This manual and the information contained herein are proprietary to ROSSLARE
ENTERPRISES LIMITED and/or its related companies and/or subsidiaries’
(hereafter: "ROSSLARE"). Only ROSSLARE and its customers have the right to
use the information.
No part of this manual may be re-produced or transmitted in any form or by any
means, electronic or mechanical, for any purpose, without the express written
permission of ROSSLARE.
ROSSLARE owns patents and patent applications, trademarks, copyrights, or
other intellectual property rights covering the subject matter in this manual.
TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN
THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS
AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND
TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION
MAY RESULT IN LEGAL PROCEEDINGS.
The furnishing of this manual to any party does not give that party or any third
party any license to these patents, trademarks, copyrights or other intellectual
property rights, except as expressly provided in any written agreement of
ROSSLARE.
ROSSLARE reserves the right to revise and change this document at any time,
without being obliged to announce such revisions or changes beforehand or
after the fact.
AYC-x6355 (Rev. A) Installation and User Manual vii
Introduction
Notice and Disclaimer
This manual’s sole purpose is to assist installers and/or users in the safe and
efficient installation and usage of the system and/or product, and/or software
described herein.
B
EFORE ATTEMPTING TO INSTALL AND/OR USE THE SYSTEM, THE INSTALLER AND THE
USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY
REQUIREMENTS AND OPERATING PROCEDURES
The system must not be used for purposes other than those for which it
was designed.
The use of the software associated with the system and/or product, if
applicable, is subject to the terms of the license provided as part of the
purchase documents.
ROSSLARE exclusive warranty and liability is limited to the warranty and
liability statement provided in an appendix at the end of this document.
This manual describes the maximum configuration of the system with the
maximum number of functions, including future options. Therefore, not all
functions described in this manual may be available in the specific system
and/or product configuration you purchased.
Incorrect operation or installation, or failure of the user to effectively
maintain the system, relieves the manufacturer (and seller) from all or any
responsibility for consequent noncompliance, damage, or injury.
The text, images and graphics contained in the manual are for the purpose
of illustration and reference only.
All data contained herein subject to change without prior notice.
In no event shall manufacturer be liable for any special, direct, indirect,
incidental, consequential, exemplary or punitive damages (including,
without limitation, any and all damages from business interruption, loss of
profits or revenue, cost of capital or loss of use of any property or capital or
injury).
All graphics in this manual are for reference only, some deviation between
the image(s) and the actual product may occur.
All wiring diagrams are intended for reference only, the photograph or
graphic of the PCB(s) are intended for clearer illustration and
understanding of the product and may differ from the actual PCB(s).
.
viii AYC-x6355 (Rev. A) Installation and User Manual
Introduction
1. Introduction
The CSN SELECT AYC-x6355 is a series of multi-credential technology
contactless smart card readers with keypad for use in access control
system solutions and includes Rosslare’s convertible technology.
CSN SELECT readers have the capability to read the Card Serial
Number (CSN) from many smart card RFID Standards
implementations. The following list shows the credential technologies
for which we have confirmed compatibility:
This list is continuously updated, for the latest compatibility list
contact your sales representative.
The standard readers output the Wiegand CSN data in Wiegand
26-Bit format. Other Wiegand formats are available upon request.
With Rosslare’s convertible technology, the unit automatically
determines whether to function as a reader or as a controller. If the
unit is connected to a standard access control unit, then it functions
as a reader. If the unit is connected to Rosslare's secured intelligent
power supply such as the PS-A25T, PS-C25T or PS-C25TU, it functions
as a secured controller.
As controllers, the units accept up to 500 users, and allow entry via a
personal identification number (PIN) and/or by presenting a proximity
card. The PIN code length for the controller has several options. The
PIN code length can be a set number of 4, 5, or 6 digits or it can be a
4-8 digits option.
For information on how the unit functions as a reader, see Chapter 6.
For information on how the unit functions as a controller, see
AYC-x6355 (Rev. A) Installation and User Manual 9
Introduction
Chapter 7.
1.1 Installation Kit
The installation kit consists of the following items to be used during
the installation procedure:
The following equipment is required to complete your installation:
1.2.1 Function as a Reader
Compatible host controller (not supplied)
1.2.2 Function as a Controller
Secured intelligent power supply (such as the PS-A25T, PS-C25T
or PS-C25TU)
The controller connects to the following:
Electric lock strike mechanism or a magnetic lock device,
which implements fail safe (power to lock) or fail secure
(power to open) functions.
REX button – Normally open type, switch is closed when
pressed.
Door monitor switch
Rosslare accessories can be found on www.rosslaresecurity.com
.
10 AYC-x6355 (Rev. A) Installation and User Manual
Technical Specifications
2. Technical Specifications
Electrical Characteristics
Power Supply Type
Operating Voltage Range
Current @ 12 V
Read Range*
Green LED Control**
Red LED Control**
Buzzer Control**
Tamper Output**
Maximum Cable Distance
to Controller
Environmental Characteristics
Operating Temp. Range
Operating Humidity
Range
Outdoor Usage
* Measured using a Rosslare MIFARE Classic EV1 (ISO Card). Read range with
other credential technologies may vary. Range also depends on electrical
environment and proximity to metal.
** Control Lines are factory programmable and can be custom configured upon
request.
Regulated
8 to 16 VDC
AYC-H/M6355: Standby: 120 mA, max: 160 mA
AYC-Q6355: Standby: 145 mA, max: 200 mA
AYC-H/M6355: 9 cm (3.5 in.)
AYC-Q6355: 5 cm (2.5 in.)
Dry Contact, N.O.
Dry Contact, N.O.
Dry Contact, N.O.
Open collector, active low, max. sink current
16 mA
Wiegand: 150 m (500 ft) with 18-AWG cable
OSDP (RS-485): 1,200 m (4,000 ft) with 2x2 18-
AWG twisted shielded cable
-35°C to 66°C (-31°F to 150°F)
0 to 95% (non-condensing)
Weather-resistant, UV-resistant, epoxy-potted,
suitable for indoor and outdoor use
AYC-x6355 (Rev. A) Installation and User Manual 11
Technical Specifications
Physical Characteristics
Dimensions
(H x W x D)
Weight
AYC-H6355: 110.7 × 75.0 × 18.2 mm
(4.4 x 3.0 x 0.7 in.)
AYC-M6355: 89.5 × 88.9 × 18.3 mm
(3.5 x 3.5 x 0.7 in.)
AYC-Q6355: 120.0 × 76.0 × 21.5 mm
(4.7 x 3.0 x 0.9 in.)
AYC-H6355: 185 g (6.5 oz)
AYC-M6355: 169 g (5.9 oz)
AYC-Q6355: 430 g (15.2 oz)
12 AYC-x6355 (Rev. A) Installation and User Manual
Mounting
To mount the units:
3. Mounting
Before mounting, you should determine the best location for the
reader.
1. Peel off the back of the self-adhesive mounting label template
and place it at the required mounting location.
2. Using the template as a guide, drill two holes (sizes indicated on
the template) used for mounting the back plate onto the surface.
3. Insert a suitable wall plug into each screw hole.
4. Drill a 10-mm (7/16”) hole for the cable. If mounting on metal,
place a grommet or electrical tape around the edge of the hole.
5. Wire the reader as described in Chapter 4. A linear type power
supply is recommended.
6. Remove the reader's snap-off front cover to reveal the two screw
holes (see Figure 1).
Figure 1: Removing the Top Cover
The location of the screws varies depending on the model
number of the reader.
AYC-x6355 (Rev. A) Installation and User Manual 13
Mounting
7. Align the two holes of the reader with those drilled in the wall
and firmly attach the reader to the wall with two screws, whose
size is indicated on the template.
8. Relocate the front cover onto the reader.
The reader can also be moun ted using strong epoxy glue. After
application, the reader should be firmly held in place until the
glue dries
14 AYC-x6355 (Rev. A) Installation and User Manual
Wiring Instructions
To connect the unit as a reader to an access control unit:
4. Wiring Instructions
An AYC-x6355 unit is supplied with a 10-conductor 22” (56-cm)
pigtail.
4.1 Wiring the Unit as a Reader
If you connect the unit to a standard access control unit, it
automatically functions as a reader.
1. Prepare the reader cable by cutting its jacket back about 3 cm
(1¼”) and strip the insulation from the wires about 1.3 cm (½").
2. Prepare the controller cable by cutting its jacket back about 3 cm
(1¼") and strip the insulation from the wires about 1.3 cm (½").
3. Splice the reader’s pigtail wires to the corresponding controller
wires (as indicated in Table 1) and cover each joint with insulating
tape.
Table 1: Wiring the Unit as a Reader to a Control Panel
Wire Color Output
Red Power
Black Ground
Green Data 0 / Data / C2
White Data 1 / Clock / C1
Orange Green LED control
Brown Red LED control
Purple Tamper Output
Yellow Buzzer control
Blue RS-485 - A / OSDP*
Gray RS-485 - B / OSDP*
* RS-485 is used for firmware update.
AYC-x6355 (Rev. A) Installation and User Manual 15
Wiring Instructions
To connect the unit as a controller:
4. Trim and cover all unused conductors.
• The individual wires from the reader are color coded according the
Wiegand standard.
• When using a separate power supply for the reader, this supply and
that of the controller must have a common ground.
• The reader’s cable shield wire should be preferably attached to an
earth ground, or a signal ground connection at the panel, or the
power supply end of the cable. This configuration is best for shielding
the reader cable from external interference.
4.2 Wiring the Unit as a Controller
If you connect the unit to a Rosslare PS-x25 secured power supply, it
automatically functions as a controller.
1. Prepare the reader cable by cutting its jacket back about 3 cm
(1¼”) and strip the insulation from the wires about 1.3 cm (½").
2. Prepare the PS-x25 secured power supply’s cable by cutting its
jacket back about 3 cm (1¼") and strip the insulation from the
wires about 1.3 cm (½").
3. Splice the controller pigtail wires to the corresponding PS-x25
secured power supply’s wires (as indicated in Table 2) and cover
each joint with insulating tape.
Table 2: Wiring the Unit as a Controller
Controller Color Functionalit y Note
12 VDC Red +DC Input Wired to the PS-x25
Shield/ Ground Black Ground Wired to the PS-x25
C 1 White Communication Wired to the PS-x25
C 2 Green Communication Wired to the PS-x25
AUX. IN Yellow Auxiliary Input Wired to input
4. Trim and cover all unused conductors.
16 AYC-x6355 (Rev. A) Installation and User Manual
Wiring Instructions
To connect the unit to the desired power supply option, refer to the
following wiring diagrams.
Figure 2 shows the wiring for the Controller Application using a dual
relay secured intelligent power supply.
Figure 2: Controller Application Wiring Diagram
This wiring diagram is for reference only. Please wire according
to actual PS- x25 samples.
AYC-x6355 (Rev. A) Installation and User Manual 17
Wiring Instructions
Figure 3 shows the auxiliary output connection using the internal
power.
Figure 3: Auxiliary Output Connection with Internal Power
Figure 4 shows the auxiliary output connection using external power.
Figure 4: Auxiliary Output Connection with Exter nal Power
18 AYC-x6355 (Rev. A) Installation and User Manual
OSDP Operation
5. OSDP Operation
• In OSDP mode, all control lines (Inputs/Outputs) are disabled.
• In OSDP mode, if a connection is not established or lost with the
controller, the LED flashes orange continuously.
CSN SELECT readers that support OSDP operation are compatible
with all reader-related OSDP commands. The reader address is set
using DIP switches on the back of the reader.
Release the screw on the back of the reader to remove the door to
access the DIP switches (Figure 5).
Figure 5: DIP Switch Compartment
AYC-x6355 (Rev. A) Installation and User Manual 19
OSDP Operation
Figure 6 shows the DIP switch settings, which are also described
below.
Figure 6: DIP Switch Settings
DIP Switch 1
This switch is used to select the reader output (Wiegand or OSDP):
Off = Wiegand
On = OSDP
DIP Switch 2
This switch is reserved for future use.
DIP Switch 3
This switch is reserved for future use.
DIP Switches 4 to 8
These switches set the address of the reader for OSDP protocol.
DIP Switch 4 is MSB and DIP Switch 8 is LSB. The address is the DIP
switch state +1.
Examples:
All the DIP switches in Off position, address = 1
All the DIP switches in On position, address = 32
20 AYC-x6355 (Rev. A) Installation and User Manual
Reader Functionality
Red
Green
6. Reader Functionality
Upon power on, the unit flashes red, then green, and then orange,
each for 1 second and a beep is heard for each color. The unit
searches for the presence of Rosslare's secured intelligent power
supply. If a secured intelligent power supply is not detected, the unit
is automatically configured as a reader.
6.1 Transmit Mode
The default mode of the reader is Transmit mode. In Transmit mode,
the unit is ready to receive data from a presented proximity card or an
entered PIN code.
When the reader is in Transmit mode, the left LED
is red and the right LED is off.
When a proximity card is presented or a keypad
entry is being transmitted, the left LED flashes
green.
Keypad data can be sent via one of eight different Keypad
Transmission Formats (see Section 6.2.3).
Proximity cards presented to the reader are sent in either various
Wiegand formats or Clock & Data format (see Section 6.2.4).
6.2 Programming as a Reader
Programming is done solely via the unit's keypad driven Programming
Menu System. During the manufacturing process, certain codes and
settings are pre-programmed. These settings are called the default
factory settings.
Table 3 shows the names of all the reader menus.
Default factory settings are marked by a "*" sign.
AYC-x6355 (Rev. A) Installation and User Manual 21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.