Rosemount Analytical designs, manufactures and tests its products to meet many national and
international standards. Because these instruments are sophisticated technical products, you
MUST properly install, use, and maintain them to ensure they continue to operate within their
normal specifications. The following instructions MUST be adhered to and integrated into your
safety program when installing, using, and maintaining Rosemount Analytical products. Failure to
follow the proper instructions may cause any one of the following situations to occur: Loss of life;
personal injury; property damage; damage to this instrument; and warranty invalidation.
• Read all instructions prior to installing, operating, and servicing the product.
• If you do not understand any of the instructions, contact your Rosemount Analytical repre-
sentative for clarification.
• Follow all warnings, cautions, and instructions marked on and supplied with the product.
• Inform and educate your personnel in the proper installation, operation, and mainte-
nance of the product.
• Install your equipment as specified in the Installation Instructions of the appropriate In-
struction Manual and per applicable local and national codes. Connect all products to the
proper electrical and pressure sources.
• To ensure proper performance, use qualified personnel to install, operate, update, program,
and maintain the product.
• When replacement parts are required, ensure that qualified people use replacement parts
specified by Rosemount. Unauthorized parts and procedures can affect the product’s performance, place the safe operation of your process at risk, and VOID YOUR WARRANTY.
Look-alike substitutions may result in fire, electrical hazards, or improper operation.
• Ensure that all equipment doors are closed and protective covers are in place, except
when maintenance is being performed by qualified persons, to prevent electrical shock
and personal injury.
The information contained in this document is subject to change without notice.
Emerson Process Management
Rosemount Analytical Inc.
Process Analytic Division
1201 N. Main St.
Orrville, OH 44667-0901
T (330) 682-9010
F (330) 684-4434
e-mail: gas.csc@EmersonProcess.com
Table 5-2. Tabulation of Percent Input Signal vs. Percent Cam Rotation ............................ 5-10
iiRosemount Analytical Inc. A Division of Emerson Process Management
Hagan 2-1/2 x 5 and 4 x 5
The purpose of this manual is to provide information concerning the components, functions, installation and maintenance of the Hagan 2-1/2 x 5 and 4 x 5 Econo Torque Type
Floor Mounted Power Positioner.
Some sections may describe equipment not used in your configuration. The user should
become thoroughly familiar with the operation of this module before operating it. Read
this instruction manual completely.
The following definitions apply to WARNINGS, CAUTIONS, and NOTES found throughout this
publication.
Instruction Manual
IB-106-322N Original Issue
June 2000
PREFACE
DEFINITIONS
Highlights an operation or maintenance
procedure, practice, condition, statement, etc. If not strictly observed, could
result in injury, death, or long-term
health hazards of personnel.
Highlights an essential operating procedure,
condition, or statement.
: EARTH (GROUND) TERMINAL
: PROTECTIVE CONDUCTOR TERMINAL
: RISK OF ELECTRICAL SHOCK
: WARNING: REFER TO INSTRUCTION BULLETIN
NOTE TO USERS
Highlights an operation or maintenance
procedure, practice, condition, statement, etc. If not strictly observed, could
result in damage to or destruction of
equipment, or loss of effectiveness.
NOTE
The number in the lower right corner of each illustration in this publication is a manual illustration number. It is not a part number, and is not related to the illustration in any technical
manner.
Rosemount Analytical Inc. A Division of Emerson Process ManagementP-1
Instruction Manual
IB-106-322N Original Issue
June 2000
FOR THE WIRING AND INSTALLATION
The following safety instructions apply specifically to all EU member states. They should
be strictly adhered to in order to assure compliance with the Low Voltage Directive. NonEU states should also comply with the following unless superseded by local or National
Standards.
1. Adequate earth connections should be made to all earthing points, internal and external,
where provided.
2. After installation or troubleshooting, all safety covers and safety grounds must be replaced.
The integrity of all earth terminals must be maintained at all times.
3. Mains supply cords should comply with the requirements of IEC227 or IEC245.
Hagan 2-1/2 x 5 and 4 x 5
IMPORTANT
SAFETY INSTRUCTIONS
OF THIS APPARATUS
4. All wiring shall be suitable for use in an ambient temperature of greater than 75°C.
5. All cable glands used should be of such internal dimensions as to provide adequate cable
anchorage.
6. To ensure safe operation of this equipment, connection to the mains supply should only be
made through a circuit breaker which will disconnect all circuits carrying conductors during a
fault situation. The circuit breaker may also include a mechanically operated isolating switch.
If not, then another means of disconnecting the equipment from the supply must be provided
and clearly marked as such. Circuit breakers or switches must comply with a recognized
standard such as IEC947. All wiring must conform with any local standards.
7. Where equipment or covers are marked with the symbol to the right, hazard-
ous voltages are likely to be present beneath. These covers should only be
removed when power is removed from the equipment — and then only by
trained service personnel.
8. Where equipment or covers are marked with the symbol to the right, there is a
danger from hot surfaces beneath. These covers should only be removed by
trained service personnel when power is removed from the equipment. Certain surfaces may remain hot to the touch.
9. Where equipment or covers are marked with the symbol to the right, refer to
the Operator Manual for instructions.
10. All graphical symbols used in this product are from one or more of the follow-
ing standards: EN61010-1, IEC417, and ISO3864.
P-2Rosemount Analytical Inc. A Division of Emerson Process Management
Hagan 2-1/2 x 5 and 4 x 5
1
DESCRIPTION AND SPECIFICATIONS
Instruction Manual
IB-106-322N Original Issue
June 2000
SECTION 1
1-1 GENERAL
The Rosemount Model PP075T Econo Torque
Power Positioner (Figure 1-1) is a pneumatic,
double-acting, piston-type power positioner. The
unit converts a pneumatic input signal to a corresponding mechanical movement for positioning devices such as guide vanes, control valves,
and dampers.
As shown by the model number explanation in
paragraph 1-3, the positioner can be supplied
with either a 2-1/2 x 5 in. or 4 x 5 in. cylinder, as
required. Both cylinders are available with either
direct linear feedback or characterized cam
feedback depending upon system application. A
non-characterized unit can easily be converted
in the field to a characterized version with the
addition of a few bolt-on parts. Consult the factory for details.
Other options include an auto/manual transfer
valve, brake, limit switches, and heater/
thermostat.
Figure 1-1. Model PP075T Power Positioner
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-1
Instruction Manual
IB-106-322N Original Issue
June 2000
1-2 SPECIFICATIONS
Refer to Descriptive Bulletin 100-322.
Repeatability........................................................3% of Full Stroke
Sensitivity ............................................................6% of Full Stroke
Temperature Limit ...............................................40° to 170° F (4° to 77° C)
Full Stroke
Time (unloaded) .......................................2 seconds or less
Air Supply
Maximum ..................................................120 psi (827.4 kPa)
Unit Weight..........................................................60 lbs (27.2 g)
1-2 Description and SpecificationsRosemount Analytical Inc. A Division of Emerson Process Management
Hagan 2-1/2 x 5 and 4 x 5
1
1-3 MODEL NUMBER ENCODING
(6296A02, REV. 2)
The complete model number for the Model
PP075T Power Positioner is derived as follows:
Pneumatic Power Positioner
Control Torque Rating – ft-lbs
Econo Torque Floor Mounted
Positioner Type
1Noncharacterized
2Characterized
Positioner Size (diameter and stroke in inches)
12-1/2 x 5 Cylinder
24 x 5 Cylinder
Instruction Manual
IB-106-322N Original Issue
June 2000
MODEL PP075T
Signal Range
13-15 psig (20.7-103.4 kPa)
23-27 psig (20.7-186.2 kPa)
30-30 psig (0-116.9 kPa)
44-20 mA (I/P Transducer mounted and piped)
Manual and Break Operation
0None
1Manual Operator Only
2Manual Operator and Brake
3Manual Operator, Manual Lock, and Soft Air Lock
4Manual Operator, Manual Lock, and Fail Safe (fails to 100%)
Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-3
Instruction Manual
IB-106-322N Original Issue
June 2000
Hagan 2-1/2 x 5 and 4 x 5
1-4 Description and SpecificationsRosemount Analytical Inc. A Division of Emerson Process Management
Hagan 2-1/2 x 5 and 4 x 5
2
INSTALLATION
Instruction Manual
IB-106-322N Original Issue
June 2000
SECTION 2
2-1 MECHANICAL (Refer to Figure 2-1)
a. Location Selection
The power positioner should be located in a
dry area free of excessive shock and vibration with a continuous ambient temperature
meeting specifications listed in paragraph
1-2.
Sufficient clearance must be allowed for the
operating lever. Allow a 24 in. (610 mm)
minimum working space for front cover removal and maintenance.
b. Mount Power Positioner
The power positioner is designed to be
mounted in an upright position. The base of
the unit can be bolted to a horizontal surface using three 0.5 in. (12.7 mm) diameter
mounting bolts (not supplied).
c. Position Operating Lever, Output Indica-
tor, and Manual Brake (Optional)
The operating lever, output indicator, and
manual brake (optional) can be installed on
either side of the power positioner as desired. This allows the unit to be used for
either right-hand or left-hand external linkage operation.
As viewed from the right side of the power
positioner, the operating lever will move
clockwise with an increasing input signal
(not reversible). To change the motion of
the operating lever with respect to the input
signal, the operating lever must be positioned on the left side of the power positioner or rotated 180 degrees.
The operating lever has an 80 degree operating angle range and can be installed at
any position around the shaft.
To prevent interference between the brake
clamp and the operating lever, provision
has been made to allow the brake clamp to
be located on either the shaft vertical or
horizontal centerline on either side of the
stand (Figure 2-1).
d. Position Limit Switches (Optional)
Both SPDT switches can be mounted on
either side of the housing; however, they
must be located on the side opposite the
output/manual lever.
The switches can be set to trip at any
position.
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-1
Instruction Manual
IB-106-322N Original Issue
June 2000
Hagan 2-1/2 x 5 and 4 x 5
Figure 2-1. Model PP075T Power Positioner, Mounting Dimensions (263C469, Rev. 2)
2-2 InstallationRosemount Analytical Inc. A Division of Emerson Process Management
Hagan 2-1/2 x 5 and 4 x 5
2
Figure 2-2. Typical Air Supply Installation
e. Connect Air Supply Piping
The air supply piping should be installed
with a manual shutoff valve and air filter as
shown in Figure 2-2. The shutoff valve is
necessary to isolate the power positioner
during servicing. Copper tubing with 1/4
inch O.D. and 0.035 in. (0.89 mm) wall
thickness is recommended for piping to the
air supply connection. A sealant may be
used, if necessary, to prevent leakage at
the connections. Use sparingly.
Air filter P/N 771B920 must be used in order
to provide reliable, continuous service.
When connected properly, the air filter will
remove finely dispersed water or oil droplets
from the air supply, thereby preventing
sticking action in the pilot valve. Port 2 (inlet) is connected to the air supply; Port 1
(outlet) is connected to the power
positioner.
Prior to connecting the air supply line to the
power positioner, the supply line should be
purged as follows:
1. Purge air supply line before connecting
air filter.
IB-106-322N Original Issue
2. Connect air filter and open drain cock.
3. Slowly open the air shutoff valve and
allow moisture and foreign particles to
be blown out through the drain cock.
4. Close the drain cock and allow compressed air to blow through the open
end of the air supply piping until all dirt
and foreign particles are blown out.
5. Shut off the compressed air supply.
6. Connect the air supply line to the 0.2518 NPT female connection on the
power positioner, Figure 1-1.
Air supply pressures are as follows:
2-1/2 x 5 Unit4 x 5 Unit
Recommended100 psig
(689.5 kPa)
Maximum120 psig
(827.4 kPa)
Minimum45 psig
(310.3 kPa)
f. Connect Input Signal Piping
Prior to connecting the input signal piping to
the power positioner, blow out piping by operating the relay station at the control panel
and manually set up a signal pressure between 50 and 100 percent. Allow the air to
blow through the open end of the tubing.
Reduce the signal pressure to zero and
connect the signal piping to the 0.25-18
NPT female connection (Figure 2-1) on the
power positioner.
Instruction Manual
June 2000
40 psig
(275.8 kPa)
50 psig
(344.8 kPa)
30 psig
(206.9 kPa)
Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-3
Instruction Manual
IB-106-322N Original Issue
June 2000
Hagan 2-1/2 x 5 and 4 x 5
2-2 ELECTRICAL
a. Heater/Thermostat Wiring (Optional)
Heater power consumption is 150 watts
using a 120 Vac, 60 Hz power source.
Feed the heater power supply wiring
through the 0.5 in. (12.7 mm) conduit hole
located on the lower left-hand side of the
housing (Figure 1-1) and connect to the internal terminal board using the No. 5 connection screws (Figure 2-3).
b. Limit Switch Wiring (Optional)
Each switch has a 0.5-14 NPSM threaded
opening suitable for a 0.5 in. (12.7 mm)
flexible conduit fitting. A removable cover on
the switch permits access to No. 6 screw
terminals.
Electrical ratings for the limit switch SPDT
contacts are as follows:
15.00A at 125 Vac, 250 Vac, or 480 Vac
0.50A at 125 Vdc
0.25A at 250 Vdc
Figure 2-3. Heater/Thermostat Wiring Diagram
2-4 InstallationRosemount Analytical Inc. A Division of Emerson Process Management
Hagan 2-1/2 x 5 and 4 x 5
3
CALIBRATION
3-1 CALIBRATION PROCEDURES
The power positioner must be calibrated so that
the piston is at its lower limit when the control
signal is at minimum pressure and moves to its
upper limit when the signal is increased to
maximum pressure.
a. Characterized Units (Figure 3-1 and
Figure 3-2).
1. Using the manual/operating lever, position the piston against its lower stop.
2. Disconnect the external mechanical
linkage at the clevis (Figure 1-1).
Instruction Manual
IB-106-322N Original Issue
June 2000
SECTION 3
3. Slide the feedback cam (Figure 3-1)
mounted on a split hub clamp along the
output shaft until hub clamp bears
against the right side of the shaft ring
(Figure 3-2).
4. Rotate the cam until the roller on feedback lever (51, Figure 7-1) drops into
the cam pocket and just starts to rise
out of the pocket. At this point, there
will be a slight upward movement at
the swivel end of the feedback lever.
NOTE
The feedback spring should be under
some slight tension to ensure the cam
roller contacts the cam face.
5. At this position, tighten the hub on the
output shaft.
6. Apply minimum control signal to the
pilot valve. The piston should move to
the lowest position, against bottom
cylinder head. Check this zero adjust in
the following manner:
Figure 3-1. Characterized Unit, Top View
(a) Maintain minimum control signal
on the pilot valve.
(b) Loosen the set screw on the posi-
tioner arm.
Rosemount Analytical Inc. A Division of Emerson Process Management Calibration 3-1
Figure 3-2. Characterized Unit, Front View
Instruction Manual
IB-106-322N Original Issue
June 2000
Hagan 2-1/2 x 5 and 4 x 5
(c) Move the positioner arm up until
the piston moves to the bottom of
the cylinder.
(d) Move the positioner arm down until
the piston begins to move upward.
(e) Move the positioner arm down until
the piston just returns to lowest
position.
(f) Lock this setting by tightening the
set screw until the positioner arm
binds to the piston rod.
7. With the piston at the bottom of the
cylinder, place a mark on either the
clevis or the 0.5 in. (12.7 mm) diameter
chrome-plated piston rod. The mark is
for use in measuring the piston stroke.
If the stroke is not correct, increase or
decrease the number of active coils in
the calibration spring. Active coils are
those that are free of the positioner
arm and that flex when under load.
Determine stroke by increasing control
signal pressure slowly and observing
travel of the mark (discussed in preceding paragraph).
(a) If the piston moves to upper limit
before the control signal reaches
maximum pressure, the number of
active coils must be decreased as
described in step 8.
(c) Determine the exact control signal
pressure at which the piston
reaches upper limit.
(d) Determine the number of active
coils required by using the following equation:
Pa
x Ca =
Pm
Where:
Pa = Signal pressure at which
Pm = Maximum control signal
Ca = Actual number of active
(e) Reduce active coils to the number
required by turning the calibration
spring further onto the positioner
arm.
(f) Repeat step 7 to check the stroke
again.
9. To increase the number of active coils,
use the following procedure:
(a) Reduce control signal to zero.
(b) Count active coils of calibration
spring. Active coils are those that
are free of the positioner arm and
that flex when under load.
Number of active
coils required
piston reaches upper limit
pressure to be used
coils
(b) If piston travel is less than desired
when maximum signal is applied,
the number of active coils must be
increased as described in step 9.
Maximum travel is approximately 5
in. (127 mm).
(c) If piston stroke is satisfactory,
perform steps 10, 11, and 12.
8. To decrease the number of active coils,
use the following procedure:
(a) Reduce control signal to zero.
(b) Count the active coils of calibration
spring. Active coils are those that
are free of the positioner arm and
that flex when under load.
3-2 CalibrationRosemount Analytical Inc. A Division of Emerson Process Management
(c) Determine exact piston stroke by
measuring amount of travel of the
mark (on piston rod or clevis) when
control signal is increased from
zero to maximum pressure.
(d) Determine the number of active
coils required by using the following equation:
Sr
x Ca =
Sa
Where:
Sa = Actual stroke
Pm = Required stroke
Ca = Actual number of active
Number of active
coils required
coils
Hagan 2-1/2 x 5 and 4 x 5
3
Instruction Manual
IB-106-322N Original Issue
June 2000
(e) Increase the number of active coils
by turning spring off of the positioner arm.
(f) Repeat step 7 to see if desired
stroke is obtained.
10. Repeat step 6 to check minimum setting again.
11. Check mechanical linkage between the
positioner and the damper or valve that
the positioner positions. All links must
be properly aligned.
12. Reconnect mechanical linkage to
clevis.
b. Noncharacterized Units (Figure 3-3).
1. Using the manual/operating lever, position the piston against its lower stop.
2. Disconnect the external mechanical
linkage at the clevis, Figure 1-1.
3. Apply minimum control signal to the
pilot valve. The piston should move to
the lowest position, against bottom
cylinder head. Check this zero adjust in
the following manner:
(a) Maintain minimum control signal
on the pilot valve.
(b) Loosen the set screw on the posi-
tioner arm.
(c) Move the positioner arm up until
the piston moves to the bottom of
the cylinder.
(d) Move the positioner arm down until
the piston begins to move upward.
(e) Move the positioner arm down until
the piston just returns to lowest
position.
(f) Lock this setting by tightening the
set screw until the positioner arm
binds to the piston rod.
4. With the piston at the bottom of the
cylinder, place a mark on either the
clevis or the 0.5 in. (12.7 mm) diameter
chrome-plated piston rod. The mark is
for use in measuring the piston stroke.
If the stroke is not correct, increase or
decrease the number of active coils in
the calibration spring. Active coils are
those that are free of the positioner
arm and that flex when under load.
Determine stroke by increasing control
signal pressure slowly and observing
travel of the mark (discussed in preceding paragraph).
(a) If the piston moves to upper limit
before the control signal reaches
maximum pressure, the number of
active coils must be decreased as
described in step 5.
(b) If piston travel is less than desired
when maximum signal is applied,
the number of active coils must be
increased as described in step 6.
Figure 3-3. Noncharacterized Unit, Front View
Rosemount Analytical Inc. A Division of Emerson Process Management Calibration 3-3
Maximum travel is approximately 5
in. (127 mm).
Instruction Manual
IB-106-322N Original Issue
June 2000
Hagan 2-1/2 x 5 and 4 x 5
(c) If piston stroke is satisfactory,
perform steps 7, 8, and 9.
5. To decrease the number of active coils,
use the following procedure:
(a) Reduce control signal to zero.
(b) Count the active coils of calibration
spring. Active coils are those that
are free of the positioner arm and
that flex when under load.
(c) Determine the exact control signal
pressure at which the piston
reaches upper limit.
(d) Determine the number of active
coils required by using the following equation:
Pa
x Ca =
Pm
Where:
Pa = Signal pressure at which
Pm = Maximum control signal
Ca = Actual number of active
(e) Reduce active coils to the number
required by turning the calibration
spring further onto the positioner
arm.
(f) Repeat step 4 to check the stroke
again.
6. To increase the number of active coils,
use the following procedure:
(a) Reduce control signal to zero.
Number of active
coils required
piston reaches upper limit
pressure to be used
coils
(b) Count active coils of calibration
spring. Active coils are those that
are free of the positioner arm and
that flex when under load.
(c) Determine exact piston stroke by
measuring amount of travel of the
mark (on piston rod or clevis) when
control signal is increased from
zero to maximum pressure.
(d) Determine the number of active
coils required by using the following equation:
Sr
x Ca =
Sa
Where:
Sa = Actual stroke
Pm = Required stroke
Ca = Actual number of active
(e) Increase the number of active coils
by turning spring off of the positioner arm.
(f) Repeat step 4 to see if desired
stroke is obtained.
7. Repeat step 3 to check minimum setting again.
8. Check mechanical linkage between the
positioner and the damper or valve that
the positioner positions. All links must
be properly aligned.
9. Reconnect mechanical linkage to
clevis.
Number of active
coils required
coils
3-4 CalibrationRosemount Analytical Inc. A Division of Emerson Process Management
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.