
PS-C18
Power Supply
Installation Manual
1
1. Introduction
The PS-C18 power supply consists of a transformer and a PCP-18
PCBA.
230 VAC, 50 Hz power is input to the transformer and is converted to
24 VAC. The 24 VAC power goes from the transformer to the PC-P18
PCBA.
If there is no 230 VAC, 50 Hz input power, the battery backup can
provide 12 VDC input directly to the PC-P18 PCBA.
The PC-P18 PCBA outputs 13.8 VDC @ 5 A for use by another device.
In addition, a LED signal is output to indicate that the output 13.8 VDC
is normal and ready for the other device.
The total current of the power supply is limited to 5A.
Figure 1: PS-C18
2. Technical Specifications
2.1 4BElectrical Characteristics
Input
Input to transformer: 230 VAC, 50Hz
Converted input from transformer: 24 VAC
Output
13.8 VDC 5 A
Battery Backup
12 VDC
Built-in charger for sealed UL certified battery lead
acid or gel up to 7 AH.
Maximum charge current 1.2 A
Automatic switch over to stand-by battery when
AC fails
Caution: Risk of explosion, when battery
is replaced by a wrong battery
type
Visual indicator
DC output LED indicator on PCB indicates that the
output 13.8 VDC is normal and ready for the other
device
Additional Features
Short circuit and thermal overload protection,
includes battery leads
2.2 5BEnvironmental Characteristics
Operating Temperature
-10°C to 60°C (14°F to 140°F)
Operating Humidity
0 to 95% (non-condensing)
2.3 6BPhysical Characteristics
Weight
4.2 kg (9.26 lbs)
Dimensions (H x W x D)
225 x 230 x 76 mm
(8.85 x 9.05 x 0.30 in.)
3. Installation and Wiring
3.1 7BInstallation
Install the power supply in accordance with article 760 of the National
Electric Code NFPA 72 as well as applicable local codes.
Circuit breaker must be close to the power supply and must be
1. Mount the power supply.
2. Connect the AC power (230 VAC, 50 Hz) to the marked terminals,
“Phase” to [L] and “Neutral” to [N]. Use 18 AWG or larger for all
power connections (battery, DC output).
3. Connect the grounding to the ground terminal. Make sure to
secure the screw tightly.
4. Connect the ACU power input to the power terminal marked
“VOUT + and (-)”.
5. [Optional] Connect the battery terminal to the power terminal
marked “+VBAT”.
When the battery is not used, loss of AC results in the loss of
output voltage. When using a backup battery, it must be a UL
certified "lead acid" or "gel" type. (battery leads are included)
3.2 8BWiring
Wire the unit according to Figure 2.
Figure 2: Wiring
Use 18 AWG or larger for all power connections.
Ensure that the power-limited circuit is wired separately from the non-
power limited wiring (120/230 VAC, battery.)

2
4. Maintenance
For proper operation, test the unit at least once a year as described
below:
Output voltage test:
Check DC output for proper voltage level under normal load
conditions.
Battery test:
Check specified voltage, at both battery terminal and board
terminals marked “+VBAT and (-)” under normal load conditions.
Verify that the battery is fully charged and insure that there is no
break in the battery connection wires.
Maximum charging current under discharges is 1.2 A.
Expected battery life is five years. However, it is recomm ended
to change batteries within four years. Dispose of used batteries
according to manufacturer's instructions