Rosslare AY-H12C, AY-M12C, AY-L12C, AY-Q12C, AY-K12C Installation Manual

Page 1
AY-x12C Series
Rosslare PROX Readers
Installation Manual
1
1. Introduction
The AY-x12C is a series of RFID proximity card readers to be installed for use with access control systems.
Figure 1: AY-x12C Series
2. Technical Specifications
2.1 Electrical Characteristics
Specification AY-M12C AY-H12C AY-L12C AY-K12C AY-Q12C
Power Supply Type
Linear (recommended)
Operating Voltage Range
5–16 VDC
Absolute Maximum (non-operating)
18 VDC
Current @ 12V
Standby: 60 mA
Maximum: 120 mA
Maximum Read Range*
10 cm (4 in.) 8 cm
(3.2 in.)
4 cm
(1.6 in.)
All Control Inputs
Dry Contact, N.O.
Tamper Output
Open collector, active low, max. sink current 16 mA
Maximum Cable Distance to Controller
18 AWG – 150 m (500 ft)
20 AWG – 90 m (300 ft)
RF Modulation
ASK, 125 kHz
* Measured using a Rosslare proximity card or equivalent. Range also depends on
installation environment, reader voltage, and proximity to metal.
2.2 Environmental Characteristics
Specification AY-M12C AY-H12C AY-L12C AY-K12C AY-Q12C
Operating Temp. Range
-31°C to 63°C (-25°F to 145°F)
Operating Humidity Range
0 to 95% (non-condensing)
2.3 Physical Characteristics
Model Dimensions
(H x W x D)
Weight
AY-M12C
89 x 89 x 15 mm
(3.5 x 3.5 x 0.6 in.)
109 g
(3.9 oz.)
AY-H12C
110 x 75 x 15 mm
(4.3 x 3.0 x 0.6 in.)
100 g
(3.5 oz)
AY-L12C
145 x 43 x 20 mm
(5.7 x 1.7 x 0.8 in.)
116 g
(4.1 oz)
AY-K12C
80 x 40 x 12.8 mm (3.2 x 1.6 x 0.5 in.)
70.5 g
(2.5 oz)
AY-Q12C
120 x 76 x 20 mm
(4.7 x 3.0 x 0.8 in.)
480 g
(17.0 oz)
3. Installation
Card readers are to be used with control panels whose power supply is UL Listed Class 2 or equivalent.
3.1 Installation Kit
The installation kit consists of the following items to be used during the installation procedure:
One self-adhesive mounting label template
Two pan head mounting screws and screw anchors One pin Torx key tool One pin Torx security screw
3.2 Mounting the AY-x12C Reader
Before mounting, you should determine the best location for the reader.
To mount the reader:
1. Peel off the back of the self-adhesive mounting label template and place it at the required mounting location.
2. Using the template as a guide, drill two holes (hole size and position is indicated on the mounting template) for mounting the reader onto the surface.
3. Insert a screw anchor into each hole.
4. Drill a 10-mm (7/16”) hole for the cable. If mounting on metal, place a grommet or electrical tape around the edge of the hole.
5. Wire the reader to the host as described in Section 4. A linear type power supply is recommended.
6. Refer to Figure 2 for correct use of mounting screws.
Figure 2: Correct Use of Mounting Screws
AY-M12C
AY-H12C AY-L12C AY-K12C AY-Q12C
Page 2
2
4. Wiring
The AY-x12C is supplied with a 10-conductor 18” pigtail.
To connect the reader to the controller:
1. Prepare the reader cable by cutting its jacket back about 3 cm (1¼") and strip the insulation from the wires about 1.2 cm (½").
2. Prepare the controller cable by cutting its jacket back 3 cm (1¼") and strip the insulation from the wires about 1.2 cm (½").
3. Splice the reader’s pigtail wires to the corresponding controller wires (as indicated in Table 1) and cover each joint with insulating tape.
4. If the tamper output is being utilized, connect the purple wire to the correct input on the controller.
5. Trim and cover all unused conductors.
When using a separate power supply for the reader, this supply and that of the controller must have a common ground.
The reader’s cable shield wire should be preferably attached to an earth ground, or a signal ground connection at the panel, or power supply end of the cable. This configuration is best for shielding the reader cable from external interference.
Table 1: Wiring
Wire Color Function
Red 5–16 VDC
Black Ground
Green Data 0 / Data
White Data 1 / Clock
Orange Green LED
Brown Red LED
Purple Tamper
Yellow Buzzer
Blue Hold
Grey Data Output Mode
5. Operation Instructions
5.1 Testing
Once the reader is wired to a power supply and to the controller, you should test the reader.
To test the reader:
1. Power up the reader.
Upon power up, the reader flashes and beeps once during Self­Test. The LED then turns red indicating the readers has entered Standby mode.
2. Apply a PROX card to the reader. The reader flashes and beeps once indicating the card has been
read successfully.
5.2 Data Output Mode Line
The Data Output Mode Line is used to select whether the reader outputs in Wiegand 26-Bit or Clock & Data format.
When the Mode Line is open, the reader outputs Wiegand 26-Bit. When the Mode Line is pulled to ground, the reader outputs Clock & Data.
5.3 LED Control
The reader has a bi-color (green/red) LED and two LED control lines, one for green LED control (orange wire) and the other for the red LED control (brown wire).
When both LED control lines are open, the reader self manages the LED behavior. In Standby mode, the LED remains red. When a card is presented, the LED flashes green and then returns to red.
When a LED control line is pulled to ground, the LED changes to the related LED color and the self-management is disabled. If both LED control lines are pulled to ground, the LED is amber colored.
5.4 Buzzer Control
When the Buzzer control line (yellow wire) is open, the reader self manages the buzzer behavior and beeps when a card is read successfully. When the Buzzer control line is pulled to ground, the buzzer sounds.
5.5 Hold Control
When the Hold control line (blue wire) is open, the reader functions normally. When the Hold line is pulled to ground, the hold function is activated. When active and a card is read, no card data is sent on the Wiegand lines; however, the reader continues to buffer the last card ID read and sends that ID data when the Hold line is released.
Page 3
3
Declaration of Conformity
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions:
This device may not cause harmful interference.
This device must accept any interference received, including
interference that may cause undesired operation.
Changes or modifications not expressly approved by the party
responsible for compliance could void the user's authority to operate the equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Limited Warranty
The full ROSSLARE Limited Warranty Statement is available in the Quick Links section on the ROSSLARE website at www.rosslaresecurity.com
.
Rosslare considers any use of this product as agreement to the Warranty Terms even if you do not review them.
Contact Information
United States and Canada
Rosslare Security Products, Inc. Southlake, TX, USA Toll Free: +1-866-632-1101 Local: +1-817-305-0006 Fax: +1-817-305-0069 support.na@rosslaresecurity.com
Europe
Rosslare Israel Ltd. Rosh HaAyin, Israel Tel: +972-3-938-6838 Fax: +972-3-938-6830 support.eu@rosslaresecurity.com
Latin America
Rosslare Latin America Buenos Aires, Argentina Tel: +54-11-4001-3104 support.la@rosslaresecurity.com
China
Rosslare Electronics (Shenzhen) Ltd. Shenzhen, China Tel: +86-755-8610-6842 Fax: +86-755-8610-6101 support.cn@rosslaresecurity.com
Asia Pacific, Middle East, Africa
Rosslare Enterprises Ltd. Kowloon Bay, Hong Kong Tel: +852-2795-5630 Fax: +852-2795-1508 support.apac@rosslaresecurity.com
India
Rosslare Electronics India Pvt Ltd. Tel/Fax: +91-20-40147830 Mobile: +91-9975768824 sales.in@rosslaresecurity.com
www.rosslaresecurity.com
0706-0960608+00
Loading...