
FORM NO. P11-775 REV. 2
Supersedes Form No. P11-775 Rev. 1
Features
■ Coils constructed with copper tubing and enhanced alu-
minum fins.
■ Strong, attractive cabinet—louvered design protects the
coil from damage.
■ Expansion Valves with Internal Check Valve—Provides
for quieter refrigerant metering.
■ Demand Defrost Control
■ Non-Cycling Reversing Valve
■ Hot Gas Muffler
■ Service Valves
■ Grille/motor mount for quiet fan operation.
■ Easily accessible control box.
■ Bi-Directional Filter Drier (shipped – not installed)
■ Certified and rated under A.R.I. Standard 240.
■ U.L listed.
Accessories/Options
■ Low Ambient Control (Model No. RXAD-A08)
■ Outdoor Thermostats (Model No. RXPT-A01, A02,
A03 or A04)
■ Heat Pump Monitor (Model No. RXPM-B01)
■ Thermostats and Subbases
(Available through the
PROSTOCK
®
department)
■ Compressor Time Delay Control (Model No.
RXMD-B01)
■ Blower Time Delay Control (Model No. RXMD-C04)
RXMD-C04 is not required if the outdoor unit is matched
with a Rheem Value Series furnace or air handler, or if
the furnace or air handler used has a blower off time
delay built-in.
■ Sound Enclosure*
■ High Pressure Control (Model No. RXAB-A07)
■ Start Components*
*Available through the PROSTOCK®department.
Applications
Rheem Value Series remote heat pumps offer comfort and
dependability for single, multi-family and light commercial
applications.
14 SEER
HEAT PUMPS
14PJL SERIES
Featuring
Earth-Friendly
R-410A Refrigerant
earth friendly refrigerant

2Rheem Heating, Cooling and Water Heating
Model Identification Number
14 P J 18
NOMINAL COOLING CAPACITY
18 = 18,000 BTU/HR [5.28 kW]
24 = 24,000 BTU/HR [7.03 kW]
30 = 30,000 BTU/HR [8.79 kW]
36 = 36,000 BTU/HR [10.55 kW]
42 = 42,000 BTU/HR [12.31 kW]
48 = 48,000 BTU/HR [14.07 kW]
60 = 60,000 BTU/HR [17.58 kW]
L A 01
14 SEER P = HEAT PUMP VOLTAGE
J = 208-230 SINGLE PHASE
L = R-410A CABINET
A = FULL METAL JACKET
RHEEM
VALUE SERIES
Performance Data ARI Standard Conditions
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
➀ Highest sales volume tested combination required by D.O.E. test procedures. [] Designates Metric Conversions
ARI Cooling Performance ARI Htg. Performance (70°F 21.0°C] Indoor)
Model Numbers
Outdoor
Unit
14PJL
Rev.
1/10/2008
18
24
30
Indoor
Coil and/or
Air Handler
RHLL-HM2417
(RCSL-H*2417A*) ➀
RCFL-H*2414A*
RCFL-H*2417A*
RBHP-17
(RCHL-24A2)
17AHLL24HM
(RCSL-H*2417A*)
17AHSL18HM
(RCSL-H*2417A*)
RHSL-HM1817
(RCSL-H*2417A*)
RHLL-HM2417
(RCSL-H*2417A*) ➀
RCFL-H*2414A*
RCFL-H*2417A*
RBHP-17
(RCHL-24A2)
17AHLL24HM
(RCSL-H*2417A*)
17AHSL24HM
(RCSL-H*2417A*)
RHSL-HM2417
(RCSL-H*2417A*)
RHLL-HM3617
(RCSL-H*3617A*) ➀
RCFL-H*3617A*
RCFL-H*3621A*
RBHP-21
(RCHL-36A1)
17AHLL36HM
(RCSL-H*3617A*)
17AHSL30HM
(RCSL-H*3617A*)
RHSL-HM3017
(RCSL-H*3617A*)
Tot al
Capacity
BTU/H
[kW]
18,600
[5.4]
18,100
[5.3]
18,100
[5.3]
17,800
[5.2]
18,600
[5.4]
18,300
[5.4]
18,300
[5.4]
24,800
[7.3]
24,200
[7.1]
24,200
[7.1]
22,400
[6.6]
24,800
[7.3]
24,200
[7.1]
24,200
[7.1]
28,800
[8.4]
28,200
[8.3]
28,200
[8.3]
28,600
[8.4]
28,800
[8.4]
28,600
[8.4]
28,600
[8.4]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35.0°C] DB Outdoor Air
Net
Sens.
BTU/H
[kW]
13,450
[3.9]
12,950
[3.8]
12,950
[3.8]
12,900
[3.8]
13,450
[3.9]
13,250
[3.9]
13,250
[3.9]
17,650
[5.2]
17,050
[5.0]
17,050
[5.0]
15,850
[4.6]
17,650
[5.2]
17,050
[5.0]
17,050
[5.0]
21,650
[6.3]
21,050
[6.2]
21,050
[6.2]
21,200
[6.2]
21,650
[6.3]
21,450
[6.3]
21,450
[6.3]
Net
Latent
BTU/H
[kW]
5,150
[1.5]
5,150
[1.5]
5,150
[1.5]
4,900
[1.4]
5,150
[1.5]
5,050
[1.5]
5,050
[1.5]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
6,550
[1.9]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,400
[2.2]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
EER
SEER
12.00 14.00 76
11.10 13.00 76
11.10 13.00 76
12.00 14.00 76
12.00 14.00 76
11.50 13.00 76
11.50 13.00 76
12.00 14.00 74
10.75 13.00 74
10.75 13.00 74
11.00 13.00 74
12.00 14.00 74
10.90 13.00 74
10.90 13.00 74
12.00 14.00 73
11.00 13.00 73
11.00 13.00 73
12.00 14.00 73
12.00 14.00 73
11.40 13.00 73
11.40 13.00 73
Snd.
Rate
dB
Indoor
CFM
[L/s]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
600
[283]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
1,000
[472]
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
16,500
[4.8]
17,000
[5.0]
17,000
[5.0]
16,500
[4.8]
16,500
[4.8]
16,800
[4.9]
16,800
[4.9]
22,200
[6.5]
22,800
[6.7]
22,800
[6.7]
22,200
[6.5]
22,200
[6.5]
22,800
[6.7]
22,800
[6.7]
26,800
[7.9]
27,400
[8.0]
27,400
[8.0]
26,800
[7.9]
26,800
[7.9]
27,800
[8.1]
27,800
[8.1]
COP
3.62
3.36
3.36
3.64
3.62
3.42
3.42
3.72
3.44
3.44
3.60
3.72
3.50
3.50
3.78
3.58
3.58
3.82
3.78
3.74
3.74
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C]
DOE Low Temp.
BTU/H
[kW]
8,300
[2.4]
8,800
[2.6]
8,800
[2.6]
9,100
[2.7]
8,300
[2.4]
8,700
[2.5]
8,700
[2.5]
13,100
[3.8]
13,800
[4.0]
13,800
[4.0]
14,500
[4.2]
13,100
[3.8]
13,600
[4.0]
13,600
[4.0]
14,400
[4.2]
15,000
[4.4]
15,000
[4.4]
14,500
[4.2]
14,400
[4.2]
15,600
[4.6]
15,600
[4.6]
COP
2.30 8.2
2.08 7.7
2.08 7.7
2.44 8.2
2.30 8.2
2.10 7.7
2.10 7.7
2.36 8.5
2.22 7.7
2.22 7.7
2.54 7.7
2.36 8.5
2.24 7.7
2.24 7.7
2.44 8.5
2.36 7.7
2.36 7.7
2.56 8.5
2.44 8.5
2.52 7.7
2.52 7.7
DOE
Region
IV
HSPF

Rheem Heating, Cooling and Water Heating 3
Performance Data ARI Standard Conditions (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
➀ Highest sales volume tested combination required by D.O.E. test procedures. [] Designates Metric Conversions
ARI Cooling Performance
Model Numbers
Outdoor
Unit
14PJL
Rev.
1/10/2008
36
42
48
60
Indoor
Coil and/or
Air Handler
RHLL-HM3617
(RCSL-H*3617A*) ➀
RCFL-H*3617A*
RCFL-H*3621A*
RBHP-21
(RCHL-36A1)
17AHLL36HM
(RCSL-H*3617A*)
17AHSL36HM
(RCSL-H*3617A*)
RHSL-HM3617
(RCSL-H*3617A*)
RHSL-HM3621
(RCSL-H*3621A*)
RHLL-HM4821
(RCSL-H*4821A*) ➀
RCFL-H*4821A*
RCFL-H*4824A*
RBHP-24
(RCHL-48A1)
21AHLL48HM
(RCSL-H*4821A*)
21AHSL42HM
(RCSL-H*4821A*)
RHSL-HM4221
(RCSL-H*4821A*)
RHLL-HM4821
(RCSL-H*4821A*) ➀
RCFL-H*4821A*
RCFL-H*4824A*
21AHLL48HM
(RCSL-H*4821A*)
21AHSL48HM
(RCSL-H*4821A*)
RHSL-HM4821
(RCSL-H*4821A*)
24AHLL48HM
(RCSL-H*4824A*)
24AHSL48HM
(RCSL-H*4824A*)
RHLL-HM4824
(RCSL-H*4824A*)
RHSL-HM4824
(RCSL-H*4824A*)
RHLL-HM6024
(RCSL-H*6024A*) ➀
RCFL-H*6024A*
24AHLL60HM
(RCSL-H*6024A*)
RHSL-HM6024
(RCSL-H*6024A*)
Capacity
BTU/H
35,000
[10.3]
33,800
33,800
35,400
[10.4]
35,000
[10.3]
34,400
[10.1]
34,400
[10.1]
34,400
[10.1]
42,000
[12.3]
41,000
[12.0]
41,000
[12.0]
40,000
[11.7]
42,000
[12.3]
41,000
[12.0]
41,000
[12.0]
47,500
[13.9]
46,000
[13.5]
46,000
[13.5]
47,500
[13.9]
46,500
[13.6]
46,500
[13.6]
48,000
[14.1]
46,500
[13.6]
48,000
[14.1]
46,500
[13.6]
59,000
[17.3]
57,500
[16.8]
59,000
[17.3]
58,500
[17.1]
80°F [126.5°C] DB/67°F [119.5°C] WB Indoor Air
95°F[135.0°C] DB Outdoor Air
Tot al
[kW]
[9.9]
[9.9]
Net
Sens.
BTU/H
[kW]
25,950
[7.6]
24,750
[7.3]
24,750
[7.3]
25,650
[7.5]
25,950
[7.6]
25,500
[7.5]
25,350
[7.4]
25,350
[7.4]
31,350
[9.2]
30,350
[8.9]
30,350
[8.9]
28,250
[8.3]
31,350
[9.2]
30,350
[8.9]
30,350
[8.9]
34,950
[10.2]
33,450
[9.8]
33,450
[9.8]
34,950
[10.2]
33,950
[9.9]
33,950
[9.9]
36,500
[10.7]
33,950
[9.9]
36,500
[10.7]
33,950
[9.9]
43,800
[12.8]
42,300
[12.4]
43,800
[12.8]
44,150
[12.9]
Net
Latent
BTU/H
[kW]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
9,750
[2.9]
9,050
[2.7]
8,900
[2.6]
9,050
[2.7]
9,050
[2.7]
10,650
[3.1]
10,650
[3.1]
10,650
[3.1]
11,750
[3.4]
10,650
[3.1]
10,650
[3.1]
10,650
[3.1]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
11,500
[3.4]
12,550
[3.7]
11,500
[3.4]
12,550
[3.7]
15,200
[4.5]
15,200
[4.5]
15,200
[4.5]
14,350
[4.2]
EER
12.00 14.00 75
10.95 13.00
10.95
11.75 13.50 75
12.00 14.00 75
11.15
11.10 13.00 75
11.10 13.00 75
12.00 14.00 77
10.90 13.00 77
10.90 13.00 77
11.80 14.00 77
12.00 14.00 77
11.05 13.00 77
11.05 13.00 77
12.00 14.00 77
10.85 13.00 77
10.85 13.00 77
12.00 14.00 77
10.90 13.00 77
10.90 13.00 77
12.00 14.00 77
10.90 13.00 77
12.00 14.00 77
10.90 13.00 77
12.00 14.00 77
11.30 13.00 77
12.00 14.00 77
11.05 13.00 77
Snd.
SEER
13.00 75
13.00 75
Rate
dB
75
Indoor
CFM
[L/s]
1,200
[566]
1,075
[507]
1,075
[507]
1,175
[554]
1,200
[566]
1,100
[519]
1,200
[566]
1,200
[566]
1,400
[661]
1,400
[661]
1,400
[661]
1,400
[661]
1,400
[661]
1,400
[661]
1,400
[661]
1,600
[755]
1,475
[696]
1,475
[696]
1,600
[755]
1,600
[755]
1,600
[755]
1,625
[767]
1,600
[755]
1,625
[767]
1,600
[755]
1,850
[873]
1,675
[790]
1,850
[873]
1,750
[826]
ARI Htg. Performance (70°F [21.0°C] Indoor)
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
34,000
[10.0]
34,400
[10.1]
34,400
[10.1]
36,000
[10.5]
34,000
[10.0]
34,600
[10.1]
34,600
[10.1]
34,600
[10.1]
41,000
[12.0]
41,500
[12.2]
41,500
[12.2]
41,500
[12.2]
41,000
[12.0]
41,500
[12.2]
41,500
[12.2]
45,500
[13.3]
46,000
[13.5]
46,000
[13.5]
45,500
[13.3]
46,000
[13.5]
46,000
[13.5]
45,500
[13.3]
46,000
[13.5]
45,500
[13.3]
46,000
[13.5]
58,500
[17.1]
57,500
[16.8]
58,500
[17.1]
59,000
[17.3]
COP
3.58
3.46
3.46
3.50
3.58
3.44
3.44
3.44
3.74
3.56
3.56
3.60
3.74
3.60
3.60
3.72
3.58
3.58
3.72
3.54
3.54
3.74
3.54
3.74
3.54
3.76
3.96
3.76
3.64
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C]
DOE Low Temp.
BTU/H
[kW]
22,000
[6.4]
22,400
[6.6]
22,400
[6.6]
23,400
[6.9]
22,000
[6.4]
22,600
[6.6]
22,600
[6.6]
22,600
[6.6]
27,000
[7.9]
27,800
[8.1]
27,800
[8.1]
28,000
[8.2]
27,000
[7.9]
27,600
[8.1]
27,600
[8.1]
29,800
[8.7]
30,400
[8.9]
30,400
[8.9]
29,800
[8.7]
30,600
[9.0]
30,600
[9.0]
29,800
[8.7]
30,600
[9.0]
29,800
[8.7]
30,600
[9.0]
38,000
[11.1]
36,800
[10.8]
38,000
[11.1]
38,500
[11.3]
COP
2.46 8.5
2.40 7.7
2.40 7.7
2.36 7.7
2.46 8.5
2.38 7.7
2.40 7.7
2.40 7.7
2.66 8.5
2.54 7.7
2.54 7.7
2.66 8.5
2.66 8.5
2.54 7.7
2.54 7.7
2.68 8.5
2.58 7.7
2.58 7.7
2.68 8.5
2.60 7.7
2.60 7.7
2.68 8.5
2.60 7.7
2.68 8.5
2.60 7.7
2.66 8.5
2.80 7.7
2.66
2.58 7.7
DOE
Region
IV
HSPF
8.5

4Rheem Heating, Cooling and Water Heating
Electrical and Physical Data
Model
Number
14PJL
ELECTRICAL PHYSICAL
Phase
Frequency (Hz)
Voltage (Volts)
Compressor
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil
Refrig.
Per
Circuit
Oz. [g]
Weight
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m2]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
30 1-60-208/230 14.1/14.1 73 0.8 19/19 25/25 30/30 13.72 [1.27] 1 2800 [1321] 101 [2863] 180 [81.6] 190 [86.2]
24 1-60-208/230 12.8/12.8 58.3 0.6 17/17 20/20 25/25 11.06 [1.03] 1 2370 [1118] 91 [2580] 130 [59] 138 [62.6]
60 1-60-208/230 26.4/26.4 150 1.2 35/35 45/45 60/60 21.85 [2.03] 2 3360 [1586] 259 [7343] 277 [125] 289 [131.1]
42 1-60-208/230 17.9/17.9 112 1.2 24/24 30/30 40/40 21.85 [2.03] 1 3575 [1687] 150 [4252] 202 [91.6] 214 [97.1]
48 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 21.85 [2.03] 1 3575 [1687] 141 [3997] 205 [93] 217 [98.4]
36 1-60-208/230 17/17 96.7 1.2 23/23 30/30 35/35 16.39 [1.52] 1 3575 [1687] 109 [3090] 215 [97.5] 227 [103]
18 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 11.06 [1.03] 1 1700 [802] 91 [2580] 144 [65.3] 152 [68.9]
Rev. 1/10/2008
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
periods stated, in accordance with the terms of the limited
warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms
and Conditions, See the Product Warranty Card.
Condenser Coil leaks caused by
factory defects ........................................Five (5) Years
Conditional Compressor* ............................Ten (10) Years
Any Other Part............................................Five (5) Years
*See Product Warranty Card for Details.
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY
INFORMATION AVAILABLE FROM YOUR RETAILER.
NOTES:
➀ 20 Fins per inch.
➁ Factory charged for 15 ft. line set.
[] Designates Metric Conversions

Rheem Heating, Cooling and Water Heating 5
Unit Dimensions
[]Designates Metric Conversions
L
H
SEE DETAIL A
w
Model Number
14PJL
18, 24 261/4 [666.75] 235/8 [600.07] 235/8 [600.07]
30 261/4 [666.75] 275/8 [701.67] 275/8 [701.67]
36 273/8 [695.32] 315/8 [803.27] 315/8 [803.27]
42, 48, 60 353/8 [898.52] 315/8 [803.27] 315/8 [803.27]
Height “H”
(Inches) [mm]
Length “L”
(Inches) [mm]
(Inches) [mm]
Width “W”

6Rheem Heating, Cooling and Water Heating
Heat Pump Refrigerant Line Size Information
NOTES:
*Standard line size
N/A = Application not recommended.
NOTES: [] Designates Metric Conversions
*Standard line size
N/A = Using suction line larger than shown in chart will result in poor oil return and is not recommended.
Line Size
System
Capacity
Connection
Size
(Inch I.D.)
[mm]
11/2 Ton
2 Ton
21/
2 Ton
3 Ton
31/
2 Ton
4 Ton
5 Ton
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
Line Size
(Inch O.D.)
[mm]
1/4 [6.35]
5/16 [7.94]
3/8* [9.53]
5/16 [7.94]
1/4 [6.35]
5/16 [7.94]
3/8* [9.53]
5/16 [7.94]
3/8* [9.53]
5/16 [7.94]
3/8* [9.53]
3/8* [9.53]
1/2 [12.7]
3/8* [9.53]
1/2 [12.7]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]
25 [7.62] 40 [12.19] 25 [7.62] 9 [2.74] N/A N/A
25 [7.62] 50 [15.24] 62 [18.90]
25 [7.62] 50 [15.24] 75 [22.86]
23 [7.01] N/A N/A N/A N/A N/A1/4 [6.35]
25 [7.62] 36 [10.97] 29 [8.84]
25 [7.62] 50 [15.24] 72 [21.95]
25 [7.62] N/A N/A N/A N/A N/A
25 [7.62] 49 [14.94] 38 [11.58]
25 [7.62] 50 [15.24] 68 [20.73]
25 [7.62] 50 [15.24] 37 [11.28] 22 [6.71] 7 [2.13] N/A
25 [7.62] 50 [15.24] 68 [20.73] 63 [19.20] 58 [17.68] 53 [16.15]
25 [7.62] 23 [7.01] 4 [1.22] N/A N/A N/A
25 [7.62] 50 [15.24] 43 [13.11] 36 [10.97] 30 [9.14] 24 [7.32]
25 [7.62] 46 [14.02] 38 [11.58] 30 [9.14] 22 [6.71] 15 [4.57]
25 [7.62] 50 [15.24] 56 [17.07] 55 [16.76] 53 [16.15] 52 [15.85]
25 [7.62] 50 [15.24] 56 [17.07] 44 [13.41] 32 [9.75] 20 [6.10]
25 [7.62] 50 [15.24] 75 [22.86] 81 [24.69] 79 [24.08] 76 [23.16]
Outdoor Unit Above or Below Indoor Coil (Heat Pumps Only)
Liquid Line Sizing (R410A)
Total Equivalent Length—Feet [m]
Maximum Vertical Separation—Feet [m]
58 [17.68] 53 [16.15] 49 [14.94]
72 [21.95]
23 [7.01] 16 [4.88] 9[2.74]
70 [21.34]
27 [8.23] 17 [5.18] 6 [1.83]
65 [19.81]
70 [21.34] 68 [20.73]
68 [20.73] 65 [19.81]3/8* [9.53]
62 [18.90] 58 [17.68]
Suction Line Length/Size versus Capacity Multiplier (R-410A)
1
/2 Ton3 Ton11/2 TonUnit Size
7/8" [22.23] I.D.
1.00
1.00
—
0.99
0.99
—
0.96
0.98
—
0.94
0.96
—
5 Ton4 Ton3
7
/8" [22.23 mm] O.D. Opt.
11/8" [28.58 mm] O.D. Std.*
1.00
1.00
—
0.99
0.99
—
0.96
0.98
—
0.95
0.96
—
1.00
1.00
—
0.99
0.99
—
0.97
0.98
—
0.94
0.97
—
Suction Line
Connection Size
Suction Line Run—
Feet [m]
25' [7.62]
50' [15.24]
100' [30.48]
150' [45.72]
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
2 Ton
3/4" [19.05] I.D.
5
/8" [15.88 mm] O.D. Opt.
3
/4" [19.05 mm] O.D. Std.*
1.00
1.00
—
0.98
0.99
—
0.95
0.96
—
0.92
0.93
—
1.00
1.00
—
0.98
0.99
—
0.95
0.96
—
0.92
0.94
—
1
2
/2 Ton
5
/8" [15.88 mm] O.D. Opt.
3
/4" [19.05 mm] O.D. Std.*
7
/8" [22.23 mm] O.D. Opt.
1.00
1.00
1.00
0.96
0.98
0.99
0.94
0.96
0.97
0.91
0.93
0.95
3
/4" [19.05 mm] O.D. Opt.
7
/8" [22.23 mm] O.D. Std.*
1.00
1.00
—
0.98
0.99
—
0.96
0.97
—
0.94
0.95
—

Rheem Heating, Cooling and Water Heating 7
NOTES

Before proceeding with installation, refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
Rheem Heating,
Cooling and
Water Heating
P. O . B o x 1 7 0 1 0, F o r t S m i th , A R 7 2 91 7
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 2-09 DC FORM NO. P11-775 REV. 2
Supersedes Form No. P11-775 Rev. 1