Rosemount Analytical 975MR Specifications

Rosemount 975MR Multi-spectrum Infrared Flame Detector
FGD-PDS-975MR
Rosemount™ 975MR
Multi-spectrum Infrared Flame Detector
The Rosemount™ 975MR multi-spectrum infrared flame detector is based on accurately analyzing the multi-spectral signals by three separate IR sensors. The Rosemount 975MR detects fuel and gas fires at long distances. For example, this product will detect a 0.1 m2 (1 ft2) gasoline pan fire at 65 m (215 ft) in less than five seconds. The Rosemount 975MR also provides the highest immunity to false alarms at such industry leading detection range.
Product Data Sheet
February 2018
Features and benefits
 Multi spectrum design - for long distance detection and
high false alarm immunity  Sensitivity selection - to ensure no zone crossover detection  Automatic and manual built-in-test (BIT) - to assure
continued reliable operation  Heated window - for operation in harsh weather conditions
(snow, ice, condensation)
Multiple output options for maximum exibility
and compatibility
Relays (3) for alarm, fault, and auxiliary
0–20 mA (stepped)
HART® protocol for maintenance and asset management
RS-485, Modbus® compatible
 High Reliability - MTBF - minimum 150,000 hours  Approved to Safety Integrity Level 2 (SIL 2 – TÜV)  Five year warranty  User programmable via HART or RS-485
Rosemount 975MR Multi-spectrum Infrared Flame Detector
Applications
 Oil and gas - Offshore and onshore process facilities Reneries  Petrochemical process facilities  Crude oil tank terminals  Automotive manufacturing facilities  Aircraft hangars  Power generation facilities  Chemical and pharmaceutical plants  Production, loading, and unloading facilities
Rosemount 975MR Multi-spectrum Infrared Flame Detector
February 2018
Specifications
Table 1 - Rosemount 975MR Multi-spectrum Infrared Flame Detector
General specifications
Spectral response Three IR bands
Detection range
(at highest sensitivitysetting for 0.1m2 (1 ft2) pan re)
Response time Typically 5 s Adjustable time delay Up to 30 s Sensitivity ranges 4 sensitivity ranges for 0.1 m2 (1 ft2) n-heptane pan re from 15 m (50 ft) to 65 m (215 ft)
Field of view Horizontal 100˚; Vertical 95˚ Built-in-test (BIT) Automatic (and manual)
Temperature range Operating: -55 ˚C to +75 ˚C (-67 ˚F to +167 ˚F)
Humidity Up to 95 % non-condensing (withstands up to 100 % relative humidity for short periods) Heated optics To eliminate condensation and icing on the window
Electrical specifications
Operating voltage 24 Vdc nominal (18–32 Vdc) Power consumption Standby: Max. 90 mA (110 mA with heated window)
Cable entries 2 x ¾ in.- 14 NPT conduits or 2 x M25 x 1.5 mm ISO
Wiring
Electrical input protection
Electromagnetic compatibility
Electrical interface
Outputs
Relays Alarm, fault, and auxiliary
0–20 mA (stepped)
HART® Protocol Optional HART communications on the 0–20 mA analog current (FSK) - used for maintenance, conguration changes
RS-485
Mechanical specifications
Materials
Enclosure options
Mounting Stainless steel 316L with electro polish nish Dimensions Detector 101.6 x 117 x 157 mm (4 x 4.6 x 6.18 in.) Weight Detector (stainless steel 316L) 2.8 kg (6.1 lb)
Environmental standards Meets MIL-STD-810C for humidity, salt and fog, vibration, mechanical shock, high temp, low temp Water and dust IP66 and IP67 per EN 60529, NEMA 250 6P
Fuel m / ft Fuel ft / m Fuel m / ft
n-Heptane Gasoline Diesel fuel JP5
*0.75 m (30 in.) high, 0.25 m (10 in.) width plume re
Option: -55 ˚C to +85 ˚C (-67 ˚F to +185 ˚F) Storage: -55 ˚C to +85 ˚C (-67 ˚F to +185 ˚F)
Alarm: Max. 130 mA (160 mA with heated window)
12–22 AWG (2.5 mm2–0.3 mm2) According to MIL-STD-1275B EMI/RFI protected to EN 61326-3 and EN 61000-6-3
The detector includes twelve (12) terminals with ve (5) wiring options (factory set).
SPST volt-free contacts rated 2 A at 30 Vdc
Sink (source option) conguration
Fault: 0 +1 mA
BIT fault: 2 mA ±10 %
and asset management, available in mA source output wiring options RS-485 Modbus compatible communication link that can be used in computer controlled installations
- Stainless steel 316L with electro polish nish
- Heavy duty copper free aluminum (less than 1 %), red epoxy enamel nish (not available in FM version)
Detector (aluminum) 1.3 kg (2.8 lb) Tilt mount 1.0 kg (2.2. lb)
65 / 215 65 / 215 45 / 150 45 / 150
Kerosene Ethanol Methanol IPA (isopropyl alcohol)
Normal: 4 mA ±10 % Warning: 16 mA ±5 %
45 / 150 40 / 135 35 / 115 40 / 135
Alarm: 20 mA ±5 %
Resistance Loop: 100–600 Ω
Methane* LPG* Polypropylene pellets
Ofce paper
45 / 150 45 / 150 35 / 115 25 / 83
2 www.Emerson.com/FlameGasDetection
Loading...