Rs Advantage User Manual

Instruction Leaflet
RS stock no. 437-648
Issued August 1997 9778
Advantage 6 Alarm Panel
Introduction
The control panel is designed to be simple to install, programme, and to use. The 16 button keypad allows you to select, change,or inhibit the many facilities available in the unit. A remote ke ypad is a v ailable separ atel y for arming ,part arming and disarming the unit
The control panel is programmed using either the user code (factory set 1234) or the engineer code (factory set 9999). It is advisable to change both code numbers to a personally selected code, using any combination from 0000 to 9999, when the installation is complete.
The engineer programmes are protected by a non volatile memory (NVM). This means that when all power has been removed and then reconnected any previously programmed information remains operative. The NVM facility also protects the control panel microchip from mains surges and spikes.
The control panel provides 6 detector zones, a personal attack circuit and two tamper circuits. All zones are capable of operation with normally open and normally closed detectors. A bank of 10 LED indicators will indicate the status whilst programming or whilst in use.
An integral battery charge circuit will enable a rechargeable battery such as RS stock no. 597-813 to provide power during mains failure. Outputs are provided for bell/sounder, and strobe.
The 6 detector zones are active only when the control panel is armed. The personal attack circuit, 24hr circuits are active 24 hours a day even if the control panel is disarmed.
The advantage keypad
The advantage keypad uses ICONS to picture the key function, a list of key functions follows in figure 1:
The control panel is factory set to be armed without the need to enter the user code. It is possible to programme the control panel so a user code is required to arm the system. If this mode is selected the user code can only be changed by either, programming under the engineer mode or, returning the control panel to symbol arming mode then the user selecting a new code and returning to control panel to user code arming code.
Note: Please ensure you read this document completely
before you begin your installation.
System planning
T o ensure the installation pr oceeds smoothly it is best to plan the work before you begin. Start by drawing a plan of the building (see figure 2 and 3). You will need to divide the building into zones. Zone 1 is always used as the final exit zone with the advantage panel and zone 2 is factory programmed as walk through (this may be altered).
Office
Factory
Lobby
Accounts
A
B
C
D
E
F
GG
H
I
J
K
A
Figure 1
Full set Arm Zone omit
Part set Reset Event replay
to Numeric keys
Figure 2 Ground floor view
A. Magnetic contact zone 1 B. Zone 2 C. Zone 3 D. Magnetic contact zone 4 E. Zone 5 F. PIR G. Siren H. Personal attack switch
I. Vibration detector J. Control panel
Note: Alarm control panel should
be located within the protected area
Note: Zone 6 may be a PIR on the
first floor landing
Figure 3 Ground floor view of a commercial premises
A. Magnetic contact zone 1 B. Zone 2 C. Dual tech zone 3 D. Vibration detector zone 4 E. Zone 5 F. Zone 6
G. PIR H. Siren I. Personal attack switch J. Control panel K. Additional keypad
09
0
G
A A
FF
BC
Lounge
Dining Room
CC
F
H
Hall
321 654 987
Garage
K
Kitchen
D
E
I
9778
2
System layout
The system layouts shown are a guide to typical positions of the system components. This will obviously vary depending on the premises and level of protection to be afforded. However the general rules given cover all installation layouts.
General rules
1. Final exit doors should have magnetic contact switches fitted to ensure that the premises cannot be vacated with the doors left open and also to protect against forced entry.
2. PIR detectors are best fitted where an intruder has to pass through an area to gain access (i.e.halls and landings) or to protect specific valuable items (i.e. lounge). Care should be taken in siting to avoid direct sunlight, strong lighting and heat sources (hence the vibration detector s in the kitchen) as these may cause nuisance tripping. They are best sited so the intruder cuts across the field of view, see figure 2 (some products are specif ically designed for long corridors in this instance this rule does not apply),hence a corner position is usually adopted.
3. PIR, ultrasonic, vibration detectors, etc. all have complex electronics. These are best given their own zone as in the event of a fault occurring isolating the fault will be quicker and nuisance tripping quickly eliminated. Magnetic door contacts tend to be very reliable if installed well within their magnetic actuation limit. Hence these can be put in ser ies together on a loop if appropriate. They are also easier to test if faulty.
4. Wir ing is best concealed where possible to prevent damage and tampering. Try to avoid running alongside mains cables as interference may occur.
5. The sounder/SAB unit should be fitted well above head height to avoid tampering. The wiring should pass directly through the wall behind the unit to make it inaccessible.
6. The control panel requires a 240V power source. An unswitched fused spur preferably direct from the consumer unit on its own fuse wired in accordance with the current IEE regulations should be provided.
Using the above general rules you should plan your installation on your sketched drawing considering the panel siting,how the cable runs can be minimised, where different types of detector will be fitted and which zone they will be on. When you have finalised your plan you can begin installation.
Installation
The following instructions should be followed in sequence to ensure trouble free installation. To begin with, the alarm panel should be tested.
The control panel
Printed circuit board (PCB) is clearly marked with each output, input, and the relevant polarity. Wire links are f itted to each of the 6 zones and the three 24 hour circuits, to simulate closed circuits. The wire links are removed during installation as each zone/circuit is connected. Wire links should never be fitted where no link is depicted across the terminals on the PCB. Most of the detectors in the security industry are normally closed contacts these must be wired in series,normally open detectors such as pressure mats can also be used, wire them between the zone and the 24 hour terminal.
Testing the control panel
The control panel is fitted with the factory fitted wire links, to enable the panel to be tested prior to installation.
1. Remove the two front cover screws (located behind the LED
flap) and the front cover, and place safely to one side in the box provided to eliminate the chance of damage.
2. Check that the 9 factory fitted links (see figure 4) are positioned across each pair of the 6 zone inputs, PA, 24 hour and SCB terminals. Press down the lid tamper spring. (It is important that this spring is depressed throughout the test to avoid the control panel activating). Or to temporarily defeat the lid tamper connect a wire between the SCB 0 terminal and the left 24 hour terminal. Do not
forget to remove this wire before commissioning the system.
3. Fit the 12V battery (
RS stock no. 597-813) to the unit using battery connecting wires provided. Observe the correct polarity, red wire to red (+) terminal, black wire to black (-) terminal. The panel is now ready to test.
4. Press (full guard),the clear LED will illuminate.
5. Remove a factory fitted link wire from zone 1 and the respective zone LED will light and a tone indication will be heard. Ref it the link and the zone LED will extinguish.
6. Repeat step 5 for all other zones. For each of the zones opened a tone indication will be heard,the number of bleeps will depend on what zone is open i.e. 1 bleep for zone 1, 2 bleeps for zone 2 and so on.
7. Test the lid tamper by releasing the tamper spring, the internal sounder will activate, replace tamper spring, and enter user code (1,2,3,4). The 24 hour LED will be illuminated and the sounder will cease. Press the (reset) key to return to standby.
8. To test the 24 hour SCB and PA circuit repeat the above sequence removing and replacing the wire link in each circuit in turn. After each test enter user code (1,2, 3, 4) then press reset to return to standby. Disconnect the battery when you have finished testing.
Siting the control panel
Site the panel in a position which is above the accessible height of small children. Try to site the control panel close to a mains electricity supply.
Mark the two fixing holes on the left and right-hand sides of the bottom and the hole in the top centre on the wall, and fix the panel loosely. Only secure tightly once installation is complete.
Wiring
Detectors
The exact positioning of the detection devices should now be decided and the detectors wired. Typically for passive infrared detectors (PIR) 6-core cable will be required (RS stock no.365-
587) and for door/window contacts 4-core cable (RS stock no.
365-571). If only a limited number of magnetic contacts are used wire 6-core throughout. Wire the correct cable to each position. Connect the detectors as shown in figure 5.
Connecting to the mains supply
WARNING - ELECTRICITY CAN KILL
Before connecting the control panel to the mains supply ensure that the supply is disconnected at the consumer unit.
The ideal mains supply is direct from the consumer unit, on its own fused spur, wired in accordance with the latest IEE regulations. You will require 5A 3-core cable suff icient in length to connect the control panel to the mains power supply.
Figure 4
Cable clamp
9778
3
Figure 4 shows the location of the cable clamp. To secure the cable,use the cable clamp located in the back of the advantage case. Break off the cable clamp fr om the case. Feed one end of the 3-core cable through the back of the control panel and connect as follows to the transformer terminal block.
Live (L) red or brown. Neutral (N) black or blue. Earth (E) green or green and yellow. Secure the cable clamp over the cable using the screws provided.
Connecting the sounder unit
Disconnect the mains supply. Run a 6-core cable to the sounder from the panel.
Connect the sounder unit to the panel as shown in figure 6. Testing should be carried out in accordance with the instructions included with the sounder unit.
RT
SWITCHED POSITIVE
STROBE + STROBE ­BELL + BELL -
SPEAKER
NVM RESET
BELL/STROBE F3 SPEAKER
AUX. F2
BATTERY F1
AUX + AUX ­BATTERY + RED BATTERY - BLACK AC AC
TRANSFORMER
SCB 24 hour
KEYSWITCH PA
ZONE 6 ZONE 5 ZONE 4
ZONE 3
ZONE 2
ZONE 1
N/C
N/C
N/C
N/C N/C
- +
These will be factory supplied with links as shown on the PCB
Figure 5 Control panel detector connections
A
B
C
D
A. Personal attack B. Zone 2 PIR C. The series 24 hour loop for each zone is best taken
back to the control panel and linked using a connector block such as RS stock no. 423-655
D. Zone 1 door/window magnetic contacts
When the mains wiring is completed restore the mains supply, the mains LED indicator and the keypad should be illuminated. The panel will bleep replace the front cover. Enter user code (1234) the 24 hour LED will be illuminated and bleeping will cease.
Press (reset), the panel will return to standby. At this stage it is worth checking the detectors for correct
operation.
Detector test
1. Press
2. Now walk around and activate each detector in turn. The panel will bleep and the LED light as each detector is activated.
Note: PIRs require a number of minutes setting time
before use.
3. When all detectors have been tested type
NVM RESET
BELL/STROBE F3
SPEAKER
AUX. F2
BATTERY F1
BELL -
BELL +
STROBE -
STROBE +
SW- +Ve
Strobe trig -Ve Strobe trig -Ve
SW-Ve
RT
SCB
Ret Sig Ret Sig
Return
0V
-Ve
0V
+Ve
+Ve
740-427 740-433 437-660
Siren trig -Ve Siren trig -Ve
Figure 6 Sounder connections
Loading...
+ 5 hidden pages