Combustion Control Solution for
Commercial and Small Industrial Boilers
CHALLENGE
With increasing environmental requirements, users of commercial and
small industrial boilers are faced with escalating compliance demands,
which in turn, increase the need for measurement and control. Some do
not currently measure combustion ue gas, leaving themselves open
to regulatory as well as energy inefciency problems. Those who are
measuring, may not be aware of available technologies that offer a higher
degree of accuracy and longer sensor life.
WHAT IF...
...boiler efficiency could be
improved with a high-quality
combustion control solution
designed without the cost and
complexity?
… combustion flue gas
measurement could be achieved
with a system that offers ease of
use and simplified service and
maintenance?
OUR SOLUTION
The Rosemount™ CX1100 In-Situ Oxygen Transmitter is a combustion
control solution designed to improve boiler efciency and meet
environmental regulatory requirements for small and midsize boiler users,
and offers ease of use, economy, and simplied maintenance. Featuring
the patented Rosemount oxygen sensing zirconia cell, it offers the same
sensor reliability found in large industrial technology, but is built to
the requirements of users in applications, such as, food and beverage,
manufacturing, and commercial and institutional power and heating.
HOW IT WORKS
• Zirconia sensing cell and the all-welded probe improve reliability
by eliminating leak points
• Does not use piped reference air which keeps installation and
maintenance costs low
• Offers an easy-replacement design that enables simplied service
• Remote transmitter architecture allows for fast conguration
and calibration that includes a large, multi-function display
with diagnostics
For more information visit:
Emerson.com/RosemountGasAnalysis
or contact your local Emerson™ Sales Representative
Key Innovations
• Rosemount patented zirconia
sensing cell
• Robust all-welded
construction
• No piped reference air
• Rated to IP66 and Type 4x
Combustion Control Solution for
Commercial and Small Industrial Boilers
Specifications
Measurement Type Oxygen, Zirconia
Repeatability ±1 % of reading or 0.1 % of O2 whichever is lower
Measurement Range 0 to 23 %
Response Time Up to 10 sec T90
Process Temperature Range Up to 752° F (400 °C)
Ambient Temperature -4 to 158 °F (-20 to 70 °C)
Dimensions Probe Length Options: 19.7 in (0.5 m), 3.3 ft (1.0 m), 6.6 ft (2.0 m)
Output Signal 4–20 mA
Associated Products
Rosemount™ 6888
In Situ Oxygen Transmitter
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd
Shakopee, MN 55379
USA
Toll Free + 800 854 8257
GAS.CSC@Emerson.com
www.Emerson.com/RosemountGasAnalysis
Rosemount™ Oxymitter™ 4000
In Situ Oxygen Transmitter
Consider it Solved.
Emerson Automation Solutions supports you with innovative
technologies and expertise to address your toughest challenges.
For more information, visit Emerson.com/RosemountGasAnalysis.