Rosslare AS-36, SA-36H, SA-36G, SA-36W Installation Instructions Manual

AS-36/SA-36G/H/W
Installation Instructions Maximum Heat Detector
0706-0960267+00
1. Introduction
The AS-36 maximum h eat detector sounds an al arm whenever the unit temperature reaches 55±2ºC. The unit is supplementary to smoke detectors and should be placed only in areas wher e smoke detectors cannot be used. AS-36 is operated by a single 9V battery, which can sustain the unit’s operation for up to 1 year.
AS-36 has an 85-decibel horn, test button , and an alarm LED indicator. The AS-36 heat detector is ideal for kitchens, garages, cellars, boiler rooms, attics and other areas where there are normally high levels of fumes, smoke or dust which preclude the use of smoke detectors due to the risk of false alarms.
The detector can connect to Rosslare's security system panel, or to any standard wireless security system. To connect the AS-36 Maximum heat detector to a wired or wireless system, mount it on Rosslare's SA-13G (wireless; 433.92MHz), SA-13H (wireless, 868.35MHz), or SA-13W (wired) base.
NOTE: A fully mounted unit (AS-36 + SA-13G/H/W) is referred to as SA-36G/H (wireless) or SA-36W (wired).
NOTE:
The AS-36 maximum heat detector is not designed to serve as a substitute for a primary fire detection system.
Figure 1: AS-36 Unit
2. Technical Specifications
2.1 Electrical Characteristics
AS-36 Detector Current:
Maximum alarm: 150 mA
Standby: 10 µA
SA13G/H Base Current:
Transmitting: 16 mA
Standby: 16 µA
Transmitting distance: up to 200m in open
space
SA13W Base Current:
Operating: 7 mA
NO output: Standby: 10 mA
NC output: Standby: 21 mA
Operating: 23 mA
Battery: 1604A (9V Alkaline) Battery Life: 1 year Low Battery Detection:
Last 7 days of battery life
2.2 Environmental Characteristics
Use Environment: Indoor Operating Temperature: 0º–60ºC (32º–140º F) Operating Humidity:
2.3 Physical Characteristics
10% to 90% non-condensing
Sensitivity: Alarm temperature 55±2ºC Alarm Indication: LED and siren Indicators Siren Volume: 85dB at 3m (10ft) Dimensions: AS-36: 118.4 x 107 x 40 mm
4.66 x 4.21 x 1.57 inch SA-36G/H 126.5 x 124 x 63.7 mm
4.98 x 4.88 x 2.5 inch SA-36W: 121 x 112.6 x 58.5 mm
4.76 x 4.43 x 2.3 inch
Weight:
SA-36W: 176g (6.2 oz)
AS-36: 130g (4.59oz)
SA-36G/H: 291.3g (10.27 oz)
3. Installation
The SA-36 is a heat detector; it can be operated as a standalone unit or as an alarm system together with the SA-13 wireless or wired base.
3.1 Wiring the SA-36W
For wiring instillations follow the instructions below.
To set and wire the SA-36W:
1. set the alarm output setting to either Normally Open or Normally Closed using the select switch on the SA-13W.
2. Connect the power between the Security Alarm system and the SA-13W’s Vin and ground terminal blocks.
3. Connect the Tamper outputs to the Security Alarm system’s inputs
4. Connect the Alarm terminal blocks to the Security Alarm system, refe r to the installation manual of the alarm system you are connecting the detec to r to.
0706-0960267+00
Figure 2: Wiring Diagram
3.2 Mounting the Detector
Before mounting the AS-36 Heat Detector, make sure that your chosen mounting area is not in fro nt of any electrical wiring or pipe work.
To mount the unit:
1. Mark two mounting points in the wall according to the base size and holes.
2. Drill into the marke d p o ints and insert wall plugs.
3. Using screws, mount the base onto the wall.
4. Mount the AS-36 unit on the base (see Figure 3).
Note: Be careful not to over-tighten the screws.
Figure 3: Mounting AS-36 on the Base Unit NOTE:
4. Operating the Heat Detector
Do not paint or cover the detector.
4.1 General Use
During normal operation, the heat detector's LED indicator should flash once per 40 seconds.
When the unit detects heat (the temperatu re reaches 55±2ºC or more), it triggers its built-in sire n . I f the detector is connected to a wireless or wired security network, it sends an alert message to the host security pan el.
4.2 Testing the Detector
To test the heat de tector, press and hold the se lf-test button. A loud pulsating siren sounds and the LED indicator flashes
quickly, wh ile a signal is emitted to the host control panel (if part of a system).
4.3 Low battery
When the detector' s battery is low, the detector beeps once per 40 seconds. The heat detector continues oper ating with a low battery for at least 7 days.
Figure 4: Test button
AS-36 Sta ndalone
SA-36 G/H Wireless Base
SA-36W Wired Base
Loading...