Russell RND10L44 User Manual

Publication No. RU-RNX-0712A
RN Series
INDOOR REMOTE
COMPRESSOR UNIT
3 THROUGH 40 HP
Unit shown with optional control
panel, oil control, liquid, &
suction line assemblies.
Standard Features: Optional Features:
• Discus or Reed Semi-hermetic Compressor (Contact factory for Hermetic Compressors)
• Suction and discharge service valves (as requires)
• Compressor springs and discharge vibrasorber
• Dual pressure control
• Liquid receiver with isolation valves
• Compressor head cooling fan (as required)
• Pressure relief valve or fusible plug
• Contactor box
• Compressor contactor and control circuit fusing
• UL and C-UL listed
• Large electrical control panel (as shown above)
• Crankcase heater
• Liquid line assembly (fi lter and vibration absorber)
• Suction line assembly (fi lter and vibration absorber)
• Suction Accumulator (mounted)
• Oil Separator (mounted)
• Air or Electric Defrost provisions (requires optional control panel)
• Pumpdown toggle switch
• Two tier stacking rack
• Oil failure control (as required)
2
INDOOR REMOTE COMPRESSOR UNIT
BTUH Capacity @ 105°F Condensing Temperature
NOM. REF. MODEL
H.P. TYPE NUMBER 40° 30° 25° 20° 10° -10° -20° -30° -40°
3 404A RNS3M44 ----- ----- 30000 26800 21000 16400 ----- ----- ----- ----­4 404A RNS4M44 ----- ----- 41500 36700 28400 21400 ----- ----- ----- ----­5 404A RND5M44 77200 62600 56000 49800 39100 30200 23200 ----- ----- ----­6 404A RND6M44 94000 76200 68300 61000 48300 37700 29200 ----- ----- -----
7.5 404A RND7M44 107600 87600 78800 70700 56600 44800 34900 ----- ----- -----
7.5 404A RND8M44 126100 102700 92400 82800 66100 52200 40700 ----- ----- ----­10 404A RND10M44 148700 121600 109600 98700 79400 63000 49100 ----- ----- ----­12 404A RND12M44 203800 166100 149450 134200 107400 85200 66900 ----- ----- ----­15 404A RND15M44 204700 167200 150600 135400 108700 86300 67700 ----- ----- ----­20 404A RND20M44 218200 179000 161000 144200 114100 88700 67100 ----- ----- ----­25 404A RND25M44 272400 226300 204600 183800 146250 114900 91200 ----- ----- ----­30 404A RND30M44 333550 273000 245800 220500 175400 137500 106150 ----- ----- ----­35 404A RND35M44 422100 343600 309000 277300 221650 175200 136400 ----- ----- ----­40 404A RND40M44 482800 398900 360900 325500 261950 208100 163350 ----- ----- -----
3 404A RNS3L44 ----- ----- ----- ----- ----- 25100 18900 13500 9100 5700 3 404A RND3L44 ----- ----- ----- ----- ----- 32800 25300 19000 13900 9600 4 404A RND4L44 ----- ----- ----- ----- ----- 39200 30400 23100 17000 11900 5 404A RND5L44 ----- ----- ----- ----- ----- 44300 34700 26600 19900 14100 6 404A RND6L44 ----- ----- ----- ----- ----- 53100 41600 32000 24000 17400
7.5 404A RND8L44 ----- ----- ----- ----- ----- 62700 49100 37900 28600 20600
9 404A RND9L44 ----- ----- ----- ----- ----- 76900 60200 46300 34700 25200 10 404A RND10L44 ----- ----- ----- ----- ----- 85200 67500 52400 39500 28700 12 404A RND12L44 ----- ----- ----- ----- ----- 88700 69500 54000 40800 28200 15 404A RND15L44 ----- ----- ----- ----- ----- 114900 91100 71800 55200 39800 22 404A RND22L44 ----- ----- ----- ----- ----- 138000 110200 86400 65400 46300 27 404A RND27L44 ----- ----- ----- ----- ----- 175800 139400 107400 80000 57180 30 404A RND30L44 ----- ----- ----- ----- ----- 198200 155900 120300 90300 64860
NOTES:
1. Increase (decrease) capacity 3% for each 5°F lower (higher) condensing temperature.
2. When ordering a R-507 model, change the model number suffi x from 44 to 57.
BTUH CAPACITY AT SUCTION TEMPERATURE (°F)
Loading...