Rosslare SA 61G, SA 61H Users Manual

SA-61
Wireless Smoke Detector
Installation Manual

1. Introduction

It is available in two frequencies:
The smoke sensor unit can easily be plugged into or detached from the wireless base unit (AS-60) for cleaning and maintenance purposes.
A mechanical key on the sensor is designed to avoid mismatching or incorrect installation of the sensor and base. The sensor chamber is engineered to sense smoke from a wide range of combustion sources. The chamber is well protected from insects and dust contamination.
A LED indicator on the sensor unit shows the operating status and Alarm mode, while an RF LED is located in the base unit and indicates RF transmissions, such as alarms and tamper.
The SA-61 smoke detector has a low profile, as well as a professional and trendy appearance.

2. Technical Specifications

2.1 Electrical Characteristics

Power Supply Voltage
Battery Life
Avg. Standby Current
Max. Alarm Current
Siren Output
Sensitivity
Frequency

2.2 Environmental Characteristics

Environment
Operating Temperature
Storage Temperature
Operating Humidity

2.3 Physical Characteristics

Weight
Dimensions (L x W x H)
CR123 3 V 1300 mAh
Three years with regular use
30 µA
75 mA
85 dB at 1 m (built-in)
2.5%/ ft nominal (0.5~4%/ft)
G (433.92 MHz), H (868.35 MHz)
Indoor
0°C to 35.8°C (32°F to 100°F)
-20°C to 70°C (-4°F to 158°F)
0 to 95% RH (non-condensing)
120 g (4.23 oz)
121.9 x 121.9 x 34 mm (4.8 x 4.8 x 1.34 in.)
433.92 MHz or 868.35 MHz.
September 2012
Figure 1: SA-61

2.4 Modes of Operation

Normal Mode
Alarm Mode
Low Battery Mode

2.5 Signaling and Events

Tamper Event
Signaling Type
Report Types
The indicated LED flashes once every 344 seconds (to save battery life) to show it is working.
The detector goes into Alarm mode if it detects smoke. In Alarm mode, the indicated LED and the RF LED quickly flashes and the Piezoelectric sounder is activated.
When the battery voltage is low, the detector beeps every 43 seconds.
When the sensor is disconnected from the base or the base unit from the ceiling.
Red LED on detector, red LED in base unit
Alarm, Tamper, Low Battery Alarm Report:
• Every 20 seconds during first 3 min
• Every 3 min from 3 min till 30 min
Alarm event is no longer sent after 30 min or
immediately upon Alarm Restore (When the am-
bient environment somke concetration is lower than
the alarm level for a zone)

3. Installation

3.1 Choosing a Mounting Location

A smoke detector should be installed according to NFPA (National Fire Protection Association) Standard 72. For complete coverage in residential units, smoke detectors should be installed in all rooms, halls, storage areas, and basements. At the least, one detector should be placed on each floor and in each sleeping area.
Install smoke detectors as close to the center of the ceiling as possible or at least 10 cm (4 inches) away from any wall or corner.
Do NOT locate smoke detectors at the top of peaked or gabled ceilings; the dead air space in these locations may prevent the unit from detecting smoke. Avoid areas with turbulent air flow such as near doors, fans or windows. Rapid air movement around the detector may prevent smoke from entering the unit and affected the accuracy.

3.2 Smoke Detector Limitations

Smoke detectors will not sense a fire if the smoke does not reach
the sensor.
Smoke detectors may not be heard. Be sure to locate the smoke
detector within hearing distance.
Smoke from a slow fire rises slowly and may not reach the smoke
detector until the fire gets bigger.
To keep your smoke detectors working properly, be sure to
maintain the unit according to manufacturer’s recommendations and UL and NFPA standards.
1

3.3 Disassembly

The unit arrives assembled, so you must disassemble the unit into its three pieces before you can mount it.
To disassemble:
1. Turn the sensor counter-clockwise to the “Loose” position as shown in Figure 2 and gently remove the sensor.
Figure 2: Loose and Lock Positions
2. Gently separate the top part of the base unit from the lower part.

3.4 Mounting the Base Unit

The AS-60 base unit provides different punch out options for different gang box standards for mounting to 3 1/2-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes (Figure 3).

3.5 Inserting the Battery

The battery compartment is designed to meet UL requirement. A lever has been inserted to avoid attaching the sensor unit without the battery being inserted.
To insert the battery:
1. Load the battery into the base compartment as shown in Figure 4.
Figure 4: Battery Installation

3.6 Assembly

Once you have mounted the base unit and inserted the battery, you are ready to close the unit.
To assemble the unit:
1. Replace the top part of the base unit with its bottom part that has been mounted by lining up the two lines as shown in Figure 5.
Figure 5: Base Cover Insertion
Figure 3: Punch Out Options for Various Gang Box Standards
To mount the base unit:
1. Mark two mounting points in the wall.
2. Drill into the marked points and insert wall plugs/gang box.
3. Screw and fix the base unit.
2. Attach the sensor unit onto the base unit as shown in Figure 6 and turn the sensor clockwise to the Lock position (Figure 2).
Figure 6: Sensor Insertion
2
Loading...
+ 2 hidden pages