FORM NO. P11-781 REV. 1
Supersedes Form No. P11-781
Features
■ Coils constructed with copper tubing and enhanced alu-
minum fins.
■ Strong, attractive cabinet—louvered design protects the
coil from damage.
■ Expansion Valves with Internal Check Valve—Provides
for quieter refrigerant metering.
■ Enhanced Demand Defrost Control
■ Factory Installed Low Pressure Control
■ Non-Cycling Reversing Valve
■ Hot Gas Muffler
■ Service Valves
■ Grille/motor mount for quiet fan operation.
■ Easily accessible control box.
■ Bi-Directional Filter Drier (shipped – not installed)
■ Certified and rated under A.R.I. Standard 240.
■ U.L listed.
Accessories/Options
■ Low Ambient Control (Model No. RXAD-A08)
■ Outdoor Thermostats (Model No. RXPT-A01, A02,
A03 or A04)
■ Heat Pump Monitor (Model No. RXPM-B01)
■ Thermostats and Subbases
(Available through the PROSTOCK®department)
■ Compressor Time Delay Control (Model No.
RXMD-B01)
■ Blower Time Delay Control (Model No. RXMD-C04)
RXMD-C04 is not required if the outdoor unit is matched
with a Rheem Value Series furnace or air handler, or if
the furnace or air handler used has a blower off time
delay built-in.
■ Sound Enclosure*
■ High Pressure Control (Model No. RXAB-A07)
■ Start Components*
■ Heat Pump Thermostat Warning Light Kit (Model No.
RXPX-D01)
*Available through the PROSTOCK
®
department.
Applications
Rheem Value Series remote heat pumps offer comfort and
dependability for single, multi-family and light commercial
applications.
14.5 SEER
HEAT PUMPS
14PJM SERIES
Featuring
New Industry Standard
R-410A Refrigerant
(IN CERTAIN
MATCHED SYSTEMS)
2 Rheem Heating, Cooling and Water Heating
Model Identification Number
14 P J 18
NOMINAL COOLING CAPACITY
18 = 18,000 BTU/HR [5.28 kW]
24 = 24,000 BTU/HR [7.03 kW]
30 = 30,000 BTU/HR [8.79 kW]
36 = 36,000 BTU/HR [10.55 kW]
42 = 42,000 BTU/HR [12.31 kW]
48 = 48,000 BTU/HR [14.07 kW]
60 = 60,000 BTU/HR [17.58 kW]
M A 01
14.5 SEER P = HEAT PUMP VOLTAGE
J = 208-230 SINGLE PHASE
M = 2ND DESIGN
(R-410A)
CABINET
A = FULL METAL JACKET
RHEEM
VALUE SERIES
Performance Data ARI Standard Conditions
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
ARI Cooling Performance ARI Htg. Performance (70°F 21.0°C] Indoor)
Model Numbers
Outdoor
Unit
14PJM
Rev.
7/29/09
18
24
Indoor
Coil and/or
Air Handler
RHLL-HM2417
(RCSL-H*2417) ➀
RCFL-H*2414
RCFL-H*2417
RCFL-H*2417
(RGFD-06?MCK?)
RCFL-H*2417
(RGFD-07?MCK?)
RCFL-H*2417
(RGGD-06?MCK?)
RCFL-H*2417
(RGGD-07?MCK?)
RCFL-H*2417
(RGJD-06?MCK?)
RCFL-H*2417
(RGJD-07?MCK?)
RCFL-H*2417
(RGLR-07?AMK?)
RCFL-H*2417
(RGPR-05?BMK?)
RCFL-H*2417
(RGPR-07?AMK?)
RCFL-H*2417
(RGRM-04?MAE?)
RCFL-H*2417
(RGRM-06?MAE?)
RCFL-H*2417
(RGRM-07?MAE?)
RHKL-HM2417
(RCSL-H*2417)
RHSL-HM1817
(RCSL-H*2417)
RHLL-HM2417
(RCSL-H*2417) ➀
RCFL-H*2414
RCFL-H*2417
RCFL-H*2417
(RGFD-06?MCK?)
RCFL-H*2417
(RGFD-07?MCK?)
Total
Capacity
BTU/H
[kW]
18,600
[5.4]
18,200
[5.3]
18,200
[5.3]
18,500
[5.4]
18,500
[5.4]
18,500
[5.4]
18,500
[5.4]
18,500
[5.4]
18,500
[5.4]
18,600
[5.4]
18,500
[5.4]
18,500
[5.4]
18,500
[5.4]
18,500
[5.4]
18,400
[5.4]
18,800
[5.5]
18,200
[5.3]
23,800
[7.0]
23,400
[6.9]
23,400
[6.9]
23,600
[6.9]
23,600
[6.9]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35.0°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
13,550
[4.0]
13,150
[3.9]
13,150
[3.9]
13,500
[4.0]
13,500
[4.0]
13,450
[3.9]
13,450
[3.9]
13,450
[3.9]
13,450
[3.9]
13,550
[4.0]
13,500
[4.0]
13,450
[3.9]
13,500
[4.0]
13,450
[3.9]
13,400
[3.9]
13,850
[4.1]
13,250
[3.9]
17,150
[5.0]
16,750
[4.9]
16,750
[4.9]
17,000
[5.0]
17,000
[5.0]
Net
Latent
BTU/H
[kW]
5,050
[1.5]
5,050
[1.5]
5,050
[1.5]
5,000
[1.5]
5,000
[1.5]
5,050
[1.5]
5,050
[1.5]
5,050
[1.5]
5,050
[1.5]
5,050
[1.5]
5,000
[1.5]
5,050
[1.5]
5,000
[1.5]
5,050
[1.5]
5,000
[1.5]
4,950
[1.5]
4,950
[1.5]
6,650
[1.9]
6,650
[1.9]
6,650
[1.9]
6,600
[1.9]
6,600
[1.9]
EER
SEER
12.00 14.50 76
11.00 13.50 76
11.00 13.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.00 14.50 76
12.50 15.00 76
12.50 15.00 76
12.00 14.50 76
12.00 14.50 76
11.50 14.00 76
12.00 14.50 74
11.00 13.00 74
11.00 13.00 74
11.50 14.00 74
11.50 14.00 74
Snd.
Rate
dB
Indoor
CFM
[L/s]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
625
[295]
600
[283]
625
[295]
600
[283]
600
[283]
600
[283]
575
[271]
600
[283]
625
[295]
650
[307]
600
[283]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
17,800
[5.2]
18,300
[5.4]
18,300
[5.4]
17,900
[5.2]
17,800
[5.2]
17,800
[5.2]
17,800
[5.2]
17,800
[5.2]
17,800
[5.2]
17,800
[5.2]
17,900
[5.2]
17,800
[5.2]
17,800
[5.2]
17,800
[5.2]
17,900
[5.2]
17,800
[5.2]
18,200
[5.3]
22,800
[6.7]
23,400
[6.9]
23,400
[6.9]
23,000
[6.7]
23,000
[6.7]
COP
3.68
3.42
3.42
3.64
3.64
3.66
3.66
3.66
3.66
3.68
3.62
3.66
3.64
3.66
3.60
3.66
3.48
3.64
3.42
3.42
3.56
3.56
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C]
DOE Low Temp.
BTU/H
[kW]
10,900
[3.2]
11,400
[3.3]
11,400
[3.3]
11,000
[3.2]
11,000
[3.2]
10,900
[3.2]
10,900
[3.2]
10,900
[3.2]
10,900
[3.2]
10,900
[3.2]
11,000
[3.2]
10,900
[3.2]
10,900
[3.2]
10,900
[3.2]
11,000
[3.2]
10,900
[3.2]
11,300
[3.3]
14,400
[4.2]
15,000
[4.4]
15,000
[4.4]
14,600
[4.3]
14,600
[4.3]
COP
2.36 8.50
2.24 8.20
2.24 8.20
2.34 8.50
2.34 8.50
2.36 8.50
2.34 8.50
2.36 8.50
2.34 8.50
2.36 8.50
2.34 8.50
2.36 8.50
2.34 8.50
2.34 8.50
2.32 8.50
2.34 8.50
2.26 8.20
2.44 9.00
2.30 8.20
2.30 8.20
2.38 8.50
2.38 8.50
DOE
Region
IV
HSPF
Rheem Heating, Cooling and Water Heating 3
Performance Data ARI Standard Conditions (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
ARI Cooling Performance
Model Numbers
Outdoor
Unit
14PJM
Rev.
7/29/09
24
30
Indoor
Coil and/or
Air Handler
RCFL-H*2417
(RGGD-06?MCK?)
RCFL-H*2417
(RGGD-07?MCK?)
RCFL-H*2417
(RGJD-06?MCK?)
RCFL-H*2417
(RGJD-07?MCK?)
RCFL-H*2417
(RGLR-07?AMK?)
RCFL-H*2417
(RGPR-05?BMK?)
RCFL-H*2417
(RGPR-07?AMK?)
RCFL-H*2417
(RGRM-04?MAE?)
RCFL-H*2417
(RGRM-06?MAE?)
RCFL-H*2417
(RGRM-07?MAE?)
RHKL-HM2417
(RCSL-H*2417)
RHSL-HM2417
(RCSL-H*2417)
RHLL-HM3617
(RCSL-H*3617) ➀
RCFL-H*3617
RCFL-H*3617
(RGFD-06?MCK?)
RCFL-H*3617
(RGFD-07?MCK?)
RCFL-H*3617
(RGGD-06?MCK?)
RCFL-H*3617
(RGGD-07?MCK?)
RCFL-H*3617
(RGJD-06?MCK?)
RCFL-H*3617
(RGJD-07?MCK?)
RCFL-H*3617
(RGLR-07?AMK?)
RCFL-H*3617
(RGPR-05?BMK?)
RCFL-H*3617
(RGPR-07?AMK?)
RCFL-H*3617
(RGRM-04?MAE?)
RCFL-H*3617
(RGRM-06?MAE?)
RCFL-H*3617
(RGRM-07?MAE?)
RCFL-H*3621
RCFL-H*3621
(RGFD-06?MCK?)
Total
Capacity
BTU/H
[kW]
23,800
[7.0]
23,800
[7.0]
23,800
[7.0]
23,800
[7.0]
23,800
[7.0]
23,600
[6.9]
23,800
[7.0]
23,600
[6.9]
23,600
[6.9]
23,800
[7.0]
24,000
[7.0]
23,400
[6.9]
29,600
[8.7]
29,200
[8.6]
29,000
[8.5]
29,200
[8.6]
29,200
[8.6]
29,200
[8.6]
29,200
[8.6]
29,200
[8.6]
29,400
[8.6]
29,200
[8.6]
29,400
[8.6]
29,000
[8.5]
29,200
[8.6]
29,000
[8.5]
29,200
[8.6]
29,200
[8.6]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35.0°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
17,150
[5.0]
17,200
[5.0]
17,150
[5.0]
17,200
[5.0]
17,150
[5.0]
17,000
[5.0]
17,150
[5.0]
17,000
[5.0]
17,000
[5.0]
17,350
[5.1]
17,500
[5.1]
16,850
[4.9]
22,050
[6.5]
21,650
[6.3]
21,600
[6.3]
21,750
[6.4]
21,750
[6.4]
21,750
[6.4]
21,750
[6.4]
21,750
[6.4]
21,900
[6.4]
21,750
[6.4]
21,900
[6.4]
21,600
[6.3]
21,750
[6.4]
21,600
[6.3]
21,650
[6.3]
21,800
[6.4]
Net
Latent
BTU/H
[kW]
6,650
[1.9]
6,600
[1.9]
6,650
[1.9]
6,600
[1.9]
6,650
[1.9]
6,600
[1.9]
6,650
[1.9]
6,600
[1.9]
6,600
[1.9]
6,450
[1.9]
6,500
[1.9]
6,550
[1.9]
7,550
[2.2]
7,550
[2.2]
7,400
[2.2]
7,450
[2.2]
7,450
[2.2]
7,450
[2.2]
7,450
[2.2]
7,450
[2.2]
7,500
[2.2]
7,450
[2.2]
7,500
[2.2]
7,400
[2.2]
7,450
[2.2]
7,400
[2.2]
7,550
[2.2]
7,400
[2.2]
Snd.
EER
SEER
11.50 14.00 74
11.50 14.00 74
11.50 14.00 74
11.50 14.00 74
12.00 14.50 74
11.50 14.00 74
12.00 14.50 74
11.50 14.00 74
11.50 14.00 74
11.50 13.50 74
12.00 14.50 74
11.00 13.50 74
12.00 14.50 73
11.00 13.00 73
11.00 13.50 73
11.00 13.50 73
11.50 14.00 73
11.00 13.50 73
11.50 14.00 73
11.00 13.50 73
11.50 14.00 73
11.00 13.50 73
11.50 14.00 73
11.50 13.50 73
11.50 13.50 73
11.00 13.00 73
11.00
11.00 13.50 73
13.00 73
Rate
dB
Indoor
CFM
[L/s]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
775
[366]
800
[378]
800
[378]
825
[389]
850
[401]
850
[401]
800
[378]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
1,025
[484]
1,000
[472]
1,025
[484]
1,025
[484]
1,000
[472]
1,000
[472]
1,025
[484]
1,000
[472]
1,025
[484]
1,000
[472]
1,000
[472]
ARI Htg. Performance (70°F 21.0°C] Indoor)
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
22,800
[6.7]
23,000
[6.7]
22,800
[6.7]
23,000
[6.7]
22,800
[6.7]
23,000
[6.7]
22,800
[6.7]
23,000
[6.7]
23,000
[6.7]
23,200
[6.8]
22,800
[6.7]
23,200
[6.8]
28,800
[8.4]
29,400
[8.6]
29,200
[8.6]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
29,200
[8.6]
29,000
[8.5]
29,200
[8.6]
29,200
[8.6]
29,400
[8.6]
29,400
[8.6]
29,200
[8.6]
COP
3.60
3.58
3.60
3.58
3.62
3.56
3.62
3.56
3.56
3.52
3.60
3.46
3.62
3.44
3.48
3.52
3.52
3.52
3.52
3.52
3.56
3.50
3.56
3.48
3.50
3.44
3.44
3.48
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C]
DOE Low Temp.
BTU/H
[kW]
14,500
[4.2]
14,500
[4.2]
14,500
[4.2]
14,500
[4.2]
14,400
[4.2]
14,600
[4.3]
14,400
[4.2]
14,600
[4.3]
14,600
[4.3]
14,700
[4.3]
14,500
[4.2]
14,900
[4.4]
17,900
[5.2]
18,500
[5.4]
18,300
[5.4]
18,200
[5.3]
18,100
[5.3]
18,200
[5.3]
18,100
[5.3]
18,200
[5.3]
18,000
[5.3]
18,200
[5.3]
18,000
[5.3]
18,300
[5.4]
18,200
[5.3]
18,500
[5.4]
18,500
[5.4]
18,300
[5.4]
COP
2.40 8.50
2.40 8.50
2.40 8.50
2.40 8.50
2.42 9.00
2.38 8.50
2.42 9.00
2.38 9.00
2.38 9.00
2.36 8.20
2.42 9.00
2.34 8.20
2.40 9.00
2.28 8.50
2.30 8.50
2.34 8.50
2.34 8.50
2.32 8.50
2.34 8.50
2.32 8.50
2.36 8.50
2.32 8.50
2.36 8.50
2.30 8.50
2.32 8.50
2.28 8.50
2.28 8.50
2.32 8.50
DOE
Region
IV
HSPF
4 Rheem Heating, Cooling and Water Heating
Performance Data ARI Standard Conditions (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
ARI Cooling Performance
Model Numbers
Outdoor
Unit
14PJM
Rev.
7/29/09
36
Indoor
Coil and/or
Air Handler
RCFL-H*3621
(RGFD-07?MCK?)
RCFL-H*3621
(RGGD-06?MCK?)
RCFL-H*3621
(RGGD-07?MCK?)
RCFL-H*3621
(RGJD-06?MCK?)
RCFL-H*3621
(RGJD-07?MCK?)
RCFL-H*3621
(RGLR-07?AMK?)
RCFL-H*3621
(RGLR-07?BRQ?)
RCFL-H*3621
(RGPR-05?BMK?)
RCFL-H*3621
(RGPR-07?AMK?)
RCFL-H*3621
(RGPR-07?BRQ?)
RCFL-H*3621
(RGRM-04?MAE?)
RCFL-H*3621
(RGRM-06?MAE?)
RCFL-H*3621
(RGRM-07?YBG?)
RHKL-HM3617
(RCSL-H*3617)
RHSL-HM3017
(RCSL-H*3617)
RHLL-HM3617
(RCSL-H*3617) ➀
RCFL-H*3617
RCFL-H*3621
RCFL-H*3621
(RGFD-09?ZCM?)
RCFL-H*3621
(RGFD-10?ZCM?)
RCFL-H*3621
(RGGD-09?ZCM?)
RCFL-H*3621
(RGGD-10?ZCM?)
RCFL-H*3621
(RGJD-09?ZCM?)
RCFL-H*3621
(RGJD-10?ZCM?)
RCFL-H*3621
(RGLR-07?AMK?)
RCFL-H*3621
(RGLR-07?BRQ?)
RCFL-H*3621
(RGLR-10?BRM?)
RCFL-H*3621
(RGPR-07?AMK?)
Total
Capacity
BTU/H
[kW]
29,200
[8.6]
29,200
[8.6]
29,200
[8.6]
29,200
[8.6]
29,200
[8.6]
29,400
[8.6]
29,600
[8.7]
29,200
[8.6]
29,400
[8.6]
29,600
[8.7]
29,200
[8.6]
29,200
[8.6]
29,000
[8.5]
29,400
[8.6]
28,800
[8.4]
35,600
[10.4]
34,400
[10.1]
34,400
[10.1]
35,800
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,000
[10.5]
36,400
[10.7]
36,200
[10.6]
36,000
[10.5]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35.0°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
21,750
[6.4]
21,750
[6.4]
21,750
[6.4]
21,750
[6.4]
21,750
[6.4]
21,900
[6.4]
22,050
[6.5]
21,750
[6.4]
21,900
[6.4]
22,050
[6.5]
21,800
[6.4]
21,750
[6.4]
21,600
[6.3]
21,900
[6.4]
21,200
[6.2]
25,700
[7.5]
24,500
[7.2]
24,500
[7.2]
26,250
[7.7]
26,600
[7.8]
26,600
[7.8]
26,600
[7.8]
26,600
[7.8]
26,600
[7.8]
26,750
[7.8]
27,200
[8.0]
26,850
[7.9]
26,750
[7.8]
Net
Latent
BTU/H
[kW]
7,450
[2.2]
7,450
[2.2]
7,450
[2.2]
7,450
[2.2]
7,450
[2.2]
7,500
[2.2]
7,550
[2.2]
7,450
[2.2]
7,500
[2.2]
7,550
[2.2]
7,400
[2.2]
7,450
[2.2]
7,400
[2.2]
7,500
[2.2]
7,600
[2.2]
9,900
[2.9]
9,900
[2.9]
9,900
[2.9]
9,550
[2.8]
9,400
[2.8]
9,400
[2.8]
9,400
[2.8]
9,400
[2.8]
9,400
[2.8]
9,250
[2.7]
9,200
[2.7]
9,350
[2.7]
9,250
[2.7]
Snd.
EER
SEER
11.50 14.00 73
11.50 14.00
11.00
13.50 73
11.50 14.00 73
11.00 13.50 73
11.50
14.00 73
12.00 14.50 73
11.00 13.50 73
11.50 14.00
12.00 14.50 73
11.503013.50 73
11.50 13.50 73
11.50 13.50
12.00
14.50 73
11.00 13.50 73
12.00 14.50 75
11.00 13.50 75
11.00 13.50 75
11.50 14.00 75
11.50 14.00 75
11.50 14.00 75
11.50 14.00 75
11.50 14.00 75
11.50 14.00 75
11.50 14.00 75
11.50 14.00 75
14.00 75
11.50
11.50 14.00 75
Rate
dB
73
73
73
Indoor
CFM
[L/s]
1,000
[472]
1,000
[472]
1,025
[484]
1,000
[472]
1,025
[484]
1,025
[484]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
1,025
[484]
1,000
[472]
975
[460]
1,025
[484]
950
[448]
1,175
[554]
1,075
[507]
1,075
[507]
1,150
[543]
1,175
[554]
1,175
[554]
1,175
[554]
1,175
[554]
1,175
[554]
1,200
[566]
1,225
[578]
1,200
[566]
1,200
[566]
ARI Htg. Performance (70°F 21.0°C] Indoor)
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
29,000
[8.5]
28,800
[8.4]
28,800
[8.4]
29,000
[8.5]
29,000
[8.5]
28,800
[8.4]
29,200
[8.6]
29,000
[8.5]
29,200
[8.6]
28,800
[8.4]
29,200
[8.6]
35,000
[10.3]
35,400
[10.4]
35,400
[10.4]
35,000
[10.3]
35,200
[10.3]
35,000
[10.3]
35,000
[10.3]
35,000
[10.3]
35,000
[10.3]
35,200
[10.3]
35,000
[10.3]
35,000
[10.3]
35,200
[10.3]
COP
3.52
3.54
3.52
3.54
3.52
3.58
3.62
3.52
3.56
3.64
3.48
3.52
3.50
3.62
3.48
3.58
3.48
3.48
3.56
3.54
3.56
3.56
3.56
3.56
3.50
3.58
3.58
3.50
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C]
DOE Low Temp.
BTU/H
[kW]
18,200
[5.3]
18,100
[5.3]
18,100
[5.3]
18,100
[5.3]
18,100
[5.3]
18,000
[5.3]
17,800
[5.2]
18,200
[5.3]
18,000
[5.3]
17,800
[5.2]
18,300
[5.4]
18,200
[5.3]
18,300
[5.4]
17,900
[5.2]
18,300
[5.4]
23,000
[6.7]
23,400
[6.9]
23,400
[6.9]
23,000
[6.7]
23,200
[6.8]
23,000
[6.7]
23,000
[6.7]
23,000
[6.7]
23,000
[6.7]
23,200
[6.8]
23,000
[6.7]
23,000
[6.7]
23,200
[6.8]
COP
2.34 8.50
2.34 8.50
2.34 8.50
2.34 8.50
2.34 8.50
2.36 8.50
2.40 9.00
2.34 8.50
2.36 8.50
2.40 9.00
2.32 8.50
2.34 8.50
2.32 8.50
2.38 9.00
2.32 8.50
2.44 9.00
2.42 8.50
2.42 8.50
2.48 8.50
2.46 8.50
2.48 8.50
2.48 8.50
2.48 8.50
2.48 8.50
2.46 8.50
2.50 8.50
2.50 8.50
2.44 8.50
DOE
Region
IV
HSPF