Rosslare MD-W11N, MD-W11BP, MD-W11F Installation Manual

MD-W11
Wireless Access Control Door Interface
Installation Manual
MD-W11BP MD-W11F MD-W11N
Copyright © 2014 by Rosslare. All rights reserved.
This manual and the information contained herein are proprietary to ROSSLARE ENTERPRISES LIMITED and/or its related companies and/or subsidiaries’ (hereafter: "ROSSLARE"). Only ROSSLARE and its customers have the right to use the information.
No part of this manual may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of ROSSLARE.
ROSSLARE owns patents and patent applications, trademarks, copyrights, or other intellectual property rights covering the subject matter in this manual.
TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION MAY RESULT IN LEGAL PROCEEDINGS.
The furnishing of this manual to any party does not give that party or any third party any license to these patents, trademarks, copyrights or other intellectual property rights, except as expressly provided in any written agreement of ROSSLARE.
ROSSLARE reserves the right to revise and change this document at any time, without being obliged to announce such revisions or changes beforehand or after the fact.
Table of Contents
MD-W11 Installation Manual iii
Table of Contents
1. Introduction ................................................................ 8
1.1 Overview ................................................................................ 8
1.2 Features.................................................................................. 9
2. Technical Specifications ............................................ 10
2.1 Supported Card Transmission Formats .................................... 11
2.2 Supported Keypad Transmission Formats ................................ 11
2.3 Available Models ................................................................... 12
3. Installation and Wiring ............................................. 13
3.1 The Installation Kit ................................................................ 13
3.2 General Installation Requirements .......................................... 14
3.3 Installing the MD-W11N Unit ................................................. 14
3.4 Wiring the MD-W11N Unit .................................................... 15
3.5 Installing the MD-W11F Unit .................................................. 18
3.6 Wiring the MD-W11F Unit ..................................................... 19
3.7 Installing the MD-W11BP Battery Pack.................................... 20
3.8 Wiring the MD-W11BP Battery Pack ....................................... 20
3.9 Indications on the Near and Far Units ..................................... 20
3.10 Installer Recommendations .................................................... 21
4. Enrollment ................................................................. 22
4.1 Enrolling the Units ................................................................. 22
4.2 DIP Switches ......................................................................... 22
4.2.1 Near and Far Unit Modes .............................................................. 23
5. Operational Information .......................................... 26
A. Declaration of Conformity........................................ 27
Table of Contents
iv MD-W11 Installation Manual
B. Limited Warranty ...................................................... 28
List of Figures
MD-W11 Installation Manual v
List of Figures
Figure 1: MD-W11 Interface .............................................................................. 8
Figure 2: MD-W11 Back Cover ........................................................................ 14
Figure 3: Near Unit Wiring Diagram ................................................................. 15
Figure 4: Sample Wiring Detail ........................................................................ 17
Figure 5: Far Unit Wiring Diagram ................................................................... 19
Figure 6: LED Display Panel .............................................................................. 20
List of Tables
vi MD-W11 Installation Manual
List of Tables
Table 1: DIP Switch Settings ............................................................................ 22
Table 2: Unit Channels Setting ........................................................................ 23
Notice and Disclaimer
MD-W11 Installation Manual vii
Notice and Disclaimer
This manual’s sole purpose is to assist installers and/or users in the safe and efficient installation and usage of the system and/or product described herein.
B
EFORE ATTEMPTING TO INSTALL AND/OR USE THE SYSTEM, THE INSTALLER AND THE
USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY REQUIREMENTS AND OPERATING PROCEDURES
.
The system must not be used for purposes other than those for which it
was designed.
The use of the software associated with the system and/or product, if
applicable, is subject to the terms of the license provided as part of the purchase documents.
ROSSLARE exclusive warranty and liability is limited to the warranty and
liability statement provided in an appendix at the end of this document.
This manual describes the maximum configuration of the system with the
maximum number of functions, including future options. Therefore, not all functions described in this manual may be available in the specific system and/or product configuration you purchased.
Incorrect operation or installation, or failure of the user to effectively
maintain the system, relieves the manufacturer (and seller) from all or any responsibility for consequent noncompliance, damage, or injury.
The text, images and graphics contained in the manual are for the purpose
of illustration and reference only.
All data contained herein is subject to change without prior notice.
In no event shall manufacturer be liable for any special, direct, indirect,
incidental, consequential, exemplary or punitive damages (including, without limitation, any and all damages from business interruption, loss of profits or revenue, cost of capital or loss of use of any property or capital or injury).
All graphics in this manual are for reference only, some deviation between
the image(s) and the actual product may occur.
All wiring diagrams are intended for reference only, the photograph or
graphic of the PCB(s) are intended for clearer illustration and understanding of the product and may differ from the actual PCB(s).
Introduction
8 MD-W11 Installation Manual
1. Introduction
1.1 Overview
The MD-W11 Wireless Access Control Door Interface is a quick and inexpensive solution for connecting remote door devices, such as readers, locks, and Request-for-Exit (REX) buttons to an access control unit.
The MD-W11 consists of two units per door – one located near the controller (the Near Unit) and the other near the door (the Far Unit) (Figure 1).
Figure 1: MD-W11 Interface
Near Unit Far Unit Battery Pack
The Near Unit is connected to a Rosslare door controller (such as AC­215, AC-225, or AC-525). The Far Unit is connected to proximity card readers or keypads (such as AY-K12 and AY-Q64B).
When a card is read or a code is entered by keypad, the Far Unit transmits the information to the Near Unit. The Near Unit, attached to the controller, determines whether or not to open the door. The controller then sends the message to the Near Unit, which transmits it to the Far Unit, and if authorized, the door is opened.
Changes or modifications to this equipment not expressly approved by the party responsible for compliance (Rosslare) could void the user’s authority to operate the equipment.
Introduction
MD-W11 Installation Manual 9
1.2 Features
The MD-W11 Wireless Access Control Door Interface includes:
Bi-directional RF data communication Supports PIN codes and card formats, such as Wiegand 26-Bit,
Wiegand 32-Bit, and Wiegand 6-Bit Rosslare formats (see Section 2.1).
Lock and door relay commands
Tamper, door monitor, and REX messages between the controller
and the interface unit
Rolling code to increase security
Four different RF channels to prevent collisions Built-in charger for up to 12 VDC, 7 Ah backup battery on the Far
Unit
Transfers proximity card information and LED control, reader
tamper, lock relay commands, REX, and door monitor events between the coupled units.
Optional MD-W11BP battery pack housing with space for 12
VDC, 800 mAh, sealed lead-acid battery.
Suitable for indoor use. Available in 869 MHz (H) and 433.92 MHz (G) bands
The Near Unit is powered from the controller's power supply. The
Far Unit is powered by a local wall transformer. A built-in charger provides battery backup.
Technical Specifications
10 MD-W11 Installation Manual
2. Technical Specifications
Electrical Characteristics
Input Voltage
Far Unit: 12–24 AC, 15–24 VDC
Near Unit: 13.8 VDC from the controller's power supply or wall adapter
Battery Charger
12 V sealed Lead-Acid, up to 7 Ah (Far Unit)
Input Current
Standby: 70 mAh Max: 160 mA
Maximum Range: (with external
antenna)
Open field: 300 m (985 ft) Range depends on RF related environmental conditions.
Response Time
Up to 500 ms with Rosslare’s AC-215 controller and reader
Response time depends on RF link quality, number of doors used, and controller and reader response time.
Output Relays
Far Unit: One 5 A Form C relay
Near Unit: Two 1A Form C relays
Output Types
Far Unit: LED CTRL – open collector
Near Unit: STAM, SPV, LBAT, AC, TMP – open collector
Communications
Bi-directional RF, narrow band Fast anti-collision, rolling code protocol with data
protection Available in 4 bands (see Section
4.2)
Data Transfer
Reader formats (based on the card and keypad transmission formats listed below), lock commands, REX, door monitor, LED control and reader tamper inputs
Supervisory & Alerts
Full supervision over the remote unit. Alert outputs at the Near Unit for supervision failure, system tamper, reader tamper, low battery and power failure.
Technical Specifications
MD-W11 Installation Manual 11
Environmental Characteristics
Operating Environment
Indoor use
Operating Temperature Range
-10°C to 50°C (14°F to 122°F)
Operating Humidity Range
0 to 95% (non-condensing)
Dimensions
H x W x D
Near/Far Units: 13 x 8.7 x 3.2 cm (5.1 x 3.42 x 1.26 in.)
Battery Pack:
12.8 x 6.9 x 3.4 cm (5.04 x 2.72 x 1.34 in.)
Weight
Near/Far Units: 155 g (5.5 oz)
Battery Pack (with battery): 433 g (15.3 oz)
2.1 Supported Card Transmission Formats
Wiegand 26-Bit (default) Wiegand 26-Bit with Facility Code Output
Wiegand 32-Bit Wiegand 32-Bit Reverse Output
Wiegand 34-Bit Wiegand 40-Bit
2.2 Supported Keypad Transmission Formats
Single Key, Wiegand 6-Bit (Rosslare format, default) Single Key, Wiegand 6-Bit with Nibble and Parity bits Single Key, Wiegand 8-Bit, Nibble Complemented
4 Keys Binary, Wiegand 26-Bit 1 to 5 Keys, Wiegand 26-Bit
6 Keys BCD and Parity Bits, Wiegand 26-Bit
Technical Specifications
12 MD-W11 Installation Manual
2.3 Available Models
MD-W11NHR (869 MHz)
MD-W11FHR (869 MHz) MD-W11NGR (433 MHz)
MD-W11FGR (433 MHz) MD-W11BP
Installation and Wiring
MD-W11 Installation Manual 13
3. Installation and Wiring
The Near and Far Units of the MD-W11 are installed and wired as explained in this chapter.
3.1 The Installation Kit
The installation kit of the MD-W11 interface includes:
MD-W11N Near Unit
The Near Unit sends the controller the proximity card ID or keypad code as though it were a local reader. Following controller code/ID verification, the lock relay receives a command (transmitted to the Far Unit) to open the door.
MD-W11F Far Unit
The Far Unit is connected to a proximity card reader and/or keypad, and controls the door lock relay.
MD-W11BP Battery Pack
The battery pack is mounted only on the MD-W11 Far Unit side (see Section 3.7).
The MD-W11N and the MD-W11F are connected to the controller and the door components (lock, door monitor, reader). Both units are transceivers; the Near Unit receives the data transmitted from the reader and sends it to the controller. If authorized, the controller sends authorization to the Near Unit, which transmits authorization to the Far Unit. The Far Unit then opens the door.
The wireless access control door interface transfers the data between the controller input, the outputs, and the door components (such as lock, reader, door monitor, and exit button) transparent, as if the door components were connected directly to the controller.
Installation and Wiring
14 MD-W11 Installation Manual
3.2 General Installation Requirements
The installation kit includes:
One drilling template (label /sticker) One security spline key
One security hex screw Four mounting screws Four wall plugs
Fixed external antenna (G Model)
3.3 Installing the MD-W11N Unit
The Near Unit can be connected to a standard Rosslare controller, such as the AC-225.
To install the Near Unit:
1. Use the spline key to remove the case security screw from the back of the unit (Figure 2).
Figure 2: MD-W11 Back Cover
A
Installation and Wiring
MD-W11 Installation Manual 15
2. Use the drilling template to determine where to drill holes in the wall.
3. Use the hardware to mount the back plate on the wall.
We highly recommend using the bottom left mounting hole, as it is acts as a back tamper when a person attempts to dislodge the unit from the wall (see Figure 2 marked with A).
4. Wire the unit as instructed in Section 3.4.
3.4 Wiring the MD-W11N Unit
Wire the following terminals between the controller's input and output to the MD-W11N Near Unit, as shown in Figure 3:
Figure 3: Near Unit Wiring Diagram
Installation and Wiring
16 MD-W11 Installation Manual
Power supply connections (+12V and GND) STAM – System tamper
SPV – Supervision failure (Far Unit has supervision failure) LBAT – Low battery (Far Unit has low battery)
AC Fail – Far Unit has power failure D0 – Data 0 D1 – Data 1
LED – Reader LED control TMP – Far Reader tamper
LOCK – Connection for lock input Relay 1 REX (output) Relay 2-Door monitor (output)
System Tamper (STAM), Supervision Failure (SPV), Low Battery (LBAT), AC FAIL (AC) are outputs that can be connected to any input of AC-225. In AxTraxNG, this input should be configured accordingly (using Panel Links).
If either the far reader, the near reader, or both have been tampered with, the STAM status changes, and retains this status until both readers have been closed.
Installation and Wiring
MD-W11 Installation Manual 17
Figure 4: Sample Wiring Detail
Figure 4 shows sample input connections to any inputs, and is relevant to AC-215/225/525.
The relevant input can be configured to result in the required outcome, using AxTrax and Panel Links.
The connection between the REX Input and Rel
ay 1 is always COM+
N.O. or COM+N.C. so that only two lines connect to this pair.
The connection between the Door Monitor Input and Relay 2 is always COM+N.O. or COM+N.C. so that only two lines connect to this pair.
Installation and Wiring
18 MD-W11 Installation Manual
3.5 Installing the MD-W11F Unit
The Far Unit can be connected to a standard Rosslare reader, such as the AY-K12. The optional battery box can then be attached to the wall next to the Far Unit.
To install the Far Unit:
1. Attach the battery box to the wall with two screws.
2. Insert the wires from the reader and from the battery to the hole in the side of the Far Unit box.
3. Attach the side of the unit box to the wall with four screws.
4. Attach the wires to the PCB.
5. Cover both the battery and the Far Unit boxes.
6. Tighten the screws on the bottom of both boxes so that they remain closed.
7. Wire the unit as instructed in Section 3.6.
Installation and Wiring
MD-W11 Installation Manual 19
3.6 Wiring the MD-W11F Unit
Wire the following terminals between the controller's input and output to the Far Unit, as shown in Figure 5:
Figure 5: Far Unit Wiring Diagram
12–24 VAC or 15–24 VDC to the VIN+ and VIN-
Optional backup battery that connects to BAT+ and BAT- 12 V and GND power output for the reader Data 0 Wiegand (D0) (input)
Data 1 Wiegand (D1) (input) LED – Reader LED control (output)
Installation and Wiring
20 MD-W11 Installation Manual
TMP – Input for receiving reader tamper alert Normally Open (NO)/Normally Closed (NC) and COM of 5A Form
C relay to the door’s lock
REX – Optional input for REX
DM – Optional input for door monitor contact
3.7 Installing the MD-W11BP Battery Pack
Only install the MD-W11BP battery pack in the MD-W11 Far Unit.
To install the battery pack:
1. Use the spline key to remove the security screw from the bottom of the case and open the unit.
2. Use the drilling template to locate where to drill holes in the wall.
3. Use the hardware provided to mount the back plate on the wall.
4. Wire the battery pack as described in Section 3.8.
The battery pack comes with a battery installed. The size of the case is compatible with Rosslare’s BT-05 12 VDC/800 mA SLA rechargeable battery.
3.8 Wiring the MD-W11BP Battery Pack
In the Far Unit only, connect the Red (+) and Black (GND) to MDW11F Bat (+) and Bat (-) (Figure 5)
3.9 Indications on the Near and Far Units
Figure 6 shows the six LEDs (that indicate the unit’s current status) on the display panel of each unit.
Figure 6: LED Display Panel
PWR – Power ON Tx – Sending transmission
Installation and Wiring
MD-W11 Installation Manual 21
Rx – Receiving transmission ENRL – Enrolling
TRBL – Trouble SYS – System OK
3.10 Installer Recommendations
To install the MD-W11 units most efficiently, place the Near and Far Units facing each other, rather than placing them at a 90º angle to one another.
Both transmission and reception are improved if the Near and Far Units have the same polarity.
In addition:
Do not place any of the MD-W11 units next to an air conditioner,
heater, blower, or an engine that generates a magnetic field.
Do not place any unit next to an electronic device that transmits
RF or next to an access control reader or device.
Assure that metal fixtures and furnishings (such as doors or
closets) are not in line with the Near and Far Units.
Assure that the Near and Far Units are at the same approximate
height, preferably above head level.
Enrollment
22 MD-W11 Installation Manual
4. Enrollment
Prevent loss of transmission data by enrolling each pair of Near and Far Units.
4.1 Enrolling the Units
One unit cannot recognize the unique ID of another unit unless both units are enrolled so that they can work together.
4.2 DIP Switches
The DIP switches on both units are set as shown in Table 1.
Table 1: DIP Switch Settings
DIP Switches 1–4
Not used Must be in the ON position
DIP Switch 5
OFF or ON Used to set the channel
DIP Switch 6
OFF or ON Used to set the channel
DIP Switch 7
Enrolling Normal mode – ON
Enrolling mode – OFF
DIP Switch 8
Not used Must be in the ON position
Only handle the DIP switches when the power is off.
Up is ON
Down is OFF
1 2 3 4 5 6 7
8
Enrollment
MD-W11 Installation Manual 23
Set the unit channels with DIP Switches 5 and 6 as shown in Table 2.
Table 2: Unit Channels Setting
DIP Switch 5 DIP Switch 6 Channel
H Model
Channel G Model
ON ON 869.50 MHz 433.60 MHz
ON OFF 868.45 MHz 433.40 MHz
OFF ON 868.30 MHz 433.20 MHz
OFF OFF 868.15 MHz 433.00 MHz
DIP Switches 5 and 6 must be synchronized in the Far and Near Units.
Choose the same channel for both units.
If the LEDs flash, the DIP switches have not been set properly. In that case, first re-set the DIP switches and then power the unit off and on.
Only handle the DIP switches when the power is OFF.
4.2.1 Near and Far Unit Modes
The current unit mode is indicated by a steady or blinking LED. The three modes (Normal, Enrolling, and Trouble) of the Near and Far Units are described in detail below.
4.2.1.1 Normal Mode
The Normal mode is “idle,” and the LEDs behave as follows:
PWR – Power ON (steady)
Tx – Sending transmission (blinking when sending) Rx – Receiving transmission (blinking when receiving)
SYS – System OK (blinking)
If SYS LED is not blinking, it indicates a serious error.
Enrollment
24 MD-W11 Installation Manual
A blinking TRBL LED indicates that there is trouble. Refer to Section
4.2.1.3 for a list of possible problems.
4.2.1.2 Enrolling Mode
Enrolling mode is used for retention of transmitted data.
To set the Enrolling mode:
1. Set DIP Switch 7 on both units (Near and Far) to Off.
2. Power up both units.
3. PWR LED is steady and ENRL LED is blinking.
4. The Far Unit sends its ID to the Near Unit and the TX LED blinks when transmitting.
5. The Near Unit receives an ID and sends it to the Far Unit.
6. The Far Unit receives the Near Unit’s ID and ENRL LED is lit steadily.
7. Set DIP Switch 7 on both units (Near and Far) to ON (normal mode).
4.2.1.3 Trouble Mode
The MD-W11 Far module detects the following troubles:
Reader tamper Far module tamper
Low battery AC Fail
RF device failure/problem Incorrect DIP switch setting
Enrollment
MD-W11 Installation Manual 25
Following detection of any of the said problems or failures, the Far module behaves as shown in the following table:
Problem Activity
Reader Tamper
Sends trouble and problem to the Near module
Far Module Tamper
Sends trouble and problem to the Near module
Low Battery
Sends trouble and problem to the Near module (Trouble LED turns on)
AC Fail
Sends trouble and problem to the Near module (Trouble LED turns on)
RF Device Failure/Problem
Trouble LED flashes at a fast rate (after power on)
Incorrect DIP Switch Setting
All LEDs flash at a slow rate (after power on)
The MD-W11 Near module detects following troubles:
Near module tamper
Supervision fail RF device failure/problem Incorrect DIP Switch setting
Following detection of any of the said problems or failures, the Near module behaves as shown in the following table:
Problem Name Activity
Near Module Tamper
Activates Near Unit’s tamper output
Supervision Failure
Activates Near Unit’s supervision output (Trouble LED turns on)
RF Device Failure/Problem
Trouble LED flashes at a fast rate (after power on)
Incorrect DIP Switch Setting
All LEDs flash at a slow rate (after power on)
Operational Information
26 MD-W11 Installation Manual
5. Operational Information
The units should be no more than 300 meters from one another in an open field.
The Far Unit has one DIP switch with eight buttons, the default for all of which is On. The end user only uses Button #7 to enroll the Near and Far Units. When the user turns Button #7 to Off, the Near Unit recognizes the Far Unit so the units work with each other.
The Far Unit can also be attached to a REX button, a door monitor to indicate whether a door is open or closed, and a tamper to check whether the cover was opened. These indications are transmitted from the Far Unit to the Near Unit, which then sends them to the controller.
The proximity reader reads card information and sends it from the Far Unit to the Near Unit and to the controller to determine which door to open. If applicable, the controller sends authorization to open the door to the Near Unit, which transmits the authorization to the Far Unit, and the door is opened.
Declaration of Conformity
MD-W11 Installation Manual 27
A. Declaration of Conformity
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
This device may not cause harmful interference.
This device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Limited Warranty
28 MD-W11 Installation Manual
B. Limited Warranty
The full ROSSLARE Limited Warranty Statement is available on the ROSSLARE website at www.rosslaresecurity.com
. Rosslare considers any use of this product as agreement to the Warranty Terms even if you do not review them.
MD-W11
Asia Pacific, Middle East, Africa
Rosslare Enterprises Ltd. Kowloon Bay, Hong Kong Tel: +852-2795-5630 Fax: +852-2795-1508 support.apac@rosslaresecurity.com
United States and Canada
Rosslare Security Products, Inc. Southlake, TX, USA Toll Free: +1-866-632-1101 Local: +1-817-305-0006 Fax: +1-817-305-0069 support.na@rosslaresecurity.com
Europe
Rosslare Israel Ltd. Rosh HaAyin, Israel Tel: +972-3-938-6838 Fax: +972-3-938-6830 support.eu@rosslaresecurity.com
Latin America
Rosslare Latin America Buenos Aires, Argentina Tel: +54-11-4001-3104 support.la@rosslaresecurity.com
China
Rosslare Electronics (Shenzhen) Ltd. Shenzhen, China Tel: +86-755-8610 6842 Fax: +86-755-8610 6101 support.cn@rosslaresecurity.com
India
Rosslare Electronics India Pvt Ltd. Tel/Fax: +91-20-40147830 Mobile: +91-9975768824 sales.in@rosslaresecurity.com
0706-0960234+01
Loading...