INSTALLATION INSTRUCTIONS FOR MINICORE VENTILATOR (MCV) WITH FACTORY
INSTALLED OPTIONS USED AS A STAND ALONE OR WITH SPLIT SYSTEMS UNITS
Energy recovery COMPONENT certied
to the AHRI Air-to-Air Energy Recovery
Ventilation Equipment Certication
Program in accordance with AHRI Standard
1060-2000. Actual performance in packaged
equipment may vary.
I - Shipping And Packing List
Package 1 of 1 contains:
1 - MiniCore Ventilator Assembly
II - Shipping Damage
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is
found.
III - General
These instructions are intended as a general guide and
do not supersede local codes in any way. Authorities
having jurisdiction should be consulted before installation.
IV - Requirements
When installed, the unit must be electrically wired and
grounded in accordance with local codes or, in the
absence of local codes, with the current National Electric
Code, ANSI/NFPA No. 70.
V - Application
MiniCore ventilators are used as a stand alone indoor
option for heat recovery ventilators used in light
commercial applications. These ventilators conserve
energy by transferring heat energy across two opposing
air streams using a polymer core heat exchanger. This
process works in the summer by rejecting the heat energy
from incoming intake air and in the winter by conserving
the heat energy from the exhaust air, allowing outdoor
ventilation rates to be increased by factors of threeor
more without additional energy penalty or increase in size
of the heating or air conditioning systems.
VI - Rigging Unit For Lifting
Danger of sharp metallic edges. Can cause injury. Take care
when servicing unit to avoid accidental contact with sharp
Electric shock hazard. Can cause injury or death.
VII - Installation
When choosing a location to mount the MiniCore
Ventilator take into consideration ductwork layout as well
as access for future lter changes and Core cleaning. See
maintenance section on Page 4 for dimensions.
CAUTION
edges.
WARNING
Before attempting to perform any service or
maintenance, turn the electrical power to unit
OFF at disconnect switch(es). Unit may have
multiple power supplies.
MC500-1ERV
ETL Certied
per UL 1995 and
CSA 22.2
1. Maximum weight of unit is:
Model#MCV-500MCV-1000
Net Weight
Ship Weight
2. Remove carton.
3. All panels must be in place for rigging.
4. Lift unit into place with a winch or jack.
182222
230270
Figure 1
Normal installation of the MiniCore Ventilator unit is
hanging from the 4 corners using the included hanging
kit though the units can be mounted on a shelf or on the
oor of a mechanical room using optional oor vibration
isolators.
1
The maximum weight of a MiniCore Ventilator is less than
225 lbs, Using 3/8" all-thread and the included hanging
brackets is the preferable method of supporting the unit
though the use of metal strap to hang the unit is also
acceptable. When hanging the unit be sure to take into
account the need to provide access for lter replacement
and Core removal as well as blower balancing or removal
through the bottom access panels.
While orientation of the heat exchanging core inside of
the MiniCore Ventilator is important for maximizing airow
orientation of the Ventilator itself is not, the MiniCore can
be mounted in a vertical or horizontal fashion. Additionally
the Fresh Air intake and Return intake can either be
mounted on the side of the MiniCore or on the end by
switching the duct collar and cover panel attached using
5/16" screws. See Figure 2.
Duct Option 1
High voltage:
115V: Connect the high voltage wires to L1 (Hot) &
L2 (Common), hook the ground wire to the provided
grounding nut. See Wiring Diagrams on Pages 6-7.
208/230V: Single phase: Connect the high voltage wires
to L1 (Hot) & L2 (Common) connect the ground wire to
the provided ground nut. Check Voltage into the unit and
adjust the voltage input to the transformer from 230V to
208V if necessary by switching wires at transformer. See
Wiring Diagrams on Pages 6-7.
Low voltage:
Standard units: Pass low voltage wire through the
provided knockout on the 2 gang terminal strip access
box next to the power disconnect, and connect R to
terminal #1 of terminal block TB38 and G to terminal #3.
See Wiring Diagrams on Pages 6-7 and Figure 3
The MiniCore Ventilator can be controlled by any dry
contact closure like those in a CO
sensor with relay,
2
switch or timer.
Duct Option 2
Figure 2
Once the MiniCore Ventilator is hung connect ductwork to
proper sectors of the unit with ¼" screws, use tape to seal
seams. Supply and Exhaust are labeled on the outside
of the cabinet and are determined by the orientation of
the Core inside of the MiniCore Ventilator, a sticker on
the Core will indicate the supply (outdoor air) vector.
The Outside Air and Return connections will always be
on the opposite side of the MiniCore Ventilator from their
respective Supply and Exhaust blowers. See Figure 2.
Wiring
A ¾" knock out is provided for high voltage on the top and
bottom of the high voltage disconnect switch mounted on
the side of the unit.
Figure 3
ECM units: Pass the low voltage wiring through the
provide knockout on the terminal access box and connect
R to terminal #1 on 7 pin terminal box TB38 and G to #3.
The default wiring for the MiniCore Ventilator with ECMs
is to operate in the modulating speed mode terminals #4-7
are for speed control. To control both blowers in unison
wire the 0-10vdc control signal to terminals 4 (10vdc+)
and 5 (10vdc com) and add a jumper between terminals
4 and 6. If the Blowers are controlled independently then
wire the exhaust blower signal to terminals 4 &5 and the
supply signal to terminals 6 & 7, See Adjusting Blower Speed in Section IX - System Check for balancing
information.
To use the motor in 2 speed operation attach the blue
wires from TB39 and TB40 to relays K163 & K164 at pin
#4. With the blue BL-25 and BL-30 wires in place the ECM
with default to 2 speed operation. See Wiring Diagram
on page 7 and Figure 4.
2 MC500-1ERV
Figure 4
VIII - Operation
How It Works
The unit uses a dPoint polymer based ERV core which
offers latent and sensible energy recovery with no cross
contamination and no moving parts. In the summer
outside heat and humidity is rejected from the incoming
outside airstream and exhausted out the building, while
in the winter the same process works to conserve wasted
heat and humidity making the building more efcient,
healthier and more comfortable.
The dense polymer membrane uses selective transfer
technology to allow heat and water vapor to permeate
through, while blocking contaminant compounds. The
transfer is driven by temperature and humidity differentials
between the airstreams. This allows you to reduce the
size of the cooling system by 30% while still meeting
outside air requirements.
The Cores material is designed to prevent mold and
bacteria growth – the material was ISO 846 tested with
a rating of 0 –, is designed to avoid virus transfer –ASTM
Method F-1671 tested with 0 penetration –, and eliminate
cross contamination from exhaust air – 0% EATR certied
to AHRI 1060. It’s polymer construction also means that it
is washable with water for easy cleaning.
IX - System Check
1. Turn off power to the unit
2. Remove access cover for the terminal strip access
box and add a jumper to terminals 1 & 3.
3. Restore power to the unit. Observe that both blower
motors are running.
4. Adjustments to the speed of the motors can be made
by changing the input on the multi tap blower motors,
the speed control on EC Motors or by adjusting the
optional speed control.
A - Blower Speed Adjustment
MCV500/1000 - Both fresh air and exhaust air blowers
are direct drive multi-tap motors. Both blowers are factory
set at "high" speed for maximum airow. To determine air
ow setting, external static pressure readings will need to
be read across the MiniCore.
B - Air Balancing Adjustment
1. Remove plastic plugs in access panels (4 total).
2. With a manometer measure pressure drop [inches of
water column] diagonally across the MiniCore. Unit
CFM for 3 speed PMC motors is determined then by
referring to Table #1 on Page 5.
3. Repeat the same process for the other airow vector
of MiniCore.
4. System can be balanced by adding dampers to
ductwork or by adjusting blower speed.
C - Adjusting Blower Speed
3 speed PCM motors: Standard units have 2 terminal
blocks available (TB39 for exhaust and TB40 for supply)
where the speed taps on the 3 speed motors can be
changed. Move the Black wire from terminal #1 to terminal
#2 (med) or #3 (low) to lower blower speeds. An additional
115 or 230 volt speed control is available (part #s?) to
balance each blower with in these ranges. The speed
control is wired in line on the Black BK-102 or BK-101
wires before the terminal block, and is mounted externally
in a 2 gang work box on or near the MiniCore. Speed is
reduced by turning the knob counter clockwise until cfm is
met. See Table #1 on Page 5 for balancing data..
Variable speed ECM units: MiniCore Ventilators with
electronically commutated motors are shipped with blue
(BL-25 and BL-30) wires attached to terminal #1 of TB39
and TB40 in the blower compartment (See Figure ?)
locking the ECM in low speed mode, to switch to high speed
move the Blue wires to terminal #2. To use the Variable
speed option these blue wires need to be disconnected
from the relays (K163 & K164?) they are attached to and
0-10 VDC control wiring should be connected to terminals
4 through 7 detailed in the Low Voltage connections on
Page 2. See Wiring Diagram on Pages 7.
X - Maintenance
1. All motors use prelubricated sealed bearings; no
further lubrication is necessary.
2. Make visual inspection of lters, motor assemblies
and MiniCore Ventilator’s Heat exchange core during
routine maintenance.
3. Filters should be checked periodically and replaced
when necessary. Filters are located in front of Core
in the unit.
MC500-1ERV 3
A - Core Removal (See Figure 5)
1. Remove Access panels by opening each panel and
then releasing the spring loaded pins in the hinges by
pinching the tabs together.
2. Remove the center divider panel by removing the two
5/16" screws at with end of the panel on the side of the
MiniCore.
3. Carefully slide the core outwards.
B - Filter Removal (See Figure 6)
1. Open the Filter Access panel by opening the two