7. INSTRUCTION FOR DEVICES WITH MCB/MINIMCB BOARDS 7
7.1. MAIN WINDOW 7
7.2. SETPOINT () 8
7.3. MENU 8
7.3.1. Status 9
7.3.2. Night cooling 10
7.3.3. Boost 10
7.3.4. Mode 11
7.3.4.1. Building protection 11
7.3.4.2. Economy 11
7.3.4.3. Comfort 11
7.3.5. Filters 12
7.3.6. Heating season 12
7.3.7. Date & time 12
7.3.8. Weekly schedule 13
7.3.9. Holiday schedule 13
7.3.10. Alarms 13
7.3.13. Settings 14
7.3.14. Adjuster 14
7.3.14.1. Airflow 14
7.3.11. Alarms history 14
7.3.12. Other 14
7.3.14.1.1. Supply 15
7.3.14.1.2. Extract 15
7.3.14.1.3. Other 15
7.3.14.2. PID 15
7.3.14.2.1. Heater 16
7.3.14.2.2. Preheater 16
7.3.14.2.3. Heat exchanger 16
7.3.14.2.4. Fans pressure 16
7.3.14.2.5. Hydraulic cooler 17
7.3.14.2.6. Fans by temperature 17
7.3.14.2.7. Recirculation by set point 17
7.3.14.3. Manual control 17
7.3.14.3.1. Block ventilation control 17
7.3.14.3.2. Heater 18
7.3.14.3.3. Preheater 18
7.3.14.3.4. Fans 18
7.3.14.3.5. Hydraulic cooler 19
7.3.14.3.6. Recirculation damper 19
7.3.14.3.7. Supply / Extract damper 20
7.3.14.3.8. Bypass 20
7.3.14.3.9. Rotor 21
7.3.14.3.10. DX cooler 21
7.3.14.3.11. Fire damper 22
7.3.14.3.12. Other 22
7.3.14.4. Status 23
7.3.14.4.1. Temperature sensors 23
7.3.14.4.2. Fans 24
7.3.14.4.3. Hydraulic cooler 24
7.3.14.4.4. Rotor 24
7.3.14.4.5. Fire damper 24
7.3.14.4.6. Status indication 25
7.3.14.4.7. Other 25
7.3.14.4.8. Version 25
7.3.14.4.9. Heater 26
2
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
FlexMCB
7.3.14.4.10. Preheater 26
7.3.14.4.11. Bypass damper 26
7.3.14.4.12. Recirculation damper 27
7.3.14.4.13. Supply / Extract damper 27
7.3.14.4.14. DX cooler 27
7.3.14.4.15. Sensors 27
7.3.14.5. Save settings 28
7.3.14.6. Logout 28
7.3.15. Service 28
7.3.15.1. Main 29
7.3.15.1.1. Block ventilation control 29
7.3.15.1.2. Air temperature control 29
7.3.15.1.3. Air temperature protection 29
7.3.15.1.4. System mode switch 30
7.3.15.1.5. Fans speed switch 30
7.3.15.1.6. Air filters protection 30
7.3.15.1.7. Fire protection 30
7.3.15.1.8. Controller cabinet heating 31
7.3.15.1.9. CO₂ reduction function 31
7.3.15.1.10. Cooking hood 31
7.3.15.1.11. Calibrations 31
7.3.15.1.11.1. Bypass damper 31
7.3.15.1.11.2. Recirculation damper 31
7.3.15.1.11.3. Pressure 31
7.3.15.2.1. Fans speed control 32
7.3.15.2.2. Fans voltage 32
7.3.15.2.3. Fans protection 32
7.3.15.2. Fans 32
7.3.15.3. Dampers 33
7.3.15.3.1. Supply / Extract damper 33
7.3.15.3.2. Recirculation damper 33
7.3.15.3.3. Fire damper 33
7.3.15.4. Heat exchanger 34
7.3.15.4.1. Type 34
7.3.15.4.2. Frost protection 34
7.3.15.4.2.1. Activation 34
7.3.15.4.2.2. Deactivation 35
7.3.15.4.2.3. Protections 35
7.3.15.5. Heaters 35
7.3.15.5.1. Heater 36
7.3.15.5.2. Preheater 36
7.3.15.5.3. Electrical heaters cooling 36
7.3.15.5.4. Hydraulic heaters protection 36
7.3.15.5.5. Control position 37
7.3.15.6. Coolers 37
7.3.15.6.1. Coolers 37
7.3.15.6.2. Coolers 37
7.3.15.7. Digital inputs 38
7.3.15.7.1. External control 38
7.3.15.7.2. Fans protection 38
7.3.15.7.3. Heater protection 39
7.3.15.7.4. Cooler protection 39
7.3.15.7.5. Filters pressure relay 39
7.3.15.7.6. Fire damper 39
7.3.15.7.7. Heat exchanger 39
7.3.15.7.8. Preheater protection 40
7.3.15.8. Sensors 40
7.3.15.8.1. 0-10VDC sensors 40
7.3.15.8.1.1. Air quality sensor 1 40
7.3.15.8.1.2. Air quality sensor 2 41
7.3.15.8.2. Temperature sensors 41
7.3.15.8.2.1. Supply air 41
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
3
FlexMCB
7.3.15.8.2.2. Extract air 42
7.3.15.8.2.3. Exhaust air 42
7.3.15.8.2.4. Outdoor air 42
7.3.15.8.2.5. Hydraulic heater water 42
7.3.15.8.2.6. Hydraulic preheater water 43
7.3.15.8.2.7. Hydraulic cooler water 43
7.3.15.8.2.8. Controller cabinet temperature 43
7.3.15.9. Communication 43
7.3.15.9.1. Internal port modbus 44
7.3.15.9.2. BMS port modbus 44
7.3.15.10. Passwords 44
7.3.15.11. Restore defaults 45
7.3.15.12. Save settings 45
7.3.15.13. Logout 45
7.3.16. About 45
8. RECYCLING 45
4
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
1. DESCRIPTION
The “FLEX MCB” control panel is used for control of ventilation units with MCB, MiniMCB control boards.
• Program the unit operation modes for one week.
• Set the temperature for supply or extracted air flow.
• Set fan motor rotation speed.
• Indication for the plate heat exchanger’s antifreeze protection.
• Fault signal indication
• Indication of the temperatures, humidity and pressure for ambient, outdoors room, exhaust and supply air.
• Automatic recognition of the controlled unit.
2. TECHNICAL DATA
PARAMETERUNITSVALUE
MountingSurface
Voltage[ VDC ]15-30
Data transmitionRS 485
Cable length[ m ]13
Dimensions (WxHxD)[ mm ]86x86x16
Safety classIP20
Ambient temperature[
Ambient humidity[ % ]<90
o
C ]10-30(50*)
FlexMCB
3. FUNCTIONALITY OF BUTTONS
NOLABEL
1“Fast Button” – used for control of the selected function.
2
3“OK” – used for confrmation of the selected line or of the set value.
4
„> “– used for increasing the setting values or for moving a line up.
„> “– used for decreasing the setting values or for moving a line
down.
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
5
FlexMCB
4. DIMENSIONS
5. MOUNTING
Surface mounting, opening is prepared in the wall for the connection cable D13 and two holes for installation of the box bottom.
Attach the box bottom cover to the wall leaving approx. 3 cm of cable from the surface. Put the battery to the socket at the
board, polarity “+” outwards, connect the plug to the board and close the box cover (see the drawing) by attaching the left side
(1–2) and then gently press the right side (3). Connect the other cable plug to the socket of the recuperator.
6
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
6. CONTENT
FlexMCB
ITEMQUANTITY, PSC
Control panel FLEX MCB1
Battery 2032 type1
Communication cable RJ45 to He1402(4 strands ) 13 meters1
7. INSTRUCTION FOR DEVICES WITH MCB/MINIMCB BOARDS
7.1. Main window
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
7
FlexMCB
NO.LABELDESCRIPTION
Options:
• Standby
1System mode
Set temperature[ °C ]
Menu
2Extract air[ °C ]
3Outsdoor air[ °C ]
4Supply air[ °C ]
5Exhaust air[ °C ]
6Standby blocking time left this dayRange: [ 0 .. 500 minutes ]
7Next event inRange: [ 0 .. 24 hours ]
7.2. Setpoint ()
Main window » Setpoint
• Building protection
• Economy
• Comfort
7.3. Menu
Main window » Menu
NO.LABEL
1Status
2Night cooling
3Boost
4Mode
5Filters
6Heating season
7Date & time
8Weekly schedule
9Holiday schedule
10Alarms
8
SALDA UAB reserves the right to perform changes without prior notice.
www.salda.lt
11Alarms history
12Other
13Settings
14Adjuster
15Service
16About
7.3.1. Status
Main window » Menu
FlexMCB
NO.LABELDESCRIPTION
1Supply air[ °C ]
2Exhaust air[ °C ]
3Extract air[ °C ]
4Outdoor air[ °C ]
Options:
• Standby
5System mode
6Boost
7Supply fan speed RPMRange: [ 0 .. 5000 RPM ]
8Extract fan speed RPMRange: [ 0 .. 5000 RPM ]
9Required supply temperature[ °C ]
10Supply air RH[ % ]
11Supply air CO₂Range: [ 0 .. 2000 PPM ]
12Extract air RHRange: [ 0 .. 100 % ]
13Extract air CO₂Range: [ 0 .. 2000 PPM ]
14Supply air ow di pressureRange: [ 0 .. 2000 PA ]
15Extract air pressureRange: [ 0 .. 2000 PA ]
16Software version
17Conguration version
18Hydraulic heater water[ °C ]
19Hydraulic preheater water[ °C ]
20Hydraulic cooler water[ °C ]
21Controller cabinet[ °C ]
• Building protection
• Economy
• Comfort
Options:
• Active
• Inactive
SALDA UAB reserves the right to perform changes without prior notice.