ruegg Saphir Giant 500, Saphir Giant, Lumo Front, Jade Front, Jade Tunnel Installation Manual

...
Page 1
CLASSIC-LINE ECO-LINE Installation Guide
3
CONTENTS
INTRODUCTION TO THE INSTRUCTIONS 5
Abbreviations 5 Images 6 Hatching 6 Pictograms 6 Terms 7
CURRENTLY APPLICABLE REGULATIONS 7
BEFORE INSTALLATION 8
GENERAL POINTS 9
Location 9 Combustion air intake 9 Fireplaces with door A1 / B1 (self closing) 10 Fireplaces with door A2 / B2 (not self closing) 10
AIR-FLOW MANAGEMENT 11
Operating modes and systems 11 Fireplaces S-type 15 Fireplaces K-type 16 Appliances on a socle 17 Sections for fireplaces with self closing door (A1 / B1) 18 Sections for fireplaces without self closing door (A / B2) 19 Fitting the sleeves 20 Fiiting the fresh air units 21 External air ducts 21
FLUE GAS EVACUATION / CHIMNEY FLUE 24
General guidelines 24 Minimum authorised sections 24
THERMAL INSTALLATION 25
General guidelines 25 Thermal insulating materials 25 Inflamable environment (inf) 26 Non inflamable environment (non-inf) 28 Substitute thermal insulation 30
SAFETY DISTANCES 31
At the front of the appliance 32 Hot air vents 32 Radiation area 33
Page 2
CLASSIC-LINE ECO-LINE Installation Guide
4
ADDITIONAL INSTALLATION INSTRUCTIONS 34
Preparation / functional test 34 Protective wall / concrete slab 34 Thermal insulation 34 Air sleeves 35 Placing the fireplace 35 Connecting up the external air 36 Connecting up the ambient air 36 Flue gas exhaust duct 36 Connecting up the convection air 37 Bearer frame 37 Room-side facing 38 Decorative beams 38
CHAMOTTE-LINED FIREPLACES 38
Jade Front / Saphir Front 39 Saphir Giant / Saphir Giant 500 41 Lumo Front 40 Jade Tunnel / Saphir Tunnel 41 Prisma / Prismalo 500 43 Ellipse 44 720 Compact 45 720 46 720 Giant 47 Pi Classic 48 Pi Compact 49 Pi-ccolo Classic 50 Pi-ccolo Compact 51
THERMOBRIKK® FIREPLACES 52
STEEL FIREPLACES 52
ADDITIONAL WEIGHTS FOR A1 APPLIANCES 53
AFTER INSTALLATION 53
USING YOUR FIREPLACE FOR THE FIRST TIME 54
DATA PLATE 54
INSTALLATION WITH HEAT STORAGE MATERIALS 55
Air circulation 55 Thermal insulation 56 Inflamable environment (inf) 57 Non inflamable environment (non-inf) 58 Heat storage jacket 59 Casing 60
TECHNICAL CHARACTERISTICS 61
Page 3
CLASSIC-LINE ECO-LINE Installation Guide
5
Introduction to the instructions
Abbreviations
non-inf. non-inflammable inf Inflammable Airwash Self-cleaning air system to prevent soot build-up on glass surfaces El 30 (non-inf) Fire resistance rating, fire resistance ≥ 30 minutes El 60 (non-inf) Fire resistance rating, fire resistance ≥ 60 minutes El 90 (non-inf) Fire resistance rating, fire resistance ≥ 90 minutes AIR-Direct Supply of combustion air, independent of ambient air ≥ Higher than or equal to ≤ Lower than or equal to < Lower than > Higher than ≈ About A1 / B1 fireplace
type
Automatically closing fireplace door
A / B2 fireplace type
Non-automatically closing fireplace door
VL Combustion air KL Convection air BImSchV German law relating to protection against emissions (D) LRV Swiss law relating to air purity (CH) S fireplace Fireplace with convection housing V fireplace Fireplace with convection housing and built-in extra fan K fireplace Fireplace without convection housing Tunnel version
fireplace
Fireplaces insert with retractable sliding door
DIN EN 13229 European standard for fireplace inserts, including four open hearth fireplaces for solid fuel 15a B-VG Energy efficiency agreement (AT) AEAI Association of Cantonal fire insurers organisations (CH) VHP Swiss Association of stove fitters and tilers (CH) Label Q Quality label for wood-fired heating systems (CH) Minergie Module Heating system approved for Minergie standard houses CH)
Page 4
CLASSIC-LINE ECO-LINE Installation Guide
6
Images
The explanations in this manual are valid for the entire range of Rüegg „Classic­Line“ fireplaces. For reasons of simplification all the same elements will be sum­marized and explained by means of 1 type of fireplace. This explains why some images may differ from your installation.
Hatching
Pictograms
NOTICE Handy information and advice
NOTICE Use a protective glove
WARNING
Warns of a very hot surface
WARNING
Potential risk for the product and the environment
Wood
Vent:
with or without active
retro-ventilation
Thermal insulation (mineral)
Thermal insulation; non-inf, RD ≥ 100 kg/m3
Wooden lintel
Concrete
Masonry or cellular concrete
Solid brick (fireplace break)
Chamotte; Facing/external surround
Non-inflammable panel
Page 5
CLASSIC-LINE ECO-LINE Installation Guide
7
Terms
Mineral materials
Flue gas regulator
with control
Inflammable environment
Cover
Thermal insulation layer
Cavity in the casing > on K fireplaces also convection
space
Hot air vent
Hearth
Concrete base
Thermal insulation layer
Thermal insulating layer
from the connector
Deflector
Hot air chamber
Hot air duct
(S fireplaces)
Throat
Hearth door
Decorative beam
Casing(non-inf) Thermal insulation layer
Door protective housing
Casing (non-inf)
Connector duct
Protective wall
Fireplace lining
(chamotte or steel)
Grid on facing
External air
External air
Fresh air regulator
Page 6
CLASSIC-LINE ECO-LINE Installation Guide
8
Currently applicable regulations
● Rüegg fireplace inserts are approved in accordance with European standard DIN EN13229.
● These instructions are based on the "Document of generally accepted prac­ tices " of the VHP, version 1.1 and on German regulations.
● Fireplace installation must be in conformity with national and local regulations. When installing a RÜEGG fireplace, in addition to the instructions contained
herein, you must ensure that the installation is in conformity with currently applicable laws and regulations in your country. These include, for example:
- Building safety regulations, professional regulations and fire regula- tions
- Laws and regulations relating to emissions
- Air purity laws and regulations
- Regulations and guidelines relating to fireplace fitters
- Laws and regulations regarding fire precautions (chimney sweep)
- Laws and regulations regarding fire insurance
● It is the fitter's responsibility to ensure conformity with the laws and regulations
in force in the country in question.
● Fireplaces should only be installed by qualified fitters.
Before installation
● Check immediately that there are no parts missing from the fireplace and that
it has not suffered any damage in transit. Check also that the dimensions are correct, that the door opens without undue noise and that the fireplace pre­sents no defect.
● Check before installation that the fireplace glass door
functions correctly. Remove the security screws from the counterweight and remove any other transport safety elements. Any defects, such as operating diffi­culties or excessive noise, must be reported to your dealer before starting the installation.
● Read the installation instructions carefully.
● Remove all the documents and accessories from the fireplace and give the
instruction manual to the end-user.
Page 7
CLASSIC-LINE ECO-LINE Installation Guide
9
General points
Location
Open hearth fireplaces must not be installed:
- in stairways, except in residential buildings with no more than two apart-
ments
- in shared corridors
- in rooms where inflammable or explosive products are used, stored or
manufactured
- in rooms or apartments where air is removed on a continuous basis by a
fan system. This requirement does not apply to rooms where air is re­moved by ventilation systems fitted with safety appliances which safely prevent the formation of a depression in the room in which the fireplace is installed or which do not allow the formation of a depression under 0.04 mbar. These requirements do not apply to rooms fitted with ventilation systems for the installation of heating systems sealed against ambient air.
Combustion air intake
Open hearth fireplaces can be installed in rooms which do not have external combustion air intake flues, provided:
- they have at least one door opening to the outside, or a window that can
be opened, or they are directly or indirectly connected to other rooms which can provide combustion air intake. If the fireplace is installed in an apartment or similar, the combustion air intake must be connected only to the room in question or to those rooms belonging to the apartment. Fire­places can only be installed in the afore mentioned locations if they have a combustion air intake of at least 360 m³ per hour per m² of hearth open­ing. These requirements do not apply to fireplaces that can be operated independently or separately from ambient air.
Open-hearth fireplaces can be installed in rooms with direct external combustion air intake, provided:
- An external air flue corresponding to the fireplace insert is connected to
the exterior from the room in question. The flue must be fitted with an hermetically-closing regulator in the room in which the fireplace is in­stalled. The regulator position must be clearly visible.
- External air flues are manufactured and installed in conformity with na-
tional construction regulations, so that in apartment buildings of more than two floors, they fit over the firewalls so as to prevent the spread of fire or smoke to other floors or rooms.
Page 8
CLASSIC-LINE ECO-LINE Installation Guide
10
A1/B1 fireplaces
A1 and B1 fireplaces are fitted with an automatically closing door, certified and tested in conformity with European standard DIN EN 13229 - A1. Open hearth operation is forbidden, nor can these fireplaces be converted for open hearth operation. The fireplace insert can be connected to a chimney flue for multiple use. The effective height of the chimney flue must be at least 4 m, from the flue gas intake. European standard DIN 4705/EN 13384-1 applies for the dimensions of the chimney flue for the installation of a fireplace insert. Calculations for type AI fireplace inserts are based on the volume of combustion air when the fireplace is operating with its door closed. Type AI fireplace inserts meet the following re­quirements:
Automatically closing door
Efficiency > 70 %
Nominal heating capacity < 11 kW
A2/B2 fireplaces
A2 and B2 fireplace inserts can also operate under open hearth conditions. It is forbidden for the chimney flues to have multiple connections. The fireplace insert must be connected to its own chimney flue, in other words only one heating unit can be installed per chimney flue.
NOTICE You should enquire as to whether multiple connections are legal in
your country.
Page 9
CLASSIC-LINE ECO-LINE Installation Guide
11
Air-flow management
Operating modes and systems
Rüegg fireplace inserts are designed so that the combustion air can be
drawn to the fireplace separately from the ambient air, for closed-door opera­tion. The combustion air is taken from outside the room in which the fireplace is installed and is channelled directly to the fireplace where it is drawn into the fire. The system is called AIR-Direct (= separate from ambient air)
● The second system for drawing air into the fireplace is the convection air
system, which is used mainly for heating the ambient air. Fireplaces in which the convection air is guided by a convection jacket are called S fireplaces, while those without the jacket are called K fireplaces. In this system, the con­vection air is taken in through a cavity in the fireplace casing and comes out into the room through vents in the fireplace apron.
● If the fireplace insert also needs to operate with the door open, the convection
air system must be connected to an external air source. This means that the external air will be heated by the convection air system and drawn into the room and will arrive in the fireplace as combustion air, going through the open door.
WARNING
If an open fired appliance is only supplied with fresh air by the AIR
DIRECT system, and the room is characterized by an airtight con­struction, a trouble free function cannot be guaranteed!
WARNING
Internal or external fans may never be attached to the combustion
air supply (AIR DRECT system) they are only used for advanced convection air supply.
The diagrams below show a number of possible variations, with their correspond­ing airflows.
Page 10
CLASSIC-LINE ECO-LINE Installation Guide
12
Fireplace type: Fireplace S, type A/B2 Operating modes: open or closed (→ closed in the diagram)
External air
Ambient air
Convection air
Airwash air
Flue gas
Page 11
CLASSIC-LINE ECO-LINE Installation Guide
13
Fireplace type: Fireplace S, type A/B2 Operating modes: open or closed (→ open in the diagram)
External air
Ambient air
Convection air
Airwash
Flue gas
Page 12
CLASSIC-LINE ECO-LINE Installation Guide
14
Fireplace type : Fireplace S, type A1/B1 Operating modes: closed only
External air
Ambient air
Convection air
Airwash air
Flue gas
Page 13
CLASSIC-LINE ECO-LINE Installation Guide
15
S-Fireplaces
On S fireplaces without a base/fan chamber, the openings for the com­bustion air inlet sleeves (VL) and the convection air inlet sleeves (KL) are laser pre-cut in the housing.
Depending on your installation, the blanking pieces can be removed on the side or at the rear, and Ø150 mm air inlet sleeves fitted. You
should take into account the amount of air required..
The convection air outlet sleeves (KL) are factory fitted.
NOTICE
The lids of not used open-
ings may never be taken away!
Convection air inlets
Attachments for fresh
air units (optional)
Convection air outlet (KL)
Fresh air inlet (VL)
AAmmbbiieenntt aaiirr iinnlleett ((KKLL))
Convection air outlet (KL)
Attachments for fresh
air units (optional)
AAmmbbiieenntt aaiirr iinnlleett
((KKLL))
Convection air outlet
(KL)
Attachments for fresh
air units (optional)
AAmmbbiieenntt aaiirr iinnlleett
((KKLL)
)
Page 14
CLASSIC-LINE ECO-LINE Installation Guide
16
K-fireplaces
On K fireplaces without a base/ fan chamber, the openings for the com­bustion air inlet sleeves (VL) are la­ser pre-cut on the housing. Depend­ing on your installation, the blanking pieces can be removed on the side or at the rear, and Ø150 mm air inlet sleeves fitted. You should take into account the amount of air required. As K fireplaces are not fitted with a convection jacket, the convection air will circulate within the casing through the openings that you will have made for this. Make sure that the inner lining of the casing is dust free and abrasion resistant.
For casings made of heat storage and radiation materials, for which a convection circuit is generally not fit­ted, there must be a sufficient supply of external air to the room in ques­tion for open hearth operation. The openings are therefore precut by la­ser in the top of the glass panel pro­tective housing. For casings made of heat storage and radiation materials, without convection, these openings can be connected up, in line with air requirements. The openings are fit­ted with fresh-air connector units with sleeves (article no. 12.59.0050), to which a fresh air conduit of Ø150 mm can be fitted.
Attachments for fresh air
units (optional)
External air inlet (VL)
AAmmbbiieenntt aaiirr iinnlleett ((KKLL))
Attachments for fresh air
units (optional)
Page 15
CLASSIC-LINE ECO-LINE Installation Guide
17
Appliances on a socle
On appliances with a socle or venti­latorbox there are only openings precut for the ambient air inlet (KL)
Der Eintrittsstutzen für die Verbren­nungsluft (VL) ist bereits ab Werk montiert.
NOTICE
The lids of not used openings may never be taken away! For a trouble free open use of the fireplace, the room must be suffi-
ciently supplied with fresh air from outside. The only use of the com­bustion air entry (VL) in this case is absolutely not sufficient.
External air inlet
(VL)
Page 16
CLASSIC-LINE ECO-LINE Installation Guide
18
Sections for fireplaces with self closing door (A1/B1)
For K fireplaces, the sections are the same as the V/S fireplaces (Ø150 mm = 175 cm²).
For A1 fireplaces with an automatically closing door (= solely in closed-door operating mode), the table below shows the minimum requirements in terms of number of connections:
* Colar-ø 125 mm
VL inlet
(external air)
KL inlet
(ambient air)
KL inlet
(external air)
KL outlet
Axinit Front S
1 4 0 4 175 cm2
700 cm2 0
cm2
700 cm2
Ellipse S/K
1 2 0 2 175 cm
2
350 cm
2
0 cm2
350 cm
2
Ellipse V
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Jade Front S/K
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Jade Tunnel S/K
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Larimar Front S
1 2 0 2 175 cm2
350 cm2 0
cm2
350 cm2
Lumo S/K
1 2 0 2
175 cm
2
350 cm
2
0 cm2
350 cm
2
Pi Classic V/S
1 4 0 4
175 cm
2
700 cm
2
0 cm2
700 cm
2
Pi Compact V/S
1 4 0 4
175 cm
2
700 cm2
0 cm2
700 cm
2
Pi-ccolo Classic V/S
1 2 0 2
* 123 cm
2
350 cm
2
0 cm2
350 cm
2
Pi-ccolo Compact V/S
1 2 0 2
* 123 cm
2
350 cm
2
0 cm2
350 cm
2
Prisma S/K
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Prisma V
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Prismalo 500 S/K
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Prismalo 500 V
1 2 0 2
175 cm2
350 cm2 0
cm2
350 cm2
Saphir Front S/K
1 4 0 4
175 cm2
700 cm2 0
cm2
700 cm2
Saphir Tunnel S/K
1 4 0 4 175 cm2
700 cm2 0
cm2
700 cm2
Saphir Giant S/K
1 4 0 4 175 cm2
700 cm2 0
cm2
700 cm2
Saphir Giant 500 S/K
1 4 0 4
175 cm2
700 cm2 0
cm2
700 cm2
720 Compact K
1 - 0 -
175 cm2 750
cm2 0
cm2 750
cm2
720 S/K (ECO)
1 2 0 2 175 cm2
350 cm2 0
cm2
350 cm2
720 V
1 2 0 2 175 cm2
350 cm2 0
cm2
350 cm2
720 Giant S/K
1 2 0 2 175 cm2
350 cm2 0
cm2
350 cm2
720 Giant V
1 2 0 2 175 cm2
350 cm2 0
cm2
350 cm2
Page 17
CLASSIC-LINE ECO-LINE Installation Guide
19
Sections for fireplaces without self closing door (A/B2)
For type A fireplaces (= open and closed door operation), the table below shows
the minimum requirement in terms of number of connections:
VL inlet
(external air)
KL inlet
(ambient air)
KL inlet
(external air)
KL outlet
Axinit Front S
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
Ellipse S/K
1 2 2 4 175 cm2
350 cm2
350 cm2
700
cm2
Ellipse V
1 1 1 2 175 cm2
175 cm2
175 cm2
350 cm2
Jade Front S/K
1 2 1 3
175 cm2
350 cm2
175 cm2
525 cm2
Jade Tunnel S/K
1 2 2 4 175 cm2
350 cm2
350 cm2
700 cm2
Larimar Front S
1 2 1 3
175 cm2
350 cm2
175 cm2
525 cm2
Lumo S/K
1 2 1 3
175 cm2
350 cm
2
175 cm
2
525 cm
2
Pi Classic V/S
1 2 2 4
175 cm
2
350 cm
2
350 cm
2
700 cm
2
Pi Compact V/S
1 2 2 4
175 cm
2
350 cm
2
350 cm
2
700 cm
2
Pi-ccolo Classic V/S
1 1 1 2 * 123 cm
2
175 cm
2
175 cm
2
350 cm
2
Pi-ccolo Compact V/S
1 1 1 2
* 123 cm
2
175 cm2
175 cm
2
350 cm
2
Prisma S/K
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
Prisma V
1 1 1 2
175 cm2
175 cm2
175 cm2
350 cm2
Prismalo 500 S/K
1 2 1 3
175 cm2
350 cm2
175 cm2
525 cm2
Prismalo 500 V
1 1 1 2 175 cm2
175 cm2
175 cm2
350 cm2
Saphir Front S/K
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
Saphir Tunnel S/K
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
Saphir Giant S/K
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
Saphir Giant 500 S/K
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
720 Compact K
1 0 0 0
175
cm2 0 cm2 0 cm2 0 cm2
720 S/K (ECO)
1 2 2 4 175 cm2
350 cm2
350 cm2
700 cm2
720 V
1 1 1 2 175 cm2
175 cm2
175 cm2
350 cm2
720 Giant S/K
1 2 2 4
175 cm2
350 cm2
350 cm2
700 cm2
720 Giant V
1 1 1 2
175cm
2
175 cm2
175 cm2
350 cm2
* colar-ø 125 mm
WARNING
In V-appliances (with built in ventilator) the number of collars can be
reduced because of the forced higher air volume. The ambient air in­takes must be mounted symmetrically on the fireplace to ensure the air heats evenly ant that the installation will not overheat on one side!
Page 18
CLASSIC-LINE ECO-LINE Installation Guide
20
Fitting the sleeves
Tools: – Hammer – Pozidriv PZ 3 screwdriver – Silicon seal (thermal resistance ≥ 250 °C)
1. Use a hammer to break out the blanking piece
2. Remove the blanking pieces
3. Install the Ø150 mm air sleeves
4. Fit the sleeve tabs into the slots in the opening
5. Fold down all the tabs 90°
NOTICE
The sleeves must be firmly fitted without any play. The connection can
be sealed with silicon sealer of temperature resistance ≥ 250° C.
Page 19
CLASSIC-LINE ECO-LINE Installation Guide
21
Fitting the fresh air units
Blanking pieces
1. Use a hammer at the points marked in red to break out the blanking piec­es
The last point should be broken by
by bending, instead of using the
hammer
5. Check that the fresh air units are
correctly fitted.
2. You can install one or two addi­ tional fresh air units. Make sure you remove the corresponding blanking piece when positioning the unit on the left and/or on the right
4. Fit each fresh air unit using the
Parker screws supplied.
3. Use a hammer to break out the blanking pieces and fit the sleeves as in the instructions on page 19. To avoid any damage, you can use a wooden block placed inside the unit
Tools : – Hammer
– Wooden block 75x75 mm – Pozidriv PZ 3 screwdriver
Wooden block H ≈ 75 mm
Page 20
CLASSIC-LINE ECO-LINE Installation Guide
22
External air ducts
● Use, if possible, round air supply ducts with a smooth internal surface.
● The internal surface of air supply ducts made of mineral materials or masonry should be abrasion resistant
● The air supply ducts must be directly connected at their base or laterally to the fireplace.
● The air supply ducts must be insulated with a non-inflammable material 3 cm thick.
● The end of the air supply duct must be fitted with a removable fine mesh grid, to prevent animals entering.
● All the systems must have an adequate supply of fresh air, with the appropri-
ate ducts and opening diameters, otherwise the system will not operate prop perly in open or closed door modes.
● If the fitter estimates that ducts of smaller diameter will satisfy combustion air requirements, then any such installation is at his own risk and responsibility, as the manufacturer cannot guarantee proper operation under these conditions.
● Do not place the end of the external air conduit next to a chimney flue or air exhaust outlet. Avoid also draw­ing external air from an area giving onto a road with heavy traffic.
● Convection air ducts:
To prevent cold air ingress, thermal bridges or condensation,
hermetically closing valves should be fitted.
● Combustion air ducts:
To prevent cold air ingress, thermal bridges or condensation, non-
hermetically-closing valves should be fitted, and a free section of 10 cm
2
should be kept, which corresponds to an opening of Ø 3 cm. This prevents dangerous build-up of gases.
Page 21
CLASSIC-LINE ECO-LINE Installation Guide
23
L
max
Convection air
Convection air
Combustion air
Air-Direct
Convection air
Convection air
VL / Air
-Direct
Top of the hearth
Non-hermetiocally-
closing valve
Hermetically­closing valve
Exception
: H
max
≤ 6 m
Normal: H
max
● The external air feed to the fireplace from the façade must never be fitted
higher than the top of the hearth. Exceptions:
When the fireplace is fitted with the AIR-Direct system (VL) ; → in this case: H
max
≤ 6 m from the top of the hearth, if the fireplace projects
above the suction source.
If the fireplace uses a convection air system with a built-in fan; → in this case: H
max
≤ 6 m from the top of the hearth
External air ducts with a section of 175 cm
2
(15 cm) should not exceed the
following maximum lengths:
→ fireplace without ventilation
With semi-ridgid ductings („Aluflex“): L
max
= 3 m
With ridgid smooth ducts: L
max
= 4 m
→ fireplace with ventilation
With semi-rigid ductings („Aluflex“): L
max
= 6 m
With ridgid smooth ducts: L
max
= 8 m
Page 22
CLASSIC-LINE ECO-LINE Installation Guide
24
Flue gas evacuation/Chimney flue
General guidelines
● Avoid chimney flues larger than those listed in the table, as these could cause the following issues:
- the flue gases cool too fast, which might cause condensation in the
chimney flue.
- insufficient chimney flue draft
● When wood fuel is used, the smoke exhaust system must be designed and certified in consequence.
● The chimney flue must never be supported by the fireplace. The chimney flue must be self-supporting and separated from the fireplace.
● When possible, a chimney flue of L < 4 m in length should not be used. To obtain a stable draft for a chimney flue of length ≤ 4 m, an extractor fan can be installed.
● If the fitter estimates that a flue of smaller section will satisfy requirements, then any such installation is at his own risk and responsibility.
● New chimney flues of Ø25 or 30 cm, with a useful length of L ≥ 8 m or over, and with good thermal insulation, can have the section reduced by a maxi­mum of 5 cm.
Minimum authorised sections
Minimum chimney flue sections
Round Ø [cm]
Square [cm]
Comment
Axinit Front S 25 25 x 25 Ellipse S/K 25 25 x 25 Jade Front S/K 25 25 x 25 Jade Tunnel S/K 25 25 x 25
non reducible *
Larimar Front S
20 20 x 20
Lumo S/K
25 25 x 25
Pi Classic + Compact V/S
30 30 x 30
Pi-ccolo Classic + Compact V/S
25 25 x 25
Prisma S/K
25 25 x 25
Prismalo 500 S/K
20 20 x 20 Saphir Front S/K 30 30 x 30 Saphir Tunnel S/K 30 30 x 30
non reducible *
Saphir Giant S/K 30 30 x 30 Saphir Giant 500 S/K 30 30 x 30 720 Compact K 20 20 x 20 720 V/S/K (ECO) 25 25 x 25 720 Giant V/S/K 25 25 x 25
non reducible *
* on fireplaces operating in open-hearth mode (A/B2)
Page 23
CLASSIC-LINE ECO-LINE Installation Guide
25
Thermal installation
General guidelines
● Fireplaces placed in a chimney system must always be thermally insulated with regard to the building walls, floors and ceilings.
● Chimney systems installed in buildings with inflammable walls, floors or ceil­ings, must be clad with thermal insulation that meets the strictest requirements (see table).
● Only insulation materials meeting the quality standards given below should be used and must be approved by the relevant authorities (such as VKF in Swit­zerland or DIBT in Germany).
Thermal resistance of the thermal insulation must be at least 700° C
● Thermal insulating materials that are in contact with circulating hot air (on all the K-type fireplaces) must also be fitted with an abrasion resistant lining (e.g. metal plates) with permanent thermal resistance.
● To prevent unpleasant odours during fireplace operation, only use thermal insulation containing low-volatile bonding agents. Information on the composi­tion of thermal insulation maybe obtained from the manufacturers.
Thermal insulating materials
Insulating material
Presenta-
tion
Use
Thermal conducti-
bility
Maximum temperature of
use
Apparent
density
W/(m K) °C kg/m3
Mineral fibres / scoria fibres Panels
Installation of the
fireplace inset
0.035 700 - 900 100 - 180
Mineral fibres / scoria fibres on one side, with a lattice-
reinforced pure aluminium lining
Bats
Insulation
Connecting pipe
0.035 750 80
Page 24
CLASSIC-LINE ECO-LINE Installation Guide
26
Inflamable environment (inf)
In conformity with the requirements of standard EN 13229, the following insulation thicknesses are applicable:
side / rear *
Tube Floor
Side and rear
walls
Ceiling
Mineral fibres
V [cm]
Concrete
slab
B1 [cm]
Mineral fibres
B2 [cm]
Protective
wall
W1 [cm]
Mineral fibres
V [cm]
Concrete
slab
B1 [cm]
Mineral fibres
B2 [cm]
Axinit Front S 3 12 6 10 8/10* 12 2 Ellipse V/S/K 3 12 0 10 7 12 2 Jade Front S/K 3 12 0 10 6 12 2 Jade Tunnel S/K 3 12 0 10 7 12 2 Larimar Front S 3 12 6 10 8 12 2 Lumo S/K 3 12 0 10 6 12 2 Pi Classic + Compact** V/S 3 12 4/0** 10 6/11** 12 2 Pi-ccolo Classic + Compact V/S
3 12 0 10 7 12 2 Prisma V/S/K 3 12 0 10 6 12 2 Prismalo 500 V/S/K 3 12 0 10 6 12 2 Saphir Front S/K 3 12 0 10 6 12 2 Saphir Tunnel S/K 3 12 0 10 7 12 2 Saphir Giant S/K 3 12 0 10 6 12 2 Saphir Giant 500 S/K 3 12 0 10 6 12 2 720 Compact K 3 12 0 10 15 12 2 720 V/S/K (ECO) 3 12 0 10 7 12 2 720 Giant V/S/K 3 12 0 10 7 12 2
Fireplace K
D
2
D
1
W2
W1
B
2
B
1
B
2
B
1
Fireplace S
V
W2
W1
D
2
D
1
V
Page 25
CLASSIC-LINE ECO-LINE Installation Guide
27
WARNING These insulation dimensions apply to convection air systems and do
not apply to heat storage fireplaces!
Floor (B1+B2)
Lay a concrete slab of a thickness of at least 12 cm directly on the floor
where the fireplace is to be installed. The concrete slab must seamlessly cov­er the whole of the installation area, inside the appliance casing cavity.
Under the fireplace insert, the concrete slab must also be fitted with thermal insulation.
WARNING
The fireplace adjustable feet must stand directly on the concrete
slab.
Side and rear walls (W1+W2)
● A protective wall at least 10 cm thick should be placed directly on the build­ing wall. It must be made of brick, concrete or similar material. The protective wall must be laid seamlessly to cover the whole of the building wall inside the appliance casing cavity.
● The thermal insulation between the protective wall and the fireplace insert must be laid seamlessly to cover the whole of the protective wall inside the appliance casing cavity.
Ceiling (D1+D2)
If the fireplace casing cavity above the fireplace inset extends to the ceiling,
then the ceiling needs to be protected by a layer of thermal insulation at least 12 cm thick.
. The thermal insulation is laid on a non-inflammable cover, with a permanent,
unchanging thermal resistance.
● If the fireplace casing cavity above the chimney inset does not extend to the ceiling, the cover does not need to be thermally insulated, but needs to be at least 50 cm away from the ceiling.
Connector (V)
The whole of the connector must be covered by thermal insulation 3 cm thick.
Page 26
CLASSIC-LINE ECO-LINE Installation Guide
28
Non inflamable environment (non-inf)
In conformity with the requirements of standard EN 13229, the following
insulation thicknesses are applicable:
Tube Floor
Wall
side and rear
Ceiling
Mineral fibres
V [cm]
Mineral fibres
V [cm]
Mineral fibres
W [cm]
Mineral fibres
D1 [cm]
Mineral fibres
V [cm]
Axinit Front S 3 6 8/10* 6 2 Ellipse V/S/K 3 0 7 6 2 Jade Front S/K 3 0 6 6 2 Jade Tunnel S/K 3 0 7 6 2 Larimar Front S 3 6 8/ 6 2 Lumo S/K 3 0 6 6 2 Pi Classic + Compact** V/S 3 4/0** 6/11** 6 2 Pi-ccolo Classic + Compact V/S 3 0 6 6 2 Prisma V/S/K 3 0 7 6 2 Prismalo 500 V/S/K 3 0 7 6 2 Saphir Front S/K 3 0 6 6 2 Saphir Tunnel S/K 3 0 7 6 2 Saphir Giant S/K 3 0 6 6 2 Saphir Giant 500 S/K 3 0 6 6 2 720 Compact K 3 0 15 6 2 720 V/S/K (ECO) 3 0 7 6 2 720 Giant V/S/K 3 0 7 6 2
side / rear *
V
W
D
2
≥12
cm
D
1
Fireplace K
B
Fireplace S
V
W
D
2
≥12
cm
D
1
B
Page 27
CLASSIC-LINE ECO-LINE Installation Guide
29
WARNING These insulation dimensions apply to convection air systems and do
not apply to heat storage fireplaces !
Floor (B)
● The fireplace-inset adjustable feet must stand directly on a load-bearing floor
● The load bearing floor under the fireplace inset must be fitted with thermal insulation.
The side and rear walls (W)
● No protective wall needed.
● The thermal insulation corresponds exactly to the insulation for inflammable
building walls or walls requiring a protective covering and seamlessly covers the whole of the building wall inside the fireplace surround cavity.
Ceiling (D)
● The room ceiling must be at least 12 cm thick.
● If the fireplace casing cavity above the fireplace inset extends to the ceiling, then the ceiling must be fitted with a layer of thermal insulation at least 6 cm thick, that is laid directly on the ceiling.
The thermal insulation is laid on a non-inflammable cover, with a permanent,
unchanging thermal resistance.
Connector (V)
The whole of the connector must be covered by thermal insulation 3 cm thick.
Page 28
CLASSIC-LINE ECO-LINE Installation Guide
30
Substitute thermal insulation
Substitute thermal insulation may be used instead of the protective wall, providing it is certified and designed for this purpose. If this type of insulation is used, the thickness of the total lagging (insulation/protective wall) may be reduced by up to 50%.
If the protective wall and thermal insulation to the front of an inflammable
wall are replaced by substitute thermal insulation, the insulation must be ap­plied in two layers and the panel joints staggered.
When certified thermal insulation is used for lagging, the reduction in total
lagging thickness (insulation/protective wall) is given by the manufacturer.
Substitute thermal insulation must have proven long-term intrinsic static
stability.
Thickness ≈ 50 %
Thickness = 100 %
Insulation by means of:
Protective wall
+
Mineral
isolation
Different insulation product
2. layer
1. layer
Page 29
CLASSIC-LINE ECO-LINE Installation Guide
31
Calcium silicate → SILCA 250 KM
Certification DIBT no. Z-43.14-117 Certification field of application Construction of ceramic fireplaces and stoves Construction material rating EN 4102-4 A1, non-inflammable Apparent density (±10 %) EN 1094-4 250 kg/m3 Porosity EN 1094-4 ca. 90 % Compression strength EN 1094-5 1.4 MPa Conductivity λ at 200° C EN 993-15 ≤ 0.1 W/mK Thermal expansion at 500° C 0.2 % Standard formats, panels; W x L [mm] 500…1200 x 500…1900 Standard thicknesses [mm] 30…100
Vermiculite → Isoboard T-700
Certification DIBT no. Z-43.14-131 Certification field of application Construction of ceramic fireplaces and stoves Construction material rating EN 4102-4 A1, non-inflammable Apparent density (±10 %) EN 1094-4 375 kg/m3 Porosity EN 1094-4 ca. 90 % Compression strength EN 1094-5 1.15 MPa Conductivity λ at 200° C EN 993-15 ≤ 0.175 W/mK Thermal expansion at 500° C ≤ 0.52 % Standard formats, panels; W x L [mm] 500…1200 x 500…1900 Standard thicknesses [mm] 30…100
Example 1: 1 On the vertical scale, choose the thick-
ness required with mineral wool insulation. 10 cm
2 Draw a horizontal line over to the red line.
3 Draw a vertical line downwards from the point of intersection. → ≈ 8 cm
1.
2.
3.
SILCA 250 KM
Example 2: 1 On the vertical scale, choose the
protective wall with mineral wool insulation thickness. 20 cm
2 Draw a horizontal line over to the red line
3 Draw a vertical line downwards from the point of intersection → ≈ 10 cm
1.
2.
3.
SILCA 250 KM
Page 30
CLASSIC-LINE ECO-LINE Installation Guide
32
Safety distances
At the front of the appliance
An inflammable coating or lining must be laid at least 40 cm in front and on each side of the loading door in solid-fuel-fired fireplaces.
In case a bench is built, the same distance is to be respected towards the fire opening.
On corner models as e.g. 720, 720 Giant, 720 Compact, Ellipse, etc., if the side distances cannot be realized, the inflammable lin­ing must be put to the wall.
If a fire bench is installed, the lining should also extend at least 40 cm out from the loading door.
Hot air vents
There must be no built-in or inflammable elements (e.g. a wooden ceiling) within 30 cm to the side or 50 cm above the hot air vents.
≥ 40
cm
≥ 40 cm
≥ 40
cm
≥ 30
cm
≥ 50
cm
≥ 40
cm
Page 31
CLASSIC-LINE ECO-LINE Installation Guide
33
≥ 5 cm
X
Radiation area
In front of the fireplace door, you have to respect a distance of X cm towards any combustible building material. If a both sides areated protection wall is built, X/2 cm is then sufficiant.
A minimum distance of 5 cm towards combustible building materials is to be respected from the side elements of the heating installation. This distance must be exposed to an air stream, that no heat congestion can ap­pear.
X
[cm]
X
[cm]
Axinit Front S 170 Prisma V/S/K 80 Ellipse V/S/K 80 Prismalo 500 V/S/K 80 Jade Front S/K 80 Saphir Front S/K 80 Jade Tunnel S/K 80 Saphir Tunnel S/K 80 Larimar Front S 160 Saphir Giant S/K 80 Lumo S/K 80 Saphir Giant 500 S/K 80 Pi Classic V/S 100 720 Compact K 160 Pi Compact V/S 100 720 V/S/K (ECO) 80 Pi-ccolo Classic V/S 80 720 Giant V/S/K 80 Pi-ccolo Compact V/S 80
Page 32
CLASSIC-LINE ECO-LINE Installation Guide
34
Additional installation instructions
Preparation / functional test
Remove all the transport securing screws
WARNING
On the 720, 720 Compact and 720 Giant
appliances, remove 2 screws!
Check the individual elements:
- raise and lower the hearth door
- swivel the hearth door
- open and close the air intake control
Remove any accessories or documents to be found in the hearth.
● S type appliances can be fitted with an optional ventilation kit. Instructions for fitting the kit are to be found in the packaging. The ventilation kit is installed at the same time as the fireplace. Fan and speed regulator electrical connections should be made before installation, by a qualified electrician. To avoid un­wanted noise and vibrations, the fan should only be fitted with the speed regu­lator supplied with it.
● The surface on which the fireplace is to be installed must be statically load­bearing. An appliance must not be laid directly on a floating floor.
● Electric wiring within the casing must be placed near the floor and insulated when required. PVC-containing protective sleeves must not be used !
● The chimney flue must meet installation requirements.
Protective wall / concrete slab
● With regard to inflammable walls or those requiring protection, the walls within the fireplace casing must be fitted with a suitable protective wall to provide the required thermal insulation.
● With regard to an inflammable floor or one requiring protection, a concrete slab must be laid directly on the load-bearing floor.
Thermal insulation
● All surfaces within the fireplace casing must be fitted with thermal insulation, in conformity with requirements, while the fireplace is being installed..
● Thermal insulation on all K fireplaces must be made of abrasion resistant ma­terials.
Page 33
CLASSIC-LINE ECO-LINE Installation Guide
35
Air sleeves
Blanking pieces for unused air sleeves must not be removed.
● Unused air outlet sleeves (convection air) must be covered with airtight
blanking pieces
Placing the fireplace
● Fit the four adjustable legs and retract them completely (they must not extend past the appliance jacket)
● Using the carrying handles and/or straps to move the appli­ance to where you wish to install it. Check that the carrying handles are screwed in firmly to the appliance jacket.
● Set the fireplace down on the pre-prepared load-bearing surface
4 screws per carrying handle
→ Corner fireplaces need 2 carrying handles, while other models need 4 handles
Page 34
CLASSIC-LINE ECO-LINE Installation Guide
36
● In buildings with high acoustic standards, check the conformity of the appli-
ance's acoustic insulation with regard to the floor where it is to be installed.
WARNING
The fireplace must be set down on the four adjustable feet. The bearing surface must be sufficiently strong to bear a load of up to 140 kg per foot. Additional static support can be added at a later stage, using point bearings. K fireplaces must not be placed directly against the thermal insulation at the rear and on the sides. A continuous convection gap of 6 to 10 cm should be left.
● Thermal insulation should be placed under the bottom of the appliance.
● Adjust the horizontal and vertical position of the fireplace, using the four ad
justable feet and a spirit level.
Connecting up the external air
● Follow the instructions on pages 15 to 22 to connect up the external air.
● Fit the fresh air regulators as near as possible to the facing.
● When fitting the regulator controls, make sure they are readily accessible..
Connecting up the ambient air
● Follow the instructions on pages 15 to 22 to connect up the ambient air.
● Only place filters in the intake vent for appliances fitted with a fan.
Flue gas exhaust duct
● The following materials are allowed:
- steel sheet, thickness ≥ 2 mm
- chrome-plated steel sheet, thickness ≥ 1 mm or in accordance with manufac-
turer recommendations
● A smoke regulator must be fitted in the connector:
1. Fit the regulator onto the appliance sleeve
2. Screw in firmly
3. Connect up the regulator rod and block it using a retaining pin
4. Connect up the regulator control and block it using a retaining pin
Page 35
CLASSIC-LINE ECO-LINE Installation Guide
37
If a flexible axle is used, it must not sit on the appliance.
The smoke regulator must not close completely within the
flue gas exhaust duct and it should leave a small gap. This gap is laser pre-cut in the RÜEGG and the cut-out can be detached using pliers.
● The connection between the exhaust duct and the smoke regulator must be completely airtight.
● Only valid for CH:
The connecting pipe must be completely insulated 3 cm
thick with incombustible material.
● The maximum authorised lengths of the flue-gas exhaust duct horizontal runs are:
A/B2 fireplaces ≤ 80 cm A1/B1 fireplaces ≤ 150 cm
These may be extended if a flue gas fan is used!
Check that horizontal runs are allowed in your country.
● The flue gas exhaust duct connects the fireplace to the
chimney flue, thereby facilitating air circulation.
● If the exhaust duct goes through construction elements containing inflammable materials, cover the duct with a mineral material, such as concrete, extending at least
20 cm outwards.
Carry out an functional test of the smoke regulator, using
the regulator control, before fitting the fireplace casing.
● The exhaust duct should never be used to bear the weight
of the chimney flue.
Connecting up the convection air
● Follow the instructions on pages 15 to 22 to connect up the convection air.
Bearer frame
● The bearer frame is used to provide static support for the fireplace apron (cas­ing) in the front part.
● An expansion gap (fibreglass strip) should be placed between the appliance and the bearer frame. There must be no direct connection between the bearer frame and the appliance. The bearer frame must provide support for the casing through the side pillars of the construction or through anchors set in the building or in the ceiling.
≥20
cm
≥20 cm
detach
Page 36
CLASSIC-LINE ECO-LINE Installation Guide
38
Room-side facing
● The facing must be made of non-inflammable material.
● A fibreglass strip should be placed to cover the whole of the space between the facing and the appliance.
● The facing must not prevent the glass door opening or closing.
● The facing does not need insulating if the free surfaces and the surfaces of the areas designed for fuel storage cannot exceed a temperature of 85° C. On sur­faces made of mineral materials, for example ceramic tiles, upon which objects might be placed, the maximum temperature is 120° C.
● Safety distances must be observed.
The materials used must meet the required thermal resistance standards and not produce odours when heated over time. This is why materials containing plastics should be avoided.
Decorative beams
Wooden beams must be protected on the inner side by a heat shield (El 30) with permanent thermal resistance. The rear of the beam must be covered by a 5 cm thick layer of brick, a cellular concrete fireproof panel or non-inflammable insula­tion and covered by an non-inflammable EL 30 panel. There is no need to insu­late the appliance, if there is a hot air chamber between the fireplace insert and the outer casing.
≤ 2 cm
Steel bearer frame
Heat shield
Fireplace insert
Parging
Facing
(inactive surface)
Hardwood beam
> 5 cm 2 cm.
Expansion gap (non-inf) e.g. fibreglass strip
No direct connection aloud between the fireplace and the facing/bearer frame.
2c m
Page 37
CLASSIC-LINE ECO-LINE Installation Guide
39
5.
Insert the right-hand base panel → push it in completely to the right
4.
Insert the right side panel → align all the vertical panels
3.
Insert the right rear panel → push it in completely to the left
2.
Insert the left rear panel → push it in completely to the left
6.
Insert the left base panel → Centre the 2 base panels → Ensure the play is evenly distributed
1.
Insert the left side panel → push it completely in
7.
-Fit all the retaining brackets
-Fit the deflector
Chamotte-lined fireplaces
Jade Front / Saphir Front
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
Page 38
CLASSIC-LINE ECO-LINE Installation Guide
40
1.
Insert the left side panel → push in completely
2.
Insert the left rear panel → push in completely to the left
3.
Insert the right side panel → push in completely
4.
Insert the right hand rear panel → Push in completely to the right
5
.
insert the rear central panel Align the three vertical panels Align the side panels
6.
Insert the left base panel
→ push in completely to the left
8.
Insert the central base panel → Align all the base panels → Ensure the play is evenly distributed
7.
Insert the right-hand base panel → push in completely to the right
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
9.
Fit all the retaining brackets
Saphir Giant / Saphir Giant 500
Page 39
CLASSIC-LINE ECO-LINE Installation Guide
41
5.
Insert the right-hand base panel → Align all the base panels → Ensure the play is evenly distributed
4.
Insert the left base panel → push in completely to the left
2.
Insert the two rear panels → push them in completely to the left
3.
Insert the two right side panels → align all the panels
1.
Insert the two left side panels → push them in completely
6.
-Fit all the retaining brackets
-Fit the deflector
WARNING
Chamotte panels
must not be sealed in
mortar or glued to the fireplace steel pan­els.
Lumo Front
Page 40
CLASSIC-LINE ECO-LINE Installation Guide
42
WARNING
Chamotte panels must not be sealed in mor­tar or glued to the fireplace steel panels.
4.
Screw back in the two external chamotte retaining brackets on the back of the hearth.
1.
Remove the two external chamotte retaining brackets on the back of the hearth.
2.
Insert and centre the two left side panels.
3.
Insert and centre the two right side panels.
6.
Fit all the retaining brackets
5.
Insert and align the base panels → Ensure the play is evenly distributed
Jade Tunnel / Saphir Tunnel
Page 41
CLASSIC-LINE ECO-LINE Installation Guide
43
1.
Insert the rear panel → Align it in the middle
6.
Fit all the retaining brackets
2.
Insert the left side panel → slide it completely to the back
3.
Insert the right side panel →slide it completely to the back
4.
Insert the right base panel
5.
Insert the left base panel → ensure the play is evenly
distributed
7.
Fit the deflector
WARNING
Chamotte panels must not be sealed in mor­tar or glued to the fireplace steel panels.
Prisma / Prismalo 500
Page 42
CLASSIC-LINE ECO-LINE Installation Guide
44
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
NOTICE
In the following instruction only the right model is displayed. For the Ellipse left model the same proce­dure has to be applied.
1.
Insert the side panel → pull to the front until behind the metallstrip
2.
Insert lower back panel → slide left against the side
panel
4.
Insert right base panel → slide to the right
3.
Insert upper back panel → slide left against the side
panel
6.
Insert back base panel → ensure the play is evenly
distributed
8.
Fit the deflector
5.
Insert left base panel
7.
Fit all the retaining brackets
Ellipse
Page 43
CLASSIC-LINE ECO-LINE Installation Guide
45
720 Compact
Insert upper deflector → Sheet steel, 2-piece
→ Lay on the air channel and slide against each other
2.
Insert the combustion chamber lining in Thermobrikk® → Follow the instructions on page 52
1.
Insert lower deflector → Vermiculite, 3-piece → Lay on the L-profile in the back and on the air channel
3.
Front view Side view
Upper deflector
Lower deflector
Thermobrikk®
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
NOTICE
In the following instruction only the right model is displayed. For the 720 Compact left model the same procedure has to be applied.
Page 44
CLASSIC-LINE ECO-LINE Installation Guide
46
2.
Insert the bottom part of the rear panel → push to the right behind the
bend of the steel panel
4.
Insert the right-hand base panel → push in completely to the right
5.
Insert the left base panel
→ Align the base panels
→ Ensure the play is evenly distributed
3.
Insert the top part of the rear panel → align with the bottom part.
6.
-Fit all the retaining brackets
-Fit the deflector
1.
Insert the left side panel
→ push in completely
WARNING
Chamotte
panels must not be sealed in mortar or
glued to the fireplace steel panels.
NOTICE
In the following instruction only the right model is displayed. For the 720 left model the same pro­cedure has to be applied.
720
Page 45
CLASSIC-LINE ECO-LINE Installation Guide
47
WARNING
Chamotte panels must not be
sealed in mortar or
glued to the fireplace steel panels.
NOTICE
In the following instruction only the right model is displayed. For the 720 Giant left model the same procedure has to be applied.
720 Giant
5.
Insert the right-hand base panel → push in completely to the right
6.
Insert the base panel → push in completely to the left
4.
Insert the left rear panel → Ensure the play is evenly distributed
7.
Insert the central base panel → Ensure the play is evenly distribut-
8.
Fit all the retaining brackets
9.
Fit the deflector
2.
Insert the right hand rear panel → push in completely to the right
1.
Insert the left side panel → push in completely
3.
Insert the central rear panel
Page 46
CLASSIC-LINE ECO-LINE Installation Guide
48
Pi Classic
4.
Fit all the retaining brackets
1.
Insert back panel → ensure that the play is evenly
distributed
5.
Fit the deflector
2.
Insert front base panel → slide completely forward
3.
Insert rear base panel → slide base parts together → distribute play evenly
6.
Center deflector and distribute play evenly
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
Page 47
CLASSIC-LINE ECO-LINE Installation Guide
49
Pi Compact
3.
Fit all retaining brackets
6.
Fit the deflector
7.
Center the deflector and distribute play evenly
2.
Insert left back panel → center both back panels
1.
Insert right back panel → slide completely to the right
4.
Insert right base panel → slide completely tot the right
5.
Insert left base panel → slide base plates together
and center them
→ distribute play evenly
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
Page 48
CLASSIC-LINE ECO-LINE Installation Guide
50
Pi-ccolo Classic
3.
Fit all retainig brackets
4.
Fit the deflector
5.
Distribute play evenly
2.
Insert base panel → distribute play evenly
1.
Insert back panel → distribute play evenly
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
Page 49
CLASSIC-LINE ECO-LINE Installation Guide
51
Pi-ccolo Compact
4.
Fit the deflector
5.
Distribute the play evenly
3.
Fit all retaining brackets
2.
Insert base panel → ditribute play evenly
1.
Insert back panel → distribute play evenly
WARNING
Chamotte panels must not be sealed in mortar or glued to the fireplace steel panels.
Page 50
CLASSIC-LINE ECO-LINE Installation Guide
52
Combustion chamber lining in Thermobrikk®
The elements of the lining in Thermobrikk® consist of several loose items. The illustrations below are applicable on all Rüegg fireplaces equipped with a lining in Thermobrikk®.
Please proceed as follows when inserting the lining:
Insert wall parts in the combustion chamber; start in the corner between back- and sidewall.
Insert wall parts in the combustion chamber. Next to the fireplace opening, slide the element behind the steel strip.
Custom cut parts must always be placed in front, next to the fireplace opening!
Fill the side- and back walls with the wall elements and slide them together without any space be­tween them.
Fix the L-Profile with screws to the wall of the combustion chamber, as a fixation for the back­and side wall elements.
Place all floor elements correctly on the steel floor, and divide the space between the different ele­ments evenly between the floor parts.
Page 51
CLASSIC-LINE ECO-LINE Installation Guide
53
Steel fireplaces
When fitting steel fireplaces, follow the special fitting instructions which are deliv­ered with the fireplace.
The instructions can also be found online on www.ruegg-cheminee.com.
Additional weights for A1 appliances
For fitting extra weights, follow the special fitting instructions, which can also be found online on www.ruegg-cheminee.com.
After the extra weights have been fitted, the door must close automatically and completely. Open-hearth operation is forbidden on AI appliances.
After installation
Once the installation is finished, a number of final steps need to be carried out:
Final visual inspection of the installation
Functional test of the glass panel and unwanted noise, by raising and lower­ing it several times.
Functional test of the hearth door by opening and closing it repeatedly.
Functional test of the combustion air adjustment control operation (slight rubbing or sliding noises are admissible)
Functional test of the flue gas regulator.
Functional test of the fresh air regulator.
Functional test of the convection air fan (if fitted).
Functional test of the flue gas fan (if fitted).
The appliance handbook, with instructions, is personally handed over to the owner
Detailed instructions must be given to the owner as to fireplace operation and safety rules.
Detailed explanation and completion of the guarantee card.
Page 52
CLASSIC-LINE ECO-LINE Installation Guide
54
Using your fireplace for the first time
The materials used (surround, parging, etc.) must be allowed to dry out complete­ly before the fireplace is used for the first time. Drying times are given in the man­ufacturers instructions.
Open the doors and windows in the room in which the fireplace is installed. Instructions for the first heating are given in the attached booklet. It is normal for odours to be given off during the first heating. These occur due
to the evaporation of rolling oil and binding agents in the paintwork. The odours are not harmful, but may be unpleasant.
When the fireplace is initially heating up or cooling down, the materials will ex-
pand or contract and may produce cracking noises. These noises can vary in intensity according to the type of fireplace.
Data plate
To ensure prompt after-sales service, we would ask you to give the following details:
Type of appliance:
Serial number:
Date of manufacture:
Description of problem:
Data plate location depends on the type of appliance. Front-opening fireplaces flat versions (Figure 1):
The data plate is located on the left of the appliance just below the middle of the space reserved for raising the door. To facilitate reading, it can be pulled out, when the fireplace has cooled down,
Other fire-place forms (Figures 2+3): The data plate, depending on the model, is located in the middle or in the right or left hand upper corners above the appliance door. To facilitate reading, it can be pulled out, when the fireplace has cooled down.
Figure 1
Figure 2
Figure 3
Type
Page 53
CLASSIC-LINE ECO-LINE Installation Guide
55
Installation with heat storage materials
Modern, well insulated houses need heating systems with a low heat release rate. This type of fireplace has a masonry heat storage jacket and a ceramic outer casing (radiation panels, etc.). In these systems, part of the heat produced by combustion is stored in the surround and then used for heating the room through radiation. The casing is closed and has no air outlet vents. It must be designed to allow the free circulation of heated air in the surround.
A heat storage system is different to a hot air appliance as regards the air flows and thermal insulation. Except when stipulated otherwise (see below), the guide­lines and instructions given above also apply to heat storage systems.
Air circulation
System and operating modes
> Page 11.
Rüegg fireplaces can also be
fed with combustion air inside a heat storage appliance, sepa­rately from the ambient air.
For open hearth operation, ad-
ditional external air must be drawn into the room. This can be achieved by fitting additional fresh air units > Instructions Page 20.
The fresh air units must be fit-
ted with an airtight connection to a fresh air duct of Ø 150 mm.
To prevent the ingress of cold
air when the appliance is not being used and to prevent thermal bridges, external air ducts should be fitted with a hermetically closing valve.
Building external wall
Heat storage jacket
Air vents
Fresh air units (optional)
Page 54
CLASSIC-LINE ECO-LINE Installation Guide
56
Sections required:
Combustion air
(external air)
Fresh air
(external air)
Axinit Front
1 2 175 cm2
350 cm2
Ellipse
1 2 175 cm2
350 cm2
Jade Front
1 1 175 cm2
175 cm2
Jade Tunnel
1 2
175 cm2
350 cm2
Larimar Front
1 1
175 cm2
175 cm2
Lumo Front
1 1
175 cm2
175 cm2
Pi
1 2
175 cm
2
350 cm
2
Pi-ccolo
1 1
175 cm
2
175 cm
2
Prisma
1 2
175 cm2
350 cm2
Prismalo 500
1 1
175 cm2
175 cm2
Saphir Front
1 2
175 cm2
350 cm2
Saphir Tunnel
1 2
175 cm2
350 cm2
Saphir Giant
1 2 175 cm2
350 cm2
Saphir Giant 500
1 2
175 cm2
350 cm2
720 Compact
1 2
175 cm2
350 cm2
720 (ECO)
1 2
175 cm2
350 cm2
720 Giant
1 2
175 cm2
350 cm2
The fresh air duct must be drawn in from behind to the fresh air units. The height difference between the sleeve on the fresh air unit and the inlet on the building wall must be at least 80 cm. The height difference can also be obtained using a siphon. The air inlet must, however, always be lower.
Thermal insulation
WARNING
There are more stringent insulation regulations for completely closed constructions, due to higher retained temperatures.
NOTICE
The following VHP regulations Version 1.1 (2009) are the up to date instructions and applicable when constructing a accumulation fireplace!
80cm
Combustion air
External air
80cm
Page 55
CLASSIC-LINE ECO-LINE Installation Guide
57
Inflammable environment (inf)
Floor
The adjustable feet of the appliance
must stand directly on the weight­bearing surface.
Within the casing, the floor under the
appliance must be covered with a con- crete slab 12 cm thick
A layer of thermal insulation, 10 cm
thick, should be placed between the
appliance and the concrete slab
Side and rear walls A protective wall of thickness of at
least 10 cm should be placed directly on the building wall. It must be made of molded brick, concrete or similar mate­rial. The protective wall must seamless­ly cover the whole of the building wall inside the fireplace casing cavity.
Thermal insulation, of a thickness of
10 cm, between the protective wall and
the fireplace inset must be laid seam­lessly, and cover the whole of the pro­tective wall inside the fireplace casing cavity.
Ceiling
If the fireplace casing cavity above the
appliance extends to the ceiling, then the ceiling needs to be protected by a layer of thermal insulation at least 12 cm thick
The thermal insulation is laid on a non-
inflammable cover, at least 6 cm thick,
with a permanent, unchanging thermal resistance.
Guidelines for the use of substitute thermal insulation are given on pages 30 and
31.
* Version with fresh air unit
> See p. 20
≥10 cm
≥10 cm
≥12
cm
≥10
cm
= 6
cm
≥12
cm
≥18
cm
Page 56
CLASSIC-LINE ECO-LINE Installation Guide
58
Non-inflammable environment (non-inf)
Floor
The appliance adjustable feet must
stand directly on a load-bearing sur­face.
A layer of thermal insulation, 3 cm thick,
should be placed between the appli­ance and the concrete slab.
Side and rear walls
No protective wall. The protection consists of a layer of
thermal insulation, at least 6 cm thick. It seamlessly covers the whole of the building wall, inside the fireplace casing cavity.
Ceiling
The room ceiling must be at least
12 cm thick.
If the fireplace casing cavity above the
appliance extends to the ceiling, then the ceiling must be fitted with a layer of thermal insulation at least 6 cm thick, that is laid directly on the ceiling.
The thermal insulation is laid on a min.
2 cm non-inflammable cover, with a permanent, unchanging thermal re­sistance.
Guidelines for the use of substitute thermal insulation are given on pages 30 and
31.
* Version with fresh air unit
> See page 20
3 cm ≥2
cm
12 cm
6 cm
≥ 6 cm
≥ 10 cm
Page 57
CLASSIC-LINE ECO-LINE Installation Guide
59
Heat storage jacket
The jacket will consist of heat storage
panels. It must be compact and fitted around the fireplace insert.
The materials used must have the fol-
lowing characteristics:
- High density (≈ 2,8 kg/dm3)
- Good conductivity
- High thermal resistance
The distance between the appliance
and the internal face of the jacket should be about 2 – 4 cm.
Air vents of about 10 x 6 cm should be
fitted at the top, bottom and on the sides of the jacket. See also the dia­gram on page 48.
The cover will be made with heat stor-
age panels, and can be thermally insu­lated on top, depending on the type of appliance.
The cover sits statically on the side
walls of the heat storage jacket. There must be no direct contact between the cover and the fireplace insert.
A distance of between 4 and 12 cm
should be left between the outside face of the jacket and the thermal insulation.
Avoid where possible any direct con-
tact between the appliance and the
heat storage system. If this cannot be avoided, the contact surfaces should be fitted with fibreglass-strip expansion gaps.
2 – 4 cm
2
4
cm
≈ 6
cm
4 – 12 cm
Air vents
Cover
≈ 10 cm
≈ 6
cm
Page 58
CLASSIC-LINE ECO-LINE Installation Guide
60
Casing
The material used must have the following characteristics:
- Good conductivity
- High thermal resistance
WARNING
Thermal insulating materials, such as expanded concrete, must not be used as they might subject the appliance to excessive thermal stress.
There must be no direct contact between the heat storage jacket and the
casing.
To ensure even heat distribution, a gap of between 4 and 12 cm should be
left between the outside of the jacket and the inside of the casing.
Ensure there is adequate internal air circulation between the appliance and
heat storage system and the storage system and the casing.
The minimum casing surface area with regard to nominal heating power
(NWL= nominal power) is given by the following equation:
If, for technical reasons, it is not possible to apply the optimal casing surface
area, an adjustable hot air vent should be fitted in the casing.
NWL
1,8
= Casing surface area in [m
2
]
Page 59
CLASSIC-LINE ECO-LINE Installation Guide
61
Technical characteristics
Jade / Larimar
Jade
Front
Jade
Tunnel
Larimar
Front
Dimensions
Hearth (Opening width) l × h
cm 78 × 58 78 × 58 78 × 58
External dimensions l × w × h
cm 100 × 60 × 123 100 × 62 × 123 100 × 50 × 123
Total weight kg 387 390 305
Technical characteristics
Nominal heating power kW 11.0 11.0 13.0
Efficiency % 80.2 80.9 81.0
CO (13% by O2 Volume) mg/Nm3 1125 1250 1125
Dust (13% by O2 Volume) mg/Nm3 21 23 23.0
Mass flow of flue gases closed (open)
g/sec 9.3 (18.8) 9.0 (19.3) 10.8 (–)
Flue gas temperature closed (open)
°C 330 (180) 325 (250) 315 (–)
Min. delivery pressure closed (open)
Pa 12 (10) 12 (10) 12 (–)
Abgasstutzen - Ø cm 25 25 20
DIN EN 13229 Nr. RRF 29 09 2101 RRF 29 09 2105 RRF 29 13 3412
Page 60
CLASSIC-LINE ECO-LINE Installation Guide
62
Lumo
Dimensions
Hearth (opening width) l x h cm 58 x 78
External dimensions l x w x h cm 80 x 60 x 163
Total weight kg 400
Technical characteristics
Nominal heating power kW 11.0
Efficiency % 80.0
CO (13% by O2 volume) mg/Nm3 750
Dust (13% by O2 volume) mg/Nm3 24
Mass flow of flue gases closed (open) g/sec 8.6 (23.8)
Flue gas temperature closed (open) °C 365 (180)
Min. delivery pressure. closed (open) Pa 12 (10)
Ø of flue gas exhaust sleeve cm 25
DIN EN 13229 no. RRF 29 09 2107
VKF (CH) no. 12735
Page 61
CLASSIC-LINE ECO-LINE Installation Guide
63
Axinit / Saphir
Axinit
Front
Saphir
Front
Saphir
Tunnel
Saphir
Giant
Saphir
Giant 500
Dimensions
Hearth (Opening width) l × h
cm 94 × 66 94 × 66 94 × 66 115 × 66 115 × 50
External dimensions l × w × h
cm
116 × 56
× 139
116 × 66
× 139
116 × 68
× 139
138 × 66
× 139
138 × 55
× 107
Total weight kg 406 480 485 554 451
Technical characteristics
Nominal heating power
kw 13.0 11.0 11.0 11.0 11.0
Efficiency % 83.0 80.3 80.1 80.2 80.2
CO (13% by O2 Volume)
mg/Nm3 1250 750 1250 750 750
Dust (13% by O2 Volume)
mg/Nm3 21.0 22.0 20.0 26.0 26.0
Mass flow of flue gases closed (open)
g/sec 10.7 ( – ) 8.9 (17.8) 9.1 (18.3)
9.3
(17.8)
9.3
(17.8)
Flue gas temperature closed (open)
°C 284 ( – ) 340 (280) 335 (230)
330
(280)
330
(280)
Min. delivery pres­sure closed (open)
Pa 12 ( – ) 12 (10) 12 (15) 12 (10) 12 (10)
Abgasstutzen - Ø cm 25 30 30 30 30
DIN EN 13229 Nr.
RRF
29 13 3411
RRF
29 09 2104
RRF
29 09 2108
RRF
29 09 2103
RRF
29 09 2103
Page 62
CLASSIC-LINE ECO-LINE Installation Guide
64
720 / Ellipse
720
Compact
720 720
Giant
Ellipse
Dimensions
Hearth (opening width) l x h
cm 94/39 × 50 56/79 × 57 113/39 × 50 78/53 × 57
External dimensions l x w x h
cm 105 × 51 × 139 89 × 67 × 153 124 × 51 × 144 90 × 67 × 153
Total weight kg 340 352 370 313
Technical characteristics
Nominal heating power kW 13.0 10.0 10.0 10.0
Efficiency % 80.0 78.4 78.2 78.1
CO (13% by O2 volume) mg/Nm3 1250 750 875 1250
Dust (13% by O2 volume) mg/Nm3 16.0 25 27 28
Mass flow of flue gases closed (open)
g/sec 11.6 ( – ) 9.3 ( – ) 9.4 ( – ) 8.3 ( – )
Flue gas temperature closed (open)
°C 343 ( – ) 335 ( – ) 350 ( – ) 345 ( – )
Min. delivery pressure closed (open)
Pa 12 ( – ) 12 ( – ) 12 ( – ) 12 ( – )
Ø of flue gas exhaust sleeve cm 20 25 25 25
DIN EN 13229 Nr.
RRF
29 13 3413
RRF
29 11 2514
RRF
29 11 2515
RRF
29 11 2517
Page 63
CLASSIC-LINE ECO-LINE Installation Guide
65
Prisma / Prismalo 500
Prisma Prismalo 500
Dimensions
Hearth (opening width) ; l x h cm 94/20 × 57 77 × 51
External dimensions ; l x w x h cm 102 × 66 × 153 84 × 58 × 141
Total weight kg 339 249
Technical characteristics
Nominal heating power kW 10.0 10.0
Efficiency % 78.0 78.0
CO (13% by O2 volume) mg/Nm3 750 750
Dust (13% by O2 volume) mg/Nm3 23 23
Mass flow of flue gases closed (open) g/sec 8.4 (31) 8.4 (31)
Flue gas temperature closed (open) °C 355 (240) 355 (240)
Min. delivery pressure. closed (open) Pa 12 (10) 12 (10)
Ø of flue gas exhaust sleeve cm 25 20
DIN EN 13229 Nr. RRF 29 11 2516 RRF 29 11 2516
Page 64
CLASSIC-LINE ECO-LINE Installation Guide
66
Pi / Pi-ccolo
Pi
Classic
Pi
Compact
Pi-ccolo
Classic
Pi-ccolo
Compact
Dimensions
Hearth (opening width) l x h
cm 66/80 × 57 86/59 × 57 50/61 × 50 66/45 × 50
External dimensions l x w x h
cm 66 × 94 × 159 86 × 73 × 159 50 × 74 × 145 66 × 60 × 145
Total weight kg 428 430 255 260
Technical characteristics
Nominal heating power kw 11.0 11.0 9.0 9.0
Efficiency % 78.9 79.3 79.5 79.5
CO (13% by O2 volume) mg/Nm3 875 1250 1250 1250
Dust (13% by O2 volume) mg/Nm3 30 37 40 40
Mass flow of flue gases closed (open)
g/sec 11.9 (33.6) 10.0 ( – ) 8.4 (36) 8.4 (36.0)
Flue gas temperature closed (open)
°C 350 (240) 266 ( – ) 314 (210) 314 (210)
Min. delivery pressure closed (open)
Pa 14 (10) 12 ( – ) 12 (14) 12 (14)
Ø of flue gas exhaust sleeve cm 30 30 25 25
DIN EN 13229 Nr.
RRF
29 05 924
RRF
29 12 2736
RRF
29 08 1675
RRF
29 08 1675
Loading...