-06-
8000B Series
Notes for Other Important Operations
CAUTION
1. Check Insulation of the Motor
Check insulation of the motor and wire when the motor is used again after
long time idle or for the rst time. Disconnect the wire between the motor and
the inverter before check insulation. Make sure the insulation resistor is not
below 5MΩ.
2. Thermal Overload Protection of the Motor
When the rated capacity of inverter is larger than that of the motor, install
thermal overload re lay for the motor or re gulate the mot or protection
parameters of the inverter.
3. Consider the Bearing Capability of the Load
The inverter can provide output frequency from 0 Hz to 600 Hz. If the motor
needs to work at over 50 Hz, user should consider the bearing capability of
the load.
4. Avoid Mechanical Resonance Frequency
Regulate the skip frequency parameter of the inverter to avoid mechanical
resonance frequency of the load.
5. Prohibition of Installation of Phase Advancing Capacitor
If a phase advancing capacitor or surge suppressor is connected in order to
improve the power factor, it may become overheated and damaged by inverter
high harmonic components. Also, the inverter may malfunction because of
over current.
6. Installation of Magnetic Contactor
If a magnetic contactor is installed at the power supply side, do not use it to
control the start of the inverter. If necessary, the time span should be one hour
or above. Otherwise frequent switching may cause the inverter to malfunction.
If a magnetic contactor is installed between the output terminals and motor
(output side of the inverter), make sure there is no output of inverter before
switch on and off. Otherwise it may cause damage to the inverter.