Safety Technology International STI Stopper II Heated Enclosure Data Sheet

FIRE PRODUCTS
®
STI STOPPER II HEATED ENCLOSURE
ADA
Compliant
®
STI-1200A-HTR
PRODUCT OVERVIEW
This protective cover has been helping stop false fire alarms around the world for more than 35 years, without restricting legitimate alarms. This Stopper II enclosure with heater allows addressable dual monitor modules to be installed inside or outside in temperatures below UL Listing limits or in other NEMA 3R environments. UL/cUL Listing requires outdoor rated stations. The cover offers excellent protection against physical damage (both accidental and intentional), as well as other environments inside and outside. Also ideal for inside of walk-in freezers.
HOW IT WORKS
Stopper II Heated Enclosure consists of a clear, super tough polycarbonate shield, frame and heater. The Stopper II is mounted on a NEMA 3R enclosure with a heater which allows an addressable manual pull station to be installed inside or outside in cold temperatures.
KEY FEATURES
General Information
· For use in areas where temperature or environmental conditions exceed the operational range of UL Listed devices.
· Heater unit cycles as required to maintain the correct range of operating temperatures.
· Fan runs continuously to maintain a uniform temperature inside the enclosure.
· Maintains operating temperature with external temperatures to -70°F (-57°C).
· Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components).
Design
· The Stopper II design is a registered trademark of Safety Technology International, Inc.
Construction
· UL Listed to U.S. and Canadian safety standards. See reverse side for details.
· Enclosure rated to NEMA 3R Standards.
· The thick, clear polycarbonate cover is UV-stabilized against discoloration.
Installation
· UL/cUL Listing requires outdoor rated stations.
· Typical working properties of polycarbonate are -40° to 250°F (-40° to 121°C).
E
lectronics
· UL Listing does not require standby or secondary power for 110 or 140 VAC 60 Hz heater.
O
ptions
· 110 VAC or 240 VAC heater.
STI Stopper II® Heated Enclosure
-80
-70
-60
-50
-40
-30
-20
-10
0
10
20
30
40
0:00:00:00.00
0:00:19:59.70
0:00:39:59.70
0:00:59:59.70
0:01:19:59.70
0:01:39:59.70
0:01:59:59.70
0:02:19:59.70
0:02:39:59.70
0:02:59:59.70
0:03:19:59.70
0:03:39:59.70
0:03:59:59.70
0:04:19:59.70
0:04:39:59.70
0:04:59:59.70
0:05:19:59.70
STI-1200A-HTR
TIME
TEMP (Deg. C)
-80
-70
-60
-50
-40
-30
-20
-10
0
10
20
30
40
0:00:00:00.00
0:00:19:59.70
0:00:39:59.70
0:00:59:59.70
0:01:19:59.70
0:01:39:59.70
0:01:59:59.70
0:02:19:59.70
0:02:39:59.70
0:02:59:59.70
0:03:19:59.70
0:03:39:59.70
0:03:59:59.70
0:04:19:59.70
0:04:39:59.70
0:04:59:59.70
0:05:19:59.70
STI-1200A-HTR
TIME
TEMP (Deg. C)
Dimensions and Technical Information
MODELS AVAILABLE
STI-1200A-HTR With 4 in. deep back box - 110 VAC STI-1200A-HTR240 With 4 in. deep back box - 240 VAC
Accessory
KIT-314 Adapter plate KIT-H18021 3/4” rigid conduit hub STI-H K3 Replacement heater
SPECIFICATIONS
INTERNAL DIMENSIONS:
PART # HEIGHT WIDTH DEPTH 1200A-HTR 6.25 in. 4.125 in. 1.25 in. 1220A-HTR240 (158mm) (104mm) (31mm)
POLYCARBONATE ENCLOSURE:
Flammability:
UL94 V-2
Wall Thickness: back box: .20 inches (5.1mm)
cover: .12 inches (3.1mm)
NEMA Rating: 3R Warranty: Three year guarantee against breakage of
polycarbonate in normal use (one year on electro mechanical and electronic components).
SILICONE LAMINATE HEATER:
STI-1200A-HTR 110 VAC 50/60 Hz UL Recognized Component STI-1200-A-HTR240 240 VAC 50/60 Hz UL Recognized Component
100 Watts Life: @ -10°C (14°F) ~ 70°C (158°F) 5 years Duty Cycle: -40°F (-40°C) 16%
4
3
5
Temp DEG C
50 40 30 20
1
10
0
-10
-20
-30
-40
-50
2
-60
-70
-80
UL Recognized Component
00:30
00:00
TC-1 TC-2 TC-3 TC-4 TC-5 External Temp
FAN :
24 VDC (±10%), 90 mA Life: 5 years continuous duty WARNING: The polarity of the circulating fan is important as it only
rotates in one direction with red lead being positive.
UP
-70°F (-57°C) 38%
-99°F (-73°C) 100%
STI-1200A-HTR
02:00
01:30
01:00
02:30
MOUNTING
SCREW ANCHORS
03:30
03:00
SURFACE
(4) PROVIDED
3/4 in. NPT MALE NIPPLE
04:00
APPROVALS & WARRANTY
TESTING
It has been tested and approved or listed by:
· UL, cUL Listed S2466 (requires outdoor rated station)
· UL File S7025 is cross referenced to File S2466 permitting STI Stopper
®
Stations, non fire, in category UEHX and Listed to UL
2017 for outdoor use
· ADA Compliant
WARRANTY
Three year guarantee against breakage of polycarbonate in normal use (one year on electro mechanical and electronic components).
WARNINGS
The enclosure is used to protect UL Listed 38 and 2017 manual initiating outdoor listed devices at temperatures down to -70˚F (-57˚C). It is the installer’s responsibility to comply with NEC 70 Articles 725 and 760, NFPA 72, and other applicable fire and electrical codes. Conduit or raceway paths need to be sealed as near to the enclosure as possible. Installer should have maintained supervision over the low temperature thermostat. The low temperature monitoring thermostat makes the circuit at +32°F (0°C) and clears the circuit at +50°F (+10°C). This listing requires that the fire alarm supervisor y control module be only of the latching type. On the appliance mounting plate is a label where you should record the installation date. Also includes serial number and installation date on the instruction sheet for quick reference.
#10 x 1 1/2 in.
PAN HEAD SCREW
(4) PROVIDED
(NOT PROVIDED)
(NOT PROVIDED)
04:30
SEALING HUB
#6-32 x 1 in. PAN HEAD SCREW
05:00
(4) PROVIDED
3/8 in. STANDOFF
ADDRESSABLE MODULE
24 VDC TERMINAL BLOCK
SEALING HUB (NOT PROVIDED)
3/4 in. NPT MALE NIPPLE (NOT PROVIDED)
DUAL MONITOR
(NOT INCLUDED)
MOUNTING TAB (4) PRO
VIDED
BACKBOX
GASKET
COVER
LOW TEMP WARNING THERMOSTAT
CIRCUT BREAKER
FAN
HIGH VOLTAGE TERMINAL BLOCK
SLIDE PLATE
#8-32 x 3/8 in. FLAT HEAD SCREW
PULL STATION (NOT INCLUDED)
PULL
IN CASE OF
FIRE
Printed in U.S.A., © 1987-2020 Safety Technology International, Inc.
10 /17Subject to change without notice.
Loading...