Royalton B2329733 User Manual

INSTALLATION INSTRUCTIONS
4HP14/15 SPLIT SYSTEM HEAT PUMP
(R410A REFRIGERANT)
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
Table of Contents
Safety Precautions ......................................................2
Installation ...................................................................2
Electrical Connections ................................................. 5
Start-Up Procedure...................................................... 6
Operation .....................................................................7
Homeowner’s Information .........................................10
NOTE TO INSTALLING DEALER
These instructions and warranty are to be given to the owner or displayed near the indoor air handler unit.
CAUTION
Improper installation, adjustment, alteration, service or maintenance will void the warranty. The qualied installer or agency must use factory-authorized kits or accessories when added to this products. Refer to the individual instructions included with the specic accessory kit.
NOTE
These instructions are intended as a general guide and do not supersede national, state or local codes in any way.
WARNING
Installation or repairs made by unqualied persons can
result in hazards to you and others. Installation MUST
conform with local building codes and with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part 1 CSA C22.1.
WARNING
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
West Columbia, SC 29170
Save these instructions for future reference
*P506318-03*
(P) 506318-03
Page 1 of 11506318-03 Issue 1850
These units are designed for use in residential and
light commercial type buildings. Heat Pumps may only be installed with indoor combinations listed in the Air
Conditioning, Heating and Refrigeration Institute (AHRI)
Directory of Certied Products.
Inspect the unit for any damage before installation. If damage is found, notify the transportation company immediately and le a concealed damage claim.

Safety Precautions

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have re extinguisher available. Read these instructions thoroughly and follow all warning or cautions attached to
the unit.
1. Always wear proper personal protection equipment.
2. Always disconnect electrical power before removing
panel or servicing equipment.
3. Keep hands and clothing away from moving parts.
4. Handle refrigerant with caution, refer to proper MSDS from refrigerant supplier.
5. Use care when lifting, avoid contact with sharp edges.

Installation

NOTE: In some cases noise in the living area has been
traced to gas pulsations from improper installation of equipment.
1. Locate unit away form windows, patios, decks, etc. where unit operation sounds may disturb customer.
2. Ensure that vapor and liquid tube diameters are
appropriate to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal
opening with RTV or other silicon-based caulk.
6. Avoid direct tubing contact with water pipes, duct work, oor joists, wall studs, oors, walls, and any structure.
7. Do not suspend refrigerant tubing from joists and
studs with a rigid wire or strap which comes in direct contact with tubing.
8. Ensure that tubing insulation is pliable and completely surrounds vapor tube.
When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft. of eld-supplied tubing. For proper unit operation, check refrigerant charge using charging information located on control box cover.
NOTE: Maximum liquid-line size is 3/8 in. O.D. for all residential applications including long lines.
Outdoor Section
Zoning ordinances may govern the minimum distance the condensing unit can be installed from the property line.
Install on a Solid, Level Mounting Pad
The outdoor section is to be installed on a solid foundation. This foundation should extend a minimum of 2” (inches) beyond the sides of the outdoor section. To reduce the
possibility of noise transmission, the foundation slab
should NOT be in contact with or be an integral part of the
building foundation.
Elevate Unit
CAUTION
Accumulation of water and ice in base pan may cause
equipment damage.
Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit. Use snow stand in areas where prolonged freezing temperatures are encountered.
If conditions or local codes require the unit be attached to pad or mounting frame, tie down bolts should be used and fastened through knockouts provided in unit base pan.
Rooftop Installations
Mount on level platform or frame 6 inches above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting
members to adequately support unit and minimize
transmission of vibration to building. Ensure roof structure and anchoring method is adequate for location. Consult local codes governing rooftop applications.
Roof mounted units exposed to winds above 5 mph may require wind bafes to achieve adequate defrost. A sheet metal bafe should be spaced 6-1/2” from the fall of the coil. The height should cover the face of the coil and the length should be 6” from the access panel.
NOTE: Unit must be level to within ± 1/4 in./ft. per
compressor manufacturer specications.
Clearance Requirements
When installing, allow sufcient space for airow clearance, wiring, refrigerant piping, and service. For proper airow, quiet operation and maximum efciency. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
506318-03Page 2 of 11 Issue 1850
Figure 1.
Liquid Vapor
Capacity
-018 3/8” 3/8” 3/4” 3/4”
-024 3/8” 3/8” 3/4” 3/4”
-030 3/8” 3/8” 3/4” 3/4”
-036 3/8” 3/8” 7/8” 7/8”
-042 3/8” 3/8” 7/8” 7/8”
-048 3/8” 3/8” 7/8” 7/8”
-060 3/8” 3/8” 7/8” *1-1/8”
* Field supplied 7/8 x 1-1/8 connector required on both ends
of vapor tubing.
Connections
Dia.
Tube
Dia.
Connections
Dia.
Tube
Dia.
Table 1. Recommended Liquid & Vapor Tube
Diameters (in.)
DO LOCATE THE UNIT:
With proper clearances on sides and top of unit
On a solid, level foundation or pad
To minimize refrigerant line lengths
DO NOT LOCATE THE UNIT:
On brick, concrete blocks or unstable surfaces
Near clothes dryer exhaust vents
Near sleeping area or near windows
Under eaves where water, snow or ice can fall directly on the unit
With clearance less than 2 ft. from a second unit
With clearance less than 4 ft. on top of unit
Operating Ambient
The minimum outdoor operating ambient in cooling mode
is 55°F, and the maximum outdoor operating ambient in
cooling mode is 125°F. The maximum outdoor operating
ambient in heating mode is 66°F.
Refrigeration Line Sets
Use only refrigerant grade copper tubes. Split systems may be installed with up to 50 feet of line set (no more than 20 feet vertical) without special consideration (see long
line set guidelines).
It is important that no tubing be cut or seals broken until you are ready to actually make connections to the evaporator and to the condenser section. DO NOT remove rubber plugs or copper caps from the tube ends until ready to make connections at evaporator and condenser. Under no circumstances leave the lines open to the atmosphere for any period of time, if so unit requires additional evacuation
to remove moisture.
Be extra careful with sharp bends. Tubing can “kink” very easily, and if this occurs, the entire tube length will have to be replaced. Extra care at this time will eliminate future service problems.
It is recommended that vertical suction risers not be up­sized. Proper oil return to the compressor should be maintained with suction gas velocity.
Filter Drier
The lter drier is very important for proper system operation
and reliability. If the drier is shipped loose, it must be
installed by the installer in the eld. Unit warranty will be
void, if the drier is not installed.
Installation of Line Sets
DO NOT fasten liquid or suction lines in direct contact with the oor or ceiling joist. Use an insulated or suspension type of hanger. Keep both lines separate, and always insulate the suction line. Long liquid line runs (30 feet or more) in an attic will require insulation. Route refrigeration
line sets to minimize length.
DO NOT let refrigerant lines come in direct contact with
foundation. When running refrigerant lines through the
foundation or wall, openings should allow for a sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between foundation or wall and refrigerant lines should be lled with
a vibration damping material.
CAUTION
If ANY refrigerant tubing is required to be buried by state
or local codes, provide a 6 inch vertical rise at service
valve.
Page 3 of 11506318-03 Issue 1850
Before making braze connections, be sure all joints are clean. Before heat is applied for brazing, dry nitrogen should be owing through the tubing to prevent oxidation and scale formation on the inside of the tubing.
The following is the recommended method for making braze connections at the refrigerant line connections:
1. Debur and clean refrigerant tube end with emery cloth or steel brush.
2. Insert tubing into swage tting connection.
3. Wrap wet rags over valves to protect from heat.
4. Allow dry nitrogen to ow through refrigerant lines.
5. Braze joint, using a suitable brazing alloy for copper to
copper joints.
6. Quench the joint and tubing with water using a wet rag. Leave rag on tting body and re-wet with water to help cool area.
Leak Check
Refrigeration lines and indoor coil must be checked for leaks after brazing and before evacuation. The recommended procedure is to apply a trace amount of vapor refrigerant (approximately two ounces or 3 psig) into the line set and indoor coil, then pressurize with 150 psig of dry nitrogen. Use a refrigerant leak detector to check all joints. The system may also be checked for leaks using a halide torch or pressure and soapy solution. After completion of leak check, relieve all pressure from system before evacuation.
Evacuating and Charging Instructions
NOTE: Intentional release of CFC or HCFC refrigerant to the atmosphere violates Federal Law. It may also violate State and Local Codes. Check all Federal, State and Local Codes before proceeding.
These outdoor units are pre-charged at the factory with
adequate refrigerant to handle 15 feet of refrigerant tubing.
NOTE: DO NOT use any portion of the charge for purging or leak testing. It is mandatory that a thorough evacuation of the refrigeration lines and indoor coil be performed.
The liquid line and suction line service valves have been closed after nal testing at the factory. DO NOT disturb
these valves until the lines have been leak checked and evacuated or the charge in the unit may be lost.
1. Connect the vacuum pump to the center hose of the manifold gauge set, the low-pressure manifold gauge to the vapor service valve and the high pressure manifold gauge to the liquid service valve.
NOTE: Unnecessary switching of hoses can be avoided and complete evacuation of all lines can be achieved by also connecting a branch hose from the manifold gauge center port to a cylinder of the proper refrigerant. Provide a separate shut-off valve to vacuum pump to avoid contaminating vacuum pump oil with refrigerant.
2. The valves should be kept in the “front seated” (closed) position. This will allow evacuation of the refrigeration lines and the indoor coil, without disturbing the factory charge in the outdoor unit.
3. Follow the vacuum pump manufacturer’s instructions. Allow the pump to operate until the system has been evacuated down to 300 microns. Allow the pump to continue running for an additional 15 minutes. Turn OFF the pump and leave the connections secured to the two (2) service valves. After 5 minutes, if the system fails to hold 500 microns or less, check all connections for tight t and repeat the evacuation procedure.
4. Isolate the vacuum pump from the system by closing the shutoff valves on the gauge-set. Disconnect the vacuum pump.
Opening Service Valves
After evacuation of the connecting lines, remove the service valve cap and fully insert the hex wrench into the stem. A back-up wrench is required on the valve body to open the valve stem. Back-out counterclockwise until the valve stem just touches the coined edge.
Wrench sizes:
3/8 service valve: 3/16” Hex wrench
3/4 service valve: 5/16” Hex wrench
7/8 service valve: 5/16” Hex wrench
Replace service valve cap and torque to 8-11 ft-lb on 3/8” valves; 12-15 ft-lb on 3/4” valves; 15-20 ft-lb on 7/8” valves. Use backup wrench on valve body when torquing valve cap.
Install Electrical Accessories
Refer to the instructions packaged with the accessories.
506318-03Page 4 of 11 Issue 1850
Loading...
+ 7 hidden pages