RTK HV 6290 Series, PV 6290 Series Installation And Operating Instructions Manual

Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
Abschlammventil Bottom blowdown valve
Vanne d’extraction des boues
Baureihe / Series / Séries HV 6290 / PV 6290
Inhaltsverzeichnis
Seite
1 Allgemeine Informationen 2 2 Montage und Anschluß 2 3 Inbetriebnahme 3 4 Wartung 3
Content
1 General Information 4 2 Installation and connection 4 3 Commissioning 5 4 Maintenance 5
Index
1 Informations générales 6 2 Installations et connexions 6 3 Mise en service : 7 4 Maintenance 7
Anhang / Appendix / Annexe
1 Drehmoment für Schrauben / torque for nuts 8 2 Ersatzteilliste / spare parts list / liste de rechange 9
Gültigkeitsbereich der Einbau- und Betriebsanleitung / Use this Installation and Operation Instruction for / Utiliser Instructions de montage et de service pour
HV 6290, PV 6290, HV 6290-E, PV 6290-E
0
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
1 Allgemeine Informationen
RTK ist ein Druckluft- bzw. Wasserdruckventil, das speziell zum Entfernen von Ablagerungen vom Dampfkesselboden bestimmt ist (Abschlammventil). Es wird zusammen mit einem Abschlamm-Timer von RTK verwendet, der die Abschlammung des Kesselbodens regelt und dadurch sicherstellt, dass die empfohlenen Abschlammzyklen unter minimalem Hitzeverlust stattfinden, so dass Wiederholungen und Auslassungen vermieden werden können.
Die Häufigkeit der Abschlammung von Dampfkesseln hängt für gewöhnlich von der Betriebsweise und den Anweisungen des Kesselherstellers ab. In der Regel sollte der Vorgang mindestens einmal täglich vorgenommen werden und höchstens fünf Sekunden dauern. Die Luft-/Wasserversorgung wird vom Magnetventil eingeschaltet, was eine Bewegung des Kolbens gegen den Federdruck verursacht. Die am Kolben angebrachte Ventilspindel bewegt den Ventilkegel vom Sitz weg, so dass das Ventil voll geöffnet wird. Während das Ventil geöffnet wird, entfernt der Abstreifring alle Ablagerungen von der Ventilspindel und schützt so die Dichtungen. Nach der Freigabe des Luft-/Wasserdrucks bewegen die Federn das Ventil wieder in die geschlossene Position. Der manuelle Override-Hebel wird nach unten gedrückt, um die untere Anschlussplatte anzuheben und das Ventil zu öffnen. Zuerst muss der Sicherungsstift entfernt werden. Das Ventil kann in der geöffneten Position gesichert werden
Die Ventile unterscheiden sich durch die Bauform, der Anschlußmaße, Nenndruckstufe sowie dem Gehäusewerkstoff, dem Dichtungswerkstoff und der Flanschausführung. Für die jeweilige Regelaufgabe werden verschiedene Regelgarnituren verwendet.
Achtung! : Ventile dürfen nur für die vorgesehenen Einsatzbedingungen eingesetzt werden.
Der Werkstoff und die Nenndruckstufe können am Gehäuse des Stellventiles abgelesen werden. Diese müssen für die Betriebsbedingungen und Medien geeignet sein.
Jedes Ventil hat eine eindeutige Seriennummer, die auf dem Typenschild unter "W. Nr." angegeben ist. Bei der Bestellung von Ersatzteilen oder bei Rückfragen sollte die "W. Nr." immer angegeben werden. Siehe Anhang, Bild 1.
Die Regelventile werden im Herstellerwerk verschiedenen Prüfungen (Druckprüfungen, Dichtheit nach außen,...) und Funktionsproben unterzogen. Eine Einstellung der Stellventile ist daher nicht notwendig.
Achtung! : Bevor Sie mit dem Einbau oder Betrieb von Ventilen beginnen, lesen Sie bitte die Druckschrift "Warnung vor
Gefahren...". 0000-7004
Einbau und Inbetriebnahme sind nur dem hierfür ausgebildeten und qualifizierten Fachpersonal gestattet.
2 Montage und Anschluß
2.1 Einbau Ventil
Beim Einbau des Regelventils muß folgendes beachtet werden:
Einbauraum:
Die Einbaustelle sollte gut zugänglich sein. Es muß genügend Raum zur Wartung und zum Öffnen der Antriebshaube vorhanden sein. Werden Motorventile im Freien montiert, so sollten Sie durch ein Regendach gegen die Witterung und direkte Sonnenbestrahlung geschützt werden.
vor dem Einbau:
Die Schutzkappen sind von den Flanschöffnungen zu entfernen.
Reinigung der Rohrleitungen:
Um einen dichten Abschluß des Stellventiles zu gewährleisten, sind die Rohrleitungen vor dem Einbau durchzuspülen. Dies verhindert, daß Schmutzteile wie Rost, Zunder oder Schweißperlen den Sitz bzw. Kegel des Stellventils beschädigen. Um das Ventil vor Verunreinigungen zu schützen, sollte vor dem Ventil ein Schmutzfänger installiert werden.
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
Anströmungsrichtung:
Bei Durchgangsventilen muß der Pfeil auf dem Ventilgehäuse mit der Strömungsrichtung übereinstimmen.
Einbaulage:
Senkrechte Einbaulage mit Antrieb nach oben oder waagerechte Einbaulagen sind möglich. Dabei muß darauf geachtet werden, daß die Säulen übereinander sind um das Gewicht des Antriebes abzustützen.
Spannung auf Ventilkörper:
Mögliche Zug- und Druckkräfte auf den Ventilkörper müssen durch geeignete Maßnahmen verhindert werden.
Rohrleitungsführung:
Für einen einwandfreie Funktion des Stellventils sollte die Rohrleitung vor dem Ventil in einer Einlaufstrecke von > 5x DN gerade, nicht verzweigt und ungestört verlaufen. Hinter dem Ventil soll die Auslaufstrecke auf > 10 x DN gerade, nicht verzweigt und ungestört ausgeführt werden.
Schutz vor Wärmestrahlung:
Um den Stellantrieb vor zu hoher Wärme zu schützen sind die Rohrleitungen zu isolieren. Dies sollte vor der ersten Inbetriebnahme erfolgen.
2.2 Montage Stellantrieb
Der Stellantrieb ist normalerweise auf das Ventil montiert und eingestellt.
2.3 Pneumatischer Anschluß
Für jeden pneumatischen Antrieb sollte ein Druckminderer vorgesehen werden, um gegenseitige Beeinflussung der Antriebe zu vermeiden.
Achtung! : Kondenswasser muß vermieden werden. Es sollte deshalb getrocknete Druckluft verwendet werden
3 Inbetriebnahme
Die Stellventile sind werksseitig eingestellt und einer Funktionsprüfung unterzogen. Eine Einstellung der Stellantriebe ist daher nicht notwendig.
Die Inbetriebnahme darf erst erfolgen, wenn die Punkte unter Kapitel „ 2 Montage und Anschluss“ abgearbeitet ist.
4 Wartung
4.1 Spindelabdichtung
Generell müssen beschädigte Spindelabdichtungen sofort ausgewechselt oder nachgezogen (bei Reingrafitpackungen) werden, da sonst eine neue Packung innerhalb kurzer Zeit wieder undicht werden kann. Der Aufbau der Spindelabdichtungen ist im jeweiligen technischen Datenblatt beschrieben. Spindelabdichtungen sind als Ersatzteilset beim Hersteller zu beziehen. Bitte geben Sie bei der Bestellung immer die "W. Nr." des Ventils an. Diese steht auf dem Typenschild, das auf der Querträgerplatte angebracht ist.
4.2 Austausch der Stopfbuchspackung
Ventil drucklos machen und Rohrleitungen entleeren gemäß Vorschriften Zum Tausch der Spindelabdichtung muß der Stellantrieb abgebaut werden. Der Auf- und Abbau
des Stellantriebes ist in der Betriebsanleitung des jeweiligen Stellantriebes beschrieben.
Die Überwurfmutter lösen und abnehmen. Alte Packung entfernen (Packungszieher) und Packungsraum säubern. Ventilspindel säubern Neue Packung, Stopfbuchse und Feder gemäß beigefügtem Schnittbild einlegen. Überwurfmutter befestigen
4.3 Austausch der Kegelgruppe
Es empfiehlt sich beim Tausch der Kegelgruppe auch die Spindelabdichtung zu erneuern. Für den Tausch der Kegelgruppe ist die Flachdichtung (503) zwischen Gehäuse und Deckel notwendig.
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
Ventile drucklos machen und Rohrleitungen entleeren gemäß Vorschriften. Zum Tausch der Kegelgruppe muß der Stellantrieb abgebaut werden (siehe hierzu die Betriebsanleitung des jeweiligen
Stellantriebes).
Durchgangs und Verteilventile: Deckel (201) vom Gehäuse (101) lösen Kegelgruppe aus Deckel (201) herausziehen und austauschen. Dichtflächen am Gehäuse reinigen Deckel (201) mit Kegelgruppe (300) auf Gehäuse (101) aufsetzen und kreuzweise festschrauben
(Anzugsmomente siehe Tabelle im Anhang)
Stellantrieb gemäß Betriebsanleitung auf Ventil aufbauen und Endabschaltung überprüfen.
1 General Information
The RTK is an air (or water) operated valve specifically designed to remove the solids which fall to the bottom of the boiler (bottom Blowdown). It is used with a RTK blowdown timer to control bottom blowdown, ensuring that the recommended boiler blowdown cycles occur with minimum heat loss, avoiding duplication or omission.
The frequency of bottom blowdown normally depends upon the boiler operating regime and the boiler manufacturers instructions, as a minimum it is typically done once a day for up to five seconds The air/water supply is switched on by the solenoid valve, causing the piston to move against the spring pressure. The valve spindle (attached to the piston) moves the valve cone away from the seat, opening the valve fully. As the valve is opened, a scraper ring removes any deposits on the valve stem protecting the seals. On release of the air/water pressure, the springs return the valve to the closed position. The manual override lever is pushed downwards to lift the lower connector plate and open the vlave. The locking pin must first be removed. The valve may be locked in the open position as shown in Figure 1 (inset)
The valve differentiates through the type, nominal bore, nominal pressure and the material of body and gaskets and the shape of flanges. For different control purposes, several different types of cones and inner designs are used.
attention!: Valves shall only be used for the appropriate design- and operation data
The body material and nominal pressure of the valve is written on the valve body. These data have to fit the operation data and have to be suitable for the medium.
Every valve has an unique serial number, which is written on the name plate of the valve in the box "W. Nr.". For ordering spare parts, always give the serial number of the valve. (see Appendix Figure 1)
Several tests (pressure testing, leakage testing,...) are done in the work shop for every valve. Also the set up of the valve is done in the work shop, therefore a calibration or set up of the valve is not necessary.
caution!: Before beginning to install or operate valve please read "hazard warings...". 0000-7004
Only trained and qualified specialist staff may install and commission valves.
2 Installation and connection
2.1 Fitting instructions
Before installing valve following items should be read:
installation space:
The installation point should allow sufficient space to ensure correct maintenance and enough space to open the cover of the actuator. Motor valves installed outdoors should have suitable weather protection such as a sun and rain hood.
before installation:
the guard caps should be removed from the flanges.
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
cleaning of pipes:
The piping should be rinsed to clear out any pollution, welding beads, rust etc. before inserting the control valve. This prevents inner leakage of the valve. A strainer should be fitted in front of the control valve to catch remaining particles.
flow direction:
For two-way valves the arrow an the valve body shows flow direction through valve.
installation position:
Actuator pointing up vertically or horizontally is suitable. If valve is vertically installed, the pillars should be over each other to hold the weight of actuator.
tension on valve body:
Precautions to prevent any stress and tension at valve have to be taken.
piping arrangement:
For correct operation of valve the inlet distance to the valve should be > 5x DN, straight, linear and undisturbed. After valve outlet the outlet distance should be > 10x DN straight, linear and undisturbed.
protection against heat:
To protect actuator against heat the piping and valve body should be insulated. This has to happen before start up.
2.2 Assembly actuator
Valves are normally delivered with actuator already fitted on valve. For removing or changing actuator please refer to installation and operating instructions of actuators.
2.3 Pneumatic connection
Provide every valve with a separate pressure regulator to prevent disconnection risk.
caution!: Avoid moist air in all cases to prevent condensate in system.
3 Commissioning
Valves are already adjusted and testing of function is done at work shop. An adjustment is therefore not necessary.
Start up may only be started when the items of chapter “ Installation and connection” are done.
4 Maintenance
4.1 Stuffing box
Generally spindle packing have to be changed or tightened immediately, because otherwise a new packing can leak again after a short period. Design of spindle packing is shown in the technical data sheets. spindle packing are available as spare parts set at manufacturer. For ordering spindle packing always give serial number of valve (written on name plate "W. Nr.").
4.2 Change of spindle packing
make valve and piping pressureless shut off and empty where valve is installed to change spindle packing actuator has to be removed. For disassembling actuator please refer to operating instructions of
actuator
loosen and remove cap nut remove old packing set and clean packing compartment clean valve spindle insert new packing set according to sectional drawing tighten cap nut and fit actuator onto valve and check limit swithes
4.3 Change of cone assembly
It is recommended to change spindle packing when changing cone assembly. For changing cone assembly gasket (503) is necessary.
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
make valve and piping pressureless shut off and empty where valve is installed to change cone assembly actuator has to be removed. For disassembling actuator please refer to operating instructions of remove bonnet (201) of body (101) remove cone assembly (300) of bonnet (201) clean gasket areas assemble bonnet (201) with cone assembly (300) on valve body (101) fit actuator onto valve and check limit switches according operating instructions of actuator.
1 Informations générales
La RTK est une vanne actionnée par air (ou par eau) spécialement conçue pour permettre l’élimination des corps solides qui se déposent au fond de la chaudière (purge par le bas). Elle est utilisée en conjonction avec une minuterie de purge RTK afin de
contrôler la purge par le bas, d’assurer que les cycles de purge recommandés pour la chaudière ont lieu avec une perte de chaleur minimale et d’éviter la duplication ou l’omission.
La fréquence de la purge par le bas dépend normalement du mode de fonctionnement de la chaudière et des instructions du fabricant de la chaudière. En règle générale, elle est effectuée au minimum une fois par jour pendant une durée maximale de cinq secondes. L’alimentation en air/eau est activée par l’électrovanne, ce qui pousse le piston contre la pression des ressorts. La tige de la vanne (fixée au piston) éloigne le cône de la soupape du siège, ouvrant la vanne complètement. Lorsque la vanne est ouverte, un segment racleur retire tout dépôt présent sur la tige protégeant les joints. Sur décharge de la pression d’air/eau, les ressorts remettent la vanne en position fermée. Le levier d’intervention manuelle est poussé vers le bas pour soulever la plaque inférieure de connexion et ouvrir la vanne. La goupille d’arrêt doit d’abord être retirée. La vanne peut être verrouillée en position ouverte comme indiqué à la Figure 1 (encart).
Le choix d’une vanne dépend de son application et des caractéristiques techniques requises ( diamètres nominaux des canalisations, pression nominale, matériau du corps de la vanne ainsi que la forme des brides). En fonction du type de contrôle désiré, différents types de clapets peuvent être adaptés.
Attention!! : Les vannes doivent être seulement utilisées dans leur champ d’application.
Le matériau du corps ainsi que la pression nominale de la vanne sont distinctement indiqués sur la vanne. Ces données doivent être adaptées aux conditions d’utilisation ainsi qu’aux fluides employés .
La tracabilité des vannes est assurée par leur numéro de série unique ,“ W.Nr “( situé sur la vanne) afin de faciliter les commandes de pièces détachées, communiquer le numéro de série de la vanne employée.
Les vannes sont mise au point et soumises à plusieurs tests après production (Exemple : Test de pression , test d’étanchéité).Aucun réglage supplémentaire n’est nécessaire.
Attention ! : Veuillez avant toute installation ou utilisation consulter les précautions d’emplois.
L’installation ou la mise en service des vannes ne devra être réalisée que pas des personnes qualifiées.
2 Installations et connexions
2.1 Instructions d’installation
Avant toute installation lire attentivement les chapitres ci-dessous
Espace d’installation :
La place nécessaire pour assurer une maintenance convenable doit être prévue (Prévoir l’ouverture du couvercle du moteur). Lors du montage des soupapes motorisées à ciel ouvert, il y a lieu de les protéger par des auvents contre les intempéries.
Pré installation :
Les carters de protection des brides doivent être retirés.
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
Nettoyage des canalisations :
Les canalisations doivent être nettoyées afin d’éliminer toute pollution (rouille , calamine, billes de soudure) avant l’insertion d’une vanne de régulation afin d’éviter d’endommager le clapet ainsi que son étanchéité. Un filtre en amont de la
vanne peut être inséré afin de limiter le passage de particules résiduelles .
Direction du flux :
Pour les vannes à deux voies, le sens de circulation est indiqué sur la vanne par une flèche .
Orientation de l’installation :
L’ensemble peut être installé soit à l’horizontal soit en pointant vers le haut à la vertical . Si l’ensemble se trouve à l’horizontal les colonnettes doivent se situées l’une au dessus de l’autre afin de pouvoir supporter le poids du moteur.
Tension sur le corps de la vanne :
Toutes les précautions doivent être prises afin de protéger la vanne de toutes contraintes extérieures.
Positionnement des canalisations :
Afin d’obtenir un fonctionnement optimal de la vanne, l’admission doit être située axialement à une distance dégagée de tout encombrement >5x DN. L’échappement doit être situé axialement à une distance dégagée de tout encombrement >
10xDN.
Protéger le moteur de la chaleur :
Afin de protéger le moteur de la chaleur, les canalisations ainsi que le corps de la vanne doivent être isolés avant le démarrage.
2.2 Assemblage du moteur
Les vannes sont généralement livrées avec le moteur pré-assemblé .Pour pivoter, remplacer ou démonter les servomoteurs, il est fortement conseillé de se référer aux instructions de maintenance.
2.3 Connexions pneumatiques
Pour chaque servomoteur pneumatique prévoir un régulateur de pression, afin d’éviter aux moteurs de s’influencer.
Attention ! la condensation dans le système doit être absolument évitée
3 Mise en service :
Toutes les vannes sont ajustées et pré-testées sur notre site. Un ajustement avant montage n’est pas nécessaire . Le démarrage ne doit être effectué qu’après la lecture des paragraphes précédents ainsi que leurs applications .
4 Maintenance
4.1 Garniture d’étanchéité de tige
Une garniture endommagée doit être ou changée ou resserrée nécessairement (dans le cas d’un système en graphite).Sinon la
garniture de remplacement pourrait à son tour, après une courte période ne plus être étanche . La structure des garnitures est détaillée dans les fiches techniques correspondantes. Les garnitures sont aussi disponibles en pièces détachées. Afin de faciliter la commande, communiquer le numéro de série de la vanne ( plaque signalétique « W.Nr »)
4.2 Changement de la garniture de la tige
Purger les canalisations et désactiver la vanne  Afin de pouvoir changer la garniture, le servomoteur doit être démonté. Afin de pouvoir démonter le servomoteur veuillez
vous référer aux instructions prévues à cet effet.
l’écrou d’accouplement doit être retiré.  Enlever l’ancienne garniture et nettoyer son emplacement. Insérer une nouvelle garniture (Voir schéma).  Resserrer l’écrou d’accouplement ,remonter le moteur et replacer les capteurs fin de course.
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
DN
PN
NPS
class
Gewinde / thread
Dichtungsmaße /
gasket dimensions
Anzugsmomente /
tightening torque
n
D / mm
d1 / mm
d2 / mm
s / mm
Ma / Nm
15 / 20
40
½” / ¾”
150/300 4 M 10
40
54
1,5
35
25 / 32
40
1”/ 1 ¼”
150/300 4 M 12
54
68
1,5
61
40 / 50
40
1½” / 2”
150/300 4 M 16
68
82
1,5
147
65
40
2 ½”
150/300 4 M 16
93
113
1,5
147
DN
PN
Gewinde / threat
Dichtungsmaße /
dimension gasket
Anzugsmomente /
torque
n
D / mm
d1 / mm
d2 / mm
s / mm
Ma / Nm
15
160
4
M 16
48
65
1,5
147
25
160
4
M 20
55
75
1,5
285
40
160
4
M 24
76
100
1,5
490
50
160
4
M 24
90
115
2,0
490
65
160
4
M 24
110
135
2,0
490
Type
Hub
KvsDN PNW. Nr.
Type
Hub
KvsDN PS
0036
TS
W. Nr.
Seriennummer / Serial number / numero de vannes
Nennweite / nominal diameter / diamètre nominale
Nenndruck / nominal pressure / pression nominale
Stellweg / stroke / course
Temperatur / temperature / température
Baureihe / Serie / series
Jahr / year / annèc
Monat / month / mois
J mm xxxx
4.3 Changement de l’ensemble clapet
Il est recommandé de changer la garniture lors d’un changement de l’ensemble clapet ainsi que le joint plat (503) qui est aussi nécessaire.
Vannes à garniture de tige
Purger les canalisations et désactiver la vanne Afin de pouvoir changer la garniture le servomoteur doit être démonté (Voir instructions de démontage). retirer le couvercle (201) du corps(101) Retirer et changer l’ensemble clapet(300) du couvercle(201) Nettoyer l’emplacement des joints Vannes a deux voies et divergentes : Assembler le couvercle (201) avec l’ensemble clapet sur le corps(101) en
croisant le resserrage
Remonter le servomoteur, recaler les capteurs fin de course et vérifier leurs calibration
Anhang / Appendix
1 Drehmoment für Schrauben / torque for nuts
Bild 1/ Figure 1 : Typenschild auf Ventil / nameplate on valves /
Maximal zulässige Betriebsdruck / Temperatur siehe technische Dokumentation
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
501
503
502
101
301
102
201
302
406
407
404
403
402
401
405
400
Pos
D
GB
FR
101
GS-C 25
BVK...
Gehäuse
body
corps
102
1.4571/Stellit
Sitzring
seat ring
siège
103
Reingraphit
FDIF…
Flachdichtring
gasket
joint plat
201
GS-C 25
BVD...
Deckel
bonnet
couverde
300
BVK...
Kegelgruppe
cone assembly
module clapets
301
1.4122
Kegelkopf
cone head
clapet
302
1.4571
Kegelspindel
cone spindle
tige
400
CVSHHNGE
Spindelabdichtung
stuffing box
garniture presse etoupe
401
CuZn 40 Pb 2
Stopfring
stuffing-ring
rondelle
402
PTFE/Kohle
Dachmanschetten
chevron rings
manchettes
403
1.4301
Scheibe
washer
rondelle
404
1.4310
Druckfeder
spring
ressort
405
NBR Abstreifring
scraper ring
anneau racleur
406
Rg 7 Führungsring
bush
douille
407
1.4301
Distanzrohr
spacer
tube d'écartement
501
C 35 Y / 24CrMo5
Sechskantmutter
nut
écrou six pans
502
Ck 35 Yk / 21CrMoV 57
Stiftschraube / Schraubenbolzen
stud
tige filetée
503
Reingraphit
FDIF...
Flachdichtring
gasket
joint plat
Maximum allowable operation pressure / temperature see technical documentation Maximum pression d’opération / température d’opération voir documentation technique
Prüfdruck / test pressure / pression de contrôle
PT = 1,5 x PN
PN...Nenndruck, nominal pressure, pression nominal
2 Ersatzteilliste / spare parts list / liste de rechange
Technische Änderung vorbehalten/ Subject to technical alteration/ Sous réserve de modifications techniques
02/2015
Einbau- und Betriebsanleitung Installation and Operating instructions Instructions de montage et de service
Pos
D
GB
FR
101
1.0976 Gehäuse
body
corps
103
1.0976 Gehäuse
body
corps
104
1.0619 Flansch
flange
bride
105
DIN 933-8.8
Sechskantschraube
bolt
vis á tete
106
DIN 127-A8
Federring
Locking washer
Rondelle élastique
107 8
Sechskantmutter
nut
écrou six pans
108
Polyamid
Verschlußstopfen
Veut screw
Bouchon d’évent
200 CMET…..
Membrantellergruppe
diaphragm group
group de membrane
202
JS 1025
Membranteller
Diaphragm plate
Plateau á membrane
203
1.0976 Membranteller
Diaphragm plate
Plateau á membrane
204
1.4404 Kolbenstange
Rod
Tige du piston
206
DIN 933 – A2
Sechskantmutter
nut
écrou six pans
207
DIN 439 – A2
Sechskantschraube
bolt
vis á tete
300 CKUK……
Kupplungsgruppe
coupling group
group d ácouplement
301
1.4104 Abstandsbolzen
pillars
boulon entretrois
302
A-021 Parallelführung
parallel motion
guidage paralèlle
303
1.4104 Kupplungsbuchse
Coupling bush
Manchon dáccouplement
304
DIN 127-A8
Federring
Locking washer
Rondelle élastique
305
DIN 439-8
Sechskantschraube
screw
Vis écrou six pans
400 CMEM……
Membrangruppe
diaphragm group
group de membrane
401
EPDM Membrane
Diaphragm
Membrane
402
P5008 Dichtring
seal ring
joint
403
NBR O-Ring
o-Ring
Joint torique
108 206 207
101 501
401
105
107
202 103
203 108 403
402
104
204 304 302 303 301
Technische Änderung vorbehalten/ Subject to technical alteration/ Sous réserve de modifications techniques
02/2015