This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
Table of Contents
Unit Dimensions ..........................................................2
A80UH1E & 80G1UHE Gas Furnace ..........................3
Shipping and Packing List ...........................................3
Safety Information .......................................................3
General ........................................................................4
Combustion, Dilution & Ventilation Air .........................5
Repair Parts List ........................................................33
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
Manufactured By
Allied Air Enterprises LLC
A Lennox International, Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
Save these instructions for future reference
507330-01Issue 1721Page 1 of 34
As with any mechanical equipment, personal injury can
result from contact with sharp sheet metal edges. Be
careful when you handle this equipment.
*P507330-01*
CAUTION
(P) 507330-01
Page 2
Unit Dimensions
1
NOTE -C20 and D20 size units installed in upow
applications that require air volumes of 1800 cfm (850 L/s or
greater must have one of the following:
1. Single side return air with transition, to accommodate 20
x 25 x 1 in. (508 x 635 x 25 mm) air lter.
2. Single side return air with optional RAB Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and one side return air.
2
Flue outlet may be horizontal but furnace must be vented
vertically.
3
Optional external side return air lter kit cannot be used with
the optional RAB Return Air Base.
*
Consider sizing requirements for optional IAQ equipment before
cutting side return opening.
A80UH1E / 80G1UHE
Capacity
045-12
070-12
090-16
090-20
110-202153319-7/850419-1/24958203
135-2024-1/262223-3/8546235849-3/4248
FRONT VIEWSIDE VIEW
ABCD
in.mmin.mmin.mmin.mm
14-1/236813-3/8340133304-3/4121
17-1/244616-3/8416164066-1/4159
507330-01Page 2 of 34Issue 1721
Page 3
A80UH1E & 80G1UHE Gas Furnace
The A80UH1E & 80G1UHE gas furnace is shipped ready
for installation in the upow or horizontal right position (for
horizontal left position the combustion air pressure switch
must be moved). The furnace is shipped with the bottom
panel in place. The bottom panel must be removed if the
unit is to be installed in horizontal or upow applications
with bottom return air.
The furnace is equipped for installation in natural gas
applications. A conversion kit (ordered separately) is
required for use in propane/LP gas applications.
Clearances
Adequate clearance must be made around the air openings
into the vestibule area. In order to ensure proper unit
operation, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code.
Vent installations must be consistent with the venting
tables (in this instruction) and applicable provisions of local
building codes.
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in Figure 7 and Figure 11.
Accessibility and service clearances must take precedence
over re protection clearances.
Shipping and Packing List
1 - Assembled Gas Furnace
1 - Bag assembly containing the following:
2 - Screws
3 - Wire nuts
1 - Snap bushing
1 - Snap Plug
1 - Wire tie
1 - Vent warning label
1 - Owner’s manual and warranty card
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
Please refer to specication sheets for available
accessories.
Safety Information
DANGER
DANGER OF EXPLOSION!
There are circumstances in which odorant used with
LP/Propane gas can lose its scent. In case of a leak,
LP/Propane gas will settle close to the oor and may be
difcult to smell. An LP/Propane leak detector should be
installed in all LP applications.
Installed Locations
For installation in a residential garage, the furnace must be
installed so that the burner(s) and the ignition source are
located no less than 18 inches (457 mm) above the oor.
The furnace must be located or protected to avoid physical
damage by vehicles. When a furnace is installed in a public
garage, hangar, or other building that has a hazardous
atmosphere, the furnace must be installed according to
recommended good practice requirements and current
National Fuel Gas Code.
Temperature Rise
NOTE: Furnace must be adjusted to obtain a temperature
rise within the range specied on the unit nameplate.
Failure to do so may cause erratic limit operation and may
result in premature heat exchanger failure.
This furnace must be installed so that its electrical
components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be
installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
See Figure 1. With a parallel ow arrangement, a damper
(or other means to control the ow of air) must adequately
pre vent chilled air from entering the furnace. If the damper
is manually operated, it must be equipped to prevent
operation of either the heating or the cooling unit, unless it
is in the full HEAT or COOL setting. See Figure 1.
Certications
These units are CSA International certied to ANSI Z21.47.
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel
Gas Code (ANSI-Z223.1). The National Fuel Gas Code is
available from the following address: American National
Standards Institute, Inc., 11 West 42nd Street, New York,
NY 10036.
507330-01Issue 1721Page 3 of 34
Page 4
Heating Unit Installed Parallel to Air Handler Unit
Heating Unit Installed Upstream of Cooling Unit
Figure 1.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National
Electric Code, ANSI/NFPA No. 70. The National Electric
Code (ANSI/NFPA No. 70) is available from the following
address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE: This furnace is designed for a minimum continuous
return air temperature of 60° F (16°C) or an intermittent
operation down to 55° F (13°C) dry bulb for cases where
a night setback thermostat is used. Return air temperature
must not exceed 85° F (29°C) dry bulb.
• A room thermostat must control the furnace. The use
of xed jumpers that will provide continuous heating is
not allowed.
• The return air duct must be provided and sealed to the
furnace.
• Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
• Air lters must be installed in the system and must be
maintained during construction.
• Air lters must be replaced upon construction
completion.
• The input rate and temperature rise must be set per
the furnace rating plate.
• One hundred percent (100%) outdoor air must be
provided for combustion air requirements during
construction. Temporary ducting may supply outdoor
air to the furnace. Do not connect duct directly to
the furnace. Size the temporary duct following these
instructions in section for Combustion, Dilution and
Ventilation Air in a conned space with air from outside.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be
thoroughly cleaned following nal construction cleanup.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be
veried according to these installation instructions.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
This furnace may be installed in alcoves, closets, attics,
basements, garages, and utility rooms in the upow or
horizontal position.
This furnace design has not been CSA certied for
installation in mobile homes, recreational vehicles, or
outdoors.
Use of Furnace as a Construction Heater
Allied Air does not recommended the use of these units
as a construction heater during any phase of construction.
Very low return air temperature, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit.
Units may be used for heating of buildings or structures
under construction, if the following conditions are met:
• The vent system must be permanently installed per
these installation instructions.
In addition to the requirements outlined previously, the
following general recommendations must be considered
when installing one of these furnaces:
• Place the furnace as close to the center of the air
distribution system as possible. The furnace should
also be located close to the chimney or vent termination
point.
• Do not install the furnace where drafts might blow
directly into it. This could cause improper combustion.
• Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other
insulated space, keep insulation away from the
furnace.
507330-01Page 4 of 34Issue 1721
Page 5
NOTE: The Commonwealth of Massachusetts stipulates
these additional requirements:
• Gas furnaces shall be installed by a licensed plumber
or tter only.
• The gas cock must be “T handle” type.
• When a furnace is installed in an attic, the passageway
to and service area surrounding the equipment shall
be oored.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects or other
reproductive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufcient
outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans,
appliance vents, chimneys, and replaces force additional
air that could be used for combustion out of the house.
Unless outside air is brought into the house for combustion,
negative pressure (outside pressure is greater than inside
pressure) will build to the point that a downdraft can occur
in the furnace vent pipe or chimney. As a result, combustion
gases enter the living space creating a potentially
dangerous situation.
WARNING
Insufcient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine base swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace
components.
In the absence of local codes concerning air for combustion
and ventilation, use the guidelines and procedures in this
section to install these furnaces to ensure efcient and
safe operation. You must consider combustion air needs
and requirements for exhaust vents and gas piping.
A portion of this information has been reprinted
with permission from the National Fuel Gas Code
(ANSI-Z223.1). This reprinted material is not the complete
and ofcial position of the ANSI on the referenced subject,
which is represented only by the standard in its entirety.
All gas red appliances require air for the combustion
process. If sufcient combustion air is not available, the
furnace or other appliances will operate inefciently
and unsafely. Enough air must be provided to meet the
needs of all fuel burning appliances and appliances such
as exhaust fans which force air out of the house. When
replaces, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is necessary to
ensure proper combustion and to prevent a downdraft.
Insufcient air causes incomplete combustion which can
result in carbon monoxide.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is
installed in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement
or large equipment room with a volume greater than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of
the combined input rating of all appliances installed in that
space. This space also includes adjacent rooms which are
not separated by a door. Though an area may appear to
be unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of
the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
507330-01Issue 1721Page 5 of 34
Page 6
When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air must be handled by
ducts which are sealed to the furnace casing and which
terminate outside the space containing the furnace. This
is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room. Even a small leak around the base of the
unit at the platform or at the return air duct connection can
cause a potentially dangerous negative pressure condition.
Air for combustion and ventilation can be brought into the
conned space either from inside the building or from
outside.
outdoors or indirectly through vertical ducts. Each opening
shall have a minimum free area of 1 square inch (645 mm2)
per 4,000 Btu (1.17 kW) per hour of total input rating of all
equipment in the enclosure. See Figure 3 and Figure 4.
When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1
square inch (645 mm2) per 2,000 Btu (.56 kW) per total
input rating of all equipment in the enclosure. See Figure 5.
When ducts are used, they shall be of the same cross
sectional area as the free area of the openings to which
they connect. The minimum dimension of rectangular
air ducts shall be no less than 3 inches (75 mm). In
calculating free area, the blocking effect of louvers, grilles,
or screens must be considered. If the design and free area
of protective covering is not known for calculating the size
opening required, it may be assumed that wood louvers
will have 20 to 25 percent free area and metal louvers and
grilles will have 60 to 75 percent free area. Louvers and
grilles must be xed in the open position or interlocked
with the equipment so that they are opened automatically
during equipment operation.
NOTE: Each opening shall have a free area of at least one square
inch per 1,000 Btu (645 mm² per .29 kW) per hour of the total
input rating of all equipment in the enclosure, but not less than 100
square inches (64546 mm²).
Figure 2. Equipment in Conned Space - All Air From
Inside
Air from Inside
If the conned space that houses the furnace adjoins a
space categorized as unconned, air can be brought in
by providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas red equipment in the conned
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See Figure 2.
Air from Outside
If air from outside is brought in for combustion and
ventilation, the conned space must have two permanent
openings. One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within
12 inches (305 mm) of the bottom. These openings must
communicate directly or by ducts with the outdoors or
spaces (crawl or attic) that freely communicate with the
NOTE: The inlet and outlet air openings shall each have a free
area of at least one square inch per 4,000 Btu (645 mm² per
1.17 kW) per hour of the total input rating of all equipment in the
enclosure.
Figure 3. Equipment in Conned Space - All Air from
Outside
(Inlet Air from Crawl Space & Outlet Air to Ventilated
Attic)
507330-01Page 6 of 34Issue 1721
Page 7
NOTE: The inlet and outlet air openings shall each have a free
area of at least one square inch per 4,000 Btu (645 mm² per
1.17 kW) per hour of the total input rating of all equipment in the
enclosure.
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not
connect the return air ducts to the back of the furnace.
Doing so will adversely affect the operation of the safety
control devices, which could result in personal injury or
death.
The gas furnace can be installed as shipped in either the
upow position or the horizontal position.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection, and
installation and service clearances [24 inches (610 mm) at
unit front]. The unit must be level.
Figure 4. Equipment in Conned Space - All Air from
Outside
(All Air through Ventilated Attic)
NOTE: Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645 mm² per .59 kW) per hour of the
total input rating of all equipment in the enclosure. If the equipment
room is located against an outside wall and the air openings
communicate directly with the outdoors, each opening shall have
a free area of at least 1 square inch per 4,000 Btu (645 mm² per
1.17 kW) per hour of the total input rating of all other equipment in
the enclosure.
NOTE: Units with 1/2 hp and 3/4 hp blower motors are
equipped with three exible legs and one rigid leg. See
Figure 6. The rigid leg is equipped with a shipping bolt and
a at white plastic washer (rather than the rubber mounting
grommet used with a exible mounting leg). The bolt and
washer must be removed before the furnace is placed into
operation. After the bolt and washer have been removed,
the rigid leg will not touch the blower housing.
Units with 1/2 HP & 3/4 HP
Blower Motor.
Figure 6.
Figure 5. Equipment in Conned Space - All Air from
Outside
507330-01Issue 1721Page 7 of 34
Page 8
Upow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in Figure 7.
2. Single side return air with optional return airbase. See
Figure 12.
3. Bottom return air.
4. Return air from both sides.
5. Bottom and one side return air.
Type of Vent
Connector
Top1 in. (25 mm)1 in. (25 mm)
*Front2-1/4 in. (57 mm)2-1/4 in. (57 mm)
Back00
Sides0†0
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
* Front clearance in alcove installation must be 24 in. (610
mm). Maintain a minimum of 24 in. (610 mm) for front service
access.
‡ For installation on a combustible oor, do not install the
furnace directly on carpeting, tile or other combustible
materials other than wood ooring.
† Left side requires 3 in. if a single wall vent is used on 14-1/2
in. cabinets.
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on Page 2.
NOTE: 20C and 20D units that require air volumes over
1800 cfm (850 L/s) must have one of the following:
Figure 8. Single Side Return Air
(with transition and lter)
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See Figure 9.
Figure 9. Removing the Bottom Panel
Horizontal Applications
The furnace can be installed in horizontal applications.
Order horizontal suspension kit (51W10) from Allied Air, or
use equivalent suspension method.
1. Single side return air with transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air lter.
(Required to maintain proper air velocity.) See Figure
8.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in Figure 11.
507330-01Page 8 of 34Issue 1721
Page 9
This furnace may be installed in either an attic or a crawl
space. Either suspend the furnace from roof rafters or oor
joists, as shown in Figure 10, or install the furnace on a
platform, as shown in Figure 13.
Figure 10. Typical Horizontal Application
Unit Suspended in Attic or Crawl Space
Type of Vent
Connector
Type CType B
1
Top00
*Front2-1/4 in. (57 mm)2-1/4 in. (57 mm)
Back00
Ends2 in. (51 mm)2 in. (51 mm)
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
* Front clearance in alcove installation must be 24 in. (610
mm). Maintain a minimum of 24 in. (610 mm) for front service
access.
‡ For installation on a combustible oor, do not install the
furnace directly on carpeting, tile or other combustible
materials other than wood ooring.
Figure 11. Horizontal Application Installation
Clearances
FRONT VIEW
NOTE: Optional Side Return Air Filter Kits are not for use with Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the eld. There are cutting guides stenciled on the cabinet for the side return air opening.
The size of the opening must not extend beyond the markings on the furnace cabinet.
² To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
SIDE VIEW
Figure 12. Optional Return Air Base
(Upow Applications Only - For Use with A, B, C and D Cabinets)
507330-01Issue 1721Page 9 of 34
Page 10
NOTE: Heavy gauge perforated sheet metal straps may
be used to suspend the unit from roof rafters or ceiling
joists. When straps are used to suspend the unit in this
way, support must be provided for both the ends. The
straps must not interfere with the plenum or exhaust
piping installation. Cooling coils and supply and return air
plenums must be supported separately.
NOTE: When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the evaporator coil to drain.
WARNING
The inner blower panel must be securely in place when
the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
Filters
Return Air - Horizontal Applications
Return air must be brought in through the end of a furnace
installed in a horizontal application. The furnace is equipped
with a removable bottom panel to facilitate installation. See
Figure 9.
Figure 13. Horizontal Application
Unit Installed on Platform
This unit is not equipped with a lter or rack. A eld provided
high velocity lter is required for the unit to operate properly.
Table 1 lists recommended lter sizes.
A lter must be in place any time the unit is operating.
Furnace Cabinet
Width
A - 14-1/2”
B - 17-1/2”16 x 25 x 1
C - 21”20 x 25 x 1
D - 24-1/2”24 x 25 x 1
Side ReturnBottom Return
16 x 25 x 1
Filter Size
14 x 25 x 1
Table 1.
Duct System
Use industry approved standards (such as those published
by Air Conditioning Contractors of America or American
Society of Heating, Refrigerating and Air Conditioning
Engineers) to size and install the supply and return air duct
system. This will result in a quiet and low static system that
has uniform air distribution.
WARNING
Improper installation of the furnace can result in
personal injury or death. Combustion and ue products
must never be allowed to enter the return air system or
the living space. Use screws and joint tape to seal the
return air system to the furnace.
In platform installations with bottom return air, the furnace
should be sealed airtight to the return air plenum. A door
must never be used as a portion of the return air duct
system. The base must provide a stable support and an
airtight seal to the furnace. Allow absolutely no sagging,
cracks, gaps, etc..
The return and supply air duct systems must never
be connected to or from other heating devices such
as a replace or stove, etc.. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property
damage could result.
NOTE: Do not operate the furnace in the heating mode
with an external static pressure that exceeds 0.8 inches
w.c. Higher external static pressures may cause erratic
limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel must be installed in the supply air duct. The
access panel should be large enough to permit inspection
(either by smoke or reected light) of the heat exchanger
for leaks after the furnace is installed. The furnace access
panel must always be in place when the furnace is operating
and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE: Return air must not be drawn from a room where
this furnace, or any other gas fueled appliance (i.e., water
heater), or carbon monoxide producing device (i.e., wood
replace) is installed.
507330-01Page 10 of 34Issue 1721
Page 11
When return air is drawn from a room, a negative pressure
is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This
reverse ow of the ue gas may result in incomplete
combustion and the formation of carbon monoxide gas.
This toxic gas might then be distributed throughout the
house by the furnace duct system.
In upow applications, the return air can be brought
in through the bottom or either side of the furnace. If a
furnace with bottom return air is installed on a platform,
make an airtight seal between the bottom of the furnace
and the platform to ensure that the unit operates properly
and safely. Use berglass sealing strips, caulking, or
equivalent sealing method between the plenum and the
furnace cabinet to ensure a tight seal. If a lter is installed,
size the return air duct to t the lter frame.
Venting
A 4 inch diameter ue transition is factory installed on
the combustion air inducer outlet of all models. Figure 15
shows the combustion air inducer as shipped from the
factory.
IMPORTANT
The unit will not vent properly with the ue transition
pointed down in the 6 o’clock position.
The combustion air inducer may be rotated clockwise
or counterclockwise by 90° to allow for top or side vent
discharge in all applications. When the unit is installed,
the ue transition must be in the 9 o’clock, 12 o’clock or
3 o’clock position.
If necessary reposition the combustion air inducer,
pressure switch and/or make-up box as needed per the
following steps. See Figure 15 through Figure 21.
1. Remove the four mounting screws (Figure 14) which
secure the combustion air inducer / pressure switch
assembly to the orice plate. Lift the assembly and
rotate it 90° clockwise or counter clockwise to either
the 3 o’clock position. Resecure with four screws.
Gasket should be left in place.
2. Use tin snips to cut preferred opening on the cabinet
for repositioning the ue outlet. Use the cut-out piece
as a cover plate to patch unused opening on cabinet.
Figure 14. Mounting Screws Location
• Gas supply piping must be brought into the unit from the right side
in order to accommodate the ue pipe.
• Cut combustion air inducer tubing from 9” to 8” to avoid
interference with inducer motor.
• Remove make-up box assembly (2 screws) and cut wire tie to
free make-up box wires. Re install make-up box on other side of
cabinet.
• Resecure make-up box wires: Either pull excess wires through
the blower compartment and secure using supplied wire tie, or
coil excess wire and secure to the gas manifold.
Figure 16. Upow Position
Left Side Vent Discharge
Figure 15. Upow Position
Top Vent Discharge
507330-01Issue 1721Page 11 of 34
Page 12
• Cut combustion air inducer tubing from 9” to 5” to avoid
interference with inducer motor.
Figure 17. Upow Position
Right Side Vent Discharge
• Disconnect pressure switch hose from barbed tting on the
pressure switch assembly. Remove pressure switch assembly
(1 screw) and cut wire tie to free pressure switch wires. Reinstall
pressure switch on the other side of orice plate and reconnect
pressure switch hose.
• Resecure pressure switch wires: Either pull excess wires
through the blower compartment and secure using supplied
wire tie, or coil excess wire and secure to the gas manifold.
Figure 18. Horizontal Left Position
Top Vent Discharge
• Cut combustion air inducer tubing from 9” to 7” to avoid
interference with inducer motor.
• Disconnect pressure switch hose from barbed tting on the
pressure switch assembly. Remove pressure switch assembly
(1 screw) and cut wire tie to free pressure switch wires. Reinstall
pressure switch on the other side of orice plate and reconnect
pressure switch hose.
• Resecure pressure switch wires: Either pull excess wires
through the blower compartment and secure using supplied
wire tie, or coil excess wire and secure to the gas manifold.
Figure 19. Horizontal Left Position
Side Vent Discharge
• Gas supply piping must be brought into the unit from the bottom
in order to accommodate the ue pipe.
• Cut combustion air inducer tubing from 9” to 8” to avoid
interference with inducer motor.
• Remove make-up box assembly (2 screws) and cut wire tie to
free make-up box wires. Reinstall make-up box on other side
of cabinet.
• Resecure make-up box wires: Either pull excess wires through
the blower compartment and secure using supplied wire tie, or
coil excess wire and secure to the gas manifold.
Figure 20. Horizontal Right Position
Top Vent Discharge
507330-01Page 12 of 34Issue 1721
Page 13
Figure 21. Horizontal Right Position
Side Vent Discharge
These series units are classied as fan assisted Category
I furnaces when vertically vented according to the latest
edition of National Fuel Gas Code (NFPA 54 / ANSI
Z223.1) in the USA. A fan assisted Category I furnace is
an appliance equipped with an integral mechanical means
to either draw or force combustion products through the
combustion chamber and/or heat exchanger. This unit is
not approved for use with horizontal venting.
NOTE: Use these instructions as a guide. They do not
supersede local codes. This furnace must be vented
according to all local codes these installation instructions,
and the provided venting tables in these instructions.
WARNING
Asphyxiation hazard. The exhaust vent for this furnace
must be securely connected to the furnace ue transition
at all times.
Figure 22. Vent Connection
Use self drilling sheet metal screws or a mechanical
fastener to rmly secure the vent pipe to the round collar of
the ue transition. If self drilling screws are used to attach
the vent pipe, it is recommended that three be used. Drive
one self drilling screw through the front and one through
each side of the vent pipe and collar. See Figure 22.
Install the rst vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet. See Figure
22.
The venting tables in this manual were extracted from the
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are
provided as a guide for proper vent installation. Proper
application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the
absence of local codes, the NFGC serves as the dening
document.
Refer to the tables and the venting information contained
in these instructions to properly size and install the venting
system.
IMPORTANT
Once the venting system is installed, attach the
“Disconnected Vent” warning sticker to a visible area
of the plenum near the vent pipe. See Figure 22. The
warning sticker is provided in the bag assembly. Order
kit 66W04 for additional stickers.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central furnaces
must be either tile lined or lined with a listed metal lining
system or dedicated gas vent. Unlined masonry chimneys
are prohibited. See Figure 23 and Figure 24 for common
venting.
A chimney with one or more sides exposed to the outside
of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile lined must be
lined with B1 vent or a listed insulated exible metal vent.
An exterior tile lined chimney that is sealed and capped
may be lined with a listed uninsulated exible metal vent.
If the existing chimney will not accommodate a listed metal
liner, either the chimney must be rebuilt to accommodate
one of these liners or an alternate approved venting
method must be found.
Insulation for the exible vent pipe must be an encapsulated
berglass sleeve recommended by the exible vent pipe
manufacturer.
507330-01Issue 1721Page 13 of 34
Page 14
NOTE 1: Refer to the provided venting tables for installations.
Refer to the capacity requirements shown in the provided venting
tables.
Figure 23. Common Venting Using Metal-Lined
Masonry Chimney
A fan assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
• The chimney is currently serving at least one drafthood
equipped appliance.
• The vent connectors and chimney are sized according
to the provided venting tables.
If type B1 double wall vent is used inside a chimney, no
other appliance can be vented into the chimney. The outer
wall of type B1 vent pipe must not be exposed to ue
products. A type B1 vent or masonry chimney liner shall
terminate above the roof surface with a listed cap or a listed
roof assembly according to the terms of their respective
listings and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting. The chimney passageway must be
checked periodically to ensure that it is clear and free of
obstructions.
DO NOT insulate the space between the liner and the
chimney wall with puffed mica or any other loose granular
insulating material.
IMPORTANT
SINGLE appliance venting of a fan assisted furnace into
a tile lined masonry chimney (interior or outside wall) is
prohibited. The chimney must rst be lined with either
type B1 vent or an insulated single wall exible vent
lining system which has been sized according to the
provided venting tables and the vent pipe manufacturer’s
instructions.
NOTE: Refer to provided
venting tables for
installations.
Do not install a manual damper, barometric draft regulator,
or ue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is
servicing a solid fuel appliance. If a replace chimney ue
is used to vent this appliance, the replace opening must
be permanently sealed.
A type B1 or listed chimney lining system that passes
through an unused masonry chimney ue is not considered
to be exposed to the outdoors.
General Venting Requirements
Vent all furnaces according to these instructions:
NOTE: The chimney must be properly
sized per provided venting tables or lined
with listed metal lining system.
Figure 24. Common Venting Using Tile Lined Interior Masonry Chimney and Combined Vent Connector
507330-01Page 14 of 34Issue 1721
Page 15
1. Vent diameter recommendations and maximum
allowable piping runs are found in the provided venting
tables.
2. In no case should the vent or vent connector diameter
be less than the diameter specied in the provided
venting tables.
3. The minimum vent capacity determined by the sizing
tables must be less than the low re input rating and
the maximum vent capacity must be greater than the
high re input rating.
4. Single appliance vents - If the vertical vent or tile
lined chimney has a larger diameter or ow area than
the vent connector, use the vertical vent diameter to
determine the minimum vent capacity and the vent
connector diameter to determine the maximum vent
capacity. The ow area of the vertical vent, however,
shall not exceed 7 times the ow area of the listed
appliance categorized vent area, drafthood outlet
area or ue collar area unless designed according to
approved engineering methods.
5. Multiple appliance vents - The ow area of the largest
section of vertical vent or chimney shall not exceed 7
times the smallest listed appliance categorized vent
area, drafthood outlet area or ue collar area unless
designed according to approved engineering methods.
6. The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
7. Single appliance venting congurations with zero lateral
lengths (Table 3) are assumed to have no elbows in
the vent system. For all other vent congurations, the
vent system is assumed to have two 90° elbows. For
each additional 90° elbow or equivalent (for example
two 45° elbows equal one 90° elbow) beyond two, the
maximum capacity listed in the venting table should
be reduced by 10% (0.90 x maximum listed capacity).
8. The common venting tables (Table 4 and Table 5) were
generated using a maximum horizontal vent connector
length of 1-1/2 feet (.46 m) for each inch (25 mm) of
connector diameter as follows:
Connector Diameter
in. (mm)
3 (76)4-1/2 (1.37)
4 (102)6 (1.83)
5 (127)7-1/2 (2.29)
6 (152)9 (2.74)
7 (178)10-1/2 (3.20)
Maximum Horizontal
Connector Length
ft. (m)
Table 2.
9. If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent
of two 90° elbows (0.80 x maximum common vent
capacity). The horizontal length of the offset shall not
exceed 1-1/2 feet (.46 m) for each inch (25 mm) of
common vent diameter.
10. The vent pipe should be as short as possible with
the least number of elbows and angles required to
complete the job. Route the vent connector to the vent
using the shortest possible route.
11. A vent connector shall be supported without any dips
or sags and shall slope a minimum of 1/4 inch (6.4
mm) per linear foot (305 mm) of connector, back
toward the appliance.
12. Vent connectors shall be rmly attached to the furnace
ue collar by self drilling screws or other approved
means,except vent connectors of listed type B vent
material which shall be assembled according to the
manufacturer’s instructions. Joints between sections
of single wall connector piping shall be fastened by
screws or other approved means.
13. When the vent connector used for Category I
appliances must be located in or pass through a crawl
space, attic or other areas which may be cold, that
portion of the vent connector shall be constructed
of listed double wall type B vent material or material
having equivalent insulation qualities.
14. All venting pipe passing through oors, walls, and
ceilings must be installed with the listed clearance to
combustible materials and be re stopped according
to local codes. In absence of local codes, refer to
NFGC (2223.1 ).
15. No portion of the venting system can extend into, or
pass through any circulation air duct or plenum.
16. Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17. If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced
by 10%, the equivalent of one 90° elbow (0.90 x
maximum common vent capacity).
18. The common vent diameter must always be at least as
large as the largest vent connector diameter.
19. In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or ue collar outlet.
20. Do not install a manual damper, barometric draft
regulator or ue restrictor between the furnace and
the chimney.
21. When connecting this appliance to an existing
dedicated or common venting system, you must
inspect the venting system’s general condition and
look for signs of corrosion. The existing vent pipe size
must conform to these instructions and the provided
venting tables. If the existing venting system does not
meet these requirements, it must be resized.
507330-01Issue 1721Page 15 of 34
Page 16
Capacity of Type B Double Wall Vents with Type B Double Wall Connectors Serving a Single Category I Appliance
Vent and Connector Diameter - D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE: Single appliance venting congurations with zero lateral lengths are assumed to have no elbows in the vent system. For
all other vent congurations, the vent system is assumed to have two 90 ° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10
percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
0078015202510375
2135118972715732232
4214930943915350227
6254636914714959223
0084016502760415
21257161092517828263
52353321034217153255
8284939985116464247
0088017502950447
21261171182319426289
52357321134118752280
103051411045417667267
0094019103270502
21169151362022622339
52265301303921949330
102959401215120664315
153553481126119576301
0097020203490540
21075141491825020377
52171291433824247367
102864381335022962351
153458461245921773337
204852551166920684322
00100021303740587
2981131661428318432
52177281603627545421
102770371504826259405
153364441415724970389
205658531326623780374
30NRNR7311 388214104346
3 inch4 inch5 inch6 inch
Appliance Input Rating in Thousands of Btu per Hour
MINMAXMINMAXMINMAXMINMAX
Table 3.
507330-01Page 16 of 34Issue 1721
Page 17
Vent
Height
H
(feet)
6
8
10
15
20
30
Vent Connector Capacity
Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances
Connector
Rise
R
(feet)
1223735664610658164
2234137754812160183
3244438814913262199
1224035724911464176
2234436805112866195
3244737675313967210
1224334784912365189
2234736865113667206
3245037925214669220
1215033894714264220
2225335964915366235
32455361025116368248
1215433994615762246
22257341054816764259
32360351105017666271
12062311134518160288
22164331184719062299
32266341234819864309
3 inch4 inch5 inch6 inch
MINMAXMINMAXMINMAXMINMAX
Vent and Connector Diameter - D (inches)
Appliance Input Rating in Thousands of Btu per Hour
Table 4.
Common Vent Capacity
Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances
Common Vent Diameter - D (inches)
Vent Height
H
(feet)
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
69281140116204161309248
810190155129224178339275
1011097169141243194367299
15125112195164283228427352
20136123215183314255475394
30152138244210361297547459
4 inch5 inch6 inch7 inch
Appliance Input Rating in Thousands of Btu per Hour
Table 5.
507330-01Issue 1721Page 17 of 34
Page 18
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from
a venting system commonly run with separate gas
appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating
and the other appliances (which are not operating) remain
connected to the common venting system. If the venting
system has been installed improperly, you must correct the
system as indicated in the general venting requirements
section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide
poisoning or death.
4. Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5. After the burners have operated for 5 minutes, test for
leaks of ue gases at the draft hood relief opening.
Use the ame of a match or candle.
6. After determining that each appliance connected to
the common venting system is venting properly, (step
3) return all doors, windows, exhaust fans, replace
dampers, and any other gas burning appliances to
their previous mode of operation.
7. If a venting problem is found during any of the
preceding tests, the common venting system must be
modied to correct the problem.
Resize the common venting system to the minimum vent
pipe size determined by using the appropriate tables in
Appendix G. (These are in the current standards of the
National Fuel Gas Code ANSI 2223.1.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1. Seal any unused openings in the common venting
system.
2. Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3. Close all building doors and windows and all doors
between the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes
dryers and any appliances not connected to the
common venting system. Turn on any exhaust fans,
such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close replace dampers.
Gas Piping
CAUTION
If a exible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe shall
be installed at the gas valve and extend outside the
furnace cabinet. The exible connector can then be
added between the black iron pipe and the gas supply
line.
Gas Supply
1. This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal
applications). Connect the gas supply to the piping
assembly.
2. When connecting the gas supply piping, consider
factors such as length of run, number of ttings, and
furnace rating to avoid excessive pressure drop. Table
6 lists recommended pipe sizes for typical applications.
NOTE: BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 25. Possible Gas Piping Congurations - Upow Applications
507330-01Page 18 of 34Issue 1721
Page 19
Nominal Iron
Pipe Size -
inches (mm)
1/2
(12.7)
Internal
Diameter
- inches
(mm)
.622
(17.799)
10
(3.048)
175
(4.96)
Gas Pipe Capacity - FT³/HR (kL/HR)
Length of Pipe - feet (m)
20
(6.096)
120
(3.40)
30
(9.144)
97
(2.75)
40
(12.192)
82
(2.32)
50
(15.240)
73
(2.07)
60
(18.288)
66
(1.87)
70
(21.336)
61
(1.73)
80
(24.384)
57
(1.61)
90
(27.432)
53
(1.50)
100
(30.480)
50
(1.42)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
4
(101.6)
NOTE: Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specic gravity gas.
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
360
(10.19)
680
(19.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
9700
(274.67)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
(12.18)
(18.41)
(34.55)
(55.22)
(97.69)
(203.88)
Table 6.
110
(3.11)
205
(5.80)
430
650
1220
1950
3450
7200
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
NOTE: BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 26. Possible Gas Piping Congurations - Horizontal Applications
507330-01Issue 1721Page 19 of 34
Page 20
3. The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb waiters,
or elevator shafts.
4. The piping should be sloped 1/4 inch (6.4 mm) per
15 feet (4.57 m) upward toward the meter from the
furnace. The piping must be supported at proper
intervals [every 8 to 10 feet (2.44 to 3.01 m)] with
suitable hangers or straps. Install a drip leg in vertical
pipe runs to the unit.
5. A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See Figure 27.
6. In some localities, codes may require the installation
of a manual main shut off valve and union (furnished
by the installer) external to the unit. The union must be
of the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
NOTE: If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect main power to the
furnace. The installer should properly label these devices.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory and eld installed) for gas leaks. Use
a leak detecting solution or other preferred means.
NOTE: If emergency shutoff is necessary, shut off the main
manual gas valve and disconnect the main power to the
furnace. The installer should properly label these devices.
Figure 27.
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and service
to protect the furnace’s electronic controls. Precautions
will help to avoid control exposure to electrostatic
discharge by putting the furnace, the control and the
technician at the same electrostatic potential. Neutralize
electrostatic charge by touching hand and all tools on
an unpainted unit surface, such as the gas valve or
blower deck, before performing any service procedure.
The unit is equipped with a eld make-up box on the left
hand side of the cabinet. The make-up box may be moved
to the right side of the furnace to facilitate installation. If
the make-up box is moved to the right side, clip the wire
ties that bundle the wires together. The excess wire must
be pulled into the blower compartment. Secure the excess
wire to the existing harness to protect it from damage.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after
leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
The furnace must be isolated by closing its individual
manual shut-off valve and disconnecting from the gas
supply system the during any pressure testing of the gas
supply system at pressures less than or equal to 1/2 psig
(3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing pressure of gas lines, gas valve must be
disconnected and isolated. See Figure 27. Gas valves
can be damaged if subjected to pressures greater than
1/2 psig (3.48 kPa, 14 inches w.c.).
Refer to Figure 31 for schematic wiring diagram and
troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
Figure 28. Interior Make-Up Box Installation
507330-01Page 20 of 34Issue 1721
Page 21
Figure 29. Interior Make-Up Box Installation
NOTE: Unit nameplate states maximum current draw.
Maximum over current protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat, check to make sure the
wires will be long enough for servicing at a later date. Make
sure that thermostat wire is long enough to facilitate future
removal of blower for service.
Complete the wiring connections to the equipment. Use
the provided unit wiring diagram shown in Figure 31. Use
18 gauge wire or larger that is suitable for Class II rating for
thermostat connections.
Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current
National Electric Code (ANSI/NFPA No. 70). A green
ground wire is provided in the eld make-up box.
connected to this terminal with the neutral leg of the circuit
being connected to one of the provided neutral terminals. If
a humidier rated at greater than one amp is connected to
this terminal, it is necessary to use an external relay.
One 24V “H” 1/4” spade terminal is provided on the furnace
control board. Any humidier rated up to 0.5 amp can be
connected to this terminal with the ground leg of the circuit
connected to ground or the “C” terminal. See Figure 32
for control board conguration. This terminal is energized
in the heating mode when the combustion air inducer is
operating.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
• The furnace requires 120 volts ± 10% (Range: 108
volts to 132 volts).
• The furnace operates at 60 Hz ± 5% (Range: 57 Hz
to 63 Hz).
• The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power.
• Generator should have a wave form distortion of less
than 5% RHO.
Thermostat
Install the room thermostat according to the instructions
provided with the thermostat. See Figure 30 for thermostat
designations. If the furnace is being matched with a
heat pump, refer to the FM21 installation instruction or
appropriate dual fuel thermostat instructions.
NOTE: This furnace contains electronic components that
are polarity sensitive. Make sure that the furnace is wired
correctly and is properly grounded.
Accessory Terminals
One line voltage “ACC” 1/4” spade terminal is provided on
the furnace integrated control. See Figure 32 for integrated
control conguration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral
leg of the circuit being connected to one of the provided
neutral terminals. If an accessory rated at greater than one
amp is connected to this terminal, it is necessary to use an
external relay.
One line voltage “HUM” 1/4” spade terminal is provided
on the furnace integrated control. See Figure 32 for
integrated control conguration. This terminal is energized
in the heating mode when the combustion air inducer is
operating. Any humidier rated up to one amp can be
507330-01Issue 1721Page 21 of 34
Figure 30. Condensing Unit Thermostat Designations
(Refer to Specic Thermostat and Outdoor Unit)
Indoor Blower Speeds
1. When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the fan speed when
there is no cooling or heating demand.
2. When the unit is running in the heating mode, the
indoor blower will run on the heating speed.
3. When there is a cooling demand, the indoor blower will
run on the cooling speed.
* Note: “R” Required on some outdoor units.
Page 22
Figure 31. Wiring Diagram
507330-01Page 22 of 34Issue 1721
Page 23
-02 Integrated Control LED Codes
Red LED Flash CodeDiagnostic Codes / Status of Furnace
LED OffNo power to control or control hardware fault detected
Heartbeat
1
Control powered - displayed during all modes of operation if no errors are detected
1 FlashReverse line voltage polarity
2 FlashesImproper earth ground
3 FlashesBurner failed to light, or lost ame during heat demand
4 FlashesLow ame signal - check ame sensor
5 FlashesWatchguard - burner failed to light, exceeded maximum number of retries or recycles
6 FlashesNot used
7 FlashesPrimary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 FlashesRollout switch open
9 FlashesPressure switch failed to close or opened during heat demand
10 FlashesWatchguard - Pressure switch opened 5 times during one heat demand
11 FlashesPressure switch stuck closed prior to activation of combustion air inducer
12 FlashesFlame sensed without gas valve energized
13 FlashesLow line voltage
1
A “heartbeat” is indicated by a “slow ash” - 1 sec on 1 sec off, repeating
NOTE: Last 10 error codes are stored in memory, including when power is shut off to the unit. To recall, press and release button.
Most recent will be displayed rst, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold
button longer than 5 seconds.
Table 7. Diagnostic Codes for -02 Control
-03 Integrated Control LED Codes
Red LED Flash Code
LED OffNo power to control or control hardware fault detected
Heartbeat
Continuous Rapid Flash Call for heat / burner operation
1 FlashReverse line voltage polarity
2 FlashesImproper earth ground
3 FlashesBurner failed to light, or lost ame during heat demand
4 FlashesLow ame signal - check ame sensor
5 FlashesWatchguard - burner failed to light, exceeded maximum number of retries or recycles
6 FlashesNot used
7 FlashesPrimary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 FlashesRollout switch open
9 FlashesPressure switch failed to close or opened during heat demand
10 FlashesWatchguard - Pressure switch opened 5 times during one heat demand
11 FlashesPressure switch stuck closed prior to activation of combustion air inducer
12 FlashesFlame sensed without gas valve energized
13 FlashesLow line voltage
1
A “heartbeat” is indicated by a “slow ash” - 1 sec on 1 sec off, repeating
2
Error codes are indicated by a “rapid ash” - the LED ashes X times at 1/2 sec on, 1/2 sec off, remains off for 3 sec, then repeats
NOTE: Last 10 error codes are stored in memory, including when power is shut off to the unit. To recall, press and release button.
Most recent will be displayed rst, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold
button longer than 5 seconds.
2
1
Normal operation - idle, continuous fan, cool
Diagnostic Codes / Status of Furnace
Table 8. Diagnostic Codes for -03 Control
507330-01Issue 1721Page 23 of 34
Page 24
RED LED
Terminal Designations
120 HUMHumidier (120 VAC)
LINEInput (120 VAC)
XFMRTransformer (120 VAC)
CIRCIndoor Blower (120 VAC)
EACElectronic Air Cleaner (120 VAC)
COOLBlower - Cooling Speed (24 VAC)
HEATBlower - Heating Speed (24 VAC)
FANBlower - Fan Speed (24 VAC)
PARKDead terminals to park all speed taps
NEUTRALSNeutral Terminals (120 VAC)
FSFlame Sense
24 COMCommon (24 VAC)
HUM 24Humidier (24 VAC)
BLOWER OFF DELAY
RECALL BUTTON
Figure 32. Integrated Control
(Automatic Hot Surface Ignition System)
Demand
CAI
Ignitor
Gas Valve
Indoor Blower
Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on “OFF TIME” Setting.
ON
OFF
1
Pre-Purge
15
Ignitor Warm-up
35
Figure 33. Heating Sequence of Operation
Unit Start-Up
FOR YOUR SAFETY, READ BEFORE LIGHTING UNIT
WARNING
Do not use this furnace if any part have been
underwater. Immediately call a licensed professional
service technician (or equivalent) to inspect the furnace
and to replace any part of the control system and any
gas control which has been underwater.
Trial for
Ignition
39
Blower
“On” Delay
5 SEC80
Post
Purge
WARNING
If overheating occurs or if gas supply fails to shut off,
shut off the manual gas valve to the appliance before
shutting off electrical supply.
CAUTION
Before attempting to perform any service or
maintenance, turn the electrical power to unit OFF at
disconnect switch.
507330-01Page 24 of 34Issue 1721
Page 25
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
The gas valve on this unit will be equipped with a gas
control switch. Use only your hand to move the switch.
Never use tools. If the switch will not turn or if the control
switch will not move by hand, do not try to repair it.
Placing the Furnace into Operation
These units are equipped with an automatic ignition
system. Do not attempt to manually light burners on these
furnaces. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get hot
when there is no call for heat on units with an automatic
ignition system.
WARNING
If you do not follow these instructions exactly, a re
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation
See Figure 34
1. STOP! Read the safety information at the beginning
of this section.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the unit.
4. This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5. Remove the upper access panel.
6. Move switch on gas valve to OFF. Do not force. See
Figure 34.
7. Wait ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step.
Gas Valve Shown in “ON” Position
9. Replace the upper access panel.
10. Turn on all electrical power to the unit.
11. Set the thermostat to desired setting.
NOTE: When unit is initially started, steps 1 through
11 may need to be repeated to purge air from gas line.
12. If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service
technician or gas supplier.
Turning Off Gas to Unit
1. Set the thermostat to the lowest setting.
2. Turn OFF all electrical power to the unit if service is to
be performed.
3. Remove the upper access panel.
4. Move switch on gas valve to OFF. Do not force.
5. Replace the upper access panel.
Failure to Operate
If the unit fails to operate, check the following:
1. Is the thermostat calling for heat?
2. Are access panels securely in place?
3. Is the main disconnect switch closed?
4. Is there a blown fuse or tripped circuit breaker?
5. Is the lter dirty or plugged? Dirty or plugged lters will
cause the limit control to shut the unit off.
6. Is gas turned on at the meter?
7. Is the manual main shut-off valve open?
8. Is the internal manual shut-off valve open?
9. Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the unit
for blockages.
10. Is pressure switch closed? Obstructed ue will cause
unit to shut off at pressure switch. Check ue and
outlet for blockages.
11. Are ame rollout switches tripped? If ame rollout
switches are tripped, call the service technician for
inspection.
Heating Sequence of Operation
See Figure 33
1. When thermostat calls for heat, combustion air blower
starts.
2. Combustion air pressure switch proves blower
operation. Switch is factory set and requires no
adjustment.
3. After a 15 second pre-purge, the hot surface ignitor
energizes.
Figure 34.
8. Move switch on gas valve to ON. Do not force. See
Figure 34.
507330-01Issue 1721Page 25 of 34
4. After a 20 second ignitor warm-up period, the gas
valve solenoid opens. A 4 second trial for ignition
period begins.
Page 26
5. Gas is ignited, ame sensor proves the ame, and the
combustion process continues.
6. If ame is not detected after rst ignition trial, the
ignition control will repeat steps 3 and 4 four more
times before locking out the gas valve. The ignition
control will then automatically repeat steps 1 through
6 after 60 minutes.
7. To interrupt the 60 minute, move thermostat from
“Heat” to “OFF” then back to “Heat”. Heating sequence
then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
Gas Meter Clocking Chart
Seconds for One Revolution
Capacity
-04580160200400
-07055110136272
-0904182102204
-110336682164
-135275468136
Natural - 1000 btu/cu ftLP - 2500 btu/cu ft
Furnace should operate at least 5 minutes before checking
gas ow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in Table
9 below. If manifold pressure matches Table 10 and rate is
incorrect, check gas orices for proper size and restriction.
Remove temporary gas meter if installed.
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
Table 9.
1 cu ft
Dial
2 cu ft
Dial
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a eld provided barbed tting and connect a
manometer to measure supply pressure. See Table 10
for proper line pressure. Replace the threaded plug after
measurements have been taken.
Manifold Pressure Measurement
1. Remove the threaded plug from the outlet side of
the gas valve and install a eld provided barbed
tting. Connect to a manometer to measure manifold
pressure.
2. Start unit and allow 5 minutes for unit to reach steady
state.
3. While waiting for the unit to stabilize, observe the
ame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
Table 10.
NOTE: Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed tting and replace threaded plug.
Manifold Pressure
Between 2000 and 7500 ft, certain units require manifold
pressure adjustments specied in Table 10. Manifold
pressure should be measured, and adjusted as required
during unit start up.
NOTE: LP/Propane installations require a gas conversion
Orice Kit as specied in Table 12.
NOTE: To obtain accurate reading, shut off all other gas
appliances connected to meter.
Manifold Pressure and Line Pressure at Various Altitudes
Manifold Pressure (in. w.c.)
Capacity
045
0703.210.02.810.0
0903.210.02.79.6
1103.510.03.09.6
1353.510.02.99.6
1
Manifold pressure adjustments based on 1020 Btu/ft3 gas for natural and 2500 Btu/ft3 gas for LP (corrected to standard conditions).
Consult local utility for actual local heating value.
2
A natural to LP/Propane gas conversion Orice Kit is required to convert this unit. Refer to kit instructions for conversion procedure.
Furnace should operate a minimum 15 minutes with correct
manifold pressure and gas ow rate before checking
combustion. Take combustion sample beyond the ue out
let and compare to the tables below. The maximum carbon
monoxide reading should not exceed 100 ppm.
CapacityCO2% for NatCO2% for LP
-045
-070
-090
7.2 - 7.87.5 - 9.0
-110
-135
Table 11.
High Altitude
This furnace is carefully designed for optimal performance
under a wide range of operating conditions. To ensure
proper operation at higher altitudes, certain adjustments
and/or kits may be required.
Pressure Switch
Between 4501 and 7500 ft, some units may require a
pressure switch change. Table 12 lists the available
Pressure Switch Kits providing the minimum allowable
pressure switch set points, in this altitude range, for each
unit. The need for a Pressure Switch Kit may be evaluated
by comparing the pressure measured at the pressure
switch under steady state conditions (after 15 minutes of
run time) against the as shipped switch set point. Insufcient
negative pressure may lead to nuisance pressure switch
trips and possible unit lock outs.
Above 7500 feet, all units require both a burner orice
change and a pressure switch change per Table 12.
Fan Control
The fan on time of 45 seconds is not adjustable. The heat
fan off delay (amount of time that the blower operates after
the heat demand has been satised) may be adjusted by
changing the jumper position across the ve pins on the
integrated control. The unit is shipped with a factory fan
off delay setting of 90 seconds. The fan off delay affects
comfort and is adjustable to satisfy individual applications.
Adjust the fan off delay to achieve a supply air temperature
between 90° and 110° F at the moment that the blower
is de-energized. Longer off delay settings provide lower
return air temperatures; shorter settings provide higher
return air temperatures. See Figure 35.
Figure 35. Heat Fan Off Time in Seconds
Orice Kits and Pressure Switch Kits at Various Altitudes
0 - 4500 ft.4501 - 7500 ft.7501 - 10000 ft.
Natural
Capacity
045
070
090
110
135
1
Minimum allowable set points for this altitude range. Application of a Pressure Switch with lower set point (less negative / closer to zero) is not
permitted.
2
Kit contains burner orices and gas valve regulator spring(s).
Pressure
Switch Kit
As Shipped
(-0.65” w.c.)
As Shipped
(-0.68” w.c.)
As Shipped
(-0.65” w.c.)
As Shipped
(-0.68” w.c.)
As Shipped
(-0.65” w.c.)
1
to LP /
Propane
Orice Kit
2
11K50
(0.034”)
LP /
Propane
to Natural
Orice Kit
73W802
(0.063”)
Pressure1
Switch Kit
80W52
(-0.60” w.c.)
80W52
(-0.60” w.c.)
80W52
(-0.60” w.c.)
80W57
(-0.65” w.c.)
80W52
(-0.60” w.c.)
Natural
to LP /
Propane
Orice Kit
11K502
(0.034”)
LP /
Propane
to Natural
Orice Kit
73W802
(0.063”)
Pressure1
Switch Kit
80W51
(-0.55” w.c.)
80W51
(-0.55” w.c.)
80W51
(-0.55” w.c.)
80W52
(-0.60” w.c.)
80W51
(-0.55” w.c.)
Natural
Orice Kit
51W01
(0.055”)
LP /
Propane
Orice Kit
11K452
(0.032”)
Table 12.
507330-01Issue 1721Page 27 of 34
Page 28
Constant Torque Motor
These units are equipped with a constant torque ECM
motor. It has a DC motor coupled to an electronic control
module,both contained in the same motor housing. The
motor is programmed to provide constant torque at each of
the ve selectable speeds. The motor has ve speed taps.
Each tap requires 24 volts to energize.
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment
vestibule panel. The secondary limits (if equipped) are
located in the blower compartment, attached to the back
side of the blower. These auto reset limits are factory set
and require no adjustment.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.
NOTE: Do not secure the electrical conduit directly to the
air ducts or structure.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC ± 10%.
3. Check amp-draw on the blower motor with inner
blower panel in place.
Unit Nameplate__________ Actual_______________
Blower Speeds
Follow the steps below to change the blower speeds.
1. Turn off electrical power to furnace.
2. Remove blower access panel.
3. Disconnect existing speed tap at integrated control
speed terminal.
NOTE: Termination of any unused motor leads must
be insulated.
4. Place unused blower speed tap on integrated control
“PARK” terminal or insulate.
5. Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
Blower performance data.
6. Connect selected speed tap at integrated control
speed terminal.
7. Resecure blower access panel.
8. Turn on electrical power to furnace.
9. Recheck temperature rise.
Flame Rollout Switches
This manually reset switches are located on the Front of
the burner box.
Pressure Switch
The pressure switch is located in the heating compartment
adjacent to the combustion air inducer. The switch checks
for proper combustion air inducer operation before allowing
ignition trial. The switch is factory set and requires no
adjustment.
Temperature Rise
After the furnace has been started, and supply and return
air temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed to
maintain the temperature rise within the range shown on
the unit nameplate. Increase the blower speed to decrease
the temperature. Decrease the blower speed to increase
the temperature rise. Failure to adjust the temperature rise
may cause erratic limit operation.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage. Before
servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
At the beginning of each heating season, a qualied
technician should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are pre-lubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas fumes,
which could contain carbon monoxide, can be drawn
into living space resulting in personal injury or death.
Filters
Filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the lters when
necessary to ensure that the furnace operates properly.
Replacement lters must be rated for high velocity airow.
Table 1 lists recommended lter sizes.
Flue and Chimney
1. Check ue pipe, chimney and all connections for
tightness and to make sure there is no blockage.
2. Check unit for proper draft.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC ± 10%.
3. Check amp draw on the blower motor with inner blower
panel in place.
Unit Nameplate___________ Actual_____________
Cleaning the Burners
NOTE: Use papers or protective covering in front of the
furnace during cleaning.
4. Turn off both electrical and gas power supplies to
furnace.
5. Label the wires from gas valve, rollout switches,
primary limit switch and make-up box then disconnect
them.
6. Disconnect gas supply piping. Remove the screw
securing the burner box cover and remove cover.
Remove the four screws securing the burner manifold
assembly to the vestibule panel and remove the
assembly from the unit.
7. To clean burners, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually
inspect inside the burners and crossovers for any
blockage caused by foreign matter. Remove any
blockage. Figure 36 shows burner detail.
8. Reinstall burner box, manifold assembly and burner
box cover.
9. Re-install gas supply and turn on electrical power to
furnace.
507330-01Page 32 of 34Issue 1721
Page 33
Figure 36. Burner Assembly Removal
Repair Parts List
The following repair parts are available through independent Allied Air dealers. When ordering parts, include the complete
furnace model number listed on the CSA International nameplate — Example: A801UH045JP24A-01. All service must be
performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
• Upper access panel
• Blower panel
• Top cap
Control Panel
• Parts Transformer
• Integrated control
• Door interlock switch
• Circuit breaker
Blower Parts
• Blower wheel
• Blower housing
• Motor
• Motor mounting frame
• Motor capacitor
• Blower housing cutoff plate
Heating Parts
• Flame sensor
• Heat exchanger assembly
• Gas manifold
• Combustion air inducer
• Gas valve
• Main burner cluster
• Main burner orices
• Pressure switch
• Ignitor
• Primary limit control
• Flame rollout switch
• Secondary limit
507330-01Issue 1721Page 33 of 34
Page 34
Requirements for Commonwealth of Massachusetts
Modications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following
requirements:
For all side wall, horizontally vented, gas-fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side
wall, horizontally vented, gas-fueled equipment, the
installing plumber or gas tter shall observe that a
hard-wired carbon monoxide detector with an alarm
and battery backup is installed on the oor level where
the gas equipment is to be installed. In addition, the
installing plumber or gas tter shall observe that a
battery-operated or hard-wired carbon monoxide
detector with an alarm is installed on each additional
level of the dwelling, building or structure served by the
side wall, horizontally vented, gas-fueled equipment.
It shall be the responsibility of the property owner to
secure the services of qualied licensed professionals
for the installation of hard-wired carbon monoxide
detectors.
a. In the event that the side wall, horizontally
vented, gas-fueled equipment is installed in a
crawl space or an attic, the hard-wired carbon
monoxide detector with alarm and battery backup
may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision
cannot be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30)
day period, a battery-operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply
with NFPA 720 and be ANSI/UL 2034 listed and IAS
certied.
3. SIGNAGE. A metal or plastic identication plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the
horizontally vented, gas-fueled heating appliance or
equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas-fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment
Not Required to Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
2. Product Approved side wall, horizontally vented, gasfueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment provides a
venting system design or venting system components
with the equipment, the instructions provided by the
manufacturer for installation of the equipment and the
venting system shall include:
1. Detailed instructions for the installation of the venting
system design or the venting system components: and
2. A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved sidewall,
horizontally vented, gas-fueled equipment does not
provide the parts for venting the ue gases, but identies
“special venting systems,” the following requirements shall
be satised by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists
for venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.
507330-01Page 34 of 34Issue 1721
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.