Roth AHTR Series, AHTR101B, AHTR151B, AHTR201B Installation & Operation Manual

P.O. Box 245
Syracuse, NY 13211
www.roth-america.com
888-266-7684
Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units
P/N: 2300100902
Table of Contents:
Section 1: Model Nomenclature
Model Nomenclature ..............................................................2
Section 2: Safety Labeling and Signal Words
Section 3: Introduction
Section 4: Installation
Section 5: Electrical Data
AHTR Electric Heat Electrical Data .........................................6
Section 6: Wiring Diagrams
Section 7: Parts Lists
Guide Revision Table:
Date By Page Note
August 2010 KT All First Published
AHTR Series Elec Heat IOM, August 2010
Section 1: Model Nomenclature
mi
: Fa
& 2
1
AH 10 1 B
TR
AH = Field Installed Electric Heater
TR = Field Installed Used on
Family:
Type:
RXT Series Models
Capacity:
10kW 15kW 20kW
Section 2: Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words Danger, Warning, Caution, and Note are used to identify levels of hazard
seriousness. The signal word Danger is only used on products label to signify and immediate hazard. The signal words Warning, Caution, and Note will be used on product labels and throughout this manual and other manuals that may apply to this product.
& 6:
ty
e
on
i
s
Capaci
o
V
7:
Voltage:
1 = 208/230V, 60Hz, 1 Phase
i
tag
l
8: Rev
Revision:
B = Current Revision
Rev.: 14 July 2010D
y
l
e
p
: Ty
& 4
5
3
SIGNAL WORDS IN MANUALS
The signal word WARNING is used throughout this manual in the following manner:
WARNING
The signal word CAUTION is used throughout this manual in the following manner:
“NOTICE” Notication of installation, operation or maintenance information which is important,
CAUTION
but which is NOT hazard-related.
Signal Words on Product Labeling
“CAUTION” Indicates a potentially hazardous
situation or an unsafe practice which, if not avoided, COULD result in minor or moderate
injury or product or property damage.
“WARNING” Indicates potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
“DANGER” Indicates an immediate hazardous situation which, if not avoided, WILL result in death or serious injury.
Signal words are used in combination with colors and/or on product labels.
“Note:” Used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
Roth AHTR Series Elec Heat IOM, August 2010
2
AHTR Series Elec Heat IOM, August 2010
Section 3: Introduction
INTRODUCTION
The AHTR electric heater is designed specically for the RXT Series Geothermal Heat Pump Unit. Engineering and quality control is built into every electric heater assembly. Good
performance depends on proper application and correct installation.
The information contained in this manual is intended for use by a qualied service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Shut OFF electric power at unit disconnect and/or service panel before beginning the
following procedures.
WARNING
ELECTRICAL SHOCK HAZARD
FAILURE TO FOLLOW THIS WARNING
COULD RESULT IN PERSONAL INJURY,
PROPERTY DAMAGE AND/OR DEATH.
INSTALLATION OR REPAIRS MADE BY UNQUALIFIED PERSONS CAN RESULT
IN HAZARDS TO YOU AND OTHERS.
INSTALLATION MUST CONFORM WITH
LOCAL BUILDING CODES OR, IN THE
ABSENCE OF LOCAL CODES, WITH
NATIONAL ELECTRICAL CODE ANSI/
NFPA 70-2008 OR CURRENT EDITION.
Note: Notify Roth’s shipping department of all damages within 15 days. It is the responsibility of the purchaser to le all necessary claims with the freight company.
UNIT PROTECTION
Protect units from damage and contamination
due to plastering (spraying), painting and
all other foreign materials that may be used at the job site. Keep all units covered on the job site with either the original packaging or equivalent protective covering. Cap or recap
unit connections and all piping until unit is
installed. Precautions must be taken to avoid physical damage and contamination which
may prevent proper start-up and may result in
costly equipment repair.
OVERVIEW
This instruction covers the physical installation of the AHTR Series electric heat kits when installed with the RXT Series Geothermal Heat Pump unit.
The electric heat accessories are used for applications of heat pump with electric heat. Each of the unit models are approved for use with specic electric heat accessories. The installation instructions list the possible combinations and other important electrical
data and limitations.
Table 1: Heater Compatibility
INSPECTION
Upon receipt of any geothermal accessory, carefully check the shipment against the packing slip and the freight company bill of lading. Verify that all units and packages have been received. Inspect the packaging of each package and each unit for damages. Insure that the carrier makes proper notation of all damages or shortage on all bill of lading papers. Concealed damage should be reported to the freight company within 15 days. If not led within 15 days the freight company
can deny all claims.
AHTR Series Elec Heat IOM, August 2010
Accessory Heater Usage
Model Description
AHTR101B
AHTR151B
AHTR201B
10kW, 60Hz, 1 Phase
w/Circuit Breaker
15kW, 60Hz, 1 Phase
w/Circuit Breaker
20kW, 60Hz, 1 Phase
w/Circuit Breaker
Used With
RXT Model
024 - 072
036 - 072
048 - 072
Note: AHTR electric heaters are not backward compatible.
Adapter and ller plates are shipped with the indoor units to be used with electric heat as needed depending on unit size and heater size.
3
Roth
AHTR Series Elec Heat IOM, August 2010
Section 4: Installation
INSTALLATION
This instruction covers the physical installation of the AHTR Series electric heat kits when installed with the RXT Series Geothermal Heat Pump Unit.
The electric heat accessories are used for applications of heat pump with electric heat. Each of the air handler unit models are approved for use with specic electric heat accessories. The installation instructions list the possible combinations and other important
electrical data and limitations.
WARNING
ELECTRICAL SHOCK HAZARD
FAILURE TO FOLLOW THIS WARNING
COULD RESULT IN PERSONAL INJURY
OR DEATH.
1. Shut OFF electrical power at unit disconnect switch or service panel.
2. Remove the upper front panel from unit and locate ller plate. Remove the (4) sheet
metal screws from plate. (See Figure 1)
Figure 1: Heater Installation
Heater Support Rod Fits into Hole
Rotate Circuit Breakers 180 Degrees for RH and
LH DN Airow
BEFORE INSTALLING, MODIFYING, OR
SERVICING SYSTEM, MAIN ELECTRICAL
DISCONNECT SWITCH MUST BE IN THE
OFF POSITION.
THERE MAY BE MORE THAN ONE
DISCONNECT SWITCH. LOCK OUT
AND TAG SWITCH WITH SUITABLE
WARNING LABEL.
CAUTION
CUT HAZARD
FAILURE TO FOLLOW THIS CAUTION
MAY RESULT IN PERSONAL INJURY.
SHEET METAL PARTS MAY HAVE SHARP
EDGES OR BURRS. USE CARE AND
WEAR PROTECTIVE CLOTHING AND
GLOVES WHEN HANDLING PARTS.
Representative drawing only, some models may vary in appearance.
RIGHT HAND AIRFLOW AND LEFT HAND DOWNFLOW APPLICATION
3. If unit is going to be used for right hand return or left hand return downow (airow) the circuit breakers will have to be removed and rotated 180 degrees, so the OFF position will be DOWN when the cabinet is positioned on the right side. This is an NEC requirement.
DO ONE BREAKER AT A TIME to make sure
wires are reconnected properly. Loosen terminal screws on the wires. Gently pull wires back from breaker. Remove screws securing the breaker and rotate 180 degrees, then reconnect the wires to breaker. Proper torque for terminal screws is 35 inch pounds.
4. Insert the heater into the cabinet opening as shown in Figure 1, so the heater support rod goes into the hole in the back of the plenum. Exercise caution to prevent damage to heater element.
5. Secure the electric heat accessory with
four screws.
Roth AHTR Series Elec Heat IOM, August 2010
4
AHTR Series Elec Heat IOM, August 2010
Section 4: Installation
LOW VOLTAGE WIRING
6. Connect the 6-Pin heater wiring harness to the receptacle located inside the cabinet (Top Cover). A perfect match and positive connection must be made between the plug and receptacle. The plug will interlock with receptacle when properly seated.
Harness contains 24 Volts wiring.
WIRING
7. Route unit power supply through knockout
in top of unit and connect to line side of disconnect. Connect ground wire to ground
lug. See wiring diagram label to make
connections. All line voltage connections
and ground connections MUST be made with copper wire.
The power supply wiring MUST have overcurrent protection. This can be either fuses or circuit breakers. The maximum size for the overcurrent protection is shown in the column labeled “Max. Fuse or NEC HACR Breaker (Amps)” in the electrical Data Table or on the unit rating plate. Connect supply voltage wires to the Circuit Breakers on the heater or to the terminal block on the heater.
NOTE: Supply voltage, amperage, fuse and
disconnect switch sizes MUST conform with all technical specications in this manual and on the unit rating plate.
GROUNDING
8.
Permanently ground the electric heat accessory in accordance with local codes and ordinances and in the United States with National Electrical Code ANSI/NFPA70­2008 or current edition. Use a copper conductor of the appropriate size from the electric heat accessory ground lug, to a grounding lug on the circuit breaker panel. On models with more than one circuit, a separate copper ground wire MUST be connected for each circuit.
8. Install top front door panel.
9. Mark an “X” in the appropriate box for the heater on the unit rating plate.
WARNING
ELECTRICAL SHOCK HAZARD
THE UNIT CABINET MUST HAVE AN
UNINTERRUPTED OR UNBROKEN
GROUND TO MINIMIZE PERSONAL
INJURY IF AN ELECTRICAL FAULT
SHOULD OCCUR. THE GROUND MAY
CONSIST OF ELECTRICAL WIRE OR
METAL CONDUIT WHEN INSTALLED WITH
EXISTING ELECTRICAL CODES.
TIME DELAY MODULE
10. The time delay module stages the heater elements for 15kW and 20kW heaters. In most cases, all of the DIP switches should be in the “ON” position, which will provide a 1,023 second (approximately 17 minute) delay between the rst and second stage of electric heat.
For example, if all of the switches are in the “ON” position of a 20kW heater, only 10kW will be energized when the thermostat calls for backup or emergency heat. After approximately 17 minutes of continuous demand from the thermostat, the second bank of electric heat will be energized, providing the full 20kW of heat. The DIP switches may be set in any manner that is desired.
There are 10 DIP switches that are
cumulative. In other words, starting with the rst switch, the time delay for each additional switch that is in the “ON” position is added to the previous switch. The switches are labeled 1, 2, 4, 8, 16, 32, 64, 128, 256, and 512. When all of the switches are in the “ON” position, all of the numbers must be added to determine the time delay. In the case of all switches in the “ON” position, the
delay is 1+2+4+8+16+32+64+128+256+512 = 1,023 seconds. If only 8 to 9 minutes
is desired between stages, place all
AHTR Series Elec Heat IOM, August 2010
5
Roth
AHTR Series Elec Heat IOM, August 2010
Section 4: Installation
but the last switch (the switch labeled “512”) in the ON position. With 9 switches in the “ON” position, the time delay is
1+2+4+8+16+32+64+128+256 = 511 seconds
(about 8.5 minutes). Other combinations of switches may be used, depending upon the desired time delay.
AIR FLOW
11. Airow requirements are different between models. Please refer to the unit Installation
Instructions for airow set-up information.
TEMPERATURE RISE CHECK
12. Temperature rise is the difference between the supply and return air temperatures.
NOTE: The temperature rise can be adjusted by changing the heating CFM. Refer to the unit’s Installation Instructions for airow information.
NOTE: The maximum outlet air temperature for
all models is 200 Degrees F (93.3 Degree C).
Section 5: Electrical Data
TECHNICAL DATA (AHTR Electric Heaters only) Single Phase w/ Circuit Breaker
Heater Model
AHTR101B
AHTR151B
AHTR201B
Supply
Voltage
240 10 Single 5 41.7 52.1
208 7.5 Single 3.75 36.1 45.1 2 6 115 1 10
240
240 Mult. 2 10 41.7 52.1 60 2 6 101 1 10
208
208 Mult. 2 7.5 36.1 45.1 60 2 6 101 1 10
240
240 Mult. 2 10 41.6 52.0 60 2 6 101 1 10
208
208 Mult. 2 7.5 48.1 60.0 60 2 6 101 1 10
Heat
kW
15
11.25
20
15
Supply
Circuit
Number
Mult. 1 5 20.8 26.0 30 2 10 118 1 10
Mult. 1 3.75 18.0 22.5 30 2 10 118 1 10
Mult. 1 10 41.6 52.0 60 2 6 101 1 10
Mult. 1 7.5 48.1 60.0 60 2 6 101 1 10
Heater kW Per Circuit
FLA
Total
AMPS
MCA
Min
Circuit
Ampacity
Maximum
Over-
Current
Protective
Device
(AMPS.)
60
Recommended
Supply Wire
75°C. Copper
# of
Wires
Wire
Size
2 6 101 1 10
Max
Length
(Ft)
Ground
Wire
# of
wires
Min Size
Roth AHTR Series Elec Heat IOM, August 2010
6
AHTR Series Elec Heat IOM, August 2010
Section 6: Wiring Diagrams - AHTR101B / 10kW
AHTR Series Elec Heat IOM, August 2010
7
Roth
AHTR Series Elec Heat IOM, August 2010
Section 6: Wiring Diagrams - AHTR151B / 15kW
Roth AHTR Series Elec Heat IOM, August 2010
8
AHTR Series Elec Heat IOM, August 2010
Section 6: Wiring Diagrams - AHTR201B / 20kW
AHTR Series Elec Heat IOM, August 2010
9
Roth
AHTR Series Elec Heat IOM, August 2010
Section 7: Parts List - AHTR101B / 10kW
Roth AHTR Series Elec Heat IOM, August 2010
10
AHTR Series Elec Heat IOM, August 2010
Section 7: Parts List - AHTR151B / 15kW
AHTR Series Elec Heat IOM, August 2010
11
Roth
AHTR Series Elec Heat IOM, August 2010
Section 7: Parts List - AHTR201B / 20kW
Roth AHTR Series Elec Heat IOM, August 2010
12
AHTR Series Elec Heat IOM, August 2010
AHTR Series Elec Heat IOM, August 2010
13
Roth
P.O. Box 245
Syracuse, NY 13211
888-266-7684 US
800-969-7684 CAN
866-462-2914 FAX
www.roth-america.com
info@roth-usa.com
*
* AHRI certication is shown as the Roth brand under the Enertech Manufacturing certication reference number
**Roth Industries geothermal heat pumps are shown as a multiple listing of Enertech Manufacturing’s ETL certication *** Roth geothermal heat pumps are listed as a brand under Enertech Manufacturing’s Energy Star ratings
***
**
Loading...