Rudd 13PJL-42 User Manual

Page 1
FORM NO. P11-774 REV. 3
Supersedes Form No. P11-774 Rev. 2
Features
Coils constructed with copper tubing and enhanced alu-
minum fins.
Includes factory installed low pressure control.
Strong, attractive cabinet—louvered design protects the
Expansion Valves with Internal Check Valve—Provides
for quieter refrigerant metering.
Demand Defrost Control
Non-Cycling Reversing Valve
Hot Gas Muffler
Service Valves
Grille/motor mount for quiet fan operation.
Easily accessible control box.
Bi-Directional Filter Drier (shipped – not installed)
Certified and rated under A.R.I. Standard 240.
U.L listed.
Accessories/Options
Low Ambient Control (Model No. RXAD-A08)
Outdoor Thermostats (Model No. RXPT-A01, A02,
A03 or A04)
Heat Pump Monitor (Model No. RXPM-B01)
Thermostats and Subbases
(Available through the PROSTOCK®department)
Compressor Time Delay Control (Model No.
RXMD-B01)
Blower Time Delay Control (Model No. RXMD-C04)
RXMD-C04 is not required if the outdoor unit is matched with a Rheem Value Series furnace or air handler, or if the furnace or air handler used has a blower off time delay built-in.
Sound Enclosure*
High Pressure Control (Model No. RXAB-A07)
Start Components*
*Available through the PROSTOCK®department.
Applications
Rheem Value Series remote heat pumps offer comfort and dependability for single, multi-family and light commercial applications.
13 SEER
HEAT PUMPS
13PJL SERIES
Featuring Earth-Friendly R-410A Refrigerant
earth friendly refrigerant
13.0
Page 2
2 Rheem Heating, Cooling and Water Heating
Model Identification Number
13 P J 18
NOMINAL COOLING CAPACITY
18 = 18,000 BTU/HR [5.28 kW] 24 = 24,000 BTU/HR [7.03 kW] 30 = 30,000 BTU/HR [8.79 kW] 36 = 36,000 BTU/HR [10.55 kW] 42 = 42,000 BTU/HR [12.31 kW] 48 = 48,000 BTU/HR [14.07 kW] 60 = 60,000 BTU/HR [17.58 kW]
L A 01
13 SEER P = HEAT PUMP VOLTAGE
J = 208-230 SINGLE PHASE
L = R-410A CABINET
A = FULL METAL JACKET
RHEEM
VALUE SERIES
Performance Data ARI Standard Conditions
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
ARI Cooling Performance ARI Htg. Performance (70°F [21.0°C] Indoor)
Model Numbers
[19.5°C] WB Indoor Air 95°F [35.0°C] DB Outdoor Air
Outdoor
Unit
13PJL
Rev.
3/31/09
18
24
30
Indoor Coil and/or Air Handler
RHSL-HM1817 (RCSL-H*2417A*)
RCFL-H*2414A*
RCFL-H*2417A*
RBHP-17 (RCHL-24A2)
RHLL-HM2417 (RCSL-H*2417A*)
RHSL-HM2417 (RCSL-H*2417A*)
RCFL-H*2414A*
RCFL-H*2417A*
RBHP-17 (RCHL-24A2)
RHLL-HM2417 (RCSL-H*2417A*)
RHSL-HM3017 (RCSL-H*3617A*)
RCFL-H*3617A*
RCFL-H*3617C*
RCFL-H*3621A*
RCFL-H*3621C*
RBHP-21 (RCHL-36A1)
RHLL-HM3617 (RCSL-H*3617A*)
RHLL-HM3617 (RCSL-H*3617C*)
RHSL-HM3017 (RCSL-H*3617C*)
Total
Capacity
BTU/H
[kW]
18,200
[5.3]
18,100
[5.3]
18,100
[5.3]
17,800
[5.2]
18,900
[5.5]
24,200
[7.1]
24,200
[7.1]
24,200
[7.1]
22,400
[6.6]
24,800
[7.3]
28,600
[8.4]
28,400
[8.3]
28,400
[8.3]
28,400
[8.3]
28,400
[8.3]
28,600
[8.4]
28,800
[8.4]
28,800
[8.4]
28,600
[8.4]
Sens.
BTU/H
[kW]
13,100
[3.8]
12,950
[3.8]
12,950
[3.8]
12,900
[3.8]
13,750
[4.0]
17,050
[5.0]
17,050
[5.0]
17,050
[5.0]
15,850
[4.6]
17,650
[5.2]
21,450
[6.3]
21,250
[6.2]
21,250
[6.2]
21,250
[6.2]
21,250
[6.2]
21,200
[6.2]
21,650
[6.3]
21,650
[6.3]
21,450
[6.3]
80°F [26.5°C] DB/67°F
Net
Latent BTU/H
[kW]
5,100
[1.5]
5,150
[1.5]
5,150
[1.5]
4,900
[1.4]
5,150
[1.5]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
6,550
[1.9]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
7,400
[2.2]
7,150
[2.1]
7,150
[2.1]
7,150
[2.1]
Net
dB
Indoor
CFM [L/s]
600
[283]
600
[283]
600
[283]
600
[283]
800
[378]
800
[378]
800
[378]
800
[378]
800
[378] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472] 1,000
[472]
Snd.
EER
SEER
11.35 13.00 76
11.10 13.00 76
11.10 13.00 76
12.00 14.00 76
12.00 14.00 76 615 [290]
10.90 13.00 74
10.75 13.00 74
10.75 13.00 74
11.00 13.00 74
12.00 14.00 74
11.40 13.00 73
11.00 13.00 73
11.00 13.00 73
11.00 13.00 73
11.00 13.00 73
12.00 14.00 73
12.00 14.00 73
12.00 14.00 73
11.40 13.00 73
Rate
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
16,900
[5.0]
17,000
[5.0]
17,000
[5.0]
16,500
[4.8]
16,500
[4.8]
22,800
[6.7]
22,800
[6.7]
22,800
[6.7]
22,200
[6.5]
22,200
[6.5]
27,800
[8.1]
27,400
[8.0]
27,400
[8.0]
27,400
[8.0]
27,400
[8.0]
26,800
[7.9]
26,800
[7.9]
26,800
[7.9]
27,800
[8.1]
COP
3.42
3.36
3.36
3.64
3.62
3.50
3.44
3.44
3.60
3.72
3.74
3.58
3.58
3.58
3.58
3.82
3.78
3.78
3.74
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C] DOE Low Temp.
BTU/H
[kW]
8,700
[2.5]
8,800
[2.6]
8,800
[2.6]
9,100
[2.7]
8,300
[2.4]
13,600
[4.0]
13,800
[4.0]
13,800
[4.0]
14,500
[4.2]
13,100
[3.8]
15,600
[4.6]
15,000
[4.4]
15,000
[4.4]
15,000
[4.4]
15,000
[4.4]
14,500
[4.2]
14,400
[4.2]
14,400
[4.2]
15,600
[4.6]
COP
2.18 7.70
2.08 7.70
2.08 7.70
2.44 8.20
2.22 8.20
2.24 7.70
2.22 7.70
2.22 7.70
2.54 7.70
2.36 8.20
2.52 8.50
2.36 8.00
2.36 8.00
2.36 8.00
2.36 8.00
2.56 9.00
2.44 9.00
2.44 9.00
2.52 8.50
Region
DOE
IV
HSPF
Page 3
Rheem Heating, Cooling and Water Heating 3
Performance Data ARI Standard Conditions (cont.)
Note: Only these combinations of indoor/outdoor units are approved and any other combinations should not be used.
Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
ARI Cooling Performance
Model Numbers
Outdoor
Unit
13PJL
Rev.
3/31/09
36
42
48
60
Indoor Coil and/or Air Handler
RHSL-HM3617 (RCSL-H*3617A*)
RCFL-H*3617A*
RCFL-H*3617C*
RCFL-H*3621A*
RCFL-H*3621C*
RBHP-21 (RCHL-36A1)
RHLL-HM3617 (RCSL-H*3617A*)
RHLL-HM3617 (RCSL-H*3617C*)
RHSL-HM3617 (RCSL-H*3617C*)
RHSL-HM3621 (RCSL-H*3621A*)
RHSL-HM3621 (RCSL-H*3621C*)
RHSL-HM4221 (RCSL-H*4821A*)
RCFL-H*4821A*
RCFL-H*4824A*
RBHP-24 (RCHL-48A1)
RHLL-HM4821 (RCSL-H*4821A*)
RHSL-HM4821 (RCFL-H*4821A*)
RHSL-HM4821 (RCSL-H*4821A*)
RCFL-H*4821A*
RCFL-H*4824A*
RHLL-HM4821 (RCSL-H*4821A*)
RHLL-HM4824 (RCSL-H*4824A*)
RHSL-HM4824 (RCSL-H*4824A*)
RHLL-HM6024 (RCSL-H*6024A*)
Capacity
BTU/H
34,400
[10.1]
33,400
33,400
33,400
33,400
35,400
[10.4]
35,000
[10.3]
35,000
[10.3]
34,400
[10.1]
34,400
[10.1]
34,400
[10.1]
41,000
[12.0]
41,000
[12.0]
41,000
[12.0]
40,000
[11.7]
42,000
[12.3]
46,500
[13.6]
46,500
[13.6]
45,500
[13.3]
45,500
[13.3]
47,500
[13.9]
48,000
[14.1]
46,500
[13.6]
58,500
[17.1]
80°F [126.5°C] DB/67°F [119.5°C] WB Indoor Air
95°F[135.0°C] DB Outdoor Air
Total
[kW]
[9.8]
[9.8]
[9.8]
[9.8]
Net
Sens.
BTU/H
[kW]
25,350
[7.4]
24,350
[7.1]
24,350
[7.1]
24,350
[7.1]
24,350
[7.1]
25,650
[7.5]
25,950
[7.6]
25,950
[7.6]
25,350
[7.4]
25,350
[7.4]
25,350
[7.4]
30,350
[8.9]
30,350
[8.9]
30,350
[8.9]
28,250
[8.3]
31,350
[9.2]
33,950
[9.9]
33,950
[9.9]
32,950
[9.7]
32,950
[9.7]
34,950
[10.2]
36,500
[10.7]
33,950
[9.9]
41,750
[12.2]
Net Latent BTU/H
[kW]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
9,750
[2.9]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
9,050
[2.7]
10,650
[3.1]
10,650
[3.1]
10,650
[3.1]
11,750
[3.4]
10,650
[3.1]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
12,550
[3.7]
11,500
[3.4]
12,550
[3.7]
16,750
[4.9]
Snd.
EER
SEER
11.10 13.00 75
10.95 13.00 75
10.95 13.00 75
10.95 13.00 75
10.95 13.00 75
11.75 13.50 75
12.00 14.00 75
12.00 14.00 75
11.10 13.00 75
11.10 13.00 75
11.10 13.00 75
11.05 13.00 77
10.90 13.00 77
10.90 13.00 77
12.00 14.00 77
12.00 14.00 77
10.90 13.00 77
10.90 13.00 77
10.85 13.00 77
10.85 13.00 77
12.00 14.00 77
12.00 14.00 77
10.90 13.00 77
10.90 13.00 77
Rate
dB
Indoor
CFM [L/s]
1,200 [566]
1,075 [507]
1,075 [507]
1,075 [507]
1,075 [507]
1,175 [554]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,200 [566]
1,400 [661]
1,400 [661]
1,400 [661]
1,400 [661]
1,400 [661]
1,600 [755]
1,600 [755]
1,475 [696]
1,475 [696]
1,600 [755]
1,625 [767]
1,600 [755]
1,875 [885]
ARI Htg. Performance (70°F [21.0°C] Indoor)
Outdoor Air
47°F DB/43°F WB
[8.5°C/6.0°C]
DOE High Temp.
BTU/H
[kW]
34,600
[10.1]
34,400
[10.1]
34,400
[10.1]
34,400
[10.1]
34,400
[10.1]
36,000
[10.5]
34,000
[10.0]
34,000
[10.0]
34,600
[10.1]
34,600
[10.1]
34,600
[10.1]
41,500
[12.2]
41,500
[12.2]
41,500
[12.2]
41,500
[12.2]
41,000
[12.0]
46,000
[13.5]
46,000
[13.5]
46,000
[13.5]
46,000
[13.5]
45,500
[13.3]
45,500
[13.3]
46,000
[13.5]
56,000
[16.4]
COP
3.44
3.46
3.46
3.46
3.46
3.50
3.58
3.58
3.44
3.44
3.44
3.60
3.56
3.56
3.60
3.74
3.54
3.54
3.58
3.58
3.72
3.74
3.54
3.64
Outdoor Air
17°F DB/15°F WB
[–8.5°C/–9.5°C] DOE Low Temp.
BTU/H
[kW]
22,600
[6.6]
22,400
[6.6]
22,400
[6.6]
22,400
[6.6]
22,400
[6.6]
23,400
[6.9]
22,000
[6.4]
22,000
[6.4]
22,600
[6.6]
22,600
[6.6]
22,600
[6.6]
27,600
[8.1]
27,800
[8.1]
27,800
[8.1]
28,000
[8.2]
27,000
[7.9]
30,600
[9.0]
30,600
[9.0]
30,400
[8.9]
30,400
[8.9]
29,800
[8.7]
29,800
[8.7]
30,600
[9.0]
34,400
[10.1]
COP
2.40 8.50
2.40 8.50
2.40 8.50
2.40 8.50
2.40 8.50
2.36 8.20
2.46 9.00
2.46 9.00
2.40 8.50
2.40 8.50
2.40 8.50
2.54 8.50
2.54 8.50
2.54 8.50
2.66 9.00
2.66 9.00
2.60 8.50
2.60 7.70
2.58 8.50
2.58 8.50
2.68 9.00
2.68 9.00
2.60 8.50
2.50 8.50
Region
DOE
IV
HSPF
Page 4
4 Rheem Heating, Cooling and Water Heating
Electrical and Physical Data
Model
Number
13PJL
ELECTRICAL PHYSICAL
Phase Frequency (Hz) Voltage (Volts)
Compressor
Fan Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil
Refrig.
Per Circuit Oz. [g]
Weight
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping Lbs. [kg]
30 1-60-208/230 14.1/14.1 73 0.8 19/19 25/25 30/30 13.72 [1.27] 1 2800 [1321] 101 [2863] 198 [89.8] 208 [94.3]
24 1-60-208/230 12.8/12.8 58.3 0.6 17/17 20/20 25/25 11.06 [1.03] 1 2370 [1118] 91 [2580] 130 [59.0] 138 [62.6]
60 1-60-208/230 26.3/26.3 134 1.2 35/35 45/45 60/60 21.85 [2.03] 1 3575 [1687] 228 [6464] 209 [94.8] 221 [100.2]
42 1-60-208/230 21.8/21.8 112 1.2 29/29 35/35 50/50 21.85 [2.03] 1 3575 [1687] 150 [4252] 202 [91.6] 214 [97.1] 48 1-60-208/230 21.8/21.8 117 1.2 29/29 35/35 50/50 21.85 [2.03] 1 3575 [1687] 141 [3997] 205 [93.0] 217 [98.4]
36 1-60-208/230 17/17 96.7 1.2 23/23 30/30 35/35 16.39 [1.52] 1 3575 [1687] 109 [3090] 215 [97.5] 227 [103]
18 1-60-208/230 9/9 48 0.6 12/12 15/15 20/20 11.06 [1.03] 1 1700 [802] 91 [2580] 144 [65.3] 152 [68.9]
Rev. 3/31/09
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or visit www
.Rheem.com.
Condenser Coil leaks caused by
factory defects ........................................Five (5) Years
Conditional Compressor* ............................Ten (10) Years
Any Other Part............................................Five (5) Years
*See Product Warranty Card for Details.
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.
NOTES:
20 Fins per inch.Factory charged for 15 ft. line set.
[ ] Designates Metric Conversions
Page 5
Rheem Heating, Cooling and Water Heating 5
Unit Dimensions
[ ] Designates Metric Conversions
L
H
SEE DETAIL A
w
Model Number
13PJL
18, 24 261/4 [666.75] 235/8 [600.07] 235/8 [600.07]
30 261/4 [666.75] 275/8 [701.67] 275/8 [701.67] 36 273/8 [695.32] 315/8 [803.27] 315/8 [803.27]
42, 48, 60 353/8 [898.52] 315/8 [803.27] 315/8 [803.27]
Height “H”
(Inches) [mm]
Length “L”
(Inches) [mm]
(Inches) [mm]
Width “W”
Page 6
6 Rheem Heating, Cooling and Water Heating
Heat Pump Refrigerant Line Size Information
NOTES: *Standard line size N/A = Application not recommended.
NOTES: [ ] Designates Metric Conversions *Standard line size N/A = Using suction line larger than shown in chart will result in poor oil return and is not recommended.
Line Size
System
Capacity
Connection
Size
(Inch I.D.)
[mm]
11/2 To n
2 Ton
21/
2 To n
3 Ton
31/
2 To n
4 Ton
5 Ton
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
3/8"
[9.53]
Line Size
(Inch O.D.)
[mm]
1/4 [6.35] 5/16 [7.94] 3/8* [9.53]
5/16 [7.94]
1/4 [6.35] 5/16 [7.94] 3/8* [9.53] 5/16 [7.94] 3/8* [9.53] 5/16 [7.94] 3/8* [9.53] 3/8* [9.53] 1/2 [12.7] 3/8* [9.53] 1/2 [12.7]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [38.10] 150 [45.72]
25 [7.62] 40 [12.19] 25 [7.62] 9 [2.74] N/A N/A 25 [7.62] 50 [15.24] 62 [18.90] 25 [7.62] 50 [15.24] 75 [22.86] 23 [7.01] N/A N/A N/A N/A N/A1/4 [6.35] 25 [7.62] 36 [10.97] 29 [8.84] 25 [7.62] 50 [15.24] 72 [21.95] 25 [7.62] N/A N/A N/A N/A N/A 25 [7.62] 49 [14.94] 38 [11.58] 25 [7.62] 50 [15.24] 68 [20.73] 25 [7.62] 50 [15.24] 37 [11.28] 22 [6.71] 7 [2.13] N/A 25 [7.62] 50 [15.24] 68 [20.73] 63 [19.20] 58 [17.68] 53 [16.15] 25 [7.62] 23 [7.01] 4 [1.22] N/A N/A N/A 25 [7.62] 50 [15.24] 43 [13.11] 36 [10.97] 30 [9.14] 24 [7.32] 25 [7.62] 46 [14.02] 38 [11.58] 30 [9.14] 22 [6.71] 15 [4.57] 25 [7.62] 50 [15.24] 56 [17.07] 55 [16.76] 53 [16.15] 52 [15.85] 25 [7.62] 50 [15.24] 56 [17.07] 44 [13.41] 32 [9.75] 20 [6.10] 25 [7.62] 50 [15.24] 75 [22.86] 81 [24.69] 79 [24.08] 76 [23.16]
Outdoor Unit Above or Below Indoor Coil (Heat Pumps Only)
Liquid Line Sizing (R410A)
Total Equivalent Length—Feet [m]
Maximum Vertical Separation—Feet [m]
58 [17.68] 53 [16.15] 49 [14.94] 72 [21.95]
23 [7.01] 16 [4.88] 9 [2.74] 70 [21.34]
27 [8.23] 17 [5.18] 6 [1.83] 65 [19.81]
70 [21.34] 68 [20.73]
68 [20.73] 65 [19.81]3/8* [9.53]
62 [18.90] 58 [17.68]
Suction Line Length/Size versus Capacity Multiplier (R-410A)
1
/2 To n3 Ton11/2 To nUnit Size
7/8" [22.23] I.D.
1.00
1.00 —
0.99
0.99 —
0.96
0.98 —
0.94
0.96 —
5 Ton4 Ton3
7
/8" [22.23 mm] O.D. Opt.
1
1
/8" [28.58 mm] O.D. Std.*
1.00
1.00 —
0.99
0.99 —
0.96
0.98 —
0.95
0.96 —
1.00
1.00
0.99
0.99
0.97
0.98
0.94
0.97
Suction Line
Connection Size
Suction Line Run—
Feet [m]
25' [7.62]
50' [15.24]
100' [30.48]
150' [45.72]
Optional Standard Optional
Optional Standard Optional
Optional Standard Optional
Optional Standard Optional
2 Ton
3/4" [19.05] I.D.
5
/8" [15.88 mm] O.D. Opt.
3
/4" [19.05 mm] O.D. Std.*
1.00
1.00 —
0.98
0.99 —
0.95
0.96 —
0.92
0.93 —
1.00
1.00 —
0.98
0.99 —
0.95
0.96 —
0.92
0.94 —
1
2
/2 To n
5
/8" [15.88 mm] O.D. Opt.
3
/4" [19.05 mm] O.D. Std.*
7
/8" [22.23 mm] O.D. Opt.
1.00
1.00
1.00
0.96
0.98
0.99
0.94
0.96
0.97
0.91
0.93
0.95
3
/4" [19.05 mm] O.D. Opt.
7
/8" [22.23 mm] O.D. Std.*
1.00
1.00 —
0.98
0.99 —
0.96
0.97 —
0.94
0.95 —
Page 7
Rheem Heating, Cooling and Water Heating 7
NOTES
Page 8
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
Rheem Heating, Cooling and Water Heating
P.O. Box 17010, Fort Smith, AR 72917
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 4-09 DC FORM NO. P11-774 REV. 3
Supersedes Form No. P11-774 Rev. 2
Loading...