OPTIONAL SURFACE MOUNT
BLUE = STROBE (+)
BLACK = GND -
YELLOW = SIREN (+)
WHITE = TAMPER
GREEN = TAMPER
+
-
Control W/POWER SUPPLY
- Alarm on trigger close
KIT-71100A SHOWN
#6 x 1.25 in. SCREW
(4) PROVIDED WITH KIT-71100A
SIREN STROBE ELECTRONIC BASE
SEALING O-RING (2) PROVIDED
SCREW #6-32 x 1 in. (2) PROVIDED
3.22 in.
(81.7mm)
4.83 in.
(122.7mm)
DRILL POINT LOCATION TOP AND
BOTTOM FOR 1/2” CONDUIT
FITTINGS. DRILL AS NEEDED.
ELECTRICAL BOX
2.10 in.
(53.3mm)
DRILL (4) 3/16 in.
DIAMETER HOLES
WALL ANCHOR
(4) PROVIDED
WITH KIT-71100A
INPUT
12 VDC, 0.42 A
24 VDC, 0.22 A
LENS TAMPER
N.C. DRY CONTACT
0.05 A @ 12 VDC
OPERATING TEMPERATURE
-4°F TO 140°F (-20°C TO 60°C)
WIRE LEADS
Housing Installation
1. Loosen screw with 3/32 HEX KEY.
2. Pull bottom of housing out and lift up until tabs are
released from slots in top of siren/strobe assembly.
Wire Connections
WHITE - TAMPER
GREEN - TAMPER
BLUE - STROBE
YELLOW - SIREN
BLACK - GROUND
CONTROL W/POWER SUPPLY
- ALARM ON TRIGGER CLOSE
STROBE & SIREN
YEL (+)
BLK (-)
-
+
BLK (-)
(NOT PROVIDED)
SIREN
SIREN ONLY
YEL (+)
-
+
BLK (-)
(NOT PROVIDED)
STROBE
STROBE ONLY
YEL (+)
-
+
SIREN
BLU (+)
TRIGGER
BLU (+)
TRIGGER
BLU (+)
GREEN
WHITE
GREEN
WHITE
GREEN
WHITE
TRIGGER
(NOT PROVIDED)
TAMPER SWITCH TO
SUPERVISORY PANEL
(OPEN DOES NOT SOUND
ALARM)
TAMPER SWITCH TO
SUPERVISORY PANEL
(OPEN DOES NOT SOUND
ALARM)
TAMPER SWITCH TO
SUPERVISORY PANEL
(OPEN DOES NOT SOUND
ALARM)
WARNING: This product can expose you to chemicals including Dichloromethane, which is known to the
State of California to cause cancer, and Bisphenol A (BPA), which is known to the State of California to
cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Three year warranty or a one year limited warranty (from date of purchase) on most products.
INSTALLATION OF STI-SA5600 SELECT ALERT SIREN/STROBE
All specifications and information shown were current as of publication and are subject to change without notice.
SA5600IS MARCH2020
S2 - STROBE CONTROL (1)
HOR
1100A)
RILL (4)
. HOLES
1 2 3 4 5 6 7 8 9 FUNCTION
* 1 1 1 LEFT TO RIGHT FLASHING (30cyc/ 1 min)
S2
1 2 3 4 5 6 7 8 9
ON
O 1 1 BREATHING ( 12cyc/1 min)
1 O 1 FLASHING (120 cyc/1 min)
O O 1 FLASHING (90 cyc/1 min)
1 1 O FLASHING (60 cyc/1 min)
O 1 O INDIRECT FLASHING (50 cyc/1 min)
1 O O INDIRECT FLASHING (30 cyc/1 min)
Strobe (1)
Siren (2)
O O O CONTINUOUS (SOLID LIGHT)
S2 - ALARM TONES (2)
1 2 3 4 5 6 7 8 9 FUNCTION
* 1 1 1 1 1 1800Hz - 3300Hz @ 150ms
O 1 1 1 1 500Hz - 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 EVACUATION)
1 O 1 1 1 520Hz, 0.5s / 0.5s OFF x 3/1.5s OFF (FIRE)
O O 1 1 1 1200Hz - 500Hz @ 1Hz (DIN 33 404)
1 1 O 1 1 500Hz - 1200Hz, 3.75s ON / 0.25s OFF (AS2220)
O 1 O 1 1 550Hz/440Hz @0.5 Hz
1 O O 1 1 970Hz, 0.5s/ 630Hz, 0.5s
O O O 1 1 800Hz / 1000Hz 0.5s each (1Hz)
1 1 1 O 1 1500Hz - 2700Hz @ 3Hz
O 1 1 O 1 800Hz / 970Hz @2Hz
1 O 1 O 1 800Hz, 0.25s ON/ 1s OFF
O O 1 O 1 2400Hz - 2900Hz @ 9 Hz
1 1 O O 1 750Hz
O 1 O O 1 970Hz
1 O O O 1 970Hz, 1s OFF/1s ON
O O O O 1 500Hz - 1200Hz, 3.5s ON/ 0.5s OFF (NEN 2575:2000 DUTCH SLOW WHOOP)
1 1 1 1 O 800Hz - 970Hz @1Hz
O 1 1 1 O 1000-2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 EVACUATION)
1 O 1 1 O 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)
O O 1 1 O 660Hz 1.8s ON/1.8s OFF
1 1 O 1 O 500Hz - 1200Hz @ 0.33Hz
O 1 O 1 O 250Hz - 1200Hz @ 12Hz
1 O O 1 O 2400Hz
O O O 1 O 800Hz / 970Hz @9Hz
1 1 1 O O 510Hz, 0.25s/ 610Hz, 0.25s
O 1 1 O O 550Hz, 0.7s/1000Hz, 0.33s
1 O 1 O O 660Hz 0.15s ON/0.15s OFF
O O 1 O O 800Hz - 970Hz @ 3Hz
1 1 O O O 420Hz 0.625s ON/0.625s OFF (AUSTRALIA AS1670 ALERT TONE)
O 1 O O O 554Hz, 0.1s/440Hz, 0.4s (AFNOR NF S 32 001)
1 O O O O 970Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)
0 O O O O 2400Hz - 2900Hz @ 3 Hz
S2 - VOLUME (3)
1 2 3 4 5 6 7 8 9 FUNCTION
* 1 VOLUME - HI
O VOLUME - LOW
*Default
INSTALLATION OF STI-SA5600 SELECT ALERT SIREN/STROBE
All specifications and information shown were current as of publication and are subject to change without notice.
Volume (3)
COVER SLOT
3/32 in. HEX KEY
SCREW
SA5600IS MARCH2020