This instruction is the >> Original Version << in your language.
These instructions are intended for authorised and trained
heating and sanitation experts who have experience in the proper
installation and maintenance of heating systems and hot water
storage tanks by virtue of their technical training and knowledge.
All the activities required for assembly are described in this
manual. All heating parameters needed for smooth operation are
already factory-set.
Ɣ Please read through this manual carefully before operating
the heating system or before adjusting the settings for it.
Ɣ Make a note of the preset values before you make any
changes to the unit configuration.
Relevant documents
– ROTEX Heat generator;
– the associated installation and maintenance instructions
for the heating company
– the operating instructions for the operator and
– the operating manual for the user/owner.
– When connecting to a ROTEX solar system; the associated
installation and operating instructions.
– If a different ROTEX Heat generator or optional accessories
are connected; the associated installation and operating
instructions.
Special warning signs
Some types of danger are represented by special symbols:
Electric power
Risk of burns
Validity
Some information in this manual has limited validity. The validity
is highlighted by a symbol.
Only applicable to oil condensing boilers
Only applicable to gas condensing boilers
Order number
Notes related to order numbers are identified by the shopping
cart symbol .
Handling instructions
Ɣ Instructions on actions are shown as a list. Actions of which
the sequential order must be maintained are numbered.
Î Results of actions are identified with an arrow.
Entry into a setting procedure
The guides are included in the scope of supply for the individual
units.
1.2Warning signs and explanation of symbols
Meaning of the warnings
Warnings in this manual are classified according into their severity and probability of occurrence.
DANGER!
Draws attention to imminent danger.
Disregarding this warning can lead to serious injury or
death.
WARNING!
Indicates a potentially dangerous situation.
Disregarding this warning can result in serious injury
or death.
CAUTION!
Indicates a situation which may cause possible
damage.
Disregarding this warning can lead to damage to
property and the environment.
Exit from a setting procedure
1.3Avoid danger
All ROTEX Heat generator conform to the state-of-the-art and
meet all recognised technical constructional requirements.
However, improper use may result in serious physical injuries or
death, as well as property damage.
To avoid danger, only operate the ROTEX Heat generator:
– as stipulated and in perfect condition,
– with an awareness of the safety and hazards involved.
This assumes knowledge and use of the contents of this manual,
all supplementary documents and the relevant accident prevention regulations as well as the recognised safety-related and
occupational health rules.
WARNING!
This unit is not intended for use by persons (including
children) with impaired physical, sensory or mental
faculties or persons with insufficient experience and/or
expertise unless supervised by a person responsible
for ensuring their safety or are given instruction by this
person on how to use the unit.
This symbol identifies user tips and particularly useful
information, but not warnings or hazards.
FA ROTEX RoCon BF - 06/2013
3
1 x Safety
1.4Proper use
The Control RoCon BF must only be used in ROTEX oil and gas
condensing boilers that have been approved for the ROTEX
RoCon regulating system. The ROTEX Control RoCon may only
operated only according to the indications in this manual.
Any other use outside the intended use is considered as improper. The operator alone shall bear responsibility for any resulting damage.
For any work on the equipment, which extends above and
beyond the operation of the regulating system, you must observe
the details provided in the supplementary documents, particularly
with regard to safety instructions.
4
FA ROTEX RoCon BF - 06/2013
2Product description
2 x Product description
2.1General
The Control RoCon BF is a constituent part of the boiler
control panel in ROTEX Heat generator.
It consists of the control panel PCB, the actors and
sensors and other components of the ROTEX regulating system RoCon connected and the operating unit
RoCon B1.
In this instruction manual we explain just the functions
and setting possibilities of the Control. More information
for the boiler control panel and containing the
equipment components can be found in the supplementary documents.
The electronic, digital Control is able to automatically control all
heating and hot water functions for the direct heating circuit, a
mixed heating circuit which can be connected as an option and a
storage tank charging circuit, depending on the boiler in question.
Together with the automatic firing unit it takes over the entire
safety management of the ROTEX Heat generator. This executes a safety switch-off in the event of a water shortage or undefined operating states. A corresponding fault message shows
the operator all the information for fault causes.
All function settings for the ROTEX Heat generator and the optional RoCon equipment connected via the data bus are carried
out with the operating elements of the integrated operating part
RoCon B1 and displayed in clear text display on a coloured
backlit display.
On the ROTEX Heat generator the regulation data bus is used to
connect the following optional equipment:
The room station RoCon U1 has the same operating panel as the
one integrated in the Heat generator (the RoCon B1).
All settings for the allocated heating circuit can be carried out in
the same way as the operating unit. With activated terminal
function, all operating possibilities that are available on the integrated operating unit are available, with the exception of certain
special functions (e.g. Emission Measurement).
A connected mixer module RoCon M1 will also be operated, after
appropriate allocation, by the control unit RoCon B1 and/or the
room station RoCon U1.
2.2Display and operating elements
01.04.13
13:35
Using the connected outdoor temperature sensor RoCon OT1
( 15 60 70) you can regulate the flow temperature in a
weather-controlled manner with a frost protection function.
If the optional gateway RoCon G1 ( 15 70 56) is installed and
connected to the internet, the ROTEX Heat generator can be
conveniently monitored and operated by remote control using a
mobile phone (App).
The Control RoCon BF contains a timer, which can be used to
set:
– 2 individually-adjustable timer programmes for room heating
(direct heating circuit),
– 2 individually-adjustable timer programmes for hot water gen-
eration,
– 1 individually-adjustable timer programme for an optional cir-
culation pump.
In addition, the Control RoCon BF has a frost protection unit for
the direct heating circuit and the storage tank charging circuit, together with the facility for incorporation of an additional heat
source (wood-burning boiler, solar system) via a potential-free
burner blocking contact.
Initial commissioning of the heating system unit is described in
the installation manual of the ROTEX Heat generator.
Certain menu points on the Control RoCon BF are only accessible to the heating expert. This security measure ensures that no
undesirable malfunctions arise during operation of the system
through incorrect settings.
1Clear text display
2Setting: Configuration
3Spare (n.a.)
4Rotary switch
5Setting: Info
6Setting: Operating Mode
Fig. 2-1 Arrangement of display and operating elements
7Setting: Set Temp Day
8Setting: Set Temp Night
9Setting: DHW Set Temp
10Rotary button
11Setting: DHW Reheating
12Setting: Time Program
13Exit button
FA ROTEX RoCon BF - 06/2013
5
2 x Product description
2.2.1 Display
All the operating steps are supported by appropriate displays in
the clear text display on a coloured background.
Menu guiding is available in 7 different languages (see
section 3.2.8).
Malfunctions are generally indicated by a fault code and
a clear text fault message on the display.
For troubleshooting instructions refer to chapter 5.
The colour of the backlighting indicates the operational status
and the operational mode:
White:Standard lighting, normal operational display.
Red:Fault status, depending on the type of fault, the
ROTEX Heat generator continues to function with
restrictions.
Green:Operating mode with operator authorisation.
Blue:Operating mode with expert authorisation.
Rotary switch
The rotary switch is used to gain rapid direct access (main
function level) to frequently required functions and setting possibilities.
Independent of the setting of the rotary switch, the
ROTEX Heat generator operates in accordance with
the operating mode set in the switch position "Oper-ating Mode"
or which has been activated by a
special programme.
ActionResult
Rotating
Direct selection of the main function level allocated to this switch position.
Tab. 2 -1 Function of rotary switch
Rotary switch
The rotary switch can be used to navigate in the individual levels,
setting values can be selected, changed and these changes can
then be accepted by pressing briefly.
01.04.13
1Date display
2Status burner activity
3Display of expert login
4Display time
5Current flow temperature
6Status heating circuit
Fig. 2-2 Display of the Control - standard display
7Current outdoor temperature
8Active operating mode
9Status of hot water generation
10Current storage tank temper-
13:35
ature
With activated screed function (see chapter 3.4.6) the upper line
on the display also shows the symbol .
2.2.2 Operating elements
CAUTION!
Never operate the operating elements on the controller with a hard, pointed object. This can cause
damage and can cause the control to malfunction.
If special key combinations or extended key pushes are required
for certain function, a separate note is made in each specific
section of this description.
ActionResult
Rotating
To the right (+): Increased regulation
To the left (–): Reduced regulation
tapping
Confirm, accept, selection and execute the
function.
Tab. 2 -2 Functions of the rotary switch
Exit button
This button can be used to jump back to the previous display
within a menu display or a function / input can be interrupted.
This button can also be used to call up the special level (see
section 3.3).
ActionResult
Brief actuation.
Press for more
than 5 secs.
– Jump back to the previous display or pre-
vious level or
– Cancellation of a special function or a
one-off active timer programme
– Special level is called up.
Tab. 2 -3 Functions of the exit button
6
FA ROTEX RoCon BF - 06/2013
3Operation
1
2
3
45
6
7
8
9
3.1General
3 x Operation
DANGER!
If electrical components come into contact with water,
this can cause an electric shock as well as cause
potentially fatal injuries and burns.
Ɣ The displays and the buttons on the Control
must be protected from the effects of moisture.
Ɣ To clean the Control use a dry cotton cloth.
Using aggressive cleaning agents and other
liquids can cause damage to equipment or lead
to an electric shock.
The operating concept of the Control RoCon BF is structured in
such a way that the frequently required setting facilities are ac-
cessible quickly and directly in the main function level (selection
using the rotary switch) and that the less frequently required
setting facilities are arranged in a lower parameter level.
1Operating Mode (section 3.2.2)
2 Set Temp Day (section 3.2.3)
3 Set Temp Night (section 3.2.4)
4 DHW Set Temp (section 3.2.5)
5 DHW Reheating (section 3.2.6)
6 Time Program (section 3.2.7)
7Configuration (section3.2.2)
8(Not used)
9 Info (section 3.2.1)
Fig. 3-1 Illustration of main function level (rotary switch position)
When the system is switched on, it regulates fully automatically,
based on the stipulations set in the Control RoCon BF, the
operation of the
– room heating and the
– sanitary hot water generation.
Independent of the setting of the rotary switch, the operates in accordance ROTEX Heat generator with the
operating mode set in the switch position "OperatingMode"
or which has been activated by a special
programme.
If the user enters a value manually, this setting remains active
until the user changes it or until the programme clock forces another operating mode.
The operating mode can be affected by additional functions:
– Weather-controlled set value regulation
– Switching time programme
– Setting the temperature target value
– Setting at the room station
– Signal from the burner blocking contact (e.g. solar system)
Button block
The operating panel on the RoCon BF can be blocked to prevent
inadvertent actuation (see fig. 3-2).
Unlocking can be carried out in the same way.
The prerequisite for this function is that, in the level "Setup", the
parameter [Keylock Function] is set to "ON" (see section 3.2.8).
Keylock Function
ON
Certain functions and parameters are restricted by access authorisation and can only be adjusted by the heating expert (see
Keylock Function
section 3.4.1).
In normal operating mode the rotary switch should be in
position .
After switching on and successful initialisation, the display automatically shows the standard display with rotary switch
position .
In the first commissioning, the setting for language selection is
Keylock Function
Off
displayed first.
Ɣ Select the language using the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Adaption to the special installation configuration is
Fig. 3-2 Activating and deactivating the button block
carried out in the rotary switch position "Configuration" (see section 3.2.8).
FA ROTEX RoCon BF - 06/2013
7
3 x Operation
Operating Mode
Standby
Reducing
Operating Mode
heating
Summer
Automatic 1
Operating Mode
Automatic 1
Automatic 2
Operating Mode
Automatic 1
Automatic 2
3.2Basic functions and operating modes
3.2.1 System information (Info)
In this rotary switch position, the rotary switch can be used to call
up all the system temperatures, the type of Heat generator,
various software information and the operating status of all
system components, one after the other. The number of displayed parameters depends on the connected components.
No settings can be made to these values.
Ɣ Place the rotary switch in the "Info" position.
Î Standard display is shown (see fig. 2-2).
Ɣ Press the rotary switch briefly.
Î The parameter overview is displayed.
Ɣ Select the desired information level with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î The overview is displayed (example see fig. 3-3).
Ɣ Select the individual information with the rotary switch.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 4.9.
Displaying the water pressure
On the Control RoCon BF, when it is switched on, you can
display the system pressure (water pressure) in the internal
circuit (direct heating circuit). The water pressure is available as
the first Info parameter (see fig. 3-3).
The permissible range of water pressure in heating mode depends on the Heat generator and the heating system. The set
values and threshold values must only be changed only by the
heating technician. If the water pressure falls below the minimum
value (set parameter value), it must be increased by topping up
the system (see installation instructions of the Heat generator).
The pressure limits for the safety switch-off and the set
pressure can be adjusted in the parameter settings in
level "System Configuration".
Info
Water Pressure
T-HS
Water Pressure
Fig. 3-3 Info value display (e.g. system pressure)
3.2.2 Setting the operating mode
The selection of the operating mode with which the ROTEX Heat
generator is to operate is undertaken on the rotary switch in the
setting "Operating Mode".
The selected operating mode is activated by briefly pushing the
rotary switch.
8
Fig. 3-4 Changing over the operating mode
(e.g.: from "Standby" to "Automatic 2")
FA ROTEX RoCon BF - 06/2013
3 x Operation
01.04.13
13:35
If a temporary heating programme (Emission Measurement, DHW Reheating, Party, Away, Holiday, Vacation, Screed, STL Test) is started during the selected
operating mode, the regulation is preferentially executed in accordance with the settings of this heating
programme.
Ɣ Place the rotary switch in the "Operating Mode"
position.
Î An overview is displayed.
Ɣ Select the desired operating mode with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î ROTEX Heat generator operates in accordance with the
set operating mode.
Î The current operating mode is indicated by an appropriate
symbol in the standard display.
Operating mode Standby
CAUTION!
A heating system that is not frost-protected can freeze
in cold weather and be damaged.
Ɣ Drain the water out of the heating system if there is
a danger of frost.
Ɣ If the heating system is not drained, the power
supply must be ensured and the main switch must
remain switched on if there is a danger of frost.
In this mode, the ROTEX Heat generator is placed in stand-by
mode. The frost-protection function remains in place. In order to
maintain this function, the system must not be disconnected from
the mains!
If the outdoor temperature is below the parameter value [T-Frost
Protect] the integrated circulation pump is switched on in order to
prevent the heating system from freezing.
Operating mode Reducing
Reduced heating mode (lower set room temperature) in accordance with the setback temperature set in the parameter
[T-Reduced] (see section 3.2.4).
Hot water generation in accordance with the set temperature in
the parameter [Room Temp Reduced] (see section 3.2.5) in the
hot water timer programme [DHW Program 1].
Operating mode heating
Heating in accordance with the room temperature set in the parameter [T-Room des 1] (see section 3.2.3). A connected outdoor
temperature sensor (weather-controlled flow temperature regulation) or a connected room station will also influence the set flow
temperature regulation.
Hot water generation in accordance with the set temperature in
the parameter [Room Temp Reduced] (see section 3.2.5) in the
hot water timer programme [DHW Program 1].
Operating mode Summer
Hot water generation only in accordance with the set temperature
in the parameter [Room Temp Reduced] (see section 3.2.5) in
the hot water timer programme [DHW Program 1].
Operating mode Automatic 1 (Timer programme)
Automatic heating and setback mode in accordance with the
permanent timer programmes (see section 3.2.7):
– [HC Program 1]
– [DHW Program 1]
Operating mode Automatic 2 (Timer programme)
Automatic heating and setback mode in accordance with the
permanent timer programmes (see section 3.2.7):
– [HC Program 2]
– [DHW Program 2]
If, in the active operating mode, the hot water generation is in setback, you can use the rotary switch
to set temporary "DHW Reheating" without having to
change any other standard settings (see section 3.2.6).
Fig. 3-5 Standard display in operating mode [Standby]
(above the frost protection limit)
In the operating mode [Standby] the burner is isolated
from the power supply (energy efficiency) when the following conditions are met:
– the burner has been off for at least 5 mins.,
– the outdoor temperature sensor (RoCon OT1,
15 60 70) is connected and correctly parame-
terised in the system configuration,
– the outdoor temperature is over 3 °C,
– the frost protection function is not active in any of
the connected heating circuits,
– there is no communication fault for the automatic fir-
ing and
– the ROTEX Heat generator has been switched on
for at least 10 mins.
In addition to these operating modes there are various different
temporary heating programmes available (see tab. 3-1), which
run according to priority after they have been activated.
Temporary
heating
programme
Emission Measure-
ment
DHW ReheatingDHW Reheatingsection 3.2.6
PartyTime Programsection 3.2.7
Away
Holiday
Vacation
Screed*Configuration > HC
STL Test*Special LevelAs requiredsection 3.3.3
* Only with expert code.
Tab. 3-1 Overview of temporary heating programmes
Setting /
activating in
level
Special LevelAs requiredsection 3.3.1
Configuration
Rotary
switch
setting
Note
section 3.4.6
FA ROTEX RoCon BF - 06/2013
9
3 x Operation
3.2.3 Temperature setting daytime room temperature
In rotary switch setting , the set room temperatures for room
heating during the day are determined.
Ɣ Place the rotary switch in the "Set Temp Day" position.
Î An overview is displayed.
The end figures of the parameter designations (1 - 3)
within this rotary switch setting designate the association with each individual cycle of the timer programme.
The 1st. set value [T-Room des 1] is used as the set
value for temporary heating programmes.
Ɣ Select the temperature block to be set with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Settings are displayed.
Ɣ Set the temperature.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 4.5.
3.2.4 Temperature setting Setback mode
In rotary switch setting , the set room temperatures for room
heating during setback are determined.
Ɣ Place the rotary switch in the "Set Temp Night"position.
Î An overview is displayed.
Ɣ Select the parameter to be set with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
– [T-Reduced]: Set value for operating mode [Reducing] or
setback by a permanent timer programme.
– [T-Absence]: Set value for temporary heating pro-
grammes ("Away" and "Vacation").
Î Settings are displayed.
Ɣ Set the temperature.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 4.6.
3.2.5 Temperature setting hot water generation
In the rotary switch setting , the hot water set temperatures for
hot water generation for each individual timer programme are determined.
Ɣ Place the rotary switch in the "DHW Set Temp" position.
The end figures of the parameter designations (1 - 3)
within this rotary switch setting designate the association with each individual cycle of the timer programme.
The 1st. set value [Room Temp Reduced] is used as
the set value for temporary heating programmes.
Ɣ Select the temperature block to be set with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Settings are displayed.
Ɣ Set the temperature.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter
4.7.
3.2.6 Unplanned hot water generation
In the rotary switch position you can charge the hot water
up manually outside a hot water timer programme to the preset
temperature set in parameter [Room Temp Reduced]. Heating up
is carried out as a priority and independently of any other heating
programmes.
Ɣ Place the rotary switch in the "DHW Reheating"position.
Î An overview is displayed.
Ɣ Select the parameter to be set with the rotary switch.
– [T-DHW 3 des]: Activating one-off hot water generation.
– [DHW Reloadtime]: Activating time-limited hot water gen-
eration.
Ɣ Confirm the changes with a brief push of the rotary switch.
Ɣ Setting parameters
Ɣ Confirm the changes with a brief push of the rotary switch.
Î One-off hot water generation starts.
The two functions cannot be combined together.
After this temporary function has expired, the Control
automatically jumps back to the previously active operating mode. The rotary switch should therefore be re-
turned to the position "Info" after activation.
Possible setting values for this rotary switch setting can be seen in chapter4.3.
3.2.7 Switching time program
Various different timer programmes are available, that are set in
the factory, but which can be adjusted to suit, to provide convenient and individual room and hot water temperature control.
The timer programmes regulate the associated heating circuit,
the storage tank charging circuit and an option connected circulation pump in accordance with the stipulated switching times.
Adjustment
In the rotary switch position we set the time intervals for
the heating circuit, the integrated hot water generation and the
optional circulation pump.
Ɣ Place the rotary switch in the "Time Program"
position.
Î An overview is displayed.
Ɣ Select the timer programme to be set with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Settings are displayed.
Ɣ Select and change the value to be set with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
More detailed explanations and possible setting values for this ro tary switch settin g
can be seen in
chapter 4 "Parameter settings".
Permanent timer programmes
For the connected heating circuits and the storage tank charging
circuit, timer programmes regulate the heating circuit temperatures or the operating times for the circulation pump in accordance with the stipulated switching cycles. The switching
cycles are saved in time blocks for which various different set
temperatures apply.
In the switching cycles the heating system is regulated differentiated into day and setback mode.
The temperature settings for this timer programme are carried out
via the set value settings "Set Temp Day", "Set Temp Night" and "DHW Set Tem p" .
10
FA ROTEX RoCon BF - 06/2013
3 x Operation
The following switching time programmes are available:
– 2 timer programmes for the heating circuit, each with 3 possi-
ble time cycles
– [HC Program 1]
– [HC Program 2]
A separate input for each individual day of the week is
possible, or in blocks of "Monday to Friday", "Saturday
to Sunday" and "Monday to Sunday".
ProgrammeTime periodSwitching cycle
HC Program 1
Single day of the week
(Monday, Tuesday ...)
Working week
(Monday to Friday)
Weekend
(Saturday to Sunday)
Entire week
(Monday to Sunday)
1st
1st
1st
1st
.
2.
3.
.
2.
3.
.
2.
3.
.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
07:00 -> 23:00
--:-- -> --:--
--:-- -> --:--
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
The setting and input structure of the timer programmes
are identical to the ones for the heating circuit timer programme (see also fig. 3-2).
– 1 timer programme for one optionally connected circula-
tion pump with 3 individual possible switching cycles
– [Circulation Time]
The setting and input structure of the timer programmes
are identical to the ones for the heating circuit timer programme (see also fig. 3-2).
For further instructions concerning settings for an optional circulation pump, see section 3.4.8.
Saved switching time programmes can be changed at any time.
To provide a better overview, we recommend making a record of
the programmed switching times and keeping it in a safe place
(see section 3.5.1).
The permanent timer programmes are preset as per tab. 3-3.
HC Program 2See HC Program 1
Tab. 3-2 M enu structure heating circuit timer programme
1st
.
2.
3.
Time settings for one switching cycle in one weekday or
block programme are also adopted for other time periods, provided that they affect the same weekdays. Examples referring to fig. 3-2:
a) For the single working day "Monday" the start time
in the 1st. switching cycle changed from 06:00 to
05:00.
Î In the time period "Working week" and "Entire
week", the 1st. time block Switching cycle also
changed from 06:00 to 05:00.
b) For the time period "Weekend", the start time in the
1st. Switching cycle changed from 07:00 to 08:00.
Î In the individual weekdays "Saturday" and "Sun-
day", the 1st. time block is automatically switching cycle also changed from 07:00 to 08:00.
c) For the time period "Entire week", the end time in
the 1st. time block switching cycle changed from
22:00 to 21:30.
Î In all the weekdays the 1st. switching cycle is
also changed from 22:00 to 21:30.
See
HC Program 1
– 2 timer programmes for the hot water circuit, each with 3 pos-
sible switching cycles
– [DHW Program 1]
– [DHW Program 2]
[T-Room des 1]: 20 °C[T-Room des 2]: 20 °C[T-Room des 3]: 20 °C
[T-Reduced]: 10 °C
"HC Program 1"
"HC Program 2"
Domestic hot water generation
"DHW Program 1"
"DHW Program 2"
"Circulation Time"
Tab. 3-3 Factory setting for the permanent switching time programmes
Temporary timer programmes
For a specific situation there are 4 temporary programmes
available, which deactivate the permanent timer programmes
or the current operating mode for the duration of their validity.
1. [Party]: Immediate one-off extension of the room heating
a) If an automatic programme is activated, the last
applicable switching cycle is always extended by an
adjustable time period.
b) In all the other operating modes, the set room temperature
of the first switching cycle applies.
– The hot water generation is not affected.
2. [Away]: Immediate one-off setb ack up to 6 hours
– The system operates in the setback mode according to
the room temperature set in the rotary switch setting "SetTemp Night"
– The system operates in the setback mode exclusively
according to the room temperature set in the rotary switch
setting "Set Temp Night"
[T-Absence].
– The hot water generation is regulated in accordance with
the settings for the entire week in the [DHW Program 1].
, in the parameter [T-Absence].
, in the parameter
3.2.8 System settings
In the rotary switch setting "Configuration" we undertake
the basic settings for the Control RoCon BF and the system configurations for the installation environment of the ROTEX Heat
generators, the direct heating circuit, the hot water generation
and any optionally connected components.
Depending on access authority (user or expert), various different
parameters are available. Certain parameters are only accessible to the heating expert.
Language, Date, Time, Setting summer/winter time
An internal pre-programmed calendar ensures automatic time reset at the annually recurring
summer/winter time changes. If required, the automatic
time changeover can be switched off.
Ɣ Place the rotary switch in the "Configuration"position.
Î An overview is displayed.
Ɣ Select the "Setup" level with the rotary switch.
Î An overview is displayed.
Ɣ Use the rotary switch to select and confirm the parameters
[Language], [Date], [Time] or [Summertime].
Ɣ Select and change the value to be changed within the
individual display using the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this ro tary switch settin g
can be seen in section 3.4 and in chapter 4.2.
12
FA ROTEX RoCon BF - 06/2013
3 x Operation
Changing the display settings
Ɣ Place the rotary switch in the "Configuration"position.
Î An overview is displayed.
Ɣ Select the "Setup" level with the rotary switch.
Î An overview is displayed.
Ɣ Use the rotary switch to select the parameters [LCD
Contrast], [LCD Brightness], [LCD Illum Time] or [RGB
Setup].
Ɣ Confirm the changes with a brief push of the rotary switch.
Ɣ Select and change the value to be changed within the
individual display using the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary swit ch setting
can be seen in chapter 4.9.
3.3Special functions
In the "Special Level" we can carry out various different func-
tions that are usually used by the heating expert.
The following special functions are possible:
– Emissions measurement (see section 3.3.1)
– Manual mode (see section 3.3.2).
– STB Test (see section 3.3.3)
– Fault display (see chapter 5)
More detailed explanations of these functions can be found in chapter4.10.
The call-up of special functions does not depend on the
setting on the rotary switch.
Ɣ Depress the exit button for at least 5 secs.
Î Menu "Special Level" is displayed.
Ɣ Select the programme to be started with the rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î The selected programme starts.
Ɣ Cancellation or jump back by:
– pushing the exit button again, or
– briefly actuating the rotary switch or
– selecting a different menu using the rotary switch.
3.3.1 Emissions measurement
Caution - danger of overheating with
underfloor heating!
In the event of a fault, or in hand mode, damage may
be caused to the screed, the structure of the floor and
the underfloor heating system by overheating.
Ɣ Before commissioning for the first time, set the
maximum permissible system temperature in the
maximum temperature limit in the Control
RoCon BF (parameter [Max T-Flow]).
During the emission measurement the flow temperature of the
Heat generators is limited to the value set in the parameter [Max
T-HS]. With additionally connected external heating circuits, the
Control RoCon BF attempts to keep the current flow temperature
in the heating circuit between 55 °C and 65 °C.
In order to cool or bring the Heat generator as quickly
as possible to temperature during emission measurement, we can impose a forced drop-off or a drop-off
block in the heating circuits using the Heat generator
(parameter [Forced Performance]). This parameter can
be used to set whether the heating circuit should react
to the drop-off demand or not.
Ɣ Depress the exit button for at least 5 secs.
Î Menu "Special Level" is displayed.
Ɣ Select the programme "Emission Measurement" with the
rotary switch.
Ɣ Confirm the changes with a brief push of the rotary switch.
Î The following load types are available for selection:
– Off: Emission measurement is switched off, any Control-
connected Heat generator that is switched on continues to
be regulated normally.
– Base Load: The Heat generator is switched on and oper-
ated at the minimum output of the Heat generators, irrespective of the set operating mode.
– Full Load: The Heat generator is switched on and oper-
ated at the maximum output of the Heat generators, irrespective of the set operating mode.
Ɣ Select the load type "Full Load" using the rotary switch, but
do not confirm it.
Î Display: "Full Load"
ÎThe burner is turned on for 30 min. and is regulated at
the stipulated maximum temperature.
ÎThe burner is turned on for 30 min. and is regulated at
maximum load.
ƔSelect the load type "Base Load" using the rotary switch,
but do not confirm it.
Î Display: "Base Load"
Î The modulating gas burner runs at minimum output for
30 mins.
Ɣ Cancellation or jump back by:
– Pushing the exit button or rotary switch again
– Selection of a different menu using the rotary switch and
confirmation.
FA ROTEX RoCon BF - 06/2013
13
3 x Operation
Emission Measurement
Off
Emission Measurement
Base Load
Emission Measurement
Full Load
Emission Measurement
Full Load
Special Level
Emission Measurement
Manual Operation
3.3.2 Manual Operation
The manual mode serves to regulate the Heat generator manually to a specific flow temperature. The manual mode should
only be used for diagnostic purposes.
With hydraulically controlled priority operation for the hot water
generation you must make sure that the flow temperature set in
manual mode is adequate to achieve the stored hot water set
temperature (parameter [Room Temp Reduced]).
During active manual mode the hot water is consistently regulated to the first set value parameter of hot water generation
([Room Temp Reduced]).
When the manual mode is ended, the Control RoCon BF auto-
matically switched to the operating mode "Standby".
Special Level
Emission Measurement
Manual Operation
Special Level
Emission Measurement
Manual Operation
STL Test
Fig. 3-6 Symbolic brief instruct ions for Emission Measurement
Manual Operation
Set
Current operating mode
Fig. 3-7 Symbolic brief instructions for Manual Operation
Actual
14
FA ROTEX RoCon BF - 06/2013
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.