Ruskin MiniCORE MCV-500, MiniCORE MCV-1000 Installation Instructions Manual

INSTALLATION INSTRUCTIONS
MiniCOREVentilator
JANUARY 10, 2018
SUPERSEDES: NONE
ENERGY RECOVERY CORE
INSTALLATION INSTRUCTIONS FOR MINICORE VENTILATOR (MCV) WITH FACTORY
INSTALLED OPTIONS USED AS A STAND ALONE OR WITH SPLIT SYSTEMS UNITS
to the AHRI Air-to-Air Energy Recovery
Ventilation Equipment Certication Program in accordance with AHRI Standard 1060-2000. Actual performance in packaged
equipment may vary.
I - Shipping And Packing List
Package 1 of 1 contains:
1 - MiniCore Ventilator Assembly
II - Shipping Damage
Check unit for shipping damage. Receiving party should contact last carrier immediately if shipping damage is found.
III - General
These instructions are intended as a general guide and do not supersede local codes in any way. Authorities having jurisdiction should be consulted before installation.
IV - Requirements
When installed, the unit must be electrically wired and grounded in accordance with local codes or, in the absence of local codes, with the current National Electric Code, ANSI/NFPA No. 70.
V - Application
MiniCore ventilators are used as a stand alone indoor option for heat recovery ventilators used in light commercial applications. These ventilators conserve energy by transferring heat energy across two opposing air streams using a polymer core heat exchanger. This process works in the summer by rejecting the heat energy from incoming intake air and in the winter by conserving the heat energy from the exhaust air, allowing outdoor ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of the heating or air conditioning systems.
VI - Rigging Unit For Lifting
Danger of sharp metallic edges. Can cause injury. Take care
when servicing unit to avoid accidental contact with sharp
Electric shock hazard. Can cause injury or death.
VII - Installation
When choosing a location to mount the MiniCore Ventilator take into consideration ductwork layout as well
as access for future lter changes and Core cleaning. See
maintenance section on Page 4 for dimensions.
CAUTION
edges.
WARNING
Before attempting to perform any service or
maintenance, turn the electrical power to unit
OFF at disconnect switch(es). Unit may have
multiple power supplies.
MC500-1ERV
ETL Certied
per UL 1995 and
CSA 22.2
1. Maximum weight of unit is:
Model# MCV-500 MCV-1000
Net Weight
Ship Weight
2. Remove carton.
3. All panels must be in place for rigging.
4. Lift unit into place with a winch or jack.
182 222 230 270
Figure 1
Normal installation of the MiniCore Ventilator unit is hanging from the 4 corners using the included hanging kit though the units can be mounted on a shelf or on the
oor of a mechanical room using optional oor vibration
isolators.
1
The maximum weight of a MiniCore Ventilator is less than 225 lbs, Using 3/8" all-thread and the included hanging brackets is the preferable method of supporting the unit though the use of metal strap to hang the unit is also acceptable. When hanging the unit be sure to take into
account the need to provide access for lter replacement
and Core removal as well as blower balancing or removal through the bottom access panels.
While orientation of the heat exchanging core inside of
the MiniCore Ventilator is important for maximizing airow
orientation of the Ventilator itself is not, the MiniCore can be mounted in a vertical or horizontal fashion. Additionally the Fresh Air intake and Return intake can either be mounted on the side of the MiniCore or on the end by switching the duct collar and cover panel attached using
5/16" screws. See Figure 2.
Duct Option 1
High voltage:
115V: Connect the high voltage wires to L1 (Hot) &
L2 (Common), hook the ground wire to the provided grounding nut. See Wiring Diagrams on Pages 6-7.
208/230V: Single phase: Connect the high voltage wires to L1 (Hot) & L2 (Common) connect the ground wire to the provided ground nut. Check Voltage into the unit and adjust the voltage input to the transformer from 230V to 208V if necessary by switching wires at transformer. See
Wiring Diagrams on Pages 6-7.
Low voltage:
Standard units: Pass low voltage wire through the
provided knockout on the 2 gang terminal strip access box next to the power disconnect, and connect R to terminal #1 of terminal block TB38 and G to terminal #3.
See Wiring Diagrams on Pages 6-7 and Figure 3
The MiniCore Ventilator can be controlled by any dry contact closure like those in a CO
sensor with relay,
2
switch or timer.
Duct Option 2
Figure 2
Once the MiniCore Ventilator is hung connect ductwork to proper sectors of the unit with ¼" screws, use tape to seal seams. Supply and Exhaust are labeled on the outside of the cabinet and are determined by the orientation of the Core inside of the MiniCore Ventilator, a sticker on the Core will indicate the supply (outdoor air) vector. The Outside Air and Return connections will always be on the opposite side of the MiniCore Ventilator from their respective Supply and Exhaust blowers. See Figure 2.
Wiring
A ¾" knock out is provided for high voltage on the top and bottom of the high voltage disconnect switch mounted on the side of the unit.
Figure 3
ECM units: Pass the low voltage wiring through the provide knockout on the terminal access box and connect R to terminal #1 on 7 pin terminal box TB38 and G to #3. The default wiring for the MiniCore Ventilator with ECMs is to operate in the modulating speed mode terminals #4-7 are for speed control. To control both blowers in unison wire the 0-10vdc control signal to terminals 4 (10vdc+) and 5 (10vdc com) and add a jumper between terminals 4 and 6. If the Blowers are controlled independently then wire the exhaust blower signal to terminals 4 &5 and the supply signal to terminals 6 & 7, See Adjusting Blower Speed in Section IX - System Check for balancing information.
To use the motor in 2 speed operation attach the blue wires from TB39 and TB40 to relays K163 & K164 at pin #4. With the blue BL-25 and BL-30 wires in place the ECM with default to 2 speed operation. See Wiring Diagram
on page 7 and Figure 4.
2 MC500-1ERV
Figure 4
VIII - Operation
How It Works
The unit uses a dPoint polymer based ERV core which offers latent and sensible energy recovery with no cross contamination and no moving parts. In the summer outside heat and humidity is rejected from the incoming outside airstream and exhausted out the building, while in the winter the same process works to conserve wasted
heat and humidity making the building more efcient,
healthier and more comfortable.
The dense polymer membrane uses selective transfer technology to allow heat and water vapor to permeate through, while blocking contaminant compounds. The transfer is driven by temperature and humidity differentials between the airstreams. This allows you to reduce the size of the cooling system by 30% while still meeting outside air requirements.
The Cores material is designed to prevent mold and bacteria growth – the material was ISO 846 tested with a rating of 0 –, is designed to avoid virus transfer –ASTM Method F-1671 tested with 0 penetration –, and eliminate
cross contamination from exhaust air – 0% EATR certied
to AHRI 1060. It’s polymer construction also means that it is washable with water for easy cleaning.
IX - System Check
1. Turn off power to the unit
2. Remove access cover for the terminal strip access box and add a jumper to terminals 1 & 3.
3. Restore power to the unit. Observe that both blower motors are running.
4. Adjustments to the speed of the motors can be made by changing the input on the multi tap blower motors, the speed control on EC Motors or by adjusting the optional speed control.
A - Blower Speed Adjustment
MCV500/1000 - Both fresh air and exhaust air blowers
are direct drive multi-tap motors. Both blowers are factory
set at "high" speed for maximum airow. To determine air ow setting, external static pressure readings will need to
be read across the MiniCore.
B - Air Balancing Adjustment
1. Remove plastic plugs in access panels (4 total).
2. With a manometer measure pressure drop [inches of water column] diagonally across the MiniCore. Unit CFM for 3 speed PMC motors is determined then by referring to Table #1 on Page 5.
3. Repeat the same process for the other airow vector of MiniCore.
4. System can be balanced by adding dampers to ductwork or by adjusting blower speed.
C - Adjusting Blower Speed
3 speed PCM motors: Standard units have 2 terminal
blocks available (TB39 for exhaust and TB40 for supply) where the speed taps on the 3 speed motors can be changed. Move the Black wire from terminal #1 to terminal #2 (med) or #3 (low) to lower blower speeds. An additional 115 or 230 volt speed control is available (part #s?) to balance each blower with in these ranges. The speed control is wired in line on the Black BK-102 or BK-101 wires before the terminal block, and is mounted externally in a 2 gang work box on or near the MiniCore. Speed is reduced by turning the knob counter clockwise until cfm is met. See Table #1 on Page 5 for balancing data..
Variable speed ECM units: MiniCore Ventilators with electronically commutated motors are shipped with blue (BL-25 and BL-30) wires attached to terminal #1 of TB39 and TB40 in the blower compartment (See Figure ?) locking the ECM in low speed mode, to switch to high speed move the Blue wires to terminal #2. To use the Variable speed option these blue wires need to be disconnected from the relays (K163 & K164?) they are attached to and 0-10 VDC control wiring should be connected to terminals 4 through 7 detailed in the Low Voltage connections on
Page 2. See Wiring Diagram on Pages 7.
X - Maintenance
1. All motors use prelubricated sealed bearings; no further lubrication is necessary.
2. Make visual inspection of lters, motor assemblies and MiniCore Ventilator’s Heat exchange core during routine maintenance.
3. Filters should be checked periodically and replaced when necessary. Filters are located in front of Core in the unit.
MC500-1ERV 3
A - Core Removal (See Figure 5)
1. Remove Access panels by opening each panel and then releasing the spring loaded pins in the hinges by pinching the tabs together.
2. Remove the center divider panel by removing the two 5/16" screws at with end of the panel on the side of the MiniCore.
3. Carefully slide the core outwards.
B - Filter Removal (See Figure 6)
1. Open the Filter Access panel by opening the two
spring loaded latches to expose lters.
2. Slide lters outwards.
Figure 6
Figure 5
A
C
Unit A B C
MCV500
MCV1000
42 ¼
51
B
15 ½
20 ¾
4 MC500-1ERV
Blower Data for PSC Motors
MCV 500 Cabinet
External Static Pressure 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Low 649 634 586 510 402 313 233 129 NA NA NA
CFM
External Static Pressure 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
CFM
External Static Pressure (in wc)
CFM
External Static Pressure (in wc)
CFM
External Static Pressure (in wc)
CFM
Medium 786 768 709 618 487 379 282 157 NA NA NA
High 957 935 927 929 900 853 800 738 688 632 535
MCV1000 Cabinet
Low 1146 1124 1079 1042 1006 969 895 918 892 853 826
Medium 1388 1361 1307 1262 1218 1174 1084 1112 1080 1033 1001
High 1618 1586 1524 1471 1420 1368 1264 1296 1259 1204 1166
Table #1
Performance Test for MCV500 with ECM Motor
Supply
Input Voltage (v)
2 259 253 158 3 345 337 254 11 2 4 431 421 350 232 83 5 516 504 447 353 228 132 49 6 602 588 543 473 373 290 216 120 7 688 672 639 593 518 448 383 301 273 216 159 8 773 755 736 714 663 607 551 481 472 430 389 9 859 839 832 834 808 765 718 662 618 568 481
10 860 840 833 835 809 766 719 663 618 568 481
Input Voltage (v)
2 38 3 138 80 15 4 238 182 121 52 5 339 284 226 164 101 50 6 439 386 332 275 216 164 7 539 488 438 386 331 278 227 175 123 71 19 8 640 590 543 498 446 393 347 298 249 200 151 9 740 692 649 609 561 507 467 421 375 330 284
10 741 693 650 610 562 508 456 410 373 326 291
Input Voltage (v)
2 3 4 642 561 472 325 5 795 734 664 575 459 301 123 6 986 953 879 815 734 643 534 396 166 7 1237 1178 1129 1050 995 935 854 795 700 604 467 8 1377 1358 1347 1290 1214 1179 1114 1066 994 914 845 9 1408 1388 1392 1366 1339 1334 1300 1284 1263 1240 1186
10 1409 1394 1370 1349 1339 1317 1310 1290 1280 1255 1239
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Exhaust
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Performance Test for MCV1000 with ECM Motor
Supply
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
External Static Pressure (in wc)
Input Voltage (v)
2 3 4 393 333 232 122
CFM
5 582 508 420 346 208 137 36 6 775 721 651 567 506 431 266 196 120 7 974 915 860 796 735 671 588 522 414 284 208 8 1168 1119 1084 1028 987 938 881 837 757 694 612 9 1304 1270 1225 1187 1137 1094 1052 1004 945 888 801
10 1375 1352 1328 1308 1285 1232 1192 1159 1111 1071 1024
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
MC500-1ERV 5
Exhaust
115V / 230V (1 PH)
MCV500 / MCV1000 UNIT WIRING DIAGRAM
Mini Ventilator W/ Factory Installed Options
Unit#: 01-C45/C75/C150-02xH-01 / -21
6 MC500-1ERV
Notes:
1. Selective voltage terminal for proper unit voltage.
115V / 230V (1 PH)
MCV500E / MCV1000E UNIT WIRING DIAGRAM
Mini Ventilator W/ Factory Installed Options
Unit#: 01-C45/C75/C150-02xE-01 / -21
MC500-1ERV 7
25 to TB39-2, BL-30 to TB40-2; for high speed.
Notes:
1 Selective voltage terminal for proper unit voltage.
2 Omit BL-25, BL-30 for 0-10V Signal Control, Wire BL-25 to TB39-1 and BL-30 to TB40-1; for low speed, Wire BL-
START UP INFORMATION SHEET
VOLTAGE - MCV UNIT
Incoming Voltage L1-L2
Running Voltage L1-L2
Secondary Voltage
AMPERAGE - MCV MOTORS
Intake Motor: Nominal HP Rated Amps Running Amps
Exhaust Motor: Nominal HP Rated Amps Running Amps
Wheel Motor: Nominal HP Rated Amps Running Amps
AIRFLOW
Intake Design CFM Pressure Drop Calculated CFM
Exhaust Design CFM Pressure Drop Calculated CFM
Amb. db Temp Return Air db Temp* Tempered Air db Temp*
Amb. wb Temp Return Air wb Temp* Tempered Air wbTemp*
* Measure after 15 minutes of run time
INSTALLATION CHECK LIST
MiniCore Model # Serial #
Owner Owner Phone #
Owner Address
Installing Contractor Start Up Mechanic
 Inspect the unit for transit damage and report any damage on the carrier's freight bill.
 Check model number to insure it matches the job requirements.
Install eld accessories and unit adapter panels as required. Follow accessory and unit installation manuals.
Verify eld wiring, including the wiring to any accessories.
 Check all multi-tap transformers, to insure they are set to the proper incoming voltage.
 Verify blower wheels are centered. Realign if needed.
 Prior to energizing the unit, inspect all the electrical connections.
 Power the unit. Bump the motor relay to check rotation. If blower motor fans are running backwards, de-
energize power to the unit, then swap reversing plug on motors to change direction. Re-check.
 Perform all start up procedures outlined in the installation manual shipped with the unit.
 Fill in the Start Up Information as outlined on the opposite side of this sheet.
 Provide owner with information packet. Explain the thermostat and unit operation.
8 MC500-1ERV
Loading...