Ross Controls 3-2 VALVES SERIES DM2 D User Manual

BULLETIN 505
BULLETIN 505
2
®
2
DM
DM
3/2 Double Valves
3/2 Double Valves
with Dynamic Monitoring &
Dynamic Memory
Kupplung/Bremse
Embreagem/Freio
®
Series D
Series D
クラッチ/ブレーキ
Iaktk@ xfrjks/kd
• Manufacturers of Premium Pneumatic Controls since 1921 •
DM

Table of Contents

Series D Double Valves
General Information
Page 3 - 4
Ordering Information
Valve Dimensions
Overview of DM2® Series D
Double Valve
Flow Information
Operating Instructions
Repair Kits
Accessories
Cautions/Warranty
Page 5
Page 6 - 7
Page 8 - 9
Page 10 - 11
Page 12
Page 13
Page 14
Page 15
The Leader in Double Valve Design
ROSS has long been in the forefront of double valve research and development.
For over 60 years ROSS has been respond­ing to the needs of press manufacturers and users by progressively improving double valve technology. Internal flow patterns of double valves developed by ROSS have included series flow, parallel flow, combined series-parallel tandem flow, and combined series-parallel Crossflow
Monitoring devices have also been offered in a variety of designs to satisfy differing requirements. Traditionally, in order to achieve complete monitoring capability, it has been necessary to add devices or components to the valve or to the control system.
2 © 2010, ROSS CONTROLS. All Rights Reserved.
TM
.
The DM monitor and the main valve components into two identical piston-poppet assemblies. Two piston-poppet assemblies provide a redundant 3/2 normally closed air flow pattern and the patented internal design provides dynamic monitoring as well as complete memory.
During valve operation air pressure acting on changing combinations of assembly surfaces cause the assemblies to move to the required position. Force balances in the valve assure positive shifting forces during normal operation as well as a positive force to hold the assemblies in a locked-out position.
Series D valve combines the
DM2® Series D Double Valves
The ROSS DM2® Series D double valves provide significant features in response to the changing demands of the mechanical press industry and its associated standards and regulations regarding the control of pneumatically controlled clutch and brake applications. The consensus requirements of the regulations and good practices require that, in case of a failure within the valve, the clutch and brake mechanisms be quickly exhausted, a monitor takes action to prevent further operation, and a method to alert personnel is incorporated. These features also make the valve suitable for use in other Category 3 & 4 safety-related applications.
A ROSS DM
Series D double valve has two valve elements independently controlled by two solenoid pilots. The two valve elements share common inlet, outlet, and exhaust ports. When the pilot valves are simultaneously energized, the valve elements operate so that the valve functions as a 3/2 normally closed valve.
If one of the valve elements does not open or close synchronously with the other, the valve goes into a faulted condition, exhausts downstream air and keeps residual outlet pressure to less than 1% of inlet supply. This is an important safety characteristic of
the ROSS DM
Series D design.
DM2® Monitoring:
The DM intermediate, lockout position) distinguished by CrossflowTM passages with poppet and spool valving on the main valve stems. This arrangement provides the valve’s outstanding flow characteristics and an integrated monitoring capability with total memory. The valve provides dynamic monitoring and dynamic memory.
is a patented 3/2 normally closed valve (with an
Valve element redundancy provides an additional safety factor, as the likelihood of a malfunction in both valve elements in the same cycle is considered extremely remote.
valves also have an internal monitor that is integrated
DM into the valve elements. Should the valve operate abnormally, the monitor will lock-out the valve and prevent further operation until corrective action is taken.
IMPORTANT NOTE:
Standards, regulations, and good practice all require that mechanical power presses or other hazardous machines using a pneumatically-controlled clutch and brake mechanism be equipped with a double valve with a self-contained monitoring device and/or an external monitoring system, which inhibits further operation of the valve and machine in the event of a failure within the valve. Of course, a double valve is just one of the components in a press control system, and all other elements of the system should be planned with safety as a primary consideration.
Dynamic Monitoring means that all monitoring components change state on every valve cycle. Should the valve elements cycle asynchronously, the valve will exhaust downstream air and lock-out, prohibiting further operation.
Dynamic Memory within a monitoring system indicates that when a valve lock-out occurs, the valve will retain the fault information regardless of air or electrical changes. The DM
system can only be reset by a defined operation/procedure, and will not self-reset (turning the valve off and on) or reset when inlet air supply is removed and re-applied. Such automatic resetting would conceal potential hazards from the operator.
Installation Example
DM
Series D Double Valve
(Status indicator – optional)
Clutch and brake
combination
Lubricator
Volume
L-O-X
www.rosscontrols.com 3
Pressure gauge
®
- Valve
Filter and
water separator
Pressure regulator
DM
Series D
Self Monitored - Clutch/Brake Control
Size 4
Double Valves with Total Dynamic Monitoring & Complete Memory
For Size 2 Certifications
Approval Pending
Size 8
Size 12
Size 2
Valve Sizes: DM2® Series D double valves are available in 5 sizes, providing a
broad range of flow capabilities to meet your needs. For convenience, valves are designated by the nominal sizes 2, 4, 8, 12, and 30 with outlet ports ranging from 1/4” to 2”.
Simplified Schematic
Size 2, 4, 8, 12 and 30
Dynamic Monitoring With Complete Memory: Memory, monitoring, and air
flow control functions are simply integrated into two identical valve elements. Valves lock-out due to asynchronous movement of valve elements during actuation or de-actuation, resulting in a residual outlet pressure of less than 1% of supply. Overt action is required for reset – cannot be reset by removing and re-applying supply pressure. Reset can only be accomplished by remote air signal, optional electrical solenoid reset signal, or optional manual reset.
Basic 3/2 Normally Closed Valve Function: Dirt tolerant, wear compensating
poppet design for quick response and high flow capacity. Teflon back-up rings on pistons to enhance valve endurance – operates with or without inline lubrication.
Status Indicator (Optional): Includes a pressure switch with both normally
open and normally closed contacts to provide status feedback to the press control system indicating whether the valve is in the lockout or ready-to-run condition. The Status Indicator can be ordered installed or purchased separately and added to any DM2® base.
Silencers: All models include high flow, clog resistant silencers.
Mounting: Base mounted – with BSPP or NPT pipe threads. Inlet and outlet
ports on both sides provide for flexible piping (plugs for unused ports included). Captive valve-to-base mounting screws.
Size 12 and 30
Intermediate Pilots: Increases pilot air flow for fast valve response, making it
possible to use the same size solenoids as valve sizes 2, 4 & 8, thereby reducing electrical power requirements for these larger valves.
Size 30
4 © 2010, ROSS CONTROLS.
All Rights Reserved.
DM2® Series D Double Valves
HOW TO ORDER
(Choose your options (in red) to configure your valve model number.)
DM2D D A 4 2 A 1 1
PRODUCT
THREAD
BSPP ............................................. D
NPT ............................................... N
N/A (no base) ................................ X
REVISION LEVEL
BASIC SIZE
2......................................................2
4......................................................4
8......................................................5
12....................................................6
30....................................................8
BASE PORT SIZE Size 2
1/4 inlet – 1/4 outlet ........................0
3/8 inlet – 3/8 outlet ........................1
Size 4
1/2 inlet – 1/2 outlet ........................2
1/2 inlet – 3/4 outlet ........................3
Size 8
3/4 inlet – 3/4 outlet ........................4
1 inlet – 1 outlet ..............................5
Size 12
1inlet – 1outlet ................................6
1inlet – 1½ outlet ............................7
Size 30
1½ inlet – 2 outlet ...........................8
Valve only (less base) ................. X
Valve Weight: Valve and base assembly with status indicator and solenoid reset.
Size 2: 5.0 lb (2.3 kg). Size 4: 6.0 lb (2.8 kg). Size 8: 9.1 lb (4.2 kg). Size 12: 15.5 lb (7.1 kg). Size 30: 32.6 lb (14.8 kg).
STATUS INDICATOR
1......................................... YES
X ...........................................N O
RESET TYPE
1..................................REMOTE
2.............................. SOLENOID
4.................................. MANUAL
VOLTAGE
A ............................. 24 volts DC
B ........... 110 volts AC, 50/60 Hz
C** ........ 220 volts AC, 50/60 Hz
** 220 VAC not available in the U.S. (OSHA regulations limit press control voltage to no more than 120 volts AC).
BASE MODEL NUMBERS and
BASE SPECIFIC INFORMATION
Valve
Port Size Base Status Weight
Size Inlet Outlet Model Number*
2 1/4 1/4 1872C91 No 1.7 (0.8) 2 1/4 1/4 1873C91 Yes 2.1 (1.0) 2 3/8 3/8 1874C91 No 1.7 (0.8) 2 3/8 3/8 1875C91 Yes 2.1 (1.0)
4 1/2 1/2 1697C91 No 1.7 (0.8) 4 1/2 1/2 1698C91 Yes 2.3 (1.1) 4 1/2 3/4 1699C91 No 1.7 (0.8) 4 1/2 3/4 1700C91 Yes 2.3 (1.1) 8 3/4 3/4 1701C91 No 3.6 (1.6) 8 3/4 3/4 1702C91 Yes 4.2 (1.9) 8 1 1 1703C91 No 3.6 (1.6) 8 1 1 1704C91 Yes 4.2 (1.9) 12 1 1 1705C91 No 6.2 (2.8) 12 1 1 1706C91 Yes 6.8 (3.1) 12 1 1½ 1707C91 No 6.2 (2.8) 12 1 1½ 1708C91 Yes 6.8 (3.1) 30 1½ 2 1709C91 No 12.0 (5.4) 30 1½ 2 1710C91 Yes 12.6 (5.7)
*NPT port threads. For BSPP threads add a “D“ prefix to the model number, e.g., D1872C91.
Indicator
lb (kg)
www.rosscontrols.com 5
DM2® Series D Double Valves
SIZE 2
CV :
1 to 2: 2.17 2 to 3: 3.66
SIZE 4
10.63 (270.0) With Status Indicator & Solenoid Reset
0.64 (16.2)
4.79 (121.6)
1.37 (34.9)
1.19 (30.2)
0.82 (20.9)
9.99 (253.8) With Status Indicator
4.50 (114.3)
4.00 (101.6)
2.99
(75.9)
2.04
(51.9)
7.73
(196.4)
0.25 (6.4)
DIMENSIONS – inches (mm)
(Base mounting hole pattern)
(Base mounting hole pattern)
(Based in overall hole dimnsions at left.)
View X
Valve envelope
(Based in overall hole dimnsions at left.)
0.22 (5.6) (4 places)
4.00 (101.6)
2.99
(75.9)
4.00 (101.6)
2.04
(51.9)
0.64 (16.3) with Solenoid Reset
View X
Valve envelope
0.25 (6.4)
:
C
V
1 to 2: 2.80 2 to 3: 6.70
SIZE 8
C
:
V
1 to 2: 4.63 2 to 3: 12.55
6 © 2010, ROSS CONTROLS.
All Rights Reserved.
(Base mounting hole pattern)
View X
Valve envelope
(Based in overall hole dimnsions at left.)
DM2® Series D Double Valves
DIMENSIONS – inches (mm)
SIZE 12
CV :
1 to 2: 8.86 2 to 3: 20.78
SIZE 30
with Pressure
11.27 (286.26)
12.61
(320.23)
Switch
(Base mounting hole pattern)
(Base mounting hole pattern)
(Based in overall hole dimnsions at left.)
View X
Valve envelope
(Based in overall hole dimnsions at left.)
View X
Valve envelope
C
:
V
1 to 2: 20.22 2 to 3: 53.68
STANDARD SPECIFICATIONS: For DM2® Series D double valves. Pilot Solenoids: According to VDE 0580. Enclosure rating
according to DIN 40050, IEC 60529 IP65. Two solenoids, rated for continuous duty (
additional solenoid on optional reset).
Standard Voltages: 110 volts, 50/60 Hz; 220** volts, 50/60 Hz; 24 volts DC. For other voltages, consult ROSS.
** 220 volts AC not available in the U.S. (OSHA regulations limit press control voltage to no more than 120 volts AC. Specify voltage and frequency on order.
Power Consumption (each solenoid):
Size 2, 4, 12, 30:
For primary and reset solenoids:
6.0 watts on DC; 15.8 VA inrush and 10.4 VA holding on AC.
Size 8:
Primary solenoids: 15 watts on DC; 36 VA inrush and 24.6 VA holding on AC.
Reset solenoid:
6.0 watts on DC; 15.8 VA inrush and 10.4 VA holding on AC.
Electrical connection:
Size 2, 4, 8, 12, 30: DIN 43650, Form A. Order connectors separately.
15.48
(393.14)
with Pressure
Switch
14.25 (361.98)
Ambient Temperature: 15° to 120°F (-10° to 50°C). Media Temperature: 40° to 175°F (4° to 80°C). Flow Media: Filtered, lubricated or unlubricated (mineral oils
according to DIN 51519, viscosity classes 32-46); 5-micron recommended.
Inlet Pressure:
Size 2: 45 to 150 psig (3.1 to 10.3 bar). Size 4, 8, 12, 30: 30 to 120 psig (2.1 to 8.3 bar).
Reset Pressure: For remote air reset option – must be equal to inlet pressure.
Manual Pressure: Encapsulated, push button actuation. Pressure Switch (Status Indicator) Rating: Contacts - 5 amps
at 250 volts AC, or 5 amps at 30 volts DC. Monitoring: Dynamically, cyclically, internally during each actuating
and de-actuating movement. Monitoring function has memory and requires an overt act to reset unit after lockout.
Mounting orientation: Preferably horizontally (valve on top of base) or vertically (with pilot solenoids on top).
IMPORTANT NOTE: Please read carefully and thoroughly all of the CAUTIONS on the inside back cover.
www.rosscontrols.com 7
Overview of DM
EXH
U
S
TTT
N
EXH
U
S
TTT
N
O
U
TLE
T
EXHAUST
OUTLET
INLET
AB
EXH
U
S
TTT
N
O
U
TLE
T
Series D Double Valve Function
Valve de-actuated:
The flow of inlet air pressure into the crossover passages
AB
is restricted by the size of the passage between the stem and the valve body opening. Flow is
A
EXHAUST
sufficient to quickly pressurize pilot supply/timing chambers A
OUTLET
and B. The inlet poppets prevent air flow from crossover passages into the outlet chamber. Air pres-
INLET
sure acting on the inlet poppets and return pistons securely hold the valve elements in the closed position. (Air passages shown out of position and reset adapter
Valve ready-to-run
omitted for clarity.)
Valve actuated:
Energizing the pilot valves
AB
simultaneously applies pres­sure to both pistons, forcing the internal parts to move to their actuated (open) position, where
A
EXHAUST
OUTLET
OUTLET
inlet air flow to crossover pas­sages is fully open, inlet poppets are fully open and exhaust pop­pets are fully closed. The outlet is then quickly pressurized, and
INLET
pressure in the inlet, crossovers, outlet, and timing chambers are quickly equalized.
De-energizing the pilots quickly
Valve actuated
causes the valve elements to return to the ready-to-run position.
Valve loked-out:
Whenever the valve elements operate in a sufficiently asynchro­nous manner, either on actuation
AB
or de-actuation, the valve will move to a locked-out position. In the locked-out position, one crossover and its related timing chamber will be exhausted, and
A
EXHAUST
OUTLET
the other crossover and its related timing chamber will be fully pres­surized. The valve element (side B) that is partially actuated has
INLET
pilot air available to fully actuate it, but no air pressure on the return piston to fully de-actuate the valve element. Air pressure
Valve locked out
in the crossover acts on the dif­ferential of side B stem diameters creating a latching force.
Side A is in a fully closed position, and has no pilot air available to actuate, but has full pressure on the inlet poppet and return piston to hold the element in the fully closed position.
Inlet air flow on side A into its crossover is restricted, and flows through the open inlet poppet on side B, through the outlet into the exhaust port, and from the exhaust port to atmosphere. Residual pressure in the outlet is less than 1% of inlet pressure. The return springs are limited in travel, and can only return the valve elements to the intermediate (locked-out) position. Sufficient air pressure acting on the return pistons is needed to return the valve elements to a fully closed position.
Resetting the valve:
The valve will remain in the locked­out position, even if the inlet air supply is removed and re-applied. A remote reset signal (air or electric), or a manual push button actuation must be applied to reset the valve. Reset is accomplished by mo­mentarily pressurizing the reset port. Actuation of the reset piston physically pushes the main valve el­ements to their closed position. Inlet air fully pressurizes the crossovers and holds the inlet poppets on seat. Actuation of the reset piston opens the reset poppet, thereby, immedi-
Valve being reset
ately exhausting pilot supply air, thus, preventing valve operation during reset. (Reset adapter added to illustration.)
De-actuation of reset pistons causes the reset poppets to close and pilot supply to fully pressurize. Reset air pressure can be applied by a remote 3/2 normally closed valve, or from an optional 3/2 normally closed solenoid, or a manual push button mounted
Status indicator (optional)
in normal ready-to-run position
on the reset adapter.
Status indicator:
The status indicator pressure switch will actuate when the main valve is operating normally, and will de-actuate when the main valve is in the locked-out position
AB
or inlet pressure is removed. This device is not part of the valve lockout function, but, rather, only reports the status of the main valve.
Size 12 and 30 valves require relatively large pilots to actuate and de-actuate the main valve elements. In order to achieve extremely quick valve response for such large pilots, a 2-stage solenoid pilot system is incorporated into the design. This keeps the electrical current required to operate the pilots, to a minimum.
Size 12 & 30 pilots
8 © 2010, ROSS CONTROLS. All Rights Reserved.
EXHAUST
OUTLET
INLET
AB
Overview of DM
MAIN VALVE INTERNALS
Series D Double Valve
VALVE SCHEMATIC
Pilot Valve B
Piston
Exhaust chamber
Exhaust poppet
Crossover passages
Inlet chamber
Spring stop
Return spring
Pilot Valve A
Pilot supply/timing chamber A
Outlet chamber
Inlet poppet
Timing orifice
Flow restrictor
Reset poppet
Reset piston
www.rosscontrols.com 9

Valve Response Charts

The charts below represent the fill and exhaust times for each of the various sizes of DM2® Series D double valves. The “fill” times were measured while raising (filling) the pressure in a volume from 0 to 30, 60, & 80 psi (0 to 2.1, 4.1, & 5.5 bar) with a 90 psi (6.2 bar) inlet pressure. Conversely, the “exhaust” times were measured while lowering the pressure (exhausting) in a volume from 90 psi (6.2 bar) down to 90 to 60, 30, & 9 psi (4.1, 2.1, & 0.6 bar). Exhausting tests performed with silencer installed.
ExhaustingFilling
Size 2
0.25 (15.25) 0.5 (30.5) 0.75 (45.75) 1 (61)
Volume litres (cubic inches)
Volume litres (cubic inches)
0.25 (15.25) 0.5 (30.5) 0.75 (45.75) 1 (61)
Volume litres (cubic inches)
Size 4
Volume litres (cubic inches)
Size 8
Volume litres (cubic inches)
10 © 2010, ROSS CONTROLS. All Rights Reserved.
Volume litres (cubic inches)
Valve Response Charts
Size 12
ExhaustingFilling
Volume litres (cubic inches)
Size 30
Volume litres (cubic inches)
Application & Safety Category
1. General
The design features of the DM importance to users of double valves, such as on mechanical power press applications and other critical applications. This is because the DM
Series D is designed to meet the latest standards requiring “control reliable”, “Category-3 & -4”, or “dynamic monitoring” capability.
Both the monitoring and memory capabilities of the DM D valve are built in to the two piston-poppet stem assemblies. During normal operation, the assemblies move between two extreme positions. The 3rd, or intermediate, position occurs only during valve lock-out. The valve will lock out whenever there is sufficiently asynchronous motion between the two piston-poppet stem assemblies. No additional external or internal devices are needed to provide monitoring and memory. When the inlet air supply is removed and re-applied, the valve “remembers” whether it was in the ready-to-run or locked-out position prior to the removal of the air supply. Resetting the valve after it has gone in to “locked out” mode requires a momentary application of a reset signal. Should the reset signal be inadvertently left on (permanent signal), the valve will nevertheless go back in to lock­out mode.
2. Description
The three way valve with DM valve systems and two pilot valve systems. The air flow paths within the main valve systems are a proven combination of both SERIES and PARALLEL paths.
Both pilot valves and both main valve elements are interconnected with each other pneumatically. The main valve elements control the air via Crossflow™ air passages from inlet (port 1) to outlet (port 2).
Series D are of considerable
Series
capability consists of two main
Volume litres (cubic inches)
Volume litres (cubic inches)
Air flows first through a control element on one side of the valve to a control element on the second side of the valve, hence a series flow path. A parallel flow path starts on the second side of the valve and flows to the first side of the valve. A total of four elements control air flow from inlet to outlet. Air flow from outlet (port 2) to exhaust port (port 3) occurs in parallel via the exhaust poppets of both main valve elements.
In normal operation, pilot air supply is maintained as long as the two main elements operate in a synchronous manner. Whenever there is asynchronous motion, however, one of the pilot air supplies will be exhausted.
Sufficient pilot pressure is necessary to move the main valve elements to their fully actuated or de-actuated positions.
Lack of sufficient pilot pressure will prevent a valve element from fully shifting, resulting in the element stopping in the intermediate, locked-out position.
3. Application
Uncontrolled movements of cylinders or rotary drives risks harm to personnel and machinery. In order to reduce risk of injuries and damage, pneumatic controls should ideally meet strict safety requirements.
ROSS developed the DM
Series D double valves for controlling pneumatic clutch and brake mechanisms on mechanical power presses. However, the features and functions built in to the valve make it an ideal product to meet the specifications and standards associated with other critical applications. Because of its redundant design and the fact that the air is directed in a Crossflow™ and SERPAR
®
pattern, the DM
valve provides a
very high level of safety.
www.rosscontrols.com 11

Operating Instructions

Start-up
Before start-up, the installation must be checked thoroughly by persons trained and experienced in the operation of pneumatic equipment. Make sure that specifications given on the valve label (e.g. “max. operating pressure” and “electrical characteristics”) will be in accordance with the operating specifications of the press. When operating pressure is initially applied, it may be necessary to actuate the reset valve momentarily to move the main valve into the ready-to-run condition. Make sure that the inlet supply and the exhaust path are not restricted. Operating pressure must comply with the minimum and maximum limits.
Functional test
Test Result
1. Solenoid “A” actuated Valve moves into lock-out mode, slight leakage at exhaust port 3
2. Solenoid “B” actuated Valve moves into lock-out mode, slight leakage at exhaust port 3
3. Solenoids “A” and “B” actuated with Valve operates properly t < 0.1 s
4. Solenoids “A” and “B” actuated with Valve moves into lock-out mode, slight leakage at exhaust port 3 t > 0.1 s
5. After lock-out, permanent signal on Valve cannot be moved into ready-to-run mode reset valve - solenoids “A” and “B” or only “A” / only “B” actuated
Pressure test
After a valve lock-out, the double valve must be moved into the ready­to-run position by using the reset valve. In general, if the valve is in the lock-out mode and one or both of the solenoids are energized, the valve should not reset with application or application and removal of the reset signal. If the valve is in the ready-to-run mode after the reset solenoid valve has been actuated momentarily, the valve will function normally with application and removal of pilot solenoid signal. However, if the valve elements cycle asynchronously, the valve will go to the lock-out mode. Provided that both solenoids are de-energized, removal of reset signal will return the valve to the ready-to-run mode.
An additional test to perform:
• With the valve in the ready-to-run mode, exhaust and re-pressurize the inlet port. The valve should remain in the ready-to-run mode.
• With the valve in the lock-out mode, exhaust and re-pressurize the inlet port. The valve should remain in the lock-out mode.
Lock-outs
Any asynchronous movement between both piston elements for a time period > 0.1 s will result in a lock-out of the valve. This can be due to various causes, for instance:
• worn piston seals
• delayed response of the main valve elements due to dirt or varnished lubricant
• electrical signals to solenoid incomplete or unable to maintain proper voltage
• independent electrical signals to solenoids are not received concurrently
• delayed response of solenoid pilots or booster pilots due to damaged components, dirt, or varnished lubricant
• collection of excessive water or lubrication
Maintenance, Testing
Maintenance and testing procedures must follow the rules and regulations set by the respective national work-safety institutions. These procedures should only be performed by persons trained and experienced in the use of pneumatic equipment. Regulations generally require that maintenance and test procedures be performed at least once a year.
Repair
ROSS would be happy to service this specialized double valve for you at its factory repair center. Call your local ROSS office or distributor (in the U.S. 1-800-GET-ROSS or +1-706-356-3708 outside the U.S.) for information. If you service the valve yourself, be sure to turn off electrical power to the valve, shut off the air supply, exhaust the air in the system, and lock-out all power sources before beginning any disassembly operation. Customers maintaining their own valves should make sure that only original spare parts (as specified in the ROSS parts lists) are used.
Pneumatic equipment should be repaired only by persons trained and experienced in the repairing of such equipment, guided by these operating instructions. Information about valve repair and/ or the exchange of a valve must be written down in the machine operation documentation.
12 © 2010, ROSS CONTROLS. All Rights Reserved.

Repair Kits

Item Description Size 2 Size 4 Size 8 Size 12 Size 30
A Valve body service kit 2101K77 2102K77 2103K77 2104K77 2105K77 B* Complete primary solenoid pilot 1480C79 1403H79 1404H79 1391K79 1391K79 C* Complete reset solenoid pilot 859C79 851C79 851C79 851C79 851C79 D* Solenoid coil - pilots 306K33 306K33 360K33 306K33 306K33 E* Solenoid coil reset 306K33 306K33 306K33 306K33 306K33 F* Pilot booster service kit 2106K77 2106K77
* Specify solenoid voltage and Hz when ordering.
Kits for optional items Status indicator assembly kit – 2151H77 (not shown in the drawings): Replacement pressure switch – 1104A30
Sizes 2, 4 & 8
Sizes 12 & 30
DB
A
A
A
A
A
A
A
A
A
A
A A A A A A
D
B
F
A
A
A
A
Reset port - 1/8
(remote reset models)
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Reset port - 1/8
A A
A
A
C E
A
A
A
C
E
A
(remote reset models)
www.rosscontrols.com 13

Accessories

STATUS INDICATOR
The Status Indicator pressure switch actuates when the valve is in a ready-to­run condition and de-actuates when the valve is in a lock-out condition or when the inlet air pressure has been removed. Although the valves can be purchased with this option already installed, the Statu s In dic ato r can be purc hased separately by ordering part number:
670B94
RESET VALVES for MODELS with REMOTE RESET
On valve models with solenoid reset, a solenoid on the valve is actuated to perform the reset function. Models for remote reset, however, require a small reset valve and the installation of a 1/8 line from the reset valve to the reset port on the double valve. ROSS offers 3/2 normally closed valves with either manual or electric control that are suitable for this purpose. The valves, pictured below, are suggested.

Model Numbers of Reset Valves
Description Valve Model Numbers**
Pushbutton: Green 1223A1005
Direct Solenoid Control 1613B1020* for line mounting
Direct Solenoid Control W1413A1409* for base mounting (Base: 516B91)
**For BSPP threads, add a D prefix to the model number, e.g., D1223A1005. In the case of the W1413A1409, the prefix should be added to the base model instead of the valve, e.g., D516B91.
* Specify solenoid voltage and Hz when ordering.
ELECTRICAL CONNECTORS
Electrical connectors are required to connect the valve solenoids to the drop cords supplying electrical power.
Each connector can be positioned so that the cord exits upward or to the side. Cords of 6-mm to 10-mm
diameter can be used. Connectors with a light in a translucent housing are also available to serve as indicator lights. Order connectors by the part numbers given in the chart below.
WIRED CONNECTORS have a 2-meter (6-1/2 ft.) cord with three 18-gauge conductors. Cord exits upward, and is available in either 6-mm or 10-mm diameter.
Part Numbers of Form A Electrical Connectors
Connector Type Without Light With Light*
For use with dropcord (Cord not included)
Wired with 6-mm cord 721K77 720K77*
Wired with 10-mm cord 371K77 383K77*
For use with threaded conduit** 723K77 724K77* *Specify solenoid voltage when ordering.
**Accept 1/2-inch electrical conduit fitting.
CAUTION: Do not use electrical connectors with surge suppressors, as this may increase valve response time when de-actuating the solenoids.
937K87 936K87*
Pushbutton Models
Green button: 1223A1005
Direct Solenoid Model
for Line Mounting
1613B1020*
* Specify solenoid voltage and Hz when ordering.
14 © 2010, ROSS CONTROLS. All Rights Reserved.
Direct Solenoid Model
for Base Mounting
Valve: W1413A1409*
Sub-Base: 516B91
CAUTIONS
PRE-INSTALLATION or SERVICE
1. Before servicing a valve or other pneumatic component, be sure that all sources of energy are turned off, the entire pneumatic system is shut off and exhausted, and all power sources are locked out (ref: OSHA 1910.147, EN 1037).
2. All ROSS products, including service kits and parts, should be installed and/or serviced only by persons having training and experience with pneumatic equipment. Because any installation can be tampered with or need servicing after installation, persons responsible for the safety of others or the care of equipment must check every installation on a regular basis and perform all necessary maintenance.
3. All applicable instructions should be read and complied with before using any fluid power system in order to prevent harm to persons or equipment. In addition, overhauled or serviced valves must be functionally tested prior to installation and use.
4. Each ROSS product should be used within its specification limits. In addition, use only ROSS parts to repair ROSS products. Failure to follow these directions can adversely affect the performance of the product or result in the potential for human injury or damage to property.
FILTRATION and LUBRICATION
5. Dirt, scale, moisture, etc. are present in virtually every air system. Although some valves are more tolerant of these contaminants than others, best performance will be realized if a filter is installed to clean the air supply, thus preventing contaminants from interfering with the proper performance of the equipment. ROSS recommends a filter with a 5-micron rating for normal applications.
6. All standard ROSS filters and lubricators with polycarbonate plastic bowls are designed for compressed air applications only. Do not fail to use the metal bowl guard, where provided, to minimize danger from high pressure fragmentation in the event of bowl failure. Do not expose these products to certain fluids, such as alcohol or liquefied petroleum gas, as they can cause bowls to rupture, creating a combustible condition, hazardous leakage, and the potential for human injury or damage to property. Immediately replace a crazed, cracked, or deteriorated bowl. When bowl gets dirty, replace it or wipe it with a clean dry cloth.
7. Only use lubricants which are compatible with materials used in the valves and other components in the system. Normally, compatible lubricants are petroleum based oils with oxidation inhibitors, an aniline point between 180°F (82°C) and 220°F (104°C), and an ISO 32, or lighter, viscosity. Avoid oils with phosphate type additives which can harm polyurethane components, potentially leading to valve failure which risks human injury, and/or damage to property.
AVOID INTAKE/EXHAUST RESTRICTION
8. Do not restrict the air flow in the supply line. To do so could reduce the pressure of the supply air below the minimum requirements for the valve and thereby cause erratic action.
9. Do not restrict a valve’s exhaust port as this can adversely affect its operation. Exhaust silencers must be resistant to clogging and must have flow capacities at least as great as the exhaust capacities of the valves. Contamination of the silencer can result in reduced flow and increased back pressure.
ROSS expressly disclaims all warranties and responsibility for any unsatisfactory performance or injuries caused by the use of the wrong type, wrong size, or an inadequately maintained silencer installed with a ROSS product.
POWER PRESSES
10. Mechanical power presses and other potentially hazardous machinery using a pneumatically controlled clutch and brake mechanism must use a press control double valve with a monitoring device. A double valve without a self-contained monitoring device should be used only in conjunction with a control system which assures monitoring of the valve. All double valve installations involving hazardous applications should incorporate a monitoring system which inhibits further operation of the valve and machine in the event of a failure within the valve mechanism.
ENERGY ISOLATION/EMERGENCY STOP
®
11. Per specifications and regulations, ROSS L-O-X L-O-X® valves with EEZ-ON® operation are defined as energy
isolation devices, NOT AS EMERGENCY STOP DEVICES.
valves and
STANDARD WARRANTY
All products sold by ROSS CONTROLS are warranted for a one-year period [with the exception of all Filters, Regulators and Lubricators (“FRLs”) which are warranted for a period of seven years] from the date of purchase to be free of defects in material and workmanship. ROSS’ obligation under this warranty is limited to repair or replacement of the product or refund of the purchase price paid solely at the discretion of ROSS and provided such product is returned to ROSS freight prepaid and upon examination by ROSS is found to be defective. This warranty becomes void in the event that product has been subject to misuse, misapplication, improper maintenance, modification or tampering.
THE WARRANTY EXPRESSED ABOVE IS IN LIEU OF AND EXCLUSIVE OF ALL OTHER WARRANTIES AND ROSS EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ROSS MAKES NO WARRANTY WITH RESPECT TO ITS PRODUCTS MEETING THE PROVISIONS OF ANY GOVERNMENTAL OCCUPATIONAL SAFETY AND/OR HEALTH LAWS OR REGULATIONS. IN NO EVENT IS ROSS LIABLE TO PURCHASER, USER, THEIR EMPLOYEES OR OTHERS FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES WHICH MAY RESULT FROM A BREACH OF THE WARRANTY DESCRIBED ABOVE OR THE USE OR MISUSE OF THE PRODUCTS. NO STATEMENT OF ANY REPRESENTATIVE OR EMPLOYEE OF ROSS MAY EXTEND THE LIABILITY OF ROSS AS SET FORTH HEREIN.
www.rosscontrols.com 15
GLOBAL Reach with a LOCAL Touch
sm
ROSS CONTROLS
Troy, MI., U.S.A. Telephone: + 1-248-764-1800 Fax: + 1-248-764-1850 In the United States:
Customer Service: 1-800-GET ROSS (438-7677) Technical Service: 1-888-TEK-ROSS (835-7677)
www.rosscontrols.com
ROSS EUROPA GmbH
Langen, Germany Telephone: + 49-6103-7597-0 Fax: + 49-6103-74694 Email: info@rosseuropa.com www.rosseuropa.com
ROSS ASIA K.K.
Kanagawa, Japan Telephone: + 81-427-78-7251 Fax: + 81-427-78-7256 www.rossasia.co.jp
ROSS SOUTH AMERICA Ltda.
São Paulo, Brazil CEP 09725-020 Telephone: + 55-11-4335-2200 Fax: + 55-11-4335-3888 Email: vendas@ross-sulamerica.com.br
DIMAFLUID s.a.s.
Saint Ouen, France Telephone: + 33-01-49-45-65-65 Fax: + 33-01-49-45-65-30 Email: dimafluid@dimafluid.com www.dimafluid.com
ROSS CONTROLS (CHINA) Ltd.
Shanghai, China Telephone: + 86-21-6915-7951 Fax: + 86-21-6915-7960 www.rosscontrolschina.com
ROSS UK Ltd.
Birmingham, United Kingdom Telephone: + 44-121-559-4900 Fax: + 44-121-559-5309 Email: sales@rossuk.co.uk
Your local ROSS distributor is:
ROSS CONTROLS INDIA Pvt. Ltd.
Chennai, India Telephone: + 91-44-2624-9040 Fax: + 91-44-2625-8730 Email: rossindia@airtelbroadband.in
There are ROSS Distributors Throughout the World
To meet your requirements across the globe, ROSS distributors are located throughout the world. Through ROSS or its distributors, guidance is available for the selection of ROSS products, both for those using pneumatic components for the first time and those designing complex pneumatic systems.
This catalog presents an overview of the extensive ROSS product line. Other literature is available for engineering, maintenance, and service requirements. If you need products or specifications not shown here, please contact ROSS or your ROSS distributor. They will be happy to assist you in selecting the best product for your application.
Printed in the U.S.A. - Rev. 10/10 © 2010, ROSS CONTROLS. All Rights Reserved.
Form A10295
Supersedes all previous editions of 505 bulletins.
Loading...