Royalton B2332509, B2332516, B2332515, B2332514, B2332510 User Manual

Page 1
INSTALLATION INSTRUCTIONS
A80UH1E & 80G1UHE
Warm Air Gas Furnace
Upow / Horizontal Left and Right Air Discharge
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
Table of Contents
Unit Dimensions ..........................................................2
A80UH1E & 80G1UHE Gas Furnace ..........................3
Shipping and Packing List ...........................................3
Safety Information .......................................................3
General ........................................................................4
Combustion, Dilution & Ventilation Air .........................5
Filters .........................................................................10
Duct System ..............................................................10
Venting.......................................................................11
Gas Piping .................................................................18
Electrical ....................................................................20
Unit Start-Up ..............................................................24
Blower Performance ..................................................29
Service.......................................................................32
Repair Parts List ........................................................33
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
Manufactured By
Allied Air Enterprises LLC
A Lennox International, Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
Save these instructions for future reference
507330-01 Issue 1721 Page 1 of 34
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
CAUTION
(P) 507330-01
Page 2

Unit Dimensions

1
NOTE -C20 and D20 size units installed in upow
applications that require air volumes of 1800 cfm (850 L/s or greater must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air lter.
2. Single side return air with optional RAB Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and one side return air.
2
Flue outlet may be horizontal but furnace must be vented
vertically.
3
Optional external side return air lter kit cannot be used with
the optional RAB Return Air Base.
*
Consider sizing requirements for optional IAQ equipment before
cutting side return opening.
A80UH1E / 80G1UHE
Capacity
045-12 070-12
090-16 090-20
110-20 21 533 19-7/8 504 19-1/2 495 8 203
135-20 24-1/2 622 23-3/8 546 23 584 9-3/4 248
FRONT VIEW SIDE VIEW
A B C D
in. mm in. mm in. mm in. mm
14-1/2 368 13-3/8 340 13 330 4-3/4 121
17-1/2 446 16-3/8 416 16 406 6-1/4 159
507330-01Page 2 of 34 Issue 1721
Page 3

A80UH1E & 80G1UHE Gas Furnace

The A80UH1E & 80G1UHE gas furnace is shipped ready for installation in the upow or horizontal right position (for horizontal left position the combustion air pressure switch must be moved). The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be installed in horizontal or upow applications with bottom return air.
The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.
Clearances
Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code. Vent installations must be consistent with the venting tables (in this instruction) and applicable provisions of local building codes.
This furnace is CSA International certied for installation clearances to combustible material as listed on the unit nameplate and in the tables in Figure 7 and Figure 11. Accessibility and service clearances must take precedence over re protection clearances.

Shipping and Packing List

1 - Assembled Gas Furnace
1 - Bag assembly containing the following:
2 - Screws
3 - Wire nuts
1 - Snap bushing
1 - Snap Plug
1 - Wire tie
1 - Vent warning label
1 - Owner’s manual and warranty card
Check equipment for shipping damage. If you nd any damage, immediately contact the last carrier.
Please refer to specication sheets for available accessories.

Safety Information

DANGER
DANGER OF EXPLOSION!
There are circumstances in which odorant used with LP/Propane gas can lose its scent. In case of a leak, LP/Propane gas will settle close to the oor and may be difcult to smell. An LP/Propane leak detector should be installed in all LP applications.
Installed Locations
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the oor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code.
Temperature Rise
NOTE: Furnace must be adjusted to obtain a temperature
rise within the range specied on the unit nameplate. Failure to do so may cause erratic limit operation and may result in premature heat exchanger failure.
This furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. See Figure 1. With a parallel ow arrangement, a damper (or other means to control the ow of air) must adequately pre vent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting. See Figure 1.
Certications
These units are CSA International certied to ANSI Z21.47.
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address: American National Standards Institute, Inc., 11 West 42nd Street, New York, NY 10036.
507330-01 Issue 1721 Page 3 of 34
Page 4
Heating Unit Installed Parallel to Air Handler Unit
Heating Unit Installed Upstream of Cooling Unit
Figure 1.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
NOTE: This furnace is designed for a minimum continuous return air temperature of 60° F (16°C) or an intermittent operation down to 55° F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85° F (29°C) dry bulb.
A room thermostat must control the furnace. The use of xed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the furnace.
Return air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained.
Air lters must be installed in the system and must be maintained during construction.
Air lters must be replaced upon construction completion.
The input rate and temperature rise must be set per the furnace rating plate.
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a conned space with air from outside.
The furnace heat exchanger, components, duct system, air lters and evaporator coils must be thoroughly cleaned following nal construction clean­up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be veried according to these installation instructions.

General

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
This furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the upow or horizontal position.
This furnace design has not been CSA certied for installation in mobile homes, recreational vehicles, or outdoors.
Use of Furnace as a Construction Heater
Allied Air does not recommended the use of these units as a construction heater during any phase of construction. Very low return air temperature, harmful vapors and operation of the unit with clogged or misplaced lters will damage the unit.
Units may be used for heating of buildings or structures under construction, if the following conditions are met:
The vent system must be permanently installed per these installation instructions.
In addition to the requirements outlined previously, the following general recommendations must be considered when installing one of these furnaces:
Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the chimney or vent termination point.
Do not install the furnace where drafts might blow directly into it. This could cause improper combustion.
Do not block the furnace combustion air openings with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
507330-01Page 4 of 34 Issue 1721
Page 5
NOTE: The Commonwealth of Massachusetts stipulates these additional requirements:
Gas furnaces shall be installed by a licensed plumber or tter only.
The gas cock must be “T handle” type.
When a furnace is installed in an attic, the passageway
to and service area surrounding the equipment shall be oored.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects or other reproductive harm.

Combustion, Dilution & Ventilation Air

In the past, there was no problem in bringing in sufcient outdoor air for combustion. Inltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents, chimneys, and replaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.
WARNING
Insufcient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this section to install these furnaces to ensure efcient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping.
A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprinted material is not the complete and ofcial position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
All gas red appliances require air for the combustion process. If sufcient combustion air is not available, the furnace or other appliances will operate inefciently and unsafely. Enough air must be provided to meet the needs of all fuel burning appliances and appliances such as exhaust fans which force air out of the house. When replaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft. Insufcient air causes incomplete combustion which can result in carbon monoxide.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconned, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by inltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Conned Space
A conned space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This denition includes furnace closets or small equipment rooms.
507330-01 Issue 1721 Page 5 of 34
Page 6
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a conned space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the conned space either from inside the building or from outside.
outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See Figure 3 and Figure 4. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See Figure 5.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be xed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
NOTE: Each opening shall have a free area of at least one square inch per 1,000 Btu (645 mm² per .29 kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (64546 mm²).
Figure 2. Equipment in Conned Space - All Air From
Inside
Air from Inside
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas red equipment in the conned space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See Figure 2.
Air from Outside
If air from outside is brought in for combustion and ventilation, the conned space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the
NOTE: The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645 mm² per
1.17 kW) per hour of the total input rating of all equipment in the enclosure.
Figure 3. Equipment in Conned Space - All Air from
Outside
(Inlet Air from Crawl Space & Outlet Air to Ventilated
Attic)
507330-01Page 6 of 34 Issue 1721
Page 7
NOTE: The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645 mm² per
1.17 kW) per hour of the total input rating of all equipment in the enclosure.
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
The gas furnace can be installed as shipped in either the upow position or the horizontal position.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level.
Figure 4. Equipment in Conned Space - All Air from
Outside
(All Air through Ventilated Attic)
NOTE: Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645 mm² per .59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645 mm² per
1.17 kW) per hour of the total input rating of all other equipment in the enclosure.
NOTE: Units with 1/2 hp and 3/4 hp blower motors are equipped with three exible legs and one rigid leg. See Figure 6. The rigid leg is equipped with a shipping bolt and a at white plastic washer (rather than the rubber mounting grommet used with a exible mounting leg). The bolt and washer must be removed before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Units with 1/2 HP & 3/4 HP Blower Motor.
Figure 6.
Figure 5. Equipment in Conned Space - All Air from
Outside
507330-01 Issue 1721 Page 7 of 34
Page 8
Upow Applications
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in Figure 7.
2. Single side return air with optional return airbase. See Figure 12.
3. Bottom return air.
4. Return air from both sides.
5. Bottom and one side return air.
Type of Vent
Connector
Top 1 in. (25 mm) 1 in. (25 mm)
*Front 2-1/4 in. (57 mm) 2-1/4 in. (57 mm)
Back 0 0
Sides 0† 0
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor 0‡ 0‡
* Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.
‡ For installation on a combustible oor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood ooring.
† Left side requires 3 in. if a single wall vent is used on 14-1/2 in. cabinets.
Type C Type B
1
Figure 7. Upow Application Installation Clearances
Return Air - Upow Applications
Return air can be brought in through the bottom or either side of the furnace installed in an upow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on Page 2.
NOTE: 20C and 20D units that require air volumes over 1800 cfm (850 L/s) must have one of the following:
Figure 8. Single Side Return Air
(with transition and lter)
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall the bottom cap. See Figure 9.
Figure 9. Removing the Bottom Panel
Horizontal Applications
The furnace can be installed in horizontal applications. Order horizontal suspension kit (51W10) from Allied Air, or use equivalent suspension method.
1. Single side return air with transition to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air lter. (Required to maintain proper air velocity.) See Figure
8.
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in Figure 11.
507330-01Page 8 of 34 Issue 1721
Page 9
This furnace may be installed in either an attic or a crawl space. Either suspend the furnace from roof rafters or oor joists, as shown in Figure 10, or install the furnace on a platform, as shown in Figure 13.
Figure 10. Typical Horizontal Application
Unit Suspended in Attic or Crawl Space
Type of Vent
Connector
Type C Type B
1
Top 0 0
*Front 2-1/4 in. (57 mm) 2-1/4 in. (57 mm)
Back 0 0
Ends 2 in. (51 mm) 2 in. (51 mm)
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor 0‡ 0‡
* Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.
‡ For installation on a combustible oor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood ooring.
Figure 11. Horizontal Application Installation
Clearances
FRONT VIEW
NOTE: Optional Side Return Air Filter Kits are not for use with Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the eld. There are cutting guides stenciled on the cabinet for the side return air opening.
The size of the opening must not extend beyond the markings on the furnace cabinet.
² To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
SIDE VIEW
Figure 12. Optional Return Air Base
(Upow Applications Only - For Use with A, B, C and D Cabinets)
507330-01 Issue 1721 Page 9 of 34
Page 10
NOTE: Heavy gauge perforated sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust piping installation. Cooling coils and supply and return air plenums must be supported separately.
NOTE: When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain.
WARNING
The inner blower panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.

Filters

Return Air - Horizontal Applications
Return air must be brought in through the end of a furnace installed in a horizontal application. The furnace is equipped with a removable bottom panel to facilitate installation. See Figure 9.
Figure 13. Horizontal Application
Unit Installed on Platform
This unit is not equipped with a lter or rack. A eld provided high velocity lter is required for the unit to operate properly. Table 1 lists recommended lter sizes.
A lter must be in place any time the unit is operating.
Furnace Cabinet
Width
A - 14-1/2”
B - 17-1/2” 16 x 25 x 1
C - 21” 20 x 25 x 1
D - 24-1/2” 24 x 25 x 1
Side Return Bottom Return
16 x 25 x 1
Filter Size
14 x 25 x 1
Table 1.

Duct System

Use industry approved standards (such as those published by Air Conditioning Contractors of America or American Society of Heating, Refrigerating and Air Conditioning Engineers) to size and install the supply and return air duct system. This will result in a quiet and low static system that has uniform air distribution.
WARNING
Improper installation of the furnace can result in personal injury or death. Combustion and ue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace.
In platform installations with bottom return air, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc..
The return and supply air duct systems must never be connected to or from other heating devices such as a replace or stove, etc.. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.
NOTE: Do not operate the furnace in the heating mode with an external static pressure that exceeds 0.8 inches w.c. Higher external static pressures may cause erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct. The access panel should be large enough to permit inspection (either by smoke or reected light) of the heat exchanger for leaks after the furnace is installed. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE: Return air must not be drawn from a room where
this furnace, or any other gas fueled appliance (i.e., water heater), or carbon monoxide producing device (i.e., wood replace) is installed.
507330-01Page 10 of 34 Issue 1721
Page 11
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the ue products can be pulled back down the vent pipe and into the room. This reverse ow of the ue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
In upow applications, the return air can be brought in through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use berglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a lter is installed, size the return air duct to t the lter frame.

Venting

A 4 inch diameter ue transition is factory installed on the combustion air inducer outlet of all models. Figure 15 shows the combustion air inducer as shipped from the factory.
IMPORTANT
The unit will not vent properly with the ue transition pointed down in the 6 o’clock position.
The combustion air inducer may be rotated clockwise or counterclockwise by 90° to allow for top or side vent discharge in all applications. When the unit is installed, the ue transition must be in the 9 o’clock, 12 o’clock or 3 o’clock position.
If necessary reposition the combustion air inducer, pressure switch and/or make-up box as needed per the following steps. See Figure 15 through Figure 21.
1. Remove the four mounting screws (Figure 14) which secure the combustion air inducer / pressure switch assembly to the orice plate. Lift the assembly and rotate it 90° clockwise or counter clockwise to either the 3 o’clock position. Resecure with four screws. Gasket should be left in place.
2. Use tin snips to cut preferred opening on the cabinet for repositioning the ue outlet. Use the cut-out piece as a cover plate to patch unused opening on cabinet.
Figure 14. Mounting Screws Location
Gas supply piping must be brought into the unit from the right side in order to accommodate the ue pipe.
Cut combustion air inducer tubing from 9” to 8” to avoid interference with inducer motor.
Remove make-up box assembly (2 screws) and cut wire tie to free make-up box wires. Re install make-up box on other side of cabinet.
Resecure make-up box wires: Either pull excess wires through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.
Figure 16. Upow Position
Left Side Vent Discharge
Figure 15. Upow Position
Top Vent Discharge
507330-01 Issue 1721 Page 11 of 34
Page 12
Cut combustion air inducer tubing from 9” to 5” to avoid
interference with inducer motor.
Figure 17. Upow Position Right Side Vent Discharge
Disconnect pressure switch hose from barbed tting on the pressure switch assembly. Remove pressure switch assembly (1 screw) and cut wire tie to free pressure switch wires. Reinstall pressure switch on the other side of orice plate and reconnect pressure switch hose.
Resecure pressure switch wires: Either pull excess wires through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.
Figure 18. Horizontal Left Position
Top Vent Discharge
Cut combustion air inducer tubing from 9” to 7” to avoid interference with inducer motor.
Disconnect pressure switch hose from barbed tting on the pressure switch assembly. Remove pressure switch assembly (1 screw) and cut wire tie to free pressure switch wires. Reinstall pressure switch on the other side of orice plate and reconnect pressure switch hose.
Resecure pressure switch wires: Either pull excess wires through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.
Figure 19. Horizontal Left Position
Side Vent Discharge
Gas supply piping must be brought into the unit from the bottom in order to accommodate the ue pipe.
Cut combustion air inducer tubing from 9” to 8” to avoid interference with inducer motor.
Remove make-up box assembly (2 screws) and cut wire tie to free make-up box wires. Reinstall make-up box on other side of cabinet.
Resecure make-up box wires: Either pull excess wires through the blower compartment and secure using supplied wire tie, or coil excess wire and secure to the gas manifold.
Figure 20. Horizontal Right Position
Top Vent Discharge
507330-01Page 12 of 34 Issue 1721
Page 13
Figure 21. Horizontal Right Position
Side Vent Discharge
These series units are classied as fan assisted Category I furnaces when vertically vented according to the latest edition of National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the USA. A fan assisted Category I furnace is an appliance equipped with an integral mechanical means to either draw or force combustion products through the combustion chamber and/or heat exchanger. This unit is not approved for use with horizontal venting.
NOTE: Use these instructions as a guide. They do not supersede local codes. This furnace must be vented according to all local codes these installation instructions, and the provided venting tables in these instructions.
WARNING
Asphyxiation hazard. The exhaust vent for this furnace must be securely connected to the furnace ue transition at all times.
Figure 22. Vent Connection
Use self drilling sheet metal screws or a mechanical fastener to rmly secure the vent pipe to the round collar of the ue transition. If self drilling screws are used to attach the vent pipe, it is recommended that three be used. Drive one self drilling screw through the front and one through each side of the vent pipe and collar. See Figure 22.
Install the rst vent connector elbow at a minimum of six inches (152 mm) from the furnace vent outlet. See Figure
22.
The venting tables in this manual were extracted from the National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are provided as a guide for proper vent installation. Proper application, termination, construction and location of vents must conform to local codes having jurisdiction. In the absence of local codes, the NFGC serves as the dening document.
Refer to the tables and the venting information contained in these instructions to properly size and install the venting system.
IMPORTANT
Once the venting system is installed, attach the “Disconnected Vent” warning sticker to a visible area of the plenum near the vent pipe. See Figure 22. The warning sticker is provided in the bag assembly. Order kit 66W04 for additional stickers.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined masonry chimney is used to vent this furnace.
Masonry chimneys used to vent Category I central furnaces must be either tile lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are prohibited. See Figure 23 and Figure 24 for common venting.
A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile lined must be lined with B1 vent or a listed insulated exible metal vent. An exterior tile lined chimney that is sealed and capped may be lined with a listed uninsulated exible metal vent.
If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting method must be found.
Insulation for the exible vent pipe must be an encapsulated berglass sleeve recommended by the exible vent pipe manufacturer.
507330-01 Issue 1721 Page 13 of 34
Page 14
NOTE 1: Refer to the provided venting tables for installations. Refer to the capacity requirements shown in the provided venting tables.
Figure 23. Common Venting Using Metal-Lined
Masonry Chimney
A fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:
The chimney is currently serving at least one drafthood equipped appliance.
The vent connectors and chimney are sized according to the provided venting tables.
If type B1 double wall vent is used inside a chimney, no other appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to ue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.
DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose granular insulating material.
IMPORTANT
SINGLE appliance venting of a fan assisted furnace into a tile lined masonry chimney (interior or outside wall) is prohibited. The chimney must rst be lined with either type B1 vent or an insulated single wall exible vent lining system which has been sized according to the provided venting tables and the vent pipe manufacturer’s instructions.
NOTE: Refer to provided venting tables for installations.
Do not install a manual damper, barometric draft regulator, or ue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is servicing a solid fuel appliance. If a replace chimney ue is used to vent this appliance, the replace opening must be permanently sealed.
A type B1 or listed chimney lining system that passes through an unused masonry chimney ue is not considered to be exposed to the outdoors.
General Venting Requirements
Vent all furnaces according to these instructions:
NOTE: The chimney must be properly sized per provided venting tables or lined with listed metal lining system.
Figure 24. Common Venting Using Tile Lined Interior Masonry Chimney and Combined Vent Connector
507330-01Page 14 of 34 Issue 1721
Page 15
1. Vent diameter recommendations and maximum allowable piping runs are found in the provided venting tables.
2. In no case should the vent or vent connector diameter be less than the diameter specied in the provided venting tables.
3. The minimum vent capacity determined by the sizing tables must be less than the low re input rating and the maximum vent capacity must be greater than the high re input rating.
4. Single appliance vents - If the vertical vent or tile lined chimney has a larger diameter or ow area than the vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent connector diameter to determine the maximum vent capacity. The ow area of the vertical vent, however, shall not exceed 7 times the ow area of the listed appliance categorized vent area, drafthood outlet area or ue collar area unless designed according to approved engineering methods.
5. Multiple appliance vents - The ow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or ue collar area unless designed according to approved engineering methods.
6. The entire length of single wall metal vent connector shall be readily accessible for inspection, cleaning, and replacement.
7. Single appliance venting congurations with zero lateral lengths (Table 3) are assumed to have no elbows in the vent system. For all other vent congurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10% (0.90 x maximum listed capacity).
8. The common venting tables (Table 4 and Table 5) were generated using a maximum horizontal vent connector length of 1-1/2 feet (.46 m) for each inch (25 mm) of connector diameter as follows:
Connector Diameter
in. (mm)
3 (76) 4-1/2 (1.37)
4 (102) 6 (1.83)
5 (127) 7-1/2 (2.29)
6 (152) 9 (2.74)
7 (178) 10-1/2 (3.20)
Maximum Horizontal
Connector Length
ft. (m)
Table 2.
9. If the common vertical vent is offset, the maximum common vent capacity listed in the common venting tables should be reduced by 20%, the equivalent of two 90° elbows (0.80 x maximum common vent
capacity). The horizontal length of the offset shall not exceed 1-1/2 feet (.46 m) for each inch (25 mm) of common vent diameter.
10. The vent pipe should be as short as possible with the least number of elbows and angles required to complete the job. Route the vent connector to the vent using the shortest possible route.
11. A vent connector shall be supported without any dips or sags and shall slope a minimum of 1/4 inch (6.4 mm) per linear foot (305 mm) of connector, back toward the appliance.
12. Vent connectors shall be rmly attached to the furnace ue collar by self drilling screws or other approved means,except vent connectors of listed type B vent material which shall be assembled according to the manufacturer’s instructions. Joints between sections of single wall connector piping shall be fastened by screws or other approved means.
13. When the vent connector used for Category I appliances must be located in or pass through a crawl space, attic or other areas which may be cold, that portion of the vent connector shall be constructed of listed double wall type B vent material or material having equivalent insulation qualities.
14. All venting pipe passing through oors, walls, and ceilings must be installed with the listed clearance to combustible materials and be re stopped according to local codes. In absence of local codes, refer to NFGC (2223.1 ).
15. No portion of the venting system can extend into, or pass through any circulation air duct or plenum.
16. Vent connectors serving Category I appliances shall not be connected to any portion of mechanical draft systems operating under positive pressure such as Category III or IV venting systems.
17. If vent connectors are combined prior to entering the common vent, the maximum common vent capacity listed in the common venting tables must be reduced by 10%, the equivalent of one 90° elbow (0.90 x maximum common vent capacity).
18. The common vent diameter must always be at least as large as the largest vent connector diameter.
19. In no case, shall the vent connector be sized more than two consecutive table size diameters over the size of the draft hood outlet or ue collar outlet.
20. Do not install a manual damper, barometric draft regulator or ue restrictor between the furnace and the chimney.
21. When connecting this appliance to an existing dedicated or common venting system, you must inspect the venting system’s general condition and look for signs of corrosion. The existing vent pipe size must conform to these instructions and the provided venting tables. If the existing venting system does not meet these requirements, it must be resized.
507330-01 Issue 1721 Page 15 of 34
Page 16
Capacity of Type B Double Wall Vents with Type B Double Wall Connectors Serving a Single Category I Appliance
Vent and Connector Diameter - D (inches)
Height
H
(feet)
6
8
10
15
20
30
NOTE: Single appliance venting congurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other vent congurations, the vent system is assumed to have two 90 ° elbows. For each additional 90° elbow or equivalent (for example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maximum listed capacity).
Lateral
L
(feet)
0 0 78 0 152 0 251 0 375
2 13 51 18 97 27 157 32 232
4 21 49 30 94 39 153 50 227
6 25 46 36 91 47 149 59 223
0 0 84 0 165 0 276 0 415
2 12 57 16 109 25 178 28 263
5 23 53 32 103 42 171 53 255
8 28 49 39 98 51 164 64 247
0 0 88 0 175 0 295 0 447
2 12 61 17 118 23 194 26 289
5 23 57 32 113 41 187 52 280
10 30 51 41 104 54 176 67 267
0 0 94 0 191 0 327 0 502
2 11 69 15 136 20 226 22 339
5 22 65 30 130 39 219 49 330
10 29 59 40 121 51 206 64 315
15 35 53 48 112 61 195 76 301
0 0 97 0 202 0 349 0 540
2 10 75 14 149 18 250 20 377
5 21 71 29 143 38 242 47 367
10 28 64 38 133 50 229 62 351
15 34 58 46 124 59 217 73 337
20 48 52 55 116 69 206 84 322
0 0 100 0 213 0 374 0 587
2 9 81 13 166 14 283 18 432
5 21 77 28 160 36 275 45 421
10 27 70 37 150 48 262 59 405
15 33 64 44 141 57 249 70 389
20 56 58 53 132 66 237 80 374
30 NR NR 73 11 3 88 214 104 346
3 inch 4 inch 5 inch 6 inch
Appliance Input Rating in Thousands of Btu per Hour
MIN MAX MIN MAX MIN MAX MIN MAX
Table 3.
507330-01Page 16 of 34 Issue 1721
Page 17
Vent
Height
H
(feet)
6
8
10
15
20
30
Vent Connector Capacity
Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances
Connector
Rise
R
(feet)
1 22 37 35 66 46 106 58 164
2 23 41 37 75 48 121 60 183
3 24 44 38 81 49 132 62 199
1 22 40 35 72 49 114 64 176
2 23 44 36 80 51 128 66 195
3 24 47 37 67 53 139 67 210
1 22 43 34 78 49 123 65 189
2 23 47 36 86 51 136 67 206
3 24 50 37 92 52 146 69 220
1 21 50 33 89 47 142 64 220
2 22 53 35 96 49 153 66 235
3 24 55 36 102 51 163 68 248
1 21 54 33 99 46 157 62 246
2 22 57 34 105 48 167 64 259
3 23 60 35 110 50 176 66 271
1 20 62 31 113 45 181 60 288
2 21 64 33 118 47 190 62 299
3 22 66 34 123 48 198 64 309
3 inch 4 inch 5 inch 6 inch
MIN MAX MIN MAX MIN MAX MIN MAX
Vent and Connector Diameter - D (inches)
Appliance Input Rating in Thousands of Btu per Hour
Table 4.
Common Vent Capacity
Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances
Common Vent Diameter - D (inches)
Vent Height
H
(feet)
FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT
6 92 81 140 116 204 161 309 248
8 101 90 155 129 224 178 339 275
10 110 97 169 141 243 194 367 299
15 125 112 195 164 283 228 427 352
20 136 123 215 183 314 255 475 394
30 152 138 244 210 361 297 547 459
4 inch 5 inch 6 inch 7 inch
Appliance Input Rating in Thousands of Btu per Hour
Table 5.
507330-01 Issue 1721 Page 17 of 34
Page 18
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
4. Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5. After the burners have operated for 5 minutes, test for leaks of ue gases at the draft hood relief opening. Use the ame of a match or candle.
6. After determining that each appliance connected to the common venting system is venting properly, (step
3) return all doors, windows, exhaust fans, replace dampers, and any other gas burning appliances to their previous mode of operation.
7. If a venting problem is found during any of the preceding tests, the common venting system must be modied to correct the problem.
Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI 2223.1.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deciencies which could cause an unsafe condition.
3. Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.

Gas Piping

CAUTION
If a exible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The exible connector can then be added between the black iron pipe and the gas supply line.
Gas Supply
1. This unit is shipped standard for left or right side installation of gas piping (or top entry in horizontal applications). Connect the gas supply to the piping assembly.
2. When connecting the gas supply piping, consider factors such as length of run, number of ttings, and furnace rating to avoid excessive pressure drop. Table 6 lists recommended pipe sizes for typical applications.
NOTE: BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 25. Possible Gas Piping Congurations - Upow Applications
507330-01Page 18 of 34 Issue 1721
Page 19
Nominal Iron
Pipe Size -
inches (mm)
1/2
(12.7)
Internal
Diameter
- inches
(mm)
.622
(17.799)
10
(3.048)
175
(4.96)
Gas Pipe Capacity - FT³/HR (kL/HR)
Length of Pipe - feet (m)
20
(6.096)
120
(3.40)
30
(9.144)
97
(2.75)
40
(12.192)
82
(2.32)
50
(15.240)
73
(2.07)
60
(18.288)
66
(1.87)
70
(21.336)
61
(1.73)
80
(24.384)
57
(1.61)
90
(27.432)
53
(1.50)
100
(30.480)
50
(1.42)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
4
(101.6)
NOTE: Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specic gravity gas.
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
4.026
(102.260)
360
(10.19)
680
(19.25)
1400
(39.64)
2100
(59.46)
3950
(111.85)
6300
(178.39)
11000
(311.48)
23000
(651.27)
250
(7.08)
465
(13.17)
950
(26.90)
460
(41.34)
2750
(77.87)
4350
(123.17)
7700
(218.03)
15800
(447.39)
200
(5.66)
375
(10.62)
770
(21.80)
1180
(33.41)
2200
(62.30)
3520
(99.67)
6250
(176.98)
12800
(362.44)
170
(4.81)
320
(9.06)
660
(18.69)
990
(28.03)
1900
(53.80)
3000
(84.95)
5300
(150.07)
10900
(308.64)
151
(4.28)
285
(8.07)
580
(16.42)
900
(25.48)
1680
(47.57)
2650
(75.04)
4750
(134.50)
9700
(274.67)
138
(3.91)
260
(7.36)
530
(15.01)
810
(22.94)
1520
(43.04)
2400
(67.96)
4300
(121.76)
9700
(274.67)
125
(3.54)
240
(6.80)
490
(13.87)
750
(21.24)
1400
(39.64)
2250
(63.71)
3900
(110.43)
8100
(229.36)
118
(3.34)
220
(6.23)
460
(13.03)
690
(19.54)
1300
(36.81)
2050
(58.05)
3700
(104.77)
7500
(212.37)
(12.18)
(18.41)
(34.55)
(55.22)
(97.69)
(203.88)
Table 6.
110
(3.11)
205
(5.80)
430
650
1220
1950
3450
7200
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)
NOTE: BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Figure 26. Possible Gas Piping Congurations - Horizontal Applications
507330-01 Issue 1721 Page 19 of 34
Page 20
3. The gas piping must not run in or through air ducts, clothes chutes, gas vents or chimneys, dumb waiters, or elevator shafts.
4. The piping should be sloped 1/4 inch (6.4 mm) per 15 feet (4.57 m) upward toward the meter from the furnace. The piping must be supported at proper intervals [every 8 to 10 feet (2.44 to 3.01 m)] with suitable hangers or straps. Install a drip leg in vertical pipe runs to the unit.
5. A 1/8” N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See Figure 27.
6. In some localities, codes may require the installation of a manual main shut off valve and union (furnished by the installer) external to the unit. The union must be of the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping must be resistant to the actions of liquied petroleum gases.
NOTE: If emergency shutoff is necessary, shut off the main manual gas valve and disconnect main power to the furnace. The installer should properly label these devices.
Leak Check
After gas piping is completed, carefully check all piping connections (factory and eld installed) for gas leaks. Use a leak detecting solution or other preferred means.
NOTE: If emergency shutoff is necessary, shut off the main manual gas valve and disconnect the main power to the furnace. The installer should properly label these devices.
Figure 27.

Electrical

ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the furnace, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before performing any service procedure.
The unit is equipped with a eld make-up box on the left hand side of the cabinet. The make-up box may be moved to the right side of the furnace to facilitate installation. If the make-up box is moved to the right side, clip the wire ties that bundle the wires together. The excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harness to protect it from damage.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, ame or other sources of ignition to check for gas leaks.
The furnace must be isolated by closing its individual manual shut-off valve and disconnecting from the gas supply system the during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
IMPORTANT
When testing pressure of gas lines, gas valve must be disconnected and isolated. See Figure 27. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa, 14 inches w.c.).
Refer to Figure 31 for schematic wiring diagram and troubleshooting.
The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate.
Figure 28. Interior Make-Up Box Installation
507330-01Page 20 of 34 Issue 1721
Page 21
Figure 29. Interior Make-Up Box Installation
NOTE: Unit nameplate states maximum current draw.
Maximum over current protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate wiring.
Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing.
Before connecting the thermostat, check to make sure the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.
Complete the wiring connections to the equipment. Use the provided unit wiring diagram shown in Figure 31. Use 18 gauge wire or larger that is suitable for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70). A green ground wire is provided in the eld make-up box.
connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidier rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.
One 24V “H” 1/4” spade terminal is provided on the furnace control board. Any humidier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the “C” terminal. See Figure 32 for control board conguration. This terminal is energized in the heating mode when the combustion air inducer is operating.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when specifying a generator for use with this equipment:
The furnace requires 120 volts ± 10% (Range: 108 volts to 132 volts).
The furnace operates at 60 Hz ± 5% (Range: 57 Hz to 63 Hz).
The furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power.
Generator should have a wave form distortion of less than 5% RHO.
Thermostat
Install the room thermostat according to the instructions provided with the thermostat. See Figure 30 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions.
NOTE: This furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
Accessory Terminals
One line voltage “ACC” 1/4” spade terminal is provided on the furnace integrated control. See Figure 32 for integrated control conguration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.
One line voltage “HUM” 1/4” spade terminal is provided on the furnace integrated control. See Figure 32 for integrated control conguration. This terminal is energized in the heating mode when the combustion air inducer is operating. Any humidier rated up to one amp can be
507330-01 Issue 1721 Page 21 of 34
Figure 30. Condensing Unit Thermostat Designations
(Refer to Specic Thermostat and Outdoor Unit)
Indoor Blower Speeds
1. When the thermostat is set to “FAN ON,” the indoor blower will run continuously on the fan speed when there is no cooling or heating demand.
2. When the unit is running in the heating mode, the indoor blower will run on the heating speed.
3. When there is a cooling demand, the indoor blower will run on the cooling speed.
* Note: “R” Required on some outdoor units.
Page 22
Figure 31. Wiring Diagram
507330-01Page 22 of 34 Issue 1721
Page 23
-02 Integrated Control LED Codes
Red LED Flash Code Diagnostic Codes / Status of Furnace
LED Off No power to control or control hardware fault detected
Heartbeat
1
Control powered - displayed during all modes of operation if no errors are detected
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost ame during heat demand
4 Flashes Low ame signal - check ame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage
1
A “heartbeat” is indicated by a “slow ash” - 1 sec on 1 sec off, repeating
NOTE: Last 10 error codes are stored in memory, including when power is shut off to the unit. To recall, press and release button. Most recent will be displayed rst, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.
Table 7. Diagnostic Codes for -02 Control
-03 Integrated Control LED Codes
Red LED Flash Code
LED Off No power to control or control hardware fault detected
Heartbeat
Continuous Rapid Flash Call for heat / burner operation
1 Flash Reverse line voltage polarity
2 Flashes Improper earth ground
3 Flashes Burner failed to light, or lost ame during heat demand
4 Flashes Low ame signal - check ame sensor
5 Flashes Watchguard - burner failed to light, exceeded maximum number of retries or recycles
6 Flashes Not used
7 Flashes Primary or Secondary limit open or watchguard mode - limit switch open longer than 3 minutes
8 Flashes Rollout switch open
9 Flashes Pressure switch failed to close or opened during heat demand
10 Flashes Watchguard - Pressure switch opened 5 times during one heat demand
11 Flashes Pressure switch stuck closed prior to activation of combustion air inducer
12 Flashes Flame sensed without gas valve energized
13 Flashes Low line voltage
1
A “heartbeat” is indicated by a “slow ash” - 1 sec on 1 sec off, repeating
2
Error codes are indicated by a “rapid ash” - the LED ashes X times at 1/2 sec on, 1/2 sec off, remains off for 3 sec, then repeats
NOTE: Last 10 error codes are stored in memory, including when power is shut off to the unit. To recall, press and release button. Most recent will be displayed rst, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.
2
1
Normal operation - idle, continuous fan, cool
Diagnostic Codes / Status of Furnace
Table 8. Diagnostic Codes for -03 Control
507330-01 Issue 1721 Page 23 of 34
Page 24
RED LED
Terminal Designations
120 HUM Humidier (120 VAC)
LINE Input (120 VAC)
XFMR Transformer (120 VAC)
CIRC Indoor Blower (120 VAC)
EAC Electronic Air Cleaner (120 VAC)
COOL Blower - Cooling Speed (24 VAC)
HEAT Blower - Heating Speed (24 VAC)
FAN Blower - Fan Speed (24 VAC)
PARK Dead terminals to park all speed taps
NEUTRALS Neutral Terminals (120 VAC)
FS Flame Sense
24 COM Common (24 VAC)
HUM 24 Humidier (24 VAC)
BLOWER OFF DELAY
RECALL BUTTON
Figure 32. Integrated Control
(Automatic Hot Surface Ignition System)
Demand CAI
Ignitor Gas Valve Indoor Blower
Blower on time will be 45 seconds after gas valve is energized. Blower off time will depend on “OFF TIME” Setting.
ON
OFF
1
Pre-Purge
15
Ignitor Warm-up
35
Figure 33. Heating Sequence of Operation

Unit Start-Up

FOR YOUR SAFETY, READ BEFORE LIGHTING UNIT
WARNING
Do not use this furnace if any part have been underwater. Immediately call a licensed professional service technician (or equivalent) to inspect the furnace and to replace any part of the control system and any gas control which has been underwater.
Trial for Ignition
39
Blower
“On” Delay
5 SEC80
Post
Purge
WARNING
If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
507330-01Page 24 of 34 Issue 1721
Page 25
BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
The gas valve on this unit will be equipped with a gas control switch. Use only your hand to move the switch. Never use tools. If the switch will not turn or if the control switch will not move by hand, do not try to repair it.
Placing the Furnace into Operation
These units are equipped with an automatic ignition system. Do not attempt to manually light burners on these furnaces. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with an automatic ignition system.
WARNING
If you do not follow these instructions exactly, a re or explosion may result causing property damage, personal injury or death.
Gas Valve Operation
See Figure 34
1. STOP! Read the safety information at the beginning of this section.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the unit.
4. This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.
5. Remove the upper access panel.
6. Move switch on gas valve to OFF. Do not force. See Figure 34.
7. Wait ve minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
Gas Valve Shown in “ON” Position
9. Replace the upper access panel.
10. Turn on all electrical power to the unit.
11. Set the thermostat to desired setting.
NOTE: When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12. If the appliance will not operate, follow the instructions “Turning Off Gas to Unit” and call your service technician or gas supplier.
Turning Off Gas to Unit
1. Set the thermostat to the lowest setting.
2. Turn OFF all electrical power to the unit if service is to be performed.
3. Remove the upper access panel.
4. Move switch on gas valve to OFF. Do not force.
5. Replace the upper access panel.
Failure to Operate
If the unit fails to operate, check the following:
1. Is the thermostat calling for heat?
2. Are access panels securely in place?
3. Is the main disconnect switch closed?
4. Is there a blown fuse or tripped circuit breaker?
5. Is the lter dirty or plugged? Dirty or plugged lters will cause the limit control to shut the unit off.
6. Is gas turned on at the meter?
7. Is the manual main shut-off valve open?
8. Is the internal manual shut-off valve open?
9. Is the unit ignition system in lock out? If the unit locks out again, call the service technician to inspect the unit for blockages.
10. Is pressure switch closed? Obstructed ue will cause unit to shut off at pressure switch. Check ue and outlet for blockages.
11. Are ame rollout switches tripped? If ame rollout switches are tripped, call the service technician for inspection.
Heating Sequence of Operation
See Figure 33
1. When thermostat calls for heat, combustion air blower starts.
2. Combustion air pressure switch proves blower operation. Switch is factory set and requires no adjustment.
3. After a 15 second pre-purge, the hot surface ignitor energizes.
Figure 34.
8. Move switch on gas valve to ON. Do not force. See Figure 34.
507330-01 Issue 1721 Page 25 of 34
4. After a 20 second ignitor warm-up period, the gas valve solenoid opens. A 4 second trial for ignition period begins.
Page 26
5. Gas is ignited, ame sensor proves the ame, and the combustion process continues.
6. If ame is not detected after rst ignition trial, the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve. The ignition control will then automatically repeat steps 1 through 6 after 60 minutes.
7. To interrupt the 60 minute, move thermostat from “Heat” to “OFF” then back to “Heat”. Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
Gas Meter Clocking Chart
Seconds for One Revolution
Capacity
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
Natural - 1000 btu/cu ft LP - 2500 btu/cu ft
Furnace should operate at least 5 minutes before checking gas ow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in Table 9 below. If manifold pressure matches Table 10 and rate is incorrect, check gas orices for proper size and restriction. Remove temporary gas meter if installed.
Natural LP
1 cu ft
Dial
2 cu ft
Dial
Table 9.
1 cu ft
Dial
2 cu ft
Dial
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a eld provided barbed tting and connect a manometer to measure supply pressure. See Table 10 for proper line pressure. Replace the threaded plug after measurements have been taken.
Manifold Pressure Measurement
1. Remove the threaded plug from the outlet side of the gas valve and install a eld provided barbed tting. Connect to a manometer to measure manifold pressure.
2. Start unit and allow 5 minutes for unit to reach steady state.
3. While waiting for the unit to stabilize, observe the ame. Flame should be stable and should not lift from burner. Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in Table 10.
NOTE: Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed tting and replace threaded plug.
Manifold Pressure
Between 2000 and 7500 ft, certain units require manifold pressure adjustments specied in Table 10. Manifold pressure should be measured, and adjusted as required during unit start up.
NOTE: LP/Propane installations require a gas conversion Orice Kit as specied in Table 12.
NOTE: To obtain accurate reading, shut off all other gas appliances connected to meter.
Manifold Pressure and Line Pressure at Various Altitudes
Manifold Pressure (in. w.c.)
Capacity
045
070 3.2 10.0 2.8 10.0
090 3.2 10.0 2.7 9.6
110 3.5 10.0 3.0 9.6
135 3.5 10.0 2.9 9.6
1
Manifold pressure adjustments based on 1020 Btu/ft3 gas for natural and 2500 Btu/ft3 gas for LP (corrected to standard conditions).
Consult local utility for actual local heating value.
2
A natural to LP/Propane gas conversion Orice Kit is required to convert this unit. Refer to kit instructions for conversion procedure.
3
A high altitude natural Orice Kit is required.
0 - 2000 ft. 2001 - 4500 ft. 4501 - 7500 ft. 7501 - 10000 ft. Minimum Max.
Nat. Gas
3.5 10.0
LP
Gas
Nat.
2
Gas
3.2 10.0 3.0 10.0
LP
Gas
Nat.
2
Gas
1
LP
Gas
Nat.
2
3
Gas
3.5 10.0 4.5 11.0 13.0
LP
Gas
2
Line Pressure (in. w.c.)
Nat. Gas
LP
Gas
Nat. &
2
LP
Table 10.
507330-01Page 26 of 34 Issue 1721
Page 27
Proper Combustion
Furnace should operate a minimum 15 minutes with correct manifold pressure and gas ow rate before checking combustion. Take combustion sample beyond the ue out let and compare to the tables below. The maximum carbon monoxide reading should not exceed 100 ppm.
Capacity CO2% for Nat CO2% for LP
-045
-070
-090
7.2 - 7.8 7.5 - 9.0
-110
-135
Table 11.
High Altitude
This furnace is carefully designed for optimal performance under a wide range of operating conditions. To ensure proper operation at higher altitudes, certain adjustments and/or kits may be required.
Pressure Switch
Between 4501 and 7500 ft, some units may require a pressure switch change. Table 12 lists the available Pressure Switch Kits providing the minimum allowable pressure switch set points, in this altitude range, for each unit. The need for a Pressure Switch Kit may be evaluated by comparing the pressure measured at the pressure switch under steady state conditions (after 15 minutes of run time) against the as shipped switch set point. Insufcient negative pressure may lead to nuisance pressure switch trips and possible unit lock outs.
Above 7500 feet, all units require both a burner orice change and a pressure switch change per Table 12.
Fan Control
The fan on time of 45 seconds is not adjustable. The heat fan off delay (amount of time that the blower operates after the heat demand has been satised) may be adjusted by changing the jumper position across the ve pins on the integrated control. The unit is shipped with a factory fan off delay setting of 90 seconds. The fan off delay affects comfort and is adjustable to satisfy individual applications. Adjust the fan off delay to achieve a supply air temperature between 90° and 110° F at the moment that the blower is de-energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures. See Figure 35.
Figure 35. Heat Fan Off Time in Seconds
Orice Kits and Pressure Switch Kits at Various Altitudes
0 - 4500 ft. 4501 - 7500 ft. 7501 - 10000 ft.
Natural
Capacity
045
070
090
110
135
1
Minimum allowable set points for this altitude range. Application of a Pressure Switch with lower set point (less negative / closer to zero) is not
permitted.
2
Kit contains burner orices and gas valve regulator spring(s).
Pressure
Switch Kit
As Shipped
(-0.65” w.c.)
As Shipped
(-0.68” w.c.)
As Shipped
(-0.65” w.c.)
As Shipped
(-0.68” w.c.)
As Shipped
(-0.65” w.c.)
1
to LP /
Propane
Orice Kit
2
11K50
(0.034”)
LP /
Propane
to Natural
Orice Kit
73W802
(0.063”)
Pressure1
Switch Kit
80W52
(-0.60” w.c.)
80W52
(-0.60” w.c.)
80W52
(-0.60” w.c.)
80W57
(-0.65” w.c.)
80W52
(-0.60” w.c.)
Natural
to LP /
Propane
Orice Kit
11K502
(0.034”)
LP /
Propane
to Natural
Orice Kit
73W802
(0.063”)
Pressure1
Switch Kit
80W51
(-0.55” w.c.)
80W51
(-0.55” w.c.)
80W51
(-0.55” w.c.)
80W52
(-0.60” w.c.)
80W51
(-0.55” w.c.)
Natural
Orice Kit
51W01
(0.055”)
LP /
Propane
Orice Kit
11K452
(0.032”)
Table 12.
507330-01 Issue 1721 Page 27 of 34
Page 28
Constant Torque Motor
These units are equipped with a constant torque ECM motor. It has a DC motor coupled to an electronic control module,both contained in the same motor housing. The motor is programmed to provide constant torque at each of the ve selectable speeds. The motor has ve speed taps. Each tap requires 24 volts to energize.
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are located in the blower compartment, attached to the back side of the blower. These auto reset limits are factory set and require no adjustment.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.
NOTE: Do not secure the electrical conduit directly to the air ducts or structure.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC ± 10%.
3. Check amp-draw on the blower motor with inner blower panel in place.
Unit Nameplate__________ Actual_______________
Blower Speeds
Follow the steps below to change the blower speeds.
1. Turn off electrical power to furnace.
2. Remove blower access panel.
3. Disconnect existing speed tap at integrated control speed terminal.
NOTE: Termination of any unused motor leads must be insulated.
4. Place unused blower speed tap on integrated control “PARK” terminal or insulate.
5. Refer to blower speed selection chart on unit wiring diagram for desired heating or cooling speed. See Blower performance data.
6. Connect selected speed tap at integrated control speed terminal.
7. Resecure blower access panel.
8. Turn on electrical power to furnace.
9. Recheck temperature rise.
Flame Rollout Switches
This manually reset switches are located on the Front of the burner box.
Pressure Switch
The pressure switch is located in the heating compartment adjacent to the combustion air inducer. The switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory set and requires no adjustment.
Temperature Rise
After the furnace has been started, and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.
507330-01Page 28 of 34 Issue 1721
Page 29

Blower Performance

A80UH1E / 80G1UHE 045*A12 Performance (Less Filter)
External
Static
Pressure
in. w.c.
0.00 1380 265 1155 165 995 120 975 115 945 105
0.10 1345 270 1120 175 950 120 880 105 865 100
0.20 1320 285 1080 190 900 125 805 105 700 85
0.30 1290 295 1055 200 875 135 750 110 640 90
0.40 1265 310 1010 205 825 145 710 120 595 95
0.50 1230 315 990 215 790 155 660 125 535 100
0.60 1190 330 990 230 750 165 630 135 500 100
0.70 1165 340 915 235 705 170 570 140 435 11 5
0.80 1130 350 880 245 670 180 535 150 380 120
A80UH1E / 80G1UHE 070*B12 Performance (Less Filter)
External
Static
Pressure
in. w.c.
0.00 1415 265 1330 170 1215 135 1175 125 1075 85
0.10 1415 280 1295 170 1145 145 1130 130 955 95
0.20 1355 290 1225 185 1110 150 1080 140 885 100
0.30 1330 300 1190 200 1060 160 1035 155 825 110
0.40 1290 310 1155 205 1015 175 970 160 770 120
0.50 1245 325 1115 215 980 180 930 170 695 125
0.60 1225 335 1045 230 920 190 865 180 625 135
0.70 1190 350 1000 235 855 205 790 190 540 140
0.80 1160 365 925 245 790 205 735 200 445 145
High Medium - High Medium Medium - Low Low
cfm watts cfm watts cfm watts cfm watts cfm watts
High Medium - High Medium Medium - Low Low
cfm watts cfm watts cfm watts cfm watts cfm watts
Air Volume / Watts at Various Blower Speeds
Air Volume / Watts at Various Blower Speeds
A80UH1E / 80G1UHE 090*B16 Performance (Less Filter)
External
Static
Pressure
in. w.c.
0.00 1785 380 1570 270 1440 220 1395 190 1190 125
0.10 1755 395 1535 275 1420 230 1350 205 1140 135
0.20 1730 415 1505 290 1380 245 1310 215 1110 145
0.30 1690 435 1460 305 1345 260 1275 230 1065 160
0.40 1645 440 1435 320 1310 270 1240 240 1010 165
0.50 1615 455 1395 335 1265 285 1180 255 955 175
0.60 1590 470 1350 350 1210 290 1150 265 915 190
0.70 1545 475 1300 360 1175 305 1095 275 860 200
0.80 N/A N/A 1270 370 1140 310 1040 285 820 210
507330-01 Issue 1721 Page 29 of 34
High Medium - High Medium Medium - Low Low
cfm watts cfm watts cfm watts cfm watts cfm watts
Air Volume / Watts at Various Blower Speeds
Page 30
0.80 1905 785 1635 560 1380 425 1215 350 975 270 1965 785 1640 555 1400 425 1210 345 1025 275
0.70 1965 755 1670 555 1420 410 1255 330 1015 255 2000 765 1675 535 1465 410 1255 325 1080 265
0.60 2010 750 1710 535 1470 390 1305 320 1080 240 2055 755 1725 515 1495 400 1305 315 1135 250
0.50 2025 730 1740 520 1500 375 1340 300 1130 225 2095 730 1770 500 1535 385 1365 300 1175 235
0.40 2050 715 1785 495 1550 360 1385 285 1175 210 2135 715 1830 485 1585 365 1395 285 1230 225
0.30 2090 695 1830 480 1595 345 1440 275 1235 200 2165 700 1850 465 1650 355 1455 275 1285 210
0.20 2135 680 1865 465 1630 330 1470 260 1280 190 2210 680 1895 460 1680 335 1510 255 1350 200
0.10 2180 655 1905 445 1690 305 1510 240 1340 175 2260 655 1945 425 1740 315 1550 240 1400 185
0.00 2230 635 1945 430 1715 295 1555 230 1470 185 2315 645 1990 415 1780 300 1610 230 1510 200
cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts
Pressure
in. w.c.
External
Static
Bottom Return Air, Side Return Air with Optional Return Air Base, Return
Air from Both Sides or Return Air from Bottom and One Side.
A80UH1E / 80G1UHE 110*C20 Performance (Less Filter)
High
0.80 1935 785 1635 560 1420 435 1225 350 1055 285 1950 795 1645 560 1415 435 1225 345 1040 285
0.70 1980 765 1680 540 1465 420 1265 330 1105 270 1990 775 1685 540 1450 425 1265 330 1095 270
0.60 2020 750 1725 525 1515 405 1320 320 1145 255 2030 760 1715 530 1495 405 1325 320 1140 255
0.50 2060 735 1760 510 1545 385 1370 305 1200 245 2070 735 1765 515 1545 390 1370 305 1180 245
0.40 2090 715 1800 495 1585 370 1405 285 1235 230 2135 720 1810 490 1595 370 1410 290 1225 230
0.30 2125 695 1835 475 1635 355 1450 275 1285 215 2165 715 1850 475 1645 355 1470 275 1285 215
0.20 2150 675 1865 450 1655 640 1490 260 1340 205 2210 695 1885 465 1680 340 1510 265 1350 205
0.10 2200 655 1910 440 1705 315 1535 240 1385 190 2250 675 1945 445 1730 320 1555 245 1400 190
0.00 2255 640 1940 420 1750 310 1580 230 1485 185 2290 655 1980 425 1775 310 1605 235 1495 195
cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts
Pressure
in. w.c.
External
Static
Bottom Return Air, Side Return Air with Optional Return Air Base, Return
Air from Both Sides or Return Air from Bottom and One Side.
A80UH1E / 80G1UHE 090*C20 Performance (Less Filter)
High
Medium -
High
Medium
Medium -
Low
Low High
Air Volume / Watts at Various Blower Speeds
Single Side Return Air - Air volumes in bold require eld fabricated transition
to accommodate 20 x 25 x 1 in. air lter in order to maintain proper air velocity.
Medium -
High
Medium
Medium -
Low
Low High
Air Volume / Watts at Various Blower Speeds
Single Side Return Air - Air volumes in bold require eld fabricated transition
to accommodate 20 x 25 x 1 in. air lter in order to maintain proper air velocity.
Medium -
High
Medium
Medium -
Low
Low
Medium -
High
Medium
Medium -
Low
Low
507330-01Page 30 of 34 Issue 1721
Page 31
Low
Low
Medium -
Medium
High
Medium -
Single Side Return Air - Air volumes in bold require eld fabricated transition
to accommodate 20 x 25 x 1 in. air lter in order to maintain proper air velocity.
Low High
Air Volume / Watts at Various Blower Speeds
Low
Medium -
Medium
High
Medium -
High
Bottom Return Air, Side Return Air with Optional Return Air Base, Return
Air from Both Sides or Return Air from Bottom and One Side.
cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts cfm watts
0.00 2495 755 2295 590 2045 435 1845 315 1650 230 2365 725 2295 575 2005 410 1820 300 1635 235
0.10 2440 780 2220 620 2015 445 1820 330 1615 245 2350 745 2210 595 2000 435 1745 320 1530 230
0.20 2390 790 2175 640 1935 470 1735 350 1550 255 2330 775 2175 625 1945 455 1730 330 1490 250
0.30 2360 805 2140 655 1895 490 1720 370 1485 275 2245 785 2135 645 1895 475 1655 355 1425 265
0.40 2285 835 2125 675 1850 510 1660 380 1455 290 2215 810 2085 660 1840 495 1600 375 1385 285
0.50 2240 860 2060 690 1815 535 1610 400 1415 310 2175 825 2045 680 1815 505 1590 390 1340 290
0.60 2225 865 2015 715 1785 550 1535 420 1330 320 2125 845 1995 700 1765 530 1525 405 1300 310
0.70 2160 895 1955 735 1755 570 1500 440 1265 340 2095 865 1950 710 1700 545 1485 420 1260 325
Static
A80UH1E / 80G1UHE 135*D20 Performance (Less Filter)
507330-01 Issue 1721 Page 31 of 34
External
in. w.c.
Pressure
0.80 2105 905 1925 750 1715 580 1435 450 1215 345 2065 880 1890 725 1680 655 1415 445 1205 345
Page 32

Service

WARNING
ELECTRICAL SHOCK, FIRE, OR EXPLOSION
HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, a qualied technician should check the system as follows:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are pre-lubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Filters
Filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the lters when necessary to ensure that the furnace operates properly. Replacement lters must be rated for high velocity airow. Table 1 lists recommended lter sizes.
Flue and Chimney
1. Check ue pipe, chimney and all connections for tightness and to make sure there is no blockage.
2. Check unit for proper draft.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC ± 10%.
3. Check amp draw on the blower motor with inner blower panel in place.
Unit Nameplate___________ Actual_____________
Cleaning the Burners
NOTE: Use papers or protective covering in front of the
furnace during cleaning.
4. Turn off both electrical and gas power supplies to furnace.
5. Label the wires from gas valve, rollout switches, primary limit switch and make-up box then disconnect them.
6. Disconnect gas supply piping. Remove the screw securing the burner box cover and remove cover. Remove the four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit.
7. To clean burners, run a vacuum cleaner with a soft brush attachment over the face of burners. Visually inspect inside the burners and crossovers for any blockage caused by foreign matter. Remove any blockage. Figure 36 shows burner detail.
8. Reinstall burner box, manifold assembly and burner box cover.
9. Re-install gas supply and turn on electrical power to furnace.
507330-01Page 32 of 34 Issue 1721
Page 33
Figure 36. Burner Assembly Removal

Repair Parts List

The following repair parts are available through independent Allied Air dealers. When ordering parts, include the complete furnace model number listed on the CSA International nameplate — Example: A801UH045JP24A-01. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Upper access panel
Blower panel
Top cap
Control Panel
Parts Transformer
Integrated control
Door interlock switch
Circuit breaker
Blower Parts
Blower wheel
Blower housing
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Heating Parts
Flame sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orices
Pressure switch
Ignitor
Primary limit control
Flame rollout switch
Secondary limit
507330-01 Issue 1721 Page 33 of 34
Page 34
Requirements for Commonwealth of Massachusetts
Modications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following
requirements:
For all side wall, horizontally vented, gas-fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall, horizontally vented, gas-fueled equipment, the installing plumber or gas tter shall observe that a hard-wired carbon monoxide detector with an alarm and battery backup is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gas tter shall observe that a battery-operated or hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas-fueled equipment. It shall be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard-wired carbon monoxide detectors.
a. In the event that the side wall, horizontally
vented, gas-fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide detector with alarm and battery backup may be installed on the next adjacent oor level.
b. In the event that the requirements of this subdivision
cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery-operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas-fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
4. INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas-fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required to Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall, horizontally vented, gas­fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall, horizontally vented, gas-fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components: and
2. A complete parts list for the venting system design or venting system.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved sidewall, horizontally vented, gas-fueled equipment does not provide the parts for venting the ue gases, but identies “special venting systems,” the following requirements shall be satised by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
507330-01Page 34 of 34 Issue 1721
Loading...