensor alarm
9RH01h_Read_Coils91
10ReturnWater01h_Read_Coils101Return water temperature sensor alarm
11ToutDoor01h_Read_Coils111
12MotorActive01h_Read_Coils131Fans ON
13InDumpper04h_Read_Input141Outside air damper actuator0-90
19Motor104h_Read_Input151Motor1 fan speed value0-3
06h_Write_Holding_
Register
06h_Write_Holding_
Register
Data
ad-
dress
01Fans speed settings0, 1, 2, 3
11Supply air temperature set0-30
Quan-
tity of
data
DescriptionValues
TJ(100) humidity sensor alarm (controller works in determining the moisture content of 70%)
Outside air temperature sensor alarm (controller continues
to work in determining ToutDoor<0C)
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
1-active,
o-passive
EN | 15RIRS 1200-5500 H EKO 3.0 v2019.06
20Motor204h_Read_Input161Motor2 fan speed value0-3
1_789.0046A.0.1.2-L-0k
Temperature sensor value real format (-3.3E38 - 3.3E38) example: 0h->0C, 7FFFh->3276.7C, 8000h->3276.8, FFFFh->-0.1C
21Tlimit04h_Read_Input01Supply air temperature valueHex: E0
22Texhaust04h_Read_Input11DTJ(100) temperature sensor valueHex: E0
23Textract04h_Read_Input21Exhaust air temperature sensor valueHex: E0
24ToutDoor04h_Read_Input31Ouside air temperature sensor valueHex: FFEC
25Twater04h_Read_Input121Return water temperature sensor valueHex: FFEC
19.4. ELECTRICAL CONNECTION OF THE HVAC UNIT
Electrical connection can only be implemented by the qualied electrician in accordance with the applicable international and national electrical
safety requirements and requirements for installation of electrical devices.
Use only power source which meets the requirements specied on the device label.
Power supply cable should be selected based on the electrical specication of the device. If the device power supply line is far from the unit, the
distance and voltage drop should be considered.
Device must be earthed.
Install the control panel at the designated place.
Install the supplied connection cable(FLEX controller) between the control panel and the HVAC unit. It is recommended to install the control panel
separately from the power cables.
Note: If cable is used together with other power cables, shielded control panel cable with earthed shield should be used.
Connect the plug (RJ10 type) to the RS485-1 socket of the unit. Connect the other end to the control panel.
RS458_1 RS458_2
NOTE: The remote control panel can be connected and (or) disconnected only after disconnecting the power supply for the HVAC unit.
Switch on the mains voltage, switch on the blade switch Q, see Fig. 5 (actual appearance of the blade switch can be dierent from the given photo
based on the model of the product).
OFF
ON
Select the desired fan rotation speed and the supply air temperature using the remote controller.
19.5. SYSTEM ADJUSTMENT GUIDELINES
L1NPE
X16
X16
PE N L1
L 1NPE
X16.7
CE7/7
L 1NP E
Power
supply cable
1f, 230V AC
123 45678910
32
1
X16.1
Y1
24VAC, 3-position
Y1 - OPEN (24VAC)
Y2 - CLOSE (24VAC)
G - System poten tial 24VAC
Water cooler
valve actuator
X16.213 1487X16.3
Y2
G
M5
Boost
456109
STOP-NO
START- NC
BOOST
Jumper
DX Cooling
Start /Stop
10987654321
11 12 13 14 15 16 17
X16.4
11 122524
1
P
3
AHU st op
AHU status
X16.4
NC
FA
Jumper
24VDC
24VDC
1.2W max
1.2W max
AHU work
Fire alarm
AHU workAHU stop
input
18 19 20 21 22
19
17 18
162015
N L
N
L
L control
LNNL L
M3
M2
230V AC230V AC
ON/OFF
Supply airExtract air
ON/OFF
damper actuatordamper actuator
X16.5
L control
222120191817161514131211
21 22
X16.6
TJ
NTC
Supply air
temp.sensor
23
X16.4
23
P
Transmitter 1
23 - 24V DC ,
24 - intput , 0-10V DC,
25 - GND,
Air quality transmitter
Supply ai r press ure
27 282624 2523
27 282624 25
X16.10
Transmitter 2
26 - 24V DC,
27 - intput, 0-10V DC,
28 - GND,
Air quality tra nsmitter
CO2;
Extract a ir pre ssure
2827P26
Figure 19.5.1. RIRS 1200-1900 HE EKO 3.0
16 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
1.790.0047A.0.1.2-L-0k
X16
L1NPE
PE N L1
L 1NPE
X16.7
CE7/7
L 1NP E
1f, 230V AC
Powe r
supply cab le
12345678910
1098765 4321
X16.1
23
1
Y2Y1
G
M5
24VAC, 3-position
Y1 - OPEN (24VAC)
Y2 - CLOSE (24VAC)
G - System potential 24VAC
Water cooler
valve actuator
781413
X16.2
STOP-NO
START-NC
BOOST
Jumper
DX Cooling
Start/Stop
Boost
X16.3
1
P
3
AHU stop A HU work
AHU status
Figure 19.5.2. RIRS 1200-1900 HW EKO 3.0
Figure 19.5.3. RIRS 2500-5500 HE EKO 3.0
171514131211
16
NC
N
FA
Jumper
ON/OFF
Fire ala rm
input
damper actuator damper actuator
16
151817
16
L control
NL
M2
230V AC
N
19
L
M3
230V AC
ON/OFF
Ext ract airSupply air
X16.5
20
L control
LLN
11 12 13 14 1517 18 19 20 21
1211X16.4 9 10654
X16.4
AHU work
1.2W max
1.2W max
AHU sto p
24VDC
24VDC
21201918
2221
TJ
NTC
Supply air
temp.sensor
22 23 24
X16.4
X16.6
Transmitter 1
23 - 24V DC,
24 - intput, 0-1 0V DC,
25 - GND,
Air qual ity trans mitter
CO2; Supply air pressure
242322
23 24
25
25
P
X16.10
25
Transmitter 2
26 - 24V DC,
27 - intput , 0-10 V DC,
28 - GND,
Air quality transmitter
Extract air pressure
26 27
34333235 36
G
M6
X16.9
TV
Water he ater
antifrost p rotect.
36
36
41
T1
302931333234 35272628
302931333234 35272628
28
X16.7
29
3130
X16.8
N
0Y
L
PE
P
circulation pump
1f, 230 V AC
Water heater
24VDC, 0-10VDC
M4
0 - GN D,
Y - 0-10V,
G - 24VDC.
Water heater
valve actuator
Figure 19.5.4. RIRS 2500-5500 HW EKO 3.0
Before commissioning, device launching and adjustment works must be done only by qualied and trained personnel. Automatic control system of
the ventilation unit must be properly adjusted to work adequately. Also, install measuring and operating devices in line with the provided guidelines.
Air temperature sensors and air quality converters. Supply air temperature sensors and air quality converters (if additionally used) must be
mounted as far as possible from the ventilation devices (within the connes of sensor cable) up to the rst branch or turn of the air transportation
system. This requirement is necessary to ensure the accuracy of measurement.
Antifreeze protection. When external supply air water heater is used, it is necessary to properly install antifreeze protection from possible
freezing of heat carrier. Antifreeze temperature sensor (TV) must be mounted in clamp on return pipe of the water heater. Capillary sensor of the
antifreeze thermostat (T1) must be mounted on the water heater and its adjustment knob must be set at +5 °C.
L damper motor ON/OFF
230V/50Hz (delay of 3 minutes after stopping fans and heaters)
L damper motor ON/OFF
230V/50Hz
Electrical heater guard from overheating
Cooling valve opening PWM
24v/50hz
Cooling valve closing PWM
24v/50hz
Cooling valve common Pulse
24v/50hz
Bypass damper opening PWM
24v/50hz
By-Pass damper closing PWM
24v/50hz
By-Pass damper common PWM
24v/50hz
Indicates when fans fail ON/OFF
24V
Indicates when fans running ON/
OFF 24V
Electric/Water heater controll signal 0-10V
Extract air fan 0-10V pressure,
CO2 transmitters
Supply air fan 0-10V pressure
transmitter
O16A100
I--
O3A100
O3A100
I--
AO--
AO--
AO--
AO100mA-
AO100mA
AO100mA
DO0.05mA-
DO0.05mA-
AO5mA-
AI--
AI--
20 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
X347A4Fans guardDI-X348A4COM--X381Extract air temperature sensor AI--
DTJ
Temp. and humidity sensor for
100
extract air.
Supply air temperature sen-
TJ
sor.
Exhaust air temperature sen-
TE
sor
PVSupply air fan.
IVExtract room(s) air fan.
X382COM--X401+5V--X402Extract air humidyti sensor AI-X403COM--X391Supply air temperature sensor AI-X392COM--X411Exhaust air temperature sensor AI-X412COM--X371V1Supply air fan 0-10VAO-X372COMCOM--X373V2Extract air fan 0-10VAO-X374COMCOM---
20.2. REGULAR SYSTEM CHECK-UP
The operation of the switching device (contactor) should be visually inspected every 3–4 months (the casing cannot be melted and should have
no other signs of the thermal damage, no extra sounds should be generated while switching or during impact).
The blade switch should be disconnected during service (if installed on the device). If blade switch is not installed, disconnect the power supply
from the distribution panel.
EN | 21RIRS 1200-5500 H EKO 3.0 v2019.06
21. ELECTRICAL CONNECTION DIAGRAM
,
1.1253.0.1.0-PS
21.1. RIRS 1200 HE EKO 3.0
W2
FA - fire alarms input,
WH(BK)
RD
GN(BU)
YE
pressure, CO2 transmitters,
14
8765439
K1
13
X29.3
R
P/U - "Transsmiter 2" extract air fan 0-10V
X02
0
C
1
2
RT1
X22
BR
BK
BU
YE
LOW X32.1
COM X32.4
AC.N
PUMP
B.0.10
COM
MIDL
HIGH
TIMER
COM
CHIL X33.9
COM X33.10
ALARM X33.11
COM
ANTI.F
+24
FAN
COM
P/U - "Transsmiter 1" supply air pressure
transmitter (0-10 VDC),
A1
A1
A2
A2
A3
A3
A4
A4
HR
TA
T.s et
COM
PWM
0
TK
TK
1
2
3
4
switch,
X35.2
X35.1
X33.13
X33.14
X32.2
X32.3
X33.1
X33.2
X33.18
X33.12
X33.17
X33.25
X33.26
X34.1
X34.2
X34.3
X34.4
X34.5
X34.6
X34.7
X34.8
X40.1
X40.2
X40.3
X38.1
X38.2
X33.23
X33.24
P - DX cooler protection, differential pressure
Lin
A1
Lout
RG2
A2
U
V
W
PE
X8
X10
K1
X37.2
X37.1
X37.4
X33.3
X33.4
RG1
X33.5
X33.16
X33.15
X35.5
X35.4
X35.3
X33.21
X33.22
X39.1
X39.2
X33.19
X33.20 COM
X41.1
X41.2
X3
X4
KE1
7 8 9 10 11 12
24VDC
R1
X16.3
A2
DX Cooling
3
1
P
BOOST
Jumper
START-NC
STOP-NO
Fan fall
1.2W max
24VDC
Fan run
1.2W max
24VDC
Transmitter 1 (24 VDC)
23 - 24V DC,
24 - i ntput, 0-10V DC,
25 - GND,
P
U
Jumper
FA
NC
Transmitter 2 (24 VDC)
26 - 24V DC,
27 - i ntput, 0-10V DC,
28 - GND,
P
U
A1
14
11
87
W3
X16.2
4561 09
X16.4
11 12
23
2524
13 14
X21.2
2
1
PS2PS1
8765
2
1
HR
U
DTJ 100
X16.10
TA
282726
RG1 - controller PRV-... V2.5,
RG2, RG3 - controller ESKM1-26/176-30,
F1 - fuse 10A (size 5x20),
R - rotor motor 15W,
Q2 - circuit breaker B16,
C - capacitor.
PS1 - supply air filter pressure relay,
PS2 - extract air filter pressure relay,
4x1000W/400V
RG4
0-10V in
N
L
N
RS485_2
RS485_1
X01
A2 A2
A2
A2
1
NL
2
3
COM
9
NO
10
COM
COM
VAL+
VAL-
VAL
COM
A.0.10
EXT-
EXT+
AC.N
T.O UT
COM
TJ
T.WAT
TE
2x400V
L2L1PEN
X16.7
N
PE
L1
GN - Green.
BK - Black.
BN - Brown.
BU - Blue.
WH - White.
RD - Red.
YE - Yellow.
X29.1
K1
A1
462
A1
531
A1
A1
EK1-EK4
K1
2
A2
A1
X51
2
1
N
L
X31L
X25
X29
X24N
X12L
X42
X2.2
X2.1
V1
V2X37.3
L (open)
L (close)
N
Remote control
4321
X29.2
5
0
C
1
6
AT1
1
2
3
4
X21.1
5
6
W3 W2
7
21
8
W4 W5
9
43
W4W5
RS485_2
RS485_1
ModBus RTU
21
X22
IV
GND
10V
0-10V
D1
K1
K1
out
in
in
L2
L1PEL1
N
X35
6
7
8
9
X52
TE
X16.6
2221
TJ
B16
42
KE2
0
C
1
2
AT2
0-10V
PE
N
L
L2
TL
in
PE
L3
N
X33
X34
X4
2
345
1
X37
L2
13
Main Switch
Q1
2P
Q2
1
3
X21.3
9 10
42
F1, 10A
12
NPE
X23
PV
10V
GND
D1
out
in
L2
L1
N
7
9
8
M2 - outside air damper actuator,
M3 - extract air damper actuator
M5 - Water cooler valve actuator,
PE
K1
K1
N
L
L1
543
TE - exhaust air temperature sensor,
PE
L3
L2
N
X32
X3
2
1
N
EXT+
EXT-
N
EXT+
EXT-
RT1 - manual reset thermostat supply air heater,
DTJ100 - extract air temperature and humidity
TL - fresh air temperature sensor,
TJ - supply air temperature sensor,
sensor,
AT1 - automatic reset thermostat supply air heater
X16.1
312
1615
1917 18
20
X16.5
KE1 - supply air heater,
N
L supply
L control
L supply
L control
IV - extract air fan EC,
G - System potential AC 24 V
Y1 - Control OPEN (AC 24 V)
Y2 - Control CLOSE (AC 24 V)
24VAC, 3-position
M5
Y2Y1
G
ON/OFF
230V AC
M2M3
L
LNNLL
N
230V AC
ON/OFF
PV - supply air fan EC,
PE
6
22 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
21.2. RIRS 1900 HE EKO 3.0
230V AC
1.1246.0.1.0-PS
3x400V
L1PEN
L3L2
GN - Green.
BK - Black.
BN - Brown.
BU - Blue.
WH - White.
RD - Red.
YE - Yellow.
X29.1
1234
X29.2
5
0
C
1
2
6
AT1
21
X22
IV
GND
10V
0-10V
D1
K1
K1
out
in
in
L2
L1PEL1
N
X35
6
7
8
9
X52
KE2
0
C
2
AT2
PE
N
L
PE
L3
L2
N
X33
X4
2
345
1
X37
TL
TE
X16.6
2221
KE1
24VDC
R1
X16.3
A2
DX Cooling
3
1
P
BOOST
Jumper
START-NC
STOP-NO
Fan fall
1.2W max
24VDC
Fan run
1.2W max
24VDC
Transmitter 1 (24 VDC)
23 - 24V DC,
24 - i ntput, 0-10V DC,
25 - GND,
P
U
Jumper
FA
NC
Transmitter 2 (24 VDC)
26 - 24V DC,
27 - i ntput, 0-10V DC,
28 - GND,
P
U
A1
14
11
87
W3
X16.2
456109
X16.4
11 1 2
23
2524
13 14
X21.2
2
1
PS2PS1
8765
2
1
HR
DTJ 100
X16.10
28272 6
W2
U
TA
WH(BK)
RD
GN(BU)
YE
WH(BK)
RD
GN(BU)
YE
14
1211109 8 7
8765439
K1
13
X29.3
R
X02
X04
0
C
1
2
RT1
X22
BR
BK
BU
YE
LOW X32.1
COM X32.4
AC.N
PUMP
B.0.10
COM
MIDL
HIGH
TIMER
COM
CHIL X33.9
COM X33.10
ALARM X33.11
COM
ANTI.F
+24
FAN
COM
A1
A1
A2
A2
A3
A3
A4
A4
HR
TA
T.s et
COM
PWM
RG2
0
TK
TK
PWM
RG3
0
TK
TK
1
2
3
4
X35.2
X35.1
X33.13
X33.14
X32.2
X32.3
X33.1
X33.2
X33.18
X33.12
RG1
X33.17
X33.25
X33.26
X34.1
X34.2
X34.3
X34.4
X34.5
X34.6
X34.7
X34.8
X40.1
X40.2
X40.3
X38.1
X38.2
X33.23
X33.24
Lin
A1
Lout
A2
Lin
A1
Lout
A2
RG4
U
V
W
PE
X8
X10
N
K1
X37.2
X37.1
X37.4
X33.3
X33.4
X33.5
X33.15
X35.5
X35.4
X35.3
X33.21
X33.22
X39.1
X39.2
X33.19
X33.20 COM
X41.1
X41.2
X3
X4
3x3000W/230V
NL
COM
NO
0-10V in
L
N
T.O UT
T.WAT
RS485_2
RS485_1
A2A2
A2
1
2
3
9
10
COM
COM
VAL+
VAL-
VAL
COMX33.16
A.0.10
EXT-
EXT+
AC.N
COM
TJ
TE
X31L
X25
X29
X24N
X12L
X42
X2.2
X2.1
X01
1212
X03
EK1-EK3
2
1
N
L
V1
V2X37.3
A1
A1
A1
L (open)
L (close)
N
K1
135
264
K1
A1
A2
X51
1
2
3
4
X21.1
567
W3 W2
21
8
W4 W5
9
43
W4W5
RS485_2
RS485_1
642
Q2
B16
1
642
53
F1, 10A
X21.3
9 10
1
PV
GND
10V
0-10V
D1
K1
out
in
in
PE
L2
L1
L1
N
X34
8
765
9
135
Main Switch
3P
Q1
12
PE
K1
N
L
L3
L2
N
432
8PE
Contacts
7
PE
PE N
X23
PE
X32
X3
1
N
EXT+
EXT-
N
EXT+
EXT-
X16.1
312
1615
1917 18
20
X16.5
N
L supply
L control
L supply
L control
G - System potential AC 24 V
Y1 - Control OPEN (AC 24 V)
Y2 - Control CLOSE (AC 24 V)
24VAC, 3-position
M5
Y2Y1
G
230V AC
M2M3
L
LNNL L
N
ON/OFFON/OFF
R - rotor motor 15W,
C - capacitor.
Q2 - circuit breaker B16,
PS2 - extract air filter pressure relay,
P/U - "Transsmiter 2" extract air fan 0-10V
FA - fire alarms input,
PS1 - supply air filter pressure relay,
pressure, CO2 transmitters,
P - DX cooler protection, differential pressure
P/U - "Transsmiter 1" supply air pressure
switch,
transmitter (0-10 VDC),
RG1 - controller PRV-... V2.5,
RG2, RG3 - controller ESKM1-26/176-30,
F1 - fuse 10A (size 5x20),
Remote control
ModBus RTU
TJ
M5 - Water cooler valve actuator,
M2 - outside air damper actuator,
M3 - extract air damper actuator
IV - extract air fan EC,
KE1 - supply air heater,
AT1 - automatic reset thermostat supply air heater
PV - supply air fan EC,
RT1 - manual reset thermostat supply air heater,
DTJ100 - extract air temperature and humidity
sensor,
TL - fresh air temperature sensor,
TJ - supply air temperature sensor,
TE - exhaust air temperature sensor,
EN | 23RIRS 1200-5500 H EKO 3.0 v2019.06
21.3. RIRS 1200-1900 HW EKO 3.0
1.1247.0.1.0-PS
NPE L1 CEE7/7
N
13
Main Switch
Q1
2P
NF1PE
PE
N
L
PE
L3
N
2
1
DTJ100 - extract air temperature and humidity
TJ - supply air temperature sensor,
X16.7
PE
X23
X32
X3
G - System potential AC 24 V
Y1 - Control OPEN (AC 24 V)
Y2 - Control CLOSE (AC 24 V)
X16.1
312
N
N
1615
L supply
EXT+
EXT-
L control
N
1917 18
EXT+
20
EXT-
X16.5
RT1 - manua l reset thermostat supply air heater ,
KE1 - supply air heater,
TL - fresh air t emperature sensor,
AT1 - automatic reset thermostat supply air heater
N
L supply
L control
IV - extract air fan EC,
24VAC, 3-position
M5
Y2Y1
G
ON/OFF
230V AC
M2M3
L
LNNLL
230V AC
ON/OFF
PV - supply air fan EC,
L1
42
KE2
0
C
1
1f, 230V AC
max. 1A
24VDC, 0-10VDC
Jumper
23 - 24V DC,
24 - intput, 0-10V DC,
25 - GND,
26 - 24V DC,
27 - intput, 0-10V DC,
28 - GND,
X16.7
29
PE
M4
30 31
N
L
DX Cooling
3
0
M6
Y
G
BOOST
START-NC
STOP-NO
Fan fall
1.2W max
24VDC
Fan run
1.2W max
24VDC
Transmitter 1 (24 VDC)
P
U
Jumper
FA
Transmitter 2 (24 VDC)
P
U
2
1
1A
F2
24VDC
R1
X16.3
A2
A1
14
11
87
1
P
X16.8
32
33 34
X16.2
4561 09
X16.4
11 12
23
2524
13 14
NC
X21.2
PS1
2
1
PS2
8765
2
1
HR
DTJ 100
X16.10
TA
282726
RG2, RG3 - controller ESKM1-26/176-30,
F1 - fuse 10A (size 5x20),
R - rotor motor 15W,
Q2 - circuit breaker B16,
C - capacitor.
W3
W2
U
RG1 - controller PRV-... V2.5,
FA - fire alarms input,
PS1 - supply air filter pressure relay,
PS2 - extract air filter pressure relay,
1
BR
2
R
BK
3
BU
4
YE
LOW X32.1
COM X32.4
AC.N
PUMP
B.0.10
COM
MIDL
HIGH
TIMER
COM
CHIL X33.9
COM X33.10
ALARM X33.11
COM
ANTI.F
+24
FAN
COM
A1
A1
A2
A2
A3
A3
A4
A4
HR
TA
T.s et
COM
P/U - "Transsmiter 1" supply air pressure
P/U - "Transsmiter 2" extract air fan 0-10V
pressure, CO2 transmitters,
switch,
transmitter (0-10 VDC),
X35.2
X35.1
X33.13
X33.14
X32.2
X32.3
X33.1
X33.2
X33.18
X33.12
X33.17
X33.25
X33.26
X34.1
X34.2
X34.3
X34.4
X34.5
X34.6
X34.7
X34.8
X40.1
X40.2
X40.3
X38.1
X38.2
X33.23
X33.24
RG4
X51
COM
2
31
9
10
COM
VAL+
VAL-
VAL
COM
A.0.10
EXT-
EXT+
AC.N
T.OUT
COM
TJ
T.WAT
TE
X31L
X25
X29
X24N
X2.2
X2.1
COM
1
2
34
X21.1
567
W3 W2
21
8
L (open)
L (close)
W4 W5
9
43
W4W5
RS485_2
RS485_1
ModBus RTU
2
1
N
L
X12L
X42
V1
V2X37.3
N
Remote control
U
NL
V
W
PE
NO
0-10V in
X8
X10
N
L
N
K1
X37.2
X37.1
X37.4
X33.3
X33.4
RG1
X33.5
X33.16
X33.15
X35.5
X35.4
X35.3
X33.21
X33.22
X39.1
X39.2
X33.19
X33.20 COM
X41.1
X41.2
X3
RS485_2
RS485_1
X4
P - DX cooler protection, differential pressure
2
AT2
IV
GND
10V
0-10V
D1
in
in
L2
L1PEL1
N
X35
8
9
X52
PE
K1
K1
N
L
out
PE
L2
L3
N
X33
X4
234
567
1
X37
TL
TE
X16.6
2221
TJ
10A
X21.3
9 10
21
PV
10V
GND
0-10V
D1
K1
K1
out
in
in
PE
L2
L2
L1
L1
N
X34
6
7
543
9
8
M2 - o utside air damper actuator,
M3 - extract air damper actuator
M5 - Water cooler valve actuator,
sensor,
TE - exhaust air temperature sensor,
24 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
21.4. RIRS 2500 HE EKO 3.0
L1PE
GN - Green - Žalia
BK - Black - Juoda
BN - B rown - Ruda
BU - Blue - Mėlyna
WH - White - Balta
RD - Red - Raudona
YE - Yellow - Geltona
KE1
24VDC
R1
X16.3
A2
DX Cooling
3
1
P
BOOST
Jumper
START-NC
STOP- NO
Fan fall
1.2W max
24VDC
Fan run
1.2W max
24VDC
Transmitter 1 (24 VDC)
17 - 24V DC,
18 - intput, 0-10V DC,
19 - GND,
P
U
FA
Transmitter 2 (24 VDC)
20 - 24V DC,
21 - intput, 0-10V DC,
22 - GND,
P
U
RG2, RG3 - reguliatoriai E SKM1-26/176-30.
RG4- valdiklis RHX2M.
PS1 - s kirtuminio slėgio relė (tiekiamo oro filtrų
PS2 - s kirtuminio slėgio relė (ištraukiamo oro filtrų
užter štumui).
užter štumui).
F1 - S augiklin ė WAGO 2006-1611,
F1 - S augiklis BT-5x20-...A,
R1 - Lizdas RT 78726 relei, relė RX114024,
C - r otorinio šilumokaičio var iklio kondensatorius
KE2 - automatik os spintos šildytuvas
AT3 - automat ikos spintos termostatas
A1
14
11
87
W3
X16.2
4561 09
X16.4
11 12
17
1918
13 14
X43.4
12 13
5 678
PS1
2
1
14 15
PS2
2
1
X42.4
X21.2
HR
U
DTJ 100
X16.10
TA
222120
S1 - r otorini o šilumokiačio apsi sukimų jutiklis.
RT1 - šild ytuvo avarinė ap sauga nuo perkaitimo.
P - fr eoninio a ušintuvo skirtuminio slėgi o relė
RG1 - valdiklis PRV-V2.5,
Q1 - ki rtiklis, OT40FT3 (su priedais)
Q2 - auto matinis jungiklis,
AT1 - šil dytuvo ri bojanti apsauga nuo perkaitimo.
3x400V
N
312
1.1259.0.1.0-PS
G - System potential AC 24 V
Y1 - Control OPEN (AC 24 V)
Y2 - Control CLOSE (AC 24 V)
24VAC, 3-position
M5
Y2Y1
G
L3L2
KL2
NC
L1
55
246
F1, 10A
KL1
212
PE
N
N
N/1
L/2
N/1
L/2
PE/3
Main Switch
Q1
12
PE
X32
X42.1
1234
N
L control
N
L supply
L control
7PE
Conntacts
8
PE
PE N
X23
X16.1
Spring back , ON/OFF
N(1) L(2)
230V AC
M2
N(1) L(2)L( 3)
230V AC
M3
ON/OFF
Q2
B16
642
KE2
0
C
2
GND
-
+
L2L1L3
N
6
7
8
N
9
EXT-
EXT+
89
EXT-
531
1
3
5
9 10
X21.3
L 1N
PV
KL1KL3
1
COM
L
PE
L2
X43.2
X45
X46
X42.2
X02
WH(BK)
RD
GN(BU)
YE
WH(BK)
RD
GN(BU)
YE
X42.5
10 11 12 13
(0- 10 VDC), CO2.
P/U - "Transs miter 2" ištr aukiamo oro slėgio keitiklis
PWM
RG2
0
TK
TK
X04
PWM
RG3
0
TK
TK
K1
0
C
13
14
1
2
RT1
X29.3
1211109 8 7
X22.2
8765439
1
2
3
4
LOW X32.1
COM X32.4
AC.N
PUMP
B.0.10
COM
MIDL
HIGH
TIMER
COM
CHIL X33.9
COM X33.10
ALARMX33.11
COM
ANTI.F
+24
FAN
COM
A1
A1
A2
A2
A3
A3
A4
A4
HR
TA
T.se t
COM
DTJ100 - ištr aukiamo oro temperatūr os, santykinės oro
drėgmės jutiklis (keitiklis),
PV - tiek iamo oro ventiliatorius EC
X35.2
X35.1
X33.13
X33.14
X32.2
X32.3
X33.1
X33.2
X33.18
X33.12
X33.17
X33.25
X33.26
X34.1
X34.2
X34.3
X34.4
X34.5
X34.6
X34.7
X34.8
X40.1
X40.2
X40.3
X38.1
X38.2
X33.23
X33.24
TE - i šmetamo or o jutiklis (TJK-10K),
U
V
W
PE
TJ - tiekiamo oro temperatūros jutikli s (TJK-10K),
BR
R
BK
BU
YE
W2
W6W7
W1
IV - i štraukia mo oro ventiliatorius EC
FA - priešgai srinio signalo įėjimas
P/U - " Transsmiter 1" tiekiamo oro slėgio keitiklis (0-10
VDC).
X01
Lin
A1
Lout
A2
2
X03
A1
A1
A1
2
1
N
L
N
L
RS485_2
RS485_1
R - r otorinio ši lumokaičio pavara
X42
COM
COM
VAL+
VAL-
VAL
COMX33.16
A.0.10
EXT-
EXT+
AC.N
T.OU T
COM
TJ
T.WA T
TE
4
6
X51
1
2
3
4
X21.1
567 8
21
9
43
N
L
X31L
X25
X29
X24N
X12
V1
V2X37.3
L (open)
L (close)
N
Remote control
Lin
A1
Lout
A2
3x3000W/230V
A2A2
A2
RG4
1
NL
2
3
COM
9
NO
10
0-10V in
X8
X10
X37.2
X37.1
X37.4
X33.3
X33.4
RG1
X33.5
X33.15
X35.5
X35.4
X35.3
X33.21
X33.22
X39.1
X39.2
X33.19
X33.20 COM
X41.1
X41.2
X3
X4
M2 - or o paėmimo sklendės pavar a,
M3 - i štraukia mo oro sklendės pavara,
M5 - vande ns aušintuvo vožtuvo pavara,
TL - š viežio or o temperatūros jutiklis (T JK-10K),
X29.1
K1
W3 W2 W4 W5
RS485_1
A2
135
W5 W4
ModBus RTU
12
3
4
X29.2
K1
56
0
C
1
2
A1
RS485_2
21
AT1
X22.1
IV
KL1KL3
2
3
1
0-10V
GND
COM
L
in
-
+
PE
L2L1L3
L2
N
X35
6
7
W6 W7
14
15
X43.5
X52
TE
X16.6
1615
50w
AT3
KL1
KL2
3
212
0-10V
PE
NC
N
in
PE
L1
N
X34
X33
X43.1
5
1234
10
11
X43.3
X37
TL
TJ
EN | 25RIRS 1200-5500 H EKO 3.0 v2019.06
21.5. RIRS 2500 HW EKO 3.0
1.1260.0.1.0-PS
(0-10
Fan fall
1.2W max
24VDC
Fan run
1.2W max
24VDC
P
22 - GND,
P
F1 - S augiklis BT-5x20-...A,
X16.7
23
PE
M4
24 25
N
L
DX Cooling
3
1
P
BOOST
BOOST
START-NC
STOP- NO
U
FA
Transmitter 2 (24 VDC)
20 - 24V DC,
21 - intput, 0-10V DC,
2
1
1A
F2
24VDC
R1
X16.3
A2
A1
14
11
87
W3
X16.8
26
27 28
X16.2
4561 09
4
X16.4
11 12
17222120
1918
13 14
X43.4
X43.4
12 13
5 678
PS1
2
1
14 15
PS2
2
1
X42.4
X21.2
HR
U
DTJ 100
X16.10
TA
U
S1 - r otorini o šilumokiačio apsi sukimų jutiklis.
Q1 - kirtiklis ON2RYS22776 (R/G),
Q2 - auto matinis jungiklis,
RG1 - valdiklis PRV-V2.2,
RG4 - valdiklis RHX2M,
F1, F 2 - Saugi klinė WAGO 2006-1611,
(0- 10 VDC), CO2.
T1 - pr iešužšaliminis termostatas,
TV - prie šužšaliminis jutiklis (TJP-10K),
P - fr eoninio a ušintuvo skirtuminio s lėgio relė.
1f, 230V AC
max. 1A
24VDC, 0-10VDC
0
M6
Y
G
Jumper
Transmitter 1 (24 VDC)
17 - 24V DC,
18 - intput, 0-10V DC,
19 - GND,
C - r otorinio šilumokaičio var iklio kondensatorius
F2 - S augiklis BT-5x20-...A,
R1 - Lizdas RT 78726 relei, relė RX114024,
KE2 - automatik os spintos šildytuvas
AT3 - automat ikos spintos termostatas
PS1 - s kirtuminio slėgio relė (tiekiamo oro filtrų
PS2 - s kirtuminio slėgio relė (ištraukiamo oro filtrų
užter štumui).
užter štumui).
NPE L1
X16.7
L1N
Q1
F1, 10A
KL1
212
PE
N
N
N/1
L/2
N/1
L/2 PE/3
42
X23
12
PE
X32
X42.1
123
N
L control
N
L supply
L control
13
N
N(1)
L(2)
N(1) L(2)L( 3)
M2
M3
PE
PE
G - System potential AC 24 V
Y1 - Control OPEN (AC 24 V)
Y2 - Control CLOSE (AC 24 V)
X16.1
24VAC, 3-position
M5
Y2Y1
312
G
Spring back , ON/OFF
230V AC
230V AC
ON/OFF
GN - Green - Žalia
BK - Black - Juoda
BN - B rown - Ruda
BU - Blue - Mėlyna
WH - White - Balta
RD - Red - Raudona
YE - Yellow - Ge ltona
KE2
50w
AT3
0
C
RG4
X51
1
1
BR
2
R
BK
3
BU
4
YE
LOW X32.1
COM X32.4
X35.2
AC.N
X35.1
PUMP
X33.13
B.0.10
X33.14
COM
W2
MIDL
X32.2
HIGH
X32.3
TIMER
X33.1
COM
X33.2
CHIL X33.9
COM X33.10
ALARMX33.11
X33.18
COM
X33.12
ANTI.F
+24
X33.17
X33.25
FAN
COM
X33.26
A1
X34.1
X34.2
A1
A2
X34.3
A2
X34.4
A3
X34.5
A3
X34.6
A4
X42.5
W6W7
10 11 12 13
VDC).
P/U - "Transs miter 2" išt raukiamo oro slėgio keitiklis
IV - i štraukia mo oro ventiliatorius EC
FA - priešgai srinio signalo įėjimas
P/U - " Transsmiter 1" tiekiamo oro slėgio keitiklis
X34.7
A4
X34.8
X40.1
HR
X40.2
X40.3
X38.1
TA
X38.2
T.se t
X33.23
COM
W1
X33.24
TL - š viežio or o temperatūros jutiklis (T JK-10K),
TJ - tiekiamo oro temperatūros jutikli s (TJK-10K),
TE - i šmetamo or o jutiklis (TJK-10K),
drėgmės jutiklis (keitiklis),
DTJ100 - ištr aukiamo oro temperatūr os, santykinės oro
Hereby conrms that the following products - Air handling units:
RIRS H EKO 3.0*
(where by “*” indicates possible unit installation type and modication)
Provided it was delivered and installed in the facility in accordance with the included installation instructions, comply
with all applicable requirements in the following directives:
The following harmonized standards are applied in applicable parts:
LST EN ISO 12100:2011 - Safety of machinery - General principles for design - Risk assessment and risk reduction.
LST EN 60204-1:2006 - Safety of machinery - Electrical equipment of machines - Part 1: General requirements.
LST EN 60335-1:2012 - Household and similar electrical appliances. Safety. Part 1: General requirements.
LST EN 60529:1999 - Degrees of protection provided by enclosures (IP code).
LST EN 61000-6-2:2005 - Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments.
LST EN 61000-6-3:2007 - Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission standard for residential, commercial and
light-industrial environments.
Should any alterations be made in the products, this declaration will no longer apply.
Notied body: VšĮ Technikos priežiūros tarnyba, Naugarduko g. 41, LT – 03227 Vilnius, Lithuania, identication number 1399.
Quality: Salda UAB activities are in line with the international quality management system standard ISO 9001:2015.
Date 2019-02-01
Giedrius Taujenis
Director product development
EN | 35RIRS 1200-5500 H EKO 3.0 v2019.06
25. WARRANTY
1. All equipment manufactured in our factory is checked in operating conditions and tested befor delivery. Test protocol is supplied together with
the unit. The equipment is shipped in good working order and condition to the direct client. The unit is warrantied for the period of two years from
the invoice date.
2. If equipment is found to have been damaged during transportation, a claim should be made against carrier, as we assume no responsibility for
such damage.
3. This warranty does not apply:
3.1. when transportation, storage, installation and maintenance instructions of the unit are violated;
3.2. when the equipment is improperly maintained, mounted - inadequate maintenance;
3.3. when the equipment without our knowledge and permission has been upgraded or unskilled repairs were made;
3.4. when the unit was used not for its original purpose.
3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where AHU is manufactured without a
control system and the control system will be installed by the client or third parties. The manufacturer’s warranty does not cover devices that
will be damaged by installing the control system.
4. This warranty does not apply at these malfunction cases:
4.1. mechanical damage;
4.2. damage caused by entering outside objects, materials, liquids;
4.3. damage caused by natural disaster, accident (voltage change in the electricity network, lightning, etc..).
5. The company assumes no liability for its products either directly or indirectly damage, if the damage is caused by failure to comply with installation and mounting regulations, deliberate or careless users or third-party behavior.
These conditions are readily discernable when the equipment is returned to our factory for inspection.
If the direct client determines that equipment is found to be faulty, or a breakdown occurred, he should inform the manufacturer within ve working
days and deliver the equipment to manufacturer. Delivery costs should be covered by customer.
Manufacturer reserves the right to change this technical passport any time without prior notice, if some typographic
errors or inaccurate information is found, as well as after improving the apps and/or the devices. Such changes will be
included in the new issues of the technical passport. All illustrations are just for information and thus may dier from the
original device.
25.1. LIMITED WARRANTY COUPON
Warranty term
24 months*
I received complete package and technical manual of the product ready for usage. I have read warranty terms and conditions and agree with them:
Dear User, we appreciate your choice and do hereby guarantee that all ventilation equipment manufactured by our Company is inspected and
thoroughly tested. An operational and high-quality product is sold to the direct buyer and shipped from the territory of the factory. It is provided with
a 24-month warranty since invoice issue date.
Your opinion is important to us, thus we always look forward to hearing your comments, feedback, or suggestions regarding technical and operational characteristics of the Products.
In order to avoid any misunderstandings, please read the instructions for installation and operation of the product as well as other technical docu-
ments of the product carefully. The number of the Limited Warranty Coupon and serial number of the product specied on the silver identication
sticker attached to the housing must match.
The Limited Warranty Coupon shall be valid provided that the seller’s stamps and records are clear. It is prohibited to change, delete, or rewrite
the data specied on it in any manner – such a coupon shall be invalid.
With this Limited Warranty Coupon the manufacturer conrms one’s obligations to implement the imperative requirements established by eective
laws on protection of consumer rights in the event of identication of any defects of the products.
The manufacturer reserves the right to refuse provision of free warranty servicing in cases when the warranty conditions listed below are disregarded.
36 | ENRIRS 1200-5500 H EKO 3.0 v2019.06
| 37RIRS 1200-5500 H EKO 3.0 v2019.06
38 | RIRS 1200-5500 H EKO 3.0 v2019.06
| 39RIRS 1200-5500 H EKO 3.0 v2019.06
PRODUCT MAINTENANCE TABLE
Product name*
LOT number*
InstalationIntervalDatum
Fan cleaningOnce a year**
Heat exchanger cleaning Once a year**
Filter replacement
* - Look at the product label.
** - At least.
NOTE. The purchaser is required to ll in the “Product maintenance table”.
Every 3-4
months**
Ragainės g. 100
Šiauliai LT-78109, LITHUANIA
MAN000133
+370 41 540 415
office@salda.lt
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.