SAJ Suntrio Plus 17K, Suntrio Plus 33K, Suntrio Plus 40K, Suntrio Plus 60K, Suntrio Plus 50K User Manual

...
User Manual
SAJ Solar Inverter
Suntrio Plus Series
www.saj-electric.com
Suntrio Plus Series
Preface
Thank you for choosing a SAJ solar inverter. We are pleased to provide you with first-class products and exceptional service.
This manual includes information for installation, operation, maintenance, trouble shooting and safety. Please follow the instructions of this manual so that we can ensure delivery of our professional guidance and wholehearted service.
Customer-orientation is forever our commitment. We hope this document proves to be of great assistance in your journey for a cleaner and greener world.
Please check for the latest version at www.saj-electric.com
Guangzhou Sanjing Electric Co., Ltd.
Building e-Energy management solution provider
Suntrio Plus Series
Content
Preface..................................................................................................... - 1 -
Content.................................................................................................... - 2 -
Chapter 1 Safety Precautions................................................................- 4 -
1.1 Scope of Application..................................................................................- 4 -
1.2 Safety Instructions......................................................................................- 4 -
1.3 Target Group...............................................................................................- 5 -
Chapter 2 Preparation...........................................................................- 6 -
2.1 Safety Instructions......................................................................................- 6 -
2.2 Explanations of Symbols........................................................................... - 8 -
Chapter 3 Product Information...........................................................- 10 -
3.1 Application Scope of Products................................................................ - 10 -
3.2 Specification for Product Model..............................................................- 11 -
3.3 Overview of products...............................................................................- 11 -
3.4 Datasheet.................................................................................................. - 13 -
Chapter 4 Instructions for installation................................................ - 17 -
4.1 Safety Instructions....................................................................................- 17 -
4.2 Pre-installation Check..............................................................................- 17 -
4.3 The Determination of the Installation Method and Position.................. - 18 -
4.4 Mounting Procedure.................................................................................- 20 -
Chapter 5 Electrical Connection.........................................................- 24 -
5.1 Safety Instruction for Hot-line Job..........................................................- 24 -
5.2 Specifications for Electrical Interface.....................................................- 25 -
5.3 AC Side Connection.................................................................................- 25 -
5.4 DC Side Connection................................................................................ - 27 -
5.5 Communication Connection.................................................................... - 30 -
Suntrio Plus Series
Chapter 6 Debugging Instructions......................................................- 32 -
6.1 Introduction of Human-computer Interface............................................ - 32 -
6.2 First Run Setup.........................................................................................- 33 -
6.3 Monitoring Operation.............................................................................. - 42 -
Chapter 7 Fault Code and Troubleshooting........................................- 43 -
Chapter 8 Recycling and Disposal..................................................... - 46 -
Chapter 9 Guarantee Service..............................................................- 47 -
Chapter 10 Contact SAJ..................................................................... - 48 -
SAJ Warranty Policy.......................................................................... - 49 -
Warranty Card........................................................................................- 53 -
Suntrio Plus Series
Chapter 1 Safety Precautions
1.1 Scope of Application
This User Manual describes instructions and detailed procedures for installing,
operating, maintaining, and troubleshooting of the following SAJ grid-tied
inverters:
Suntrio Plus 12K; Suntrio Plus 15K; Suntrio Plus 17K; Suntrio Plus 20K;
Suntrio Plus 25K; Suntrio Plus 33K; Suntrio Plus 40K; Suntrio Plus 50K
Suntrio Plus 60K
Please keep this manual all time available in case of emergency.
1.2 Safety Instructions
DANGER
· DANGER indicates a hazardous situation which, if not avoided, will result in death or
serious injury.
WARNING
· WARNING indicates a hazardous situation which, if not avoided, can result in death or serious injury or moderate injury.
CAUTION
· CAUTION indicates a hazardous condition which, if not avoided, can result in minor or
moderate injury.
NOTICE
· NOTICE indicates a situation that can result in potential damage, if not avoided.
Suntrio Plus Series
1.3 Target Group
Only qualified electricians who have read and fully understood all safety
regulations contained in this manual can install, maintain and repair the inverter.
Operators must be aware of the high-voltage device.
Suntrio Plus Series
Chapter 2 Preparation
2.1 Safety Instructions
DANGER
· Dangerous due to electrical shock and high voltage.
· Do not touch the operating component of the inverter, or it might result in burning or death.
· To prevent risk of electric shock during installation and maintenance, please make sure that all AC and DC terminals are plugged out.
· Do not touch the surface of the inverter while the housing is wet, or it might lead to electrical shock.
· Do not stay close to the inverter while there are severe weather conditions including storm, lighting, etc.
· Before opening the housing, the SAJ inverter must be disconnected from the grid and PV generator; you must wait for at least five minutes to let the energy storage capacitors fully be discharged after disconnecting from power source.
WARNING
·The installation,service, recycling and disposal of the inverters must be performed by qualified personnel only in compliance with national and local standards and regulations.
·Any unauthorized actions including modification of product functionality of any form may cause lethal hazard to the operator, third parties, the units or their property. SAJ is not responsible for the loss and these warranty claims.
·The SAJ inverter must only be operated with PV generator. Do not connect any other source of energy to the SAJ inverter.
·Be sure that the PV generator and inverter are well grounded in order to protect safety of people’s life and property.
CAUTION
·The PV inverter will become hot during operation. Please do not touch the heat sink or peripheral surface during or shortly after operation.
·Risk of damage due to improper modifications.
Suntrio Plus Series
NOTICE
·Public utility only
·The PV inverter is designed to feed AC power directly to the public utility power grid; do not connect AC output of the inverter to any private AC equipment.
Suntrio Plus Series
2.2 Explanations of Symbols
Symbol Description
Dangerous electrical voltage
This device is directly connected to public grid, thus all work to the inverter shall only be carried out by qualified personnel.
DANGER to life due to high electrical voltage!
There might be residual currents in inverter because of large capacitors. Wait for 5 MINUTES before you remove the front lid.
NOTICE, danger!
This is directly connected with electricity generators and public grid.
Danger of hot surface
The components inside the inverter will release a lot of heat during operation. Do not touch metal plate housing during operating.
An error has occurred
Please go to Chapter 9 “Troubleshooting” to remedy the error.
This device SHALL NOT be disposed of as residential waste
Please go to Chapter 8 “Recycling and Disposal” for proper treatments.
Without Transformer
This inverter does not use transformer for the isolation function.
Security Certificate
The inverter complies with
European product safety instructions.
CE Mark
Equipment with the CE mark fulfills the basic requirements of the Guideline Governing Low-Voltage and Electro-magnetic Compatibility.
SAA Mark
The inverter complies with the requirement of Equipment and Product Safety Act in Australia.
CQC Mark
The inverter complies with the safety instructions from China's Quality Center.
Suntrio Plus Series
No unauthorized operations or modifications
Any unauthorized operations or modifications are strictly forbidden, if any defect or damage (device/person) occurs, SAJ shall not take any responsibility for it.
Suntrio Plus Series
-10-
Chapter 3 Product Information
3.1 Application Scope of Products
Suntrio Plus series products are grid-tied three phase inverters without
transformers, and the inverters are important components of grid-tied solar power
systems.
The Suntrio Plus inverters change the DC generated by solar panels into AC which
is in accordance with the requirements of public grid, and send the AC into the grid,
Table 3.1 shows the structural diagram of the typical application system of Suntrio
Plus inverters.
Name Description Remarks
A Solar panels
Monocrystalline or polycrystalline silicon, and thin-film PV modules with II protection and need no ground connection
B Inverters Suntrio Plus 12K/15K/17K//20K/25K/33K/40K/50K/60K
C
Metering
equipment
Standard metering tool for measuring the output electric power of inverters
D Power grid
TTTN-CTN-STN-C-S
Table 3.1 Systematic Configuration Diagram
Suntrio Plus Series
-11-
3.2 Specification for Product Model
Suntrio Plus XK
1
Suntrio Plus represents for product name.
XK represents rated power XkW of inverter, for example 12K means 12kW.
3.3 Overview of products
Figure 3.2 Overview of Suntrio Plus 12K/15K/17K/20K
Figure 3.3 Overview of Suntrio Plus 25K/33K
Suntrio Plus Series
-12-
Figure 3.4 Overview of Suntrio Plus 40K/50K/60K
Suntrio Plus Series
-13-
3.4 Datasheet
Sunttrio Plus 12K/15K/17K/20K
Type
Suntrio Plus
12K
Suntrio Plus
15K
Suntrio Plus
17K
Suntrio Plus
20K
Input (DC)
Max. DC Power [W]
14520 18150 20570 24200
Max. DC Voltage [V]
1000
MPPT Voltage Range [V]
180-900
Nominal DC Voltage [V]
600
Start Voltage[V]
200
Min. DC Voltage[V]
180
Max. DC Input Current PV1 / PV2 [A]
22/11 22/22 22/22 22/22
Number of MPPT 2
Number of DC Connection Sets per MPPT
2/1 2/2 2/2 2/2
DC Switch Integrated
Output (AC)
Rated AC Power [W] (@230V,50Hz)
12000 15000 17000 20000
Max. AC Power [VA]
13200 16500 18700 22000
Rated AC Current[A]
17.4 21.7 24.6 29.0
Max. AC Current [A]
20.0 25.0 28.3 33.0
Nominal AC voltage/ range 3/N/PE, 220/380V,230/400V,240/415V;180V-280V/312V-485V
Grid frequency/ range 50Hz,60Hz /44Hz-55Hz,54Hz-65Hz
Power factor,adjustable 0.8 leading~0.8lagging
Total Harmonic Distortion (THDi)
< 3% (at nominal power)
Feed-in Grid
3L+N+PE
Efficiency
Max. Efficiency
98.3% 98.4% 98.5% 98.5%
Euro Efficiency (at 600Vdc)
98.0% 98.1% 98.2% 98.2%
MPPT Accuracy >99.5%
Protection
Internal Over-voltage Protection
Integrated
DC Insulation Monitoring Integrated
DCI Monitoring Integrated
GFCI Monitoring Integrated
Grid Monitoring Integrated
AC Short Circuit Current Protection
Integrated
Thermal Protection Integrated
Suntrio Plus Series
-14-
AC Surge Protection
Integrated),Ⅱ(Optional
Low Voltage Ride Through Integrated
String Current Monitoring Integrated
Anti-PID Module Optional
DC Fuse Optional
DC Surge Protection
Optional
Anti-island protection monitoring
AFD
Interface
DC Connection MC4/H4
AC Connection Terminal Block
LCD Display
3.5 inch Graphic LCD Display
Display Language English
Communication Port 2*RS485+1*RS232
Communication Mode Wi-Fi/GPRS/Ethernet (Optional)
General Data
Topology Transformerless
Consumption at Night [W] <0.6
Consumption at Standby [W] <10
Operating Temperature Range -25°C to +60°C(45°C to 60°C with derating)
Cooling Method
Intelligent Fan
Ambient Humidity 0 to 100% Non-condensing
Altitude 3000m (>2000m power derating)
Noise [dBA]
<35
Ingress Protection IP65 (Indoor & Outdoor Installation)
Mounting Rear Panel
Dimensions (H*W*D) [mm]
640*450*232
NetWeight[kg]
29 33
Standard Warranty [Year] 5 (standard)/10/15/20/25 (Optional)
Certificates
IEC62109-1/2, IEC61000-6-2/3, IEC61683, IEC60068-2, IEC62116, IEC61727, PEA/MEA, NRS 097-2-1, UTE-C-15-712-1, VDE0126-1-1/A1, VDE-AR-N 4105, AS4777.2, AS4777.3, C-TICK, CQC NB/T 32004, G83-2,NBR 16149, NBR 16150,TF 3.2.1
Suntrio Plus Series
-15-
Sunttrio Plus 25K/33K/40K/50K/60K
Type
Suntrio Plus
25K
Suntrio Plus
33K
Suntrio Plus
40K
Suntrio Plus
50K
Suntrio Plus
60K
Input (DC)
Max. DC Power [W]
30300 36300 48400 60500 72000
Max. DC Voltage [V]
1000
MPPT Voltage Range [V]
180-900 280-900
Nominal DC Voltage [V]
600
Start Voltage[V]
200 300
Min. DC Voltage[V]
180 250
Max. DC Input Current PV1 / PV2 [A]
22/22/22 40/30/30 40/40/40
Number of MPPT 3
Number of DC Connection Sets per MPPT
2/2/2 4/3/3 4/4/4
DC Switch Integrated
Output (AC)
Rated AC Power [W] (@230V,50Hz)
25000 30000 40000 50000 60000
Max. AC Power [VA]
27500 33000 44000 55000 60000
Rated AC Current[A]
36.2 43.5 58.0 72.5 87.0
Max. AC Current [A]
42.0 50.0 65.0 80.0 90.0
Nominal AC voltage/ range 3/N/PE, 220/380V,230/400V,240/415V;180V-280V/312V-485V
Grid frequency/ range 50Hz,60Hz /44Hz-55Hz,54Hz-65Hz
Power factor,adjustable 0.8 leading~0.8lagging
Total Harmonic Distortion (THDi)
< 3% (at nominal power)
Feed-in Grid
3L+N+PE
Efficiency
Max. Efficiency
98.6% 98.8% 98.8% 98.8% 98.9%
Euro Efficiency (at 600Vdc)
98.4% 98.5% 98.5% 98.5% 98.6%
MPPT Accuracy >99.5%
Protection
Internal Over-voltage Protection
Integrated
DC Insulation Monitoring Integrated
DCI Monitoring Integrated
GFCI Monitoring Integrated
Grid Monitoring Integrated
AC Short Circuit Current Protection
Integrated
Thermal Protection Integrated
AC Surge Protection
Integrated
Low Voltage Ride Through Integrated
Suntrio Plus Series
-16-
String Current Monitoring Integrated
Anti-PID Module Optional
DC Fuse Optional
DC Surge Protection
Integrated
Anti-island protection monitoring
AFD
Interface
DC Connection MC4/H4
AC Connection Terminal Block
LCD Display
3.5 inch Graphic LCD Display
Display Language English
Communication Port 2*RS485+1*RS232
Communication Mode Wi-Fi/GPRS/Ethernet (Optional)
General Data
Topology Transformerless
Consumption at Night [W] <0.6
Consumption at Standby [W] <10
Operating Temperature Range -25°C to +60°C(45°C to 60°C with derating)
Cooling Method
Intelligent Fan
Ambient Humidity 0 to 100% Non-condensing
Altitude 3000m (>2000m power derating)
Noise [dBA]
<35
Ingress Protection IP65 (Indoor & Outdoor Installation)
Mounting Rear Panel
Dimensions (H*W*D) [mm]
700*530*260 800*550*280
NetWeight[kg]
48 68
Standard Warranty [Year] 5 (standard)/10/15/20/25 (Optional)
Certificates
IEC62109-1/2, IEC61000-6-2/3, IEC61683, IEC60068-2, IEC62116, IEC61727, PEA/MEA, NRS 097-2-1, UTE-C-15-712-1, VDE0126-1-1/A1, VDE-AR-N 4105, AS4777.2, AS4777.3, C-TICK, CQC NB/T 32004, G83-2,NBR 16149, NBR 16150,TF 3.2.1
Suntrio Plus Series
-17-
Chapter 4 Instructions for installation
4.1 Safety Instructions
DANGER
· Dangerous to life due to potential fire or electricity shock.
· Do not install the inverter near any inflammable or explosive items.
· This inverter will be directly connected with HIGH VOLTAGE power generation device; the installation must be performed by qualified personnel only in compliance with national and local standards and regulations.
NOTICE
· This equipment is suitable for the pollution degree II.
· Inappropriate or unharmonized installation environment may jeopardize the life span of the inverter.
· Installation directly exposed under intensive sunlight is not recommended.
· The installation site must have good ventilation condition.
4.2 Pre-installation C hec
k
4.2.1 Check the Package
Although SAJ’s inverters have surpassed stringent testing and are checked before
they leave the factory, it is possible that the inverters may suffer damages during
transportation. Please check the package for any obvious signs of damage and if
such evidence is present, do not open the package and contact your dealer as soon
as possible.
4.2.2 Check the Assembly Parts
Please refer to the Packing List inside the package container.
Suntrio Plus Series
-18-
4.3 The Determination of the Installation Method and Position
4.3.1 Mounting Method
Please mount the inverter correctly as shown in Figure4.1 below.
Figure 4.1 Mounting Method
The equipment employs natural convection cooling, and it can be installed
indoor or outdoor.
Please install the equipment under the guidance of Figure4.1. Vertical installation on floor level is recommended. Mount vertically or tilted backwards by max. 15°. Never install the inverter tilted forward, sideways, horizontally or upside down.
Install the inverter at eye level for convenience when checking the LCD display
and possible maintenance activities.
When mounting the inverter, please consider that disassembly for service work
may be required.
4.3.2 Installation Position
Do not expose the inverter to direct solar irradiation as this could cause power derating due to overheating.The ambient temperature should be between -25°C
+60°C
-13° F
140° F)to ensure optimum operation.Choose locations with
sufficient air exchange. Ensure additional ventilation,if necessary.
To make sure the installation spot is suitably ventilated, if multiple SAJ grid-tied solar inverters are installed in the same area, the following safety clearance in Figure4.2 shall be followed for appropriate ventilation conditions.
Suntrio Plus Series
-19-
30CM
50CM50CM30CM
30CM
50cm
80cm
50cm
50cm
50cm
80cm 80cm
80cm 80cm
30cm
30cm
50cm
50cm
50cm
50cm
50cm
50cm
Figure 4.2 Minimum Clearance
Suntrio Plus Series
-20-
4.4 Mounting Procedure
4.4.1 Mark the Positions of the Drill Holes of the Rear Panel
The position of the drill holes can be determined by using rear panel.
508.5
348
120
400
457
Figure 4.3 Dimensions of Rear Panel Suntrio Plus 12K/15K/17K/20K
538
200.4
279.6
498
Figure 4.4 Dimensions of Rear Panel Suntrio Plus 25K/33K
Suntrio Plus Series
-21-
558
324
120
388
8
261
Figure 4.5 Dimensions of Rear Panel Suntrio Plus 40K/50K/60K
4.4.2 Drill Holes and Place the Expansion Tubes
According to the guides, drill 3 holes in the wall as shown in Figure 4.6、4.7、4.8
(in conformity with position marked in the above mentioned figure), and then
place expansion tubes in the holes using a rubber mallet.
Figure 4.6 Drill Holes Suntrio Plus 12K/15K/17K/20K
Suntrio Plus Series
-22-
Figure 4.7 Drill Holes Suntrio Plus 25K/33K
Figure 4.8 Drill Holes Suntrio Plus 40K/50K/60K
Suntrio Plus Series
-23-
4.4.3 Mount the Screws and the Rear Panel
The panels should be mounted in the mounting position by screws as shown in
Figure 4.9.
Figure 4.9 Mount the Rear Panel
4.4.4 Mount the Inverter
Carefully mount the inverter to the rear panel. Make sure that the rear part of the
equipment is closely mounted to the rear panel.
Figure 4.10 Mount the Inverter
Suntrio Plus Series
-24-
Chapter 5 Electrical Connection
5.1 Safety I nstruction for Hot-line Job
Electrical connection must only be operated on by professional technicians. Please
keep in mind that the inverter is a bi-power supply equipment. Before connection,
necessary protective equipment must be employed by technicians including
insulating gloves, insulating shoes and safety helmet.
DANGER
· Dangerous to life due to potential fire or electricity shock.
· When power-on, the equipment should be in conformity with national rules and regulations.
· The direct connection between the converter and high voltage power systems must be operated by qualified technicians in accordance with local and national power grid standards and regulations.
WARNING
·W
hen the photovoltaic array is exposed to light, it supplies a d.c voltage to the inverter.
NOTICE
·Electrical connection should be in conformity with proper stipulations, such as
stipulations for cross-sectional area of conductors, fuse and ground protection.
·The overvoltage category on DC input port is II,and that on AC output port is III.
Suntrio Plus Series
-25-
5.2 Specifications for Electrical Interface
Figure 5.1 Electrical Interface
Table 5.1 Specifications for Interface
Code Name
A DC Input
B RS232/Wi-Fi Port
C Decompression valves
D AC output
E RS485 Port
F Ground Connecting port
GDCSwitch
5.3 AC Side Connection
Type
Recommended copper cable cross section area(mm²)
external diametermm
Suntrio Plus 12K
4×6+1×4 15.6
Suntrio Plus 15K/17K/20K
4×10+1×6 18.1
Suntrio Plus 25K/33K
4×16+1×10 20.8
Suntrio Plus 40K/50K/60K
4×35+1×16 27.1
Table 5.2 Recommended Specifications of AC Cables
Suntrio Plus Series
-26-
5.3.1 Open the lid of installion area.
Figure 5.2 open cover
There are some optional functons can be added into the inverter,such as AC surge
protection(Class 2),DC suege protection,Anti-PID,and DC fuses. Them are
installed in the inverters before they leave the factory.
5.3.2 Feed AC cable t hrough the AC cable hole, and connect the cable to terminals as the marks L1,L2,L3,N,PE shows.
Figure 5.3 Connect the Cables
Suntrio Plus Series
-27-
5.3.3 Secure all parts of the AC waterproof connector tightly.
Figure 5.4 Screw the Connector
5.3.4 Cover the lid and tighten the screws
Figure 5.5 Cover the lid
5.4 DC Side Connection
Cross-sectional Area of Cablesmm²
Outside Diameter of the
Cablesmm
Scope Recommended Value
4.0-6.0 4.0 4.2~5.3
Table5.3 Recommended Specifications of DC Cables
Suntrio Plus Series
-28-
DC connector is made up of the positive connector and the cathode connector
1. Insulated Enclosure 2. Lock Screw 3. Positive Connector
Figure 5.6 Positive Connector
1. Insulated Enclosure 2. Lock Screw 3. Cathode Connector
Figure 5.7 Cathode Connector
NOTICE
·Please place the connector separately after unpacking in order to avoid confusion for connection of cables.
·Please connect the positive connector to the positive side of the solar panels, and connect the cathode connector to the cathode side of the solar side. Be sure to connect them in right position.
Connecting Procedures:
(1)Tighten the lock screws on positive and cathode connector.
(2)Use specified strip tool to strip the insulated enclosure of the positive and
cathode cables to the appropriate length.
1.Positive Cable 2. Cathode Cable
Figure 5.8 Connecting Cables
Suntrio Plus Series
-29-
(3)
Feed the positive and cathode cables into corresponding lock screws.
(4)
Put the metal positive and cathode terminals into positive cable and cathode
cable whose insulated enclosure has been stripped, and crimp them tightly with a
wire crimper. Make sure that the withdrawal force of the pressed cable is bigger
than 400N.
(5)
Plug the pressed positive and cathode cables into relevant insulated enclosure,
a “click” should be heard or felt when the contact cable assembly is seated
correctly.
(6)
Fasten the lock screws on positive and negative connectors into respondent
insulated enclosure and make them tight.
(7)
Connect the positive and cathode connectors into positive and negative DC
input terminals of the inverter, a “click” should be heard or felt when the contact
cable assembly is seated correctly.
1. Connection Port
Figure 5.9 Connect the Inverter
NOTICE
·Before inserting the connector into the DC input terminal of the inverter, please make sure that the DC switch of the inverter is OFF.
Suntrio Plus Series
-30-
5.5 Communication Connection
Suntrio Plus 12K/15K/17K/20K/25K/33K/40K/50K/60K is equipped with a RS232 and RS485 interface.
Figure 5.10 Pins of Nine Serial Port Cable
Table 5.5 Instruction of Nine Serial Port Pins
Pin No. Name
1DCD
Data Carrier Detect
2RxD
Received Data
3TxD
Transmitted Ready
4DTR
Data Terminal
5GND
Signal Ground
6DSR
Data Send Ready
7 RTS (Request To Send)
8CTS(ClearToSend)
9 RI(Ring Indicator)
1)RS232 can externally connect with Wi-Fi module.For more details, please refer
to the operating manual of Wi-Fi module.
2)RS232 can externally connect with Wi-Fi module.For more details, please refer
to the operating manual of Ethernet module.
3)RS232 can externally connect with Wi-Fi module.For more details, please refer
to the operating manual of GPRS module.
When using RS485 for monitoring, multi- point monitoring can be achieved by
Suntrio Plus Series
-31-
connecting the inverter with RS485 cable. Each connection port should be attached
to the connector as shown in Figure 5.11 and Table 5.4. Make sure the connection
is tight and secure.
Figure 5.11 3 Ports connector
Table 5.4 RS485 Assembly Sequence of RS485
Number of connector Color of cable
1B-
2A+
3 Metal-shielded wire
Suntrio Plus Series
-32-
Chapter 6 Debugging Instructions
6.1 Introduction of Human-computer Interface
Figure 6.1 Human-computer Interface
Object Description
A
Communication light: blue light flashing = receiving data yellow light flashes = sending data
B
Status indicator lamp: Red LED light = Fault; Green LED light = operation; when red and green light are all off, the inverter is in initializing state or countdown for grid-tie.
C
Power indicator light: yellow light: the power system of inverter is operating normally
D
Moves the cursor or the focus point to the left
E
Moves the cursor or the focus point to the right
F(ENT) Starts the menu / button to confirm selection
G
Moves the cursor up or increases the setting value
H
Moves the cursor down or reduces the setting value
The inverter provides five buttons for inquiry of operational information and
parameters, these five buttons can be used repeatedly.
Suntrio Plus Series
-33-
6.2 First Run Setup
6.2.1 Set the Country
When the solar inverter begins to run for the first time, please configure the time of
usage, and the inverter LCD will display as below:
Figure 6.2 Set the Time
Users can press Up, Down, Left, Right and ENT buttons to set local time and
confirm the selection.Then the inverter will display the interface for country
selection as shown in Figure 6.3:
Figure 6.3 Set The Country
Please press the "ENT" button, LCD will show the countries for option. Users can
press "
"or" " to select the correct country and press "ENT" button to confirm
the selection.
Note: The configuration of the country of usage must be set before inverter starts
to run for its first time, otherwise the inverter will not be on-gird.If users can not
locate the corresponding country, please abort the setting and contact the after
sales for confirmation.
Suntrio Plus Series
-34-
6.2.2 State
If the country has been set the LCD shows the machine type when the inverter is
started up, then it automatically displays the inverter operation status: Initialization,
Normal,Wait, Fault or Update.
Data name Explanation
Initialization Initialization of the system
Normal The inverter in normal (function) operation
Wait The inverter in stand-by state
Fault A fault occurs during operation
Update The state of updating firmware
Turn on the AC switch, the LCD begins to count backwards, after this, the inverter
initiates connection to the grid.
6.2.3 LCD Menu
Figure 6.4 LCD Menu
Suntrio Plus Series
-35-
6.2.4 Settings of General Parameters of the Inverter
LCD Display Operation Steps
1. Settings of figures
Graph Set
In the main LCD interface, press “ENT” button to enter into the selection of “Graph”, press or to select. The LCD displays daily, monthly, yearly and gross generating capacity.
2. Settings of System Parameter
Communicate Set
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2. Press ENT to enter into” Communication Settings”. Press andto set the communication address of Wi-Fi and RS485. The Fault address is
1.
Suntrio Plus Series
-36-
Language & Time
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2. PressandthenpressENTto enter into “Language & Time”. Pressand to set the language, date and time.
Grid Compliance
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2. PressandthenpressENTto enter password and enter into country setting. Attention: Please contact SAJ if you need password.
Suntrio Plus Series
-37-
Grid Compliance
3. Pressandto select country, Then click OK to save the changes.
Clear Errors
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2. PressandthenpressENTto enter into “Clear Fault Records”, click OK or return back.
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph
Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Communicate Set Language & Time Grid Compliance
Clear Energy LCD Setting Factory Reset Change Password PV Mode Setting Exit
Clear Error
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph
Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Communicate Set Language & Time Grid Compliance Clear Error
LCD Setting Factory Reset Change Password PV Mode Setting Exit
Clear Energy
Suntrio Plus Series
-38-
Clear Energy
2. PressandthenpressENTto enter into “Clear Energy”, click OK or return back.
LCD Setting
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2. PressandthenpressENTto enter into “Display Settings”, andthenpressandto change the sleep time of LCD, click OK or return back.
Factory Reset
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph
Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Communicate Set Language & Time Grid Compliance Clear Error Clear Energy
Factory Reset Change Password PV Mode Setting Exit
LCD Setting
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph
Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Communicate Set Language & Time Grid Compliance Clear Error Clear Energy LCD Setting
Change Password PV Mode Setting Exit
Factory Reset
Suntrio Plus Series
-39-
Factory Reset
2. PressandthenpressENTto enter password, and then enter into Factory Settings. Attention: Please contact SAJ if you need password.
3. Click OK to save the changes.
Change Password
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2. Pressand then press ENT to enter password, and then enter into Reset Password. Attention: Please contact SAJ if you need password.
Power 1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph
Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Communicate Set Language & Time Grid Compliance Clear Error Clear Energy LCD Setting Factory Reset
PV Mode Setting Exit
Change Password
Suntrio Plus Series
-40-
Change Password
3. Enter the new password and click OK to save the change.
PV Mode Setting
1. In the main LCD interface, press “ENT” button, then press to enter into “Setting”.
2.PressandthenpressENTto enter into “PV Mode Setting”. Pressand to choose PV mode.then choose to confirm. 1-- PV1,PV3,PV2 independent 2--PV1//PV2; PV3 independent 3--PV1//PV3; PV2 independent 4--PV2//PV3; PV1 independent 5-- PV1//PV2// PV3 Attention: This mode shall be set before the inverter is connected to the power grid, and don’t set it when the inverter is being connected to the grid.
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph
Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Communicate Set Language & Time Grid Compliance Clear Error Clear Energy LCD Setting Factory Reset Change Password
Exit
PV Mode Setting
Suntrio Plus Series
-41-
6.2.5 Inquiry of Parameters of Inverter
1. Inquiry of Operating Parameters
1. In the main LCD interface, press “ENT” button, then press to
enter into “Parameters”.
2. Press ENT to enter into “Run-Info”, then press orto select the needed parameters,press ENT to enter and to check the parameters.
2. Inquiry of the Information of Inverter
1. In the main LCD interface, press “ENT” button, then press to
enter into “About”.
2. Press ENT to enter into “About” to check the equipment type, series number, machine code, software version of display panel, mainframe version of the control panel and the settings of country.
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph Setting
Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
DC-Parameters Error-Records Module-Inform Exit
AC-Parameter
Power
1230W
E-Today
11.33 kWh
T-Today
1.7 h
T-Total
4.6 h
15-07-09 15:47
Graph Setting Run-Info
About
0
3.7
7.4
11.1
14.8
18.5
22.2
25.9
29.6
kW
33.3
3 5 7 9 11 13 15 17 19 21h
E-Total
14.35 kWh
E-Today 11.33 kWhNormal
Suntrio Plus Series
-42-
6.3 Monitoring Operation
The equipment is equipped with a RS232 and a RS485 interface, and the RS232 interface can be connected to Wi-Fi module, Ethernet module, GPRS module which can be used in the monitoring of the operation status.
By connecting the Internet through Wi-Fi module and uploading the inverter data to the server, users can monitor the operational information of the inverter by web version web portal or mobile APP (please download the mobile APP from SAJ official website) remotely.
By connecting the Internet through Ethernet module and uploading the inverter data to the server, users can monitor the operational information of the inverter by web version web portal or mobile APP (please download the mobile APP from SAJ official website) remotely.
By connecting the Internet through GPRS module and uploading inverter data to the server, users can monitor the operational information of the inverter by web version web portal or mobile APP (please download the mobile APP from SAJ official website) remotely.
Users can apply a Modbus protocol through RS485 together with a SAJ Logger to monitor the data of the inverter. For detailed operation please refer to the SAJ Logger User Manual.
Suntrio Plus Series
-43-
Chapter 7 Fault Code and Troubleshooting
LCD displays Fault codes as shown in the table below:
Error Code Explanation
01 Relay Error Master
02 Storer Error Master
03 High Temperature Master
04 Low Temperature Master
05 Lost Interior Communication Master
06 GFCI Devices Error Master
07 DCI Devices Error Master
08 Current Sensor Master
09/11/13 L1/L2/L3 Voltage High Master
10/12/14 L1/L2L3 Voltage Low Master
15/16/17 L1/L2/L3 Average Voltage of 10 minutes High Master
18/20/22 L1/L2/L3 Frequency High Master
19/21/23 L1/L2/L3 Frequency Low Master
24/25/26 L1/L2/L3 Grid Lost Error Master
27 GFCI Error Master
28/29/30 L1/L2/L3 DCI Error Master
31 Insulation Error Master
32 Bus Voltage Unbalance Master
33 Bus Voltage High Master
34 Bus Voltage Low Master
35/36/37 L1/L2/L3 Current High Master
38 Bus Voltage High Of Hardware Master
39/40 PV1/PV2,PV3 Current High of Hardware Master
41/42/43 L1/L2/L3 Current High of Hardware of Grid Master
45/46/47/48 Fan 1/2/3/4 Error Master
50 Lost interior communication Slave
51/52/53 L1/L2/L3 Data Consistency of Voltage Error Slave
54/55/56 L1/L2/L3 Data Consistency of Frequency Error Slave
Suntrio Plus Series
-44-
57 Data Consistency of GFCI Slave
58/59/60 L1/L2/L3 Data Consistency of DCI Slave
61/63/65 L1/L2/L3 Grid Voltage High Slave
62/64/66 L1/L2/L3 Grid Voltage Low Slave
67/69/71 L1/L2/L3 Frequency High Slave
68/70/72 L1/L2/L3 Frequency Low Slave
73/74/75 L1/L2/L3 No Grid Error Slave
76/77/80 PV1 /PV2/PV3 Voltage High Slave
78/79/82 PV1/PV2/PV3 Current High Slave
81
Lost Communication Between Display board & Control board Master
83
Grouding detect Error Master
84
PV Input Error Master
Table7.1 Error Code
General troubleshooting methods for inverter are as follows:
Table 7.2 Troubleshooting
Error Troubleshooting
Relay Error
If this error occurs frequently, please contact your distributor or phone SAJ.
Storer Error
If this error occurs frequently, please contact your distributor or phone SAJ.
Temperature High Error
Check whether the radiator is blocked, whether the inverter is in too high or too low temperature, if the above mentioned are in normal, please contact your distributor or phone SAJ.
GFCI Device Error
If this error occurs frequently, please contact your distributor or phone SAJ.
DCI Device Error
If this error occurs frequently, please contact your distributor or phone SAJ.
Current Sensor Error
If this error occurs frequently, please contact your distributor or phone SAJ.
AC Voltage Error
·Check the connection between the inverter and the grid.
·Check the settings of the on-grid standards of the inverter.
·If the volt of the grid is higher than the volt regulated by local grid, please inquire the local grid workers whether they can adjust the volt at the feed point or change the value of the regulated volt.
·If the voltage of the grid is in regulated range as allowed and LCD
Suntrio Plus Series
-45-
still in this error, please contact your distributor or phone SAJ.
Frequency Error
Check the set of country and check the frequency of the local grid, if the above mentioned are in normal, please contact your distributor or phone SAJ.
No Grid Error
Check the connection status between the AC side of the inverter and the grid, if the above mentioned are in normal, please contact your distributor or phone SAJ.
GFCI Error
Check the insulation resistance of the positive side and cathode side of the solar panel; check whether the inverter is in wet environment; check the grounding of the inverter. If the above mentioned are in normal, please contact your distributor or phone SAJ.
DCI Error
If this error exists always, please contact your distributor or phone SAJ.
ISO Error
Check the insulation resistance of the positive side and cathode side of the solar panel; check whether the inverter is in wet environment; check whether the grounding of the inverter is loose or not. If the above mentioned are in normal, please contact your distributor or phone SAJ.
Current High
Check the connection status between the inverter and the grid and test whether the volt of the grid is stable or not, if the above mentioned are in normal, please contact your distributor or phone SAJ.
Bus Voltage High
Check the settings of the solar panel. SAJ’s system design software can help you.If the above mentioned are in normal, please contact your distributor or phone SAJ.
PV Current High
If this error exists always, please contact your distributor or phone SAJ.
PV Voltage Fault
Check the settings of the solar panel. SAJ’s system design software can help you. If the above mentioned are in normal, please contact your distributor or phone SAJ.
Lost Communication
Check the connection of communication cables between control
board and display board. If the above mentioned are in normal,
please contact your distributor or phone SAJ.
Grouding detect Error
Check Gird phase line connect to ground or not. If the above
mentioned are in normal, please contact your distributor or phone
SAJ.
PV Input Error Check PV mode setting is right or not.If the above mentioned are in
normal, please contact your distributor or phone SAJ.
Suntrio Plus Series
-46-
Chapter 8 Recycling and Disposal
This device should not be disposed as residential waste. An Inverter that has
reached the end of its life and is not required is to be returned to your dealer or you
must find an approved collection and recycling facility in your area.
Suntrio Plus Series
-47-
Chapter 9 Guarantee Service
Please refer to the warranty card.
Suntrio Plus Series
-48-
Chapter 10 Contact SAJ
Guangzhou Sanjing Electric Co., Ltd.
SAJ Innovation Park, No.9, Lizhishan Road, Guangzhou Science City, Guangdong,
P.R.China.
Postcode: 510663
Web: http: //www.saj-electric.com
Technical Support & Service
Tel: +86 20 6660 8588
Fax: +86 20 6660 8589
E-mail: service@saj-electric.com
International Sales
Tel: +86 20 6660 8618/6660 8619/6660 8588/6660 0086
Fax:+86 020 6660 8589
E-mail: info@saj-electric.com
Domestic Sales
Tel: 020-66600058/66608588
Fax: 020-66608589
Suntrio Plus Series
-49-
SAJ Warranty Policy
Standard Warranty Period
Guangzhou Sanjing Electric, Co., Ltd (“SAJ”) grants a standard warranty period of
66 months (5.5 years) for the Sununo-TL Series inverters & Suntrio-TL Series
inverters and Sununo Plus Series inverters & Suntrio Plus Series inverters, starting
from the date of shipment from SAJ factory or 60 months (5 years) starting from
the date of purchased invoice marked (whichever is longer).
Extension of Warranty
The purchaser of SAJ inverters (Sununo-TL Series inverters & Suntrio-TL Series
inverters and Sununo Plus Series inverters & Suntrio Plus Series inverters) should
extend the warranty period in 18 months from the date of settlement or 30 months
from the date of shipment from SAJ by providing the serial number of the unit and
purchased receipt (whichever is shorter). You can purchase the warranty extension
for 10 years, 15 years, 20 years or 25 years but do not apply the extension beyond
the specified date, or else your application will be unacceptable. Please refer to the
Warranty Extension Order Form for more details.
Once the purchase of the warranty extension goes into effect, SAJ will send the
warranty extension certificate to the customer for confirming the extended
warranty period.
Warranty Conditions
If your inverter gets fault and requires troubleshooting, please contact your
distributor or dealer directly. Alternatively, feedback briefly to SAJ service hotline
for logging and send your warranty card to our service department by fax/email to
process the warranty claim.
During the Warranty Period, SAJ covers all costs for replacing any product or parts
Suntrio Plus Series
-50-
of the product proved to be defective in design or manufacture. To claim the
warranty under the warranty policy of SAJ, you need to supply us with the
following information and documentation regarding the faulty inverter:
1.Product Model No.(e.g. Suntrio Plus 20K) and serial number.
(e.g.22030G1825EN00001)
2. Copy of the invoice and warranty certificate of the inverter.
3. Copy of the installation report and installation date.
4.Error message on LCD screen (if available) or any information which would be
helpful to determine the defect.
5.Detailed information about the entire system (modules, circuits, etc.).
6.Documentation of previous claims/exchanges (if applicable).
After receiving above information, SAJ will decide how to proceed the service
1.Repaired by SAJ factory, or SAJ authorized service center overhaul.
2.Repaired on-site by SAJ Service Center.
3. Offer a replacement device of equivalent value according to model and age.
In the case of an exchange, the remaining portion of the original warranty period
will be transferred to the replacement device. You will not receive a new certificate,
as your entitlement is documented at SAJ.
If the inverter needs to be replaced following assessment, SAJ will send a
replacement unit immediately. The defective inverter should be sent back to the
closest SAJ Service Center by packing in its original package if possible.
Suntrio Plus Series
-51-
Service after warranty expiration
If the inverters for maintenance are out of warranty, SAJ charges an on-site service
fee, parts, labor cost and logistic fee to end-user. Detailed standard refers to the
listed table.
Item Return Factory Maintenance On-site Maintenance
Without parts
replacement
Labor + Logistic fee
(to & from SAJ)
Labor + On-site attendance
fee
With parts replacement
Labor + Parts + logistic fee
(to & from SAJ)
Labor + On-site attendance
fee + Parts
On-site attendance fee: Cost of travel and time for the technician in attending
on-site.
Parts: Cost of replacement parts (including any shipping/admin fee that may
apply).
Labor: Labor time fee charged for the technician, who is repairing, maintaining,
installing (hardware or software) and debugging the faulty product.
Logistic fee: Cost of delivery, tariff and other derived expense when defective
products are sent from user to SAJ or/and repaired products are sent from SAJ to
user.
Exclusion of Liability
Any defect caused by the following circumstances will not be covered by the
manufacturer’s warranty (the Dealers or Distributors are responsible and
authorized by SAJ for the following investigation):
“Warranty Card” not being sent back to Distributor/Dealer or SAJ;
Product modified, parts replaced or attempt to maintain;
Changes, or attempted repairs and erasing of series number or seals by non SAJ
Suntrio Plus Series
-52-
technician;
Incorrect installation or commissioning;
Failure to comply with the safety regulations (VDE standards, etc.);
The inverter has been improperly stored and damaged while being stored by the
Dealer or the end user;
Transport damage (including scratch caused by movement inside
packaging during shipping).A Claim should be made directly to shipping
company/insurance Company as soon as the container/packaging is unloaded and
such damage is identified;
Failure to follow any / all of the user manual, the installation guide and the
maintenance regulations;
Improper use or misuse of the inverter;
Insufficient ventilation of the inverter;
Influence of foreign objects and force majeure (lightning, grid overvoltage,
severe weather, fire, etc.)
For further information on SAJ warranty regulation and reliability, please visit
our website: www.saj-electric.com.
Suntrio Plus Series
-53-
Warranty Card
The installer should fill in the second form while installing the inverter. For
warranty claim, please complete the below forms and send this page to SAJ
attached with the Customer’s invoice.
For Customer to fill in
Name:
City: Country: Zip:
Tel: Fax: E-mail:
Information on Device
Device type: Serial No.(S/N):
Invoice No: Commissioning date::
Fault time:
Error message (Display reading):
Brief fault description & photo:
Signature:
Date:
Suntrio Plus Series
-54-
For Installer to fill in
Modules Used:
Modules Per String: No. of String:
Installation Company: Contractor License Number:
Company:
City: Country: Zip:
Tel: Fax: E-mail:
Signature:
Date:
Guangzhou Sanjing Electric CO., LTD.
ADD: SAJ Innovation Park, No.9, Lizhishan Road, Science City,
Guangzhou High-tech Zone, Guangdong, P.R.China
Zip: 510663 Tel: +86 20 6660 8588 Fax: +86 20 6660 8589
Web: http: //www.saj-electric.com
Edition No: V1.01