Rosemount Analytical 6888 Operating Manual

Page 1
Quick Start Guide
CMB-QSG-6888C, Rev B
October 2017
Rosemount™ 6888C In-Situ Combustion Oxygen Analyzer
For use in Hazardous Areas
Page 2
This guide provides basic guidelines for Rosemount 6888 In-Situ Oxygen Analyzers. It does not provide instructions for configuration, diagnostics, maintenance, service, troubleshooting, or flame-proof installations. Refer to the
Rosemount 6888C Manual for more instruction.

Essential instructions

Read this page before proceeding!
Emerson designs, manufactures, and tests its products to meet many national and international standards. Because these instruments are sophisticated technical products, you must properly install, use, and maintain them to ensure they continue to operate within their normal specifications. The following instructions must be adhered to and integrated into your safety program when installing, using, and maintaining Emerson products. Failure to follow the proper instructions may cause any one of the following situations to occur: loss of life, personal injury, property damage, damage to this instrument, and warranty invalidation.
Read all instructions prior to installing, operating, and servicing the product.
If you do not understand any of the instructions, contact your Emerson representative for clarification.
Follow all warnings, cautions, and instructions marked on and supplied with the product.
Inform and educate your personnel in the proper installation, operation, and maintenance of the product.
Install your equipment as specified in the installation instructions of the appropriate instruction manual and per applicable
local and national codes. Connect all products to the proper electrical and pressure sources.
To ensure proper performance, use qualified personnel to install, operate, update, program, and maintain the product.
Use only factory documented components for repair. Tampering and unauthorized substitution and parts can affect
product performance and cause unsafe operation of your process.
The Field Communicator must be upgraded to System Software 2.0 with graphic license for operation with the 6888C O Transmitter. The AMS software must be upgraded to AMS 8.0 or above. Contact Emerson's Global Service Center (GSC) at 1-800-833-8314 to upgrade the Field Communicator software to System Software 2.0 with graphic license.
2
Symbols
Earth (ground) terminal
Protective conductor terminal
Risk of electrical shock
Refer to Instruction Manual
The following definitions apply to Warnings, Cautions, and Notices found throughout this publication.
WARNING!
Highlights an operation or maintenance procedure, practice, condition, statement, etc., which if not strictly observed, could result in injury, death, or long-term health hazards of personnel.
CAUTION!
Highlights an operation or maintenance procedure, practice, condition, statement, etc., which if not strictly observed, could result in damage to or destruction of equipment or loss of effectiveness.
Page 3
Highlights an essential operating procedure, condition, or statement.
WARNING!
EXPLOSION Do not open when an explosive atmosphere may be present.
WARNING!
ELECTRIC SHOCK Do not open while energized.
CAUTION!
EQUIPMENT DAMAGE
For the standard housing probe and direct replacement probe, only use supply cables & certified cable glands rated > 105 °C (221 °F).
CAUTION!
EQUIPMENT DAMAGE
For the autocal housing, only use supply cables and certified cable glands rated > 85 °C (185 °F).
Page 4
Page 5

Contents

Contents
Chapter 1 Installation .....................................................................................................................1
1.1 Mechanical installation ................................................................................................................ 1
1.1.1 Rosemount 6888C Probe installation ............................................................................ 1
1.2 Electrical ...................................................................................................................................... 4
1.2.1 Wiring for Rosemount 6888 Transmitter Probe only (no Rosemount 6888 Xi
Electronics) ................................................................................................................... 5
1.2.2 Standard housing transmitter probe with Rosemount 6888 Xi Electronics .................... 6
1.2.3 Connecting the Transmitter probe with integral autocal to HART
communications ......................................................................................................... 10
1.2.4 Connecting the Transmitter probe with integral autocal to FOUNDATION Fieldbus
communications ......................................................................................................... 12
1.2.5 Connecting the traditional architecture system to the direct replacement probe ........17
1.3 Pneumatic installation ............................................................................................................... 19
1.3.1 Calibration gas ............................................................................................................ 21
Chapter 2 Configuration, startup, and operation .......................................................................... 23
2.1 Powering up Rosemount 6888 Transmitter without Rosemount 6888Xi ....................................23
2.2 Powering up Rosemount 6888 Transmitter with single/dual channel or single channel ..............23
2.3 Powering up the Rosemount 6888 Direct Replacement Probe (no electronics inside) with
traditional architecture Rosemount 6888 Xi .............................................................................. 24
2.4 Rosemount 6888 Xi Quick Start Wizard ..................................................................................... 24
2.5 Calibration .................................................................................................................................25
2.5.1 Manual/semi-automatic calibration ............................................................................ 26
2.5.2 Fully automatic calibration ..........................................................................................26
2.5.2.1 Rosemount 6888 Probes with standard electronics housing ............................26
2.5.2.2 Rosemount 6888 Probe with integral autocal housing .....................................27
Appendices and reference
Appendix A Rosemount™ 6888C Product Certifications ................................................................... 29
A.1 European Directive information ................................................................................................. 29
A.2 Ordinary location certification ................................................................................................... 29
A.3 Installing equipment in North America ...................................................................................... 29
A.4 USA/Canada .............................................................................................................................. 29
A.5 Europe ....................................................................................................................................... 30
Quick Start Guide i
Page 6
Contents
ii 6888C
Page 7
1 Installation
WARNING!
Before installing this equipment, read the Essential Instructions at the front of this Quick Start Guide. Failure to follow safety instructions could result in serious injury or death.
WARNING!
ELECTRIC SHOCK Install all protective equipment covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death.

1.1 Mechanical installation

Note that most combustion processes run only slightly negative or positive in pressure, so that the probe flange is for mechanical mounting only. The probe is not rated for high pressures. If this is a new installation, a weld plate for welding to the flue gas duct can be supplied.

Installation

1.1.1
WARNING!
ELECTRIC SHOCK Install all protective equipment covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death. Do not install the transmitter or the Rosemount 6888 Xi in hazardous areas or in the vicinity of flammable liquids.

Rosemount 6888C Probe installation

Complete the following steps to install the Rosemount 6888C Probe in the duct.
Prerequisites
Ensure all components are available to install the Rosemount 6888C O2 probe.
Procedure
1. If using the optional ceramic diffusion element, the vee-deflector must be correctly oriented. Before inserting the Rosemount 6888C probe, check the direction of gas flow in the duct. Orient the vee-deflector so the apex points upstream towards the flow.
2. If using the standard square weld plate or an optional flange mounting plate, weld or bolt the plate onto the duct.
The through hole diameter in the stack or duct wall and refractory material must be at least 2-1/2 in. (63.5 mm).
Quick Start Guide 1
Page 8
Installation
3. Insert probe through the opening in the mounting flange and bolt the unit to the flange.
6888C Probe with Standard Terminations/Electronics HousingFigure 1-1:
Note
All dimensions are in inches with millimeters in parentheses.
6888C Probe with Integral Autocal HousingFigure 1-2:
Removal/InstallationTable 1-1:
DIM B removal en-
DIM A insertion
Probe length
18 in. (457 mm) probe
3 ft (0.91 m) probe 32.52 (826) 46.6 (1182) 50.1 (1271)
depth
16.10 (409) 15.77 (401) 19.26 (490)
velope standard housing
DIM B removal en­velope accessory housing
2 6888C
Page 9
Installation
Removal/Installation (continued)Table 1-1:
DIM B removal en-
DIM A insertion
Probe length
6 ft (1.83 m) probe 68.52 (1740) 82.6 (2097) 86.1 (2186)
depth
velope standard housing
DIM B removal en­velope accessory housing
Probe InstallationFigure 1-3:
Mounting FlangeTable 1-2:
ANSI DIN
Flange dia 8.25 (210)
Hold dia .75 (20)
(4) holes eq sp on BC 6.00 (152) 6.70 (170)
Installation weld plate outlineTable 1-3:
ANSI DIN
A
B thread .625 (11) (M-16x2)
C dia 6.00 (152) 6.70 (170)
7.75 (197) 8.5 (215)
Quick Start Guide 3
Page 10
Installation
Drip Loop and Insulation RemovalFigure 1-4:
1.2
A. Line voltage B. Logic I/O, 4-20 mA signal C. Stack or duct metal wall D. Adapter plate E. Insulation F.
Note
Replace insulation after installing Rosemount 6888C.
Note
Standard housing probe shown. Accessory housing is similar. Probe may be vertical or horizontal.

Electrical

All wiring must conform to local and national codes. Multiple wiring diagrams are shown in this section. Always refer to the diagrams that apply to your transmitter configuration and disregard all other wiring diagrams.
4 6888C
Page 11
Installation
WARNING!
ELECTRIC SHOCK Disconnect and lock out power before connecting the power supply.
Install all protective covers and safety ground leads after installation. Failure to install covers and ground leads could result in serious injury or death.
To meet the safety requirements of IEC 61010-1 (EC requirement) and ensure safe operation of this equipment, connection to the main electrical power supply must be made through a circuit breaker (min 10 A) which will disconnect all current-carrying conductors during a fault situation. The circuit breaker should also include a mechanically operated isolating switch. If not, then another external means of disconnecting the supply from the equipment should be located close by. Circuit breakers or switches must comply with a recognized standard such as IEC 60947.
To maintain proper earth grounding, ensure a positive connection exists between the transmitter housing and earth. The connecting ground wire must be 14 AWG minimum.
1.2.1
Line voltage, signal, and relay wiring should be rated for at least 105 °C (221 °F).

Wiring for Rosemount 6888 Transmitter Probe only (no Rosemount 6888 Xi Electronics)

The Rosemount 6888 Transmitter Probe has built-in electronics that control the heater temperature and amplify the raw O2 millivolt signal to a linear 4-20 mA.
The 4-20 mA signal lines can be run directly to the control room and also power the transmitter electronics. There is no O2 display or keypad on the probe, so setup must be conducted through HART communications via a 475 handheld communicator or Asset Management Solutions (AMS).
Procedure
1. Remove the cover from the probe.
2. Connect the line (L1 wire) to the L1 terminal, the neutral (L2 wire) to the L2/N terminal, and the ground wire to the ground lug.
The Rosemount 6888C accepts line voltage at 120/240 Vac ±10%, 50/60 Hz. No setup is required.
3. Connect the 4-20 mA signal wires at the transmitter. Use a shielded twisted wire pair. Do not allow bare shield wires to contact the circuit boards. Insulate the shield wires prior to termination.
The transmitter electronics are loop-powered, i.e., the 4-20 mA signal wires supply 24 Vdc from the DCS or an external power supply.
Quick Start Guide 5
Page 12
Installation
Rosemount 6888C Standard Probe HousingFigure 1-5:
1.2.2
4. Terminate the shield only at the transmitter electronics housing unless using a Rosemount 6888 Xi. When using the Rosemount 6888 Xi Advanced Electronics, terminate the shield at both ends.
5. Reinstall cover on transmitter.

Standard housing transmitter probe with Rosemount 6888 Xi Electronics

The Rosemount 6888 Xi Electronics serves as an operatoer interface unit with a back-lit display and keypad. It is capable of two channels, serving up to two Rosemount 6888 probes.
1. Remove cover screws from the front cover of the Rosemount 6888 Xi. Swing down the front cover of the interface box.
2. Pull out the I/O board on the right side of the card rack inside the Rosemount 6888 Xi.
If your system is configured to operate two transmitter probes, there are two I/O interface boards.
3. Connect the 4-20 mA signal wires at J4 of the I/O board. Attach the supplied ferrite clamp over the 4-20 mA OUT wires that extend past the shield.
6 6888C
Page 13
Installation
Installation of the ferrite clamp over the 4-20 mA OUT wires is required for compliance with the European EMC directive.
4. Terminate the shield of the 4-20 mA signal wires at the designated ground terminal of the Rosemount 6888 Xi. Do not allow bare shield wires to contact the circuit boards. Insulate the shield wires prior to termination.
5. Connect the signal wires from the SPS or IMPS (if used) to the applicable terminals of J3.
Refer to the SPS or IMPS instruction manual for wiring details.
6. Reinstall the I/O board in the card rack of the Rosemount 6888 Xi.
7. If your system is configured for two channel operation, repeat steps 2 through 6 to connect the other probe's signal wires.
8. Remove the probe's connector from the power supply board located on the left side of the card rack inside the Rosemount 6888 Xi.
9. Connect the line, or L1, wire to the L1 terminal and the neutral, or L2, wire to the N terminal.
10. Reinstall the power supply connector to the power supply board.
Quick Start Guide 7
Page 14
Installation
Wiring Diagrams - Single/Dual Channel Wiring DiagramFigure 1-6:
A. Except for JP5, JP7, and JP8 on IO board, jumper and switch settings are factory set and are
shown for reference only.
B. IO board 4-20 mA loop power settings
JP5: Pins 1-2 internal power Rosemount 6888 Xi to Rosemount 6888 Transmitter
Pins 2-3 external power Rosemount 6888 Xi to Rosemount 6888 Transmitter (requires
resistor across J4, PR+ to PR-
250
JP7/JP8: Pins 1-2 internal power Rosemount 6888 Xi to DCS
Pins 2-3 external power Rosemount 6888 Xi to DCS
8 6888C
Page 15
Installation
Wiring Diagrams - Single/Dual Channel Wiring DiagramFigure 1-7:
A. Power supply board B. Channel #2 IO board C. Shield ground D. Channel #1 IO board E. AC input to P/S F. Plug G. Channel #2 alarm relay SPS/IMPS H. Channel #2 4-20 mA / HART output I. Channel #1 alarm relay SPS/IMPS J. Channel #1 4-20 mA/HART output
Quick Start Guide 9
Page 16
Installation

1.2.3 Connecting the Transmitter probe with integral autocal to HART communications

This probe contains gas-switching solenoids so that the Rosemount 6888 Xi Electronics can control the introduction of calibration gases. Calibrations can be initiated via a calibration recommended diagnostic, time since last calibration, manually via external dry contact, HART communications, or from the Rosemount 6888 Xi local operator interface keypad. The integral autocal feature can only be implemented when the probe is used with a Rosemount 6888 Xi.
1. Remove the two covers from the transmitter.
2. Connect the line (L1 wire) to the L1 terminal, the neutral (L2 wire) to the L2/N
terminal, and the ground wire to the ground lug.
The Rosemount 6888C accepts line voltage at 120/240 Vac ±10%, 50/60 Hz. No setup is required.
3. Connect the 4-20 mA signal wires from the Rosemount 6888 Xi to the connections
in the side chamber of the transmitter.
Do not connect the signal wires to the terminals in the main chamber where the AC input wires are connected. Use a shielded twisted wire pair. Do not allow bare shield wires to contact the circuit boards. Insulate the shield wires prior to termination. The 24 Vdc loop power is sourced from the Rosemount 6888 Xi.
4. Terminate the shield at both the probe and the Rosemount 6888 Xi Advanced
Electronics.
5. Reinstall both covers on transmitter.
10 6888C
Page 17
Installation
Integral autocal and HART communicationsFigure 1-8:
A. Ferrite clamp B. Signal C. Test points D. #8 pan htd scr (internal ground) E. Power F. Test point group
A. Except for JP5, JP7, and JP8 on IO board, jumper and switch settings are factory set and are shown for reference
only.
Quick Start Guide 11
Page 18
Installation
B. IO board: 4-20 mA/HART loop power settings
JP5
Pins 1-2: internal power Rosemount 6888 Xi to Rosemount 6888 transmitter
Pins 2-5: external power Rosemount 6888 Xi to Rosemount 6888 transmitter (requires 2,500 resistor across
J4, PR+ to PR-)
JP7/JP8
Pins 1-2: internal power to DCS
Pins 2-3: external power Rosemount 6888 Xi to DCS
I/O board - Channel 2 is a duplicate of Channel 1.
1.2.4 Connecting the Transmitter probe with integral autocal to FOUNDATION Fieldbus™ communications
This probe contains gas-switching solenoids so that the Rosemount 6888 Xi Electronics can control the introduction of calibration gases. Calibrations can be initiated via a calibration recommended diagnostic, time since last calibration, manually via external dry contact, HART communications, or from the Rosemount 6888 Xi local operator interface keypad. The integral autocal feature can only be implemented when the probe is used with a Rosemount 6888 Xi.
1. Remove the two covers from the transmitter.
2. Connect the line (L1 wire) to the L1 terminal, the neutral (L2) wire to the L2/N
terminal, and the ground wire to the ground lug.
The Rosemount 6888C accepts line voltage at 120/240 Vac ±10%, 50/60 Hz. No setup is required.
3. Connect the FOUNDATION Fieldbus wires from the Rosemount 6888 side housing to
the FF segment.
Note that the Rosemount 6888 probe is not rated as intrinsically safe and will render any IS or FISCO segment it is wired to as non-IS. Use a shielded twisted wire pair. Do not allow bare shield wires to contact the circuit boards.
4. Terminate the shield at both the probe and the Rosemount 6888 Xi Advanced
Electronics.
The FOUNDATION Fieldbus signal represents the O2 value and also powers the probe­mounted electronics.
5. Reinstall both covers on transmitter.
12 6888C
Page 19
Installation
Figure 1-9:
Integral Autocal and FOUNDATION Fieldbus Communications without Optional Rosemount 6888 Xi
A. Signal B. Not used C. #8 pan htr scr (internal ground) D. Power E. Probe test point group
Quick Start Guide 13
Page 20
Installation
Figure 1-10:
Integral autocal and FOUNDATION Fieldbus Communications with Rosemount 6888 Xi
A. Ribbon cable to display board J2 Sensor 1 B. Signal C. HART connection (Used as a communication bus from probe transmitter electronics to optional
Rosemount 6888 Xi. Not accessible to 475 communicator or AMS) D. #8 pan htr scr (internal ground) E. Power F. Probe test point group
IO board switch/jumpers
Jumper settings
JP1: Pins 2-3
JP2: Pins 2-3
JP5
Pins 1-2 internal power
14 6888C
Page 21
Installation
Pins 2-3 external power
JP7
Pins 1-2 internal power
Pins 2-3 external power
JP8
Pins 1-2 internal power
Pins 2-3 external power
SW4 switch settings
Position 1 - Off
Postion 2 - Off
Position 3 - Off
Position 4 - Off
A. Except for JP5, JP7, and JP8 on IO board, jumper and switch settings are factory set and are
shown for reference only. B. IO board 4-20 mA/HART loop power settings
JP5
Pins 1-2 internal power Rosemount 6888 Xi to Rosemount 6888 Transmitter
Pins 2-3 external power Rosemount 6888 Xi to Rosemount 6888 Transmitter (requires
2,500 resistor across J4, PR+ to PR-)
JP7/JP8
Pins 1-2 internal power Rosemount 6888Xi to DCS
Pins 2-3 external power Rosemount 6888Xi to DCS
Quick Start Guide 15
Page 22
Installation
Figure 1-11:
Wiring Diagrams - Integral Autocal and FOUNDATION Fieldbus, Communications with Rosemount 6888Xi
A. Power supply board B. Channel #2 IO board C. Shield ground D. Channel #1 IO board E. AC input to P/S F. Plug G. Channel #2 alarm relay, SPS/IMPS H. Channel #2 4-20 mA/HART output I. Channel #1 alarm relay, SPS/IMPS J. Channel #! 4-20 mA/HART output
16 6888C
Page 23
Installation

1.2.5 Connecting the traditional architecture system to the direct replacement probe

A traditional architecture configuration is used to provide for remote location of the transmitter electronics. All electronics are housed inside the Rosemount 6888 Xi. A multi­conductor power/signal cable connnects between the probe and the Rosemount 6888Xi. Use the following procedure to connect the traditional architecture probe to the Rosemount 6888 Xi.
The traditional architecture cable is provided at the specified length and is ready for installation. The cable glands must be properly terminated to maintain EMC/EMI noise protection.
Procedure
1. Run the 7-conductor cable between the traditional architecture probe and the
installation site for the Rosemount 6888 Xi. Use new cable conduit or trough as needed.
2. Install the cable and lead wires to the probe per manufacturer's instructions.
3. Install the cable at the probe housing and at the Rosemount 6888 Xi enclosure
according to the following procedure:
a. Unscrew locking nut from gland assembly and slide locking nut back along cable.
b. Pull the gland body away from the plastic insert. Use care not to damage the
cable shield braid.
c. Insert the cable wires into the proper entry port in either the probe housing or
the Rosemount 6888 Xi enclosure.
d. At the probe housing, apply Teflon tape or similar sealing compound to the
tapered pipe threads. Thread the gland body into the probe housing until properly seated.
e. At the Rosemount 6888 Xi enclosure, insert the gland body into the left front
cable port from the inside of the enclosure. Use the rubber O-ring provided to seal the cable port.
f. Ensure the cable shield braid is evenly formed over the gray insert.
When properly formed, the braid should be evenly spaced around the circumference of the insert and not extend beyond the narrow diameter portion.
g. Carefully press the gray insert into the gland body.
The grooves on the insert should align with similar grooves inside the gland body. Press the insert in until it bottoms out in the gland body.
h. Slide the locking nut up and thread it onto the gland body. Tighten the locking
nut so the rubber grommet inside the plastic insert compresses against the cable wall to provide an environmental seal.
4. At the Rosemount 6888 Xi, connect the cable leads to the connectors on the
transmitter I/O board.
Quick Start Guide 17
Page 24
Installation
Figure 1-12:
Wiring Diagrams - Traditional Architecture with Direct Replacement Probe (no Electronics Inside)
A. See the Rosemount 6888Xi Instruction Manual for additional installation and operating
instructions. B. All wiring marked with an asterisk (*) is factory wiring inside the Rosemount 6888Xi. C. Except for JP7 and JP8 on IO board, jumper and switch settings are factory set and are shown
for reference only.
18 6888C
Page 25
Installation
Figure 1-13:
Wiring Diagrams - Traditional Architecture with Direct Replacement Probe (no Electronics Inside)
A. Power supply board B. DR board C. Shield ground D. IO board E. Plug F. Probe cable G. AC input H. Alarm relay, SPS/IMPS I. 4-20 mA / HART output
1.3
Quick Start Guide 19

Pneumatic installation

Reference air package
After the Rosemount 6888C is installed, connect the reference air set to the unit. Refer to the schematic diagram and the mounting dimensions in Figure 1-14 for a locally assembled reference air supply.
Page 26
Installation
Instrument air (reference air): 5 psi (34 kPa) minimum, 8 psi (54 kPa) maximum at 2.0 scfh (1.01 L/min) maximum; less than 40 parts per million total hydrocarbons. Regulator outlet pressure should be set at 5 psi (34 kPa).
Plant air schematic diagram, standard housingFigure 1-14:
A. Vent B. Calibration gas: 1/4 in. tube C. Reference air flowmeter D. 0.25-18 NPT female inlet connection E. 0.25 or 6 mm O.D. tubing (supplied by customer) F. Reference gas: 1/4 in. tube
Plant air schematic diagram, accessory housingFigure 1-15:
A. Vent B. Calibration gas 1: 1/4 in. tube C. Calibration gas 2: 1/4 in. tube D. Reference air flowmeter E. 0.25-18 NPT female inlet connection F. 0.25 or 6 mm O.D. tubing (supplied by customer) G. Reference gas: 1/4 in. tube
20 6888C
Page 27

1.3.1 Calibration gas

Two calibration gas concentrations are used with this transmitter, low gas - 0.4% O2, balance N2, and high gas - 8% O2, balance N2.
See Figure 1-16 for the Rosemount 6888C probe calibration gas connection ports.
Rosemount 6888C Calibration Gas ConnectionsFigure 1-16:
Installation
A. Cal gas in B. Ref air vent C. Ref air in
CAUTION!
READING ERRORS
Do not use 100% nitrogen as a low gas (zero gas). Emerson suggests that gas for the low (zero) be between 0.4% and 2.0% O2. Do not use gases with hydrocarbon concentrations of more than 40 parts per million. Failure to use proper gases will result in erroneous readings.
CAUTION!
EQUIPMENT DAMAGE
If the ducts will be washed down during outage, MAKE SURE to power down the Rosemount 6888C units and remove them from the wash areas.
Upon completing installation, make sure that the transmitter is turned on and operating prior to firing up the combustion process. Damage can result from having a cold Rosemount 6888C unit exposed to the process gases. During outages, if possible, leave all Rosemount 6888C units running to prevent condensation and premature aging from thermal cycling.
Quick Start Guide 21
Page 28
Installation
22 6888C
Page 29

Configuration, startup, and operation

2 Configuration, startup, and operation
WARNING!
ELECTRIC SHOCK Install all protective equipment covers and safety ground leads before equipment startup. Failure to install covers and ground leads could result in serious injury or death.
CAUTION!
EQUIPMENT DAMAGE
If external loop power is used, the power supply must be a safety extra low voltage (SELV) type.
2.1 Powering up Rosemount 6888 Transmitter
2.2
without Rosemount 6888Xi
Complete the following steps to apply power to the Rosemount 6888 Transmitter without connecting it to the Rosemount 6888Xi.
1. Apply AC line power to the transmitter.
2. Apply 24 Vdc loop power to the transmitter.
3. Using either the DCS control or a Field Communicator, verify communications to the
transmitter.
The transmitter probe takes approximately 45 minutes to warm up to the 736 °C
(1357 °F) heater setpoint. The 4-20 mA signal remains at a default value of 3.5 mA,
and the O2 reading remains at 0% through this warm-up period. After warm-up, the
probe begins reading oxygen, and the 4-20 mA output is based on the default range
of 0-10% O2.
If there is an error condition at startup, an alarm message is displayed. Refer to the
full instruction manual for troubleshooting alarms.

Powering up Rosemount 6888 Transmitter with single/dual channel or single channel

Complete the following steps to power up the Rosemount 6888 Transmitter using the Rosemount 6888Xi Electronics.
1. Apply AC line power to the transmitter.
2. Apply AC line power to the Rosemount 6888Xi. Run the Quick Start Wizard as
described below. At the Auto Cal Device screen, select the calibration method based
on the Rosemount 6888 Transmitter as follows:
Quick Start Guide 23
Page 30
Configuration, startup, and operation
a. Standard Probe Housing Configuration - Select None, SPS, or IMPS as appropriate.
b. Integral Autocal Probe housing - Select Integral only. If Integral is not selected,
3. Verify communications between the transmitter and the Rosemount 6888Xi.
The Rosemount 6888Xi display is preconfigured to display O2 and cell temperature
for single channel configurations and both O2 readings for dual channel
configurations.
The transmitter probe takes approximately 45 minutes to warm up to the 736 °C
(1357 °F) heater setpoint. The 4-20 mA signal remains at a default value of 3.5 mA,
and the O2 reading remains at 0% through this warm-up period. After warm-up, the
probe begins reading oxygen, and the 4-20 mA output is based on the default range
of 0-10% O2.
If there is an error condition at startup, an alarm message is displayed. Refer to the
full instruction manual for troubleshooting alarms.
Do not select Integral or calibration will not be possible.
calibration will not be possible.

2.3 Powering up the Rosemount 6888 Direct Replacement Probe (no electronics inside) with traditional architecture Rosemount 6888 Xi

Complete the following steps to power up the Rosemount 6888 Direct Replacement Probe with the Rosemount 6888 Xi Electronics.
1. Apply AC line power to the Rosemount 6888 Xi.
2. Run the Quick Start Wizard as described in Section 2.4.
3. At the Auto Cal Device screen, select None, SPS, or IMPS as appropriate.
Do not select Integral or calibration will not be possible.
The transmitter probe takes approximately 45 minutes to warm up to the 736 °C (1357 °F) heater setpoint. The 4-20 mA signal remains at a default value of 3.5 mA, and the O reading remains at 0% through this warm-up period. After warm up, the probe begins reading oxygen, and the 4-20 mA output is based on the default range of 0-10% O2.
If there is an error condition at startup, an alarm message is displayed.
2.4

Rosemount 6888 Xi Quick Start Wizard

2
When the Rosemount 6888 Xi is first powered, a short wizard program guides you through the basic setup. Once configured, the Rosemount 6888 Xi retains the setup, and the wizard will not repeat.
1. Apply power to the Rosemount 6888 Xi.
24 6888C
Page 31
Configuration, startup, and operation
Once boot-up is complete, the Quick Start Wizard screen appears. With a dual channel Rosemount 6888 Xi, the wizard runs for both channels in succession.
2. Press Enter to continue.
3. At the Sensor Type screen, use the Up and Down keys to select O2.
Do not select CO as this option is reserved for future use.
4. Press Enter to continue.
5. At the Device Type screen use the Up and Down keys to select HART® or FF
(FOUNDATION Fieldbus™), whichever applies.
6. At the Auto Cal Device screen, use the Up and Down keys to select the calibration
method to be used. The methods are defined as follows:
None - Manual calibration with the standard probe housing configuration
SPS - Automatic calibration with the standard probe housing configuration using
the Rosemount SPS 4001B
IMPS - Automatic calibration with the standard probe housing configuration
using the Rosemount IMPS
Integral - Automatic calibration with the integral autocal probe housing
configuration
7. Press Enter to continue.
2.5
If SPS, IMPS, or Integral is selected, you must still configure automatic calibration as On. Other parameters, such as test gas values and gas times, should be verified as well. Refer to the Rosemount 6888 Xi instruction manual for calibration setup details.
8. When prompted by Setup Correct?, use the Up and Down keys to select Yes.
If you select No, the wizard restarts.
9. Press Enter to continue.
The Rosemount 6888 Xi displays several screens while saving the configuration, resets itself, and then returns to the main screen.

Calibration

The Rosemount 6888 O2 Analyzer System can be calibrated in the installed condition without removing the instrument from the process duct and also while the combustion process is on-line. A stainless steel tube runs the length of the probe and delivers the calibration gases into the cell area. Factory calibration is usually satisfactory for initial startup and operation, but most accurate measurement is gained by executing a calibration under normal operating conditions.
Quick Start Guide 25
Page 32
Configuration, startup, and operation
Emerson recommends using 0.4% O2 and 8% O2 as calibration gases, with a balance of nitrogen in the gas bottles, but other values can be used as long as the electronics are configured identically. Emerson does not recommend instrument air or pure nitrogen as calibration gas values. Use a two-stage pressure regulator to establish a pressure of 20 psi from the bottles and set the flowmeter to 5 scfh flow rate.

2.5.1 Manual/semi-automatic calibration

The Rosemount 6888 probe with the standard housing can be calibrated in a semi­automatic fashion with a technician following prompts via the display of the Rosemount 6888 Xi Electronics or via HART® communications to a Field Communicator or AMS console. The technician needs to manually switch the gases based upon these prompts. Emerson recommends using 0.4% O2 and 8% O2, balance nitrogen as calibration gases. Always use a two-stage pressure regulator set to 20 psi. Set the calibration gas flowmeter for a maximum of 5 scfh with the cal gas fitting removed from the probe. A diffuser/filter that is plugged over time may cause the flowmeter to deliver less flow to the sensing cell, but never readjust the flow rate until a new diffuser is installed. Readjusting the flowmeter back up to the 5 scfh level could pressurize the cell during calibration and cause the O reading to shift downwards.
2
2.5.2
The electronics determine if the calibration was successful and calculate new calibration values. New calibration values are not automatically loaded into the electronics after a successful calibration, however. The technician has the opportunity to accept or reject the new values. (A significant calibration change may cause a bump in the O2 readings at the DCS console, causing operator concern). Record the calibration data on a log (cell slope, constant, and impedance, as well as the speed of response data). If the electronics is used, it stores calibration data for the past 10 successful calibrations.
CAUTION!
READING ERRORS
Make sure the calibration gas cap is replaced tightly after calibration is complete. A loose or missing cap can permit fresh air to bias the O2 readings high in processes that run at negative pressure.

Fully automatic calibration

For fully automatic calibration, the Rosemount 6888 Xi Electronics must manage the actuation of solenoids to introduce gases into the probe.
Rosemount 6888 Probes with standard electronics housing
In addition to the Rosemount 6888 Xi, this arrangement requires a separate single probe sequencer (SPS), which is a solenoid box for switching calibration gases or a larger intelligent multiprobe sequencer (IMPS) which can handle the autocal for up to four probes in one box.
The automatic calibrations can be initiated in several ways:
26 6888C
Page 33
Configuration, startup, and operation
Via a calibration recommended diagnostic that is periodically checking cell
impedance
Via push button on the Rosemount 6888 Xi Electronics
Via HART communications from a 475 handheld communicator or AMS
Via an external contact closure
Via time since the last successful calibration
If the O2 measurement is being used for automatic control, always place the O2 control loop into manual prior to calibrating. Always inform the operator prior to calibrating. The Rosemount 6888 Xi Electronics provides an in cal contact closure for this purpose. An initiate cal contact is also provided.
The Rosemount 6888 Xi Electronics sequences the calibration gases in turn into the sensing cell. A 300 second flow time is the factory default for both gases and also for the purge cycle, which lets the probe signal come back to the normal flue gas readings. The 4-20 mA signal representing O2 can be held during the calibration cycle or permitted to vary with the bottled gases, in which case a record of the calibration can be trended at the DCS.
Calibration setup is found under the detailed setup menu.
Rosemount 6888 Probe with integral autocal housing
This probe contains the autocal solenoids within the blue electronics housing, eliminating the need and cost for an SPS or IMPS solenoid enclosure. Both calibration gases are permanently piped into two ports on the probe. It's important to confirm that there are no piping leaks or the calibration bottles will leak down permanently.
The calibration sequence from the Rosemount 6888 Xi Electronics is identical to that for the manual/semiautomatic calibration, but note that with the integral autocal version of this probe it is not possible to conduct a manual calibration. The factory offers a probe rebuild capability if solenoid or other failures occur.
CAUTION!
LEAKS
Calibration gas bottles ARE piped and under pressure at all times, so be sure to leak-check all fittings, tubing, and connections. Always use dual-stage pressure regulators.
Quick Start Guide 27
Page 34
Configuration, startup, and operation
28 6888C
Page 35
Rosemount™ 6888C Product Certifications
Appendix A Rosemount™ 6888C Product Certifications
A.1 European Directive information
A copy of the EC Declaration of Conformity can be found at the end of this Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at
Emerson.com/Rosemount.
A.2 Ordinary location certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
A.3 Installing equipment in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The marking must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes.
A.4
USA/Canada
Model String Option Code
CSA Certificate
Standards
C
70100758
CAN/CSA Standard C22.2 No.0-10:2015, CAN/CSA C22.2 No. 61010-1-12 Harmonized UL 61010-1:2012 (3rd Edition), CAN/CSA Standard C22.2 No. 94.1-15 Harmonized ANSI/UL Standard 50 (2nd Edition), CAN/CSA Standard C22.2 No. 94.2-15 Harmonized ANSI/UL Standard 50 (2nd Edition), CAN/CSA C22.2 No. 60529:16 and ANSI/ISA 60529:04, CAN/CSA Standard C22.2 No. 30-M1986: 2016, CAN/CSA­C22.2 No. 60079-0: 2015, CAN/CSA-C22.2 No. 60079-1:2016, FM 3600:2011, FM 3615:2006, ANSI/UL-60079-0:2013 (6th Edition), ANSI/ UL-60079-1:2015 (7th Edition)
Quick Start Guide 29
Page 36
Rosemount
6888C Product Certifications
Markings
Conditions of acceptability
1. The unit is intended to be connected to supply mains by qualified personnel in accordance with national (e.g. CEC, NEC, etc) and local codes.
2. Suitable APPROVED switch and fuse or a circuit breaker shall be provided to facilitate the disconnection of mains power.
3. The maximum operating ambient is considered as follows: 90 °C for 6888C DR Probe, 70 °C for 6888C Transmitter.
4. Mounting Flange temperature shall not exceed 190 °C during combustion process.
5. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gas mixture of which oxygen represents no more than that normally present in air.
6. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during the normal operations of the equipment.
7. The 6888C O2 Analyzers are used with the 6888 Xi Advanced Electronics, which must be installed in a Non-Hazardous Location, per wiring diagram 6R00131.
8. Meets Enclosure Type 4X & IP66 ratings when the reference air vent is routed to a dry area.
9. Units installed with conduit runs must have suitably certified conduit seals installed at the enclosure.
10. Units installed with other than conduit runs and conduit seals, must be fitted with certified or listed cable glands for use in “Class I, Zone 1, Ex/AEx d IIB+H2” and “Class I, Division 1, Group B, C and D” or better, suitable for the ambient temperature range.
11. Flameproof joints are not intended to be repaired.
Type 4X, IP66, Class 1, Division 1, Groups B, C and D; T3, Class 1, Zone 1, AEx db IIB+H2 T3 Gb, Ex db IIB+H2 T3 Gb: -40 °C ≤ Ta ≤ +70 °C ( Autocal Housing and Probe assembly); -40 °C ≤ Ta ≤ +90 °C (Standard Housing and Probe assembly eq. “DR Probe”)
A.5
30 6888C
Europe
Model String Option Code
ATEX Certificate
Standards
Markings
Special conditions for safe use (X):
1. Mounting flange temperatures shall not exceed 190 °C during combustion process.
A
Sira 14ATEX1031X
EN 60079-0:2012/A11:2013, EN 60079-1:2014
II 2 G Ex db IIB+H2 T3 Gb; IP66; -40 °C ≤ Ta ≤ +70°C ( Autocal Housing and Probe assembly); -40 °C ≤ Ta ≤ +90°C (Standard Housing and Probe assembly eq. “DR Probe”)
Page 37
Rosemount
6888C Product Certifications
2. The 6888C O2 Analyzers are used with the 6888 Xi Advanced Electronics (associated equipment not part of this certification) which must be installed in a Safe Area.
3. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gas other than inert/oxygen gas mixture of which oxygen represents no more than that normally present in air.
4. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during the normal operations of the equipment.
5. Fasteners property class must be A2-70 Stainless Steel.
6. Flameproof joints are not intended to be repaired.
Model String Option
A
Code
IECEx Certificate
Standards
Markings
IECEx CSA 14.0044X
IEC 60079-0:2012/A11:2013, IEC 60079-1:2014
Ex db IIB+H2 T3 Gb; IP66; -40°C ≤ Ta ≤ +70°C ( Autocal Housing and Probe assembly ); -40 °C ≤ Ta ≤ +90°C (Standard Housing and Probe assembly eq. “DR Probe”)
Special conditions for safe use (X):
1. Mounting Flange temperature shall not exceed 190 °C during combustion process.
2. The 6888C O2 Analyzers are used with the 6888 XI Advanced Electronics (associated equipment not part of this certification) which must be installed in a safe area.
3. Calibration air lines and reference air lines shall not contain pure oxygen or combustible gases other than inert/oxygen gas mixture of which oxygen represents no more than that normally present in air.
4. The pressure within the enclosure and gas lines shall not be higher than 1.1 times the atmospheric pressure during the normal operations of the equipment.
5. Fasteners property class must be A2-70 Stainless Steel.
6. Flameproof joints are not intended to be repaired.
Quick Start Guide 31
Page 38
EU DECLARATION OF CONFORMITY
(No. 1700912)
6888A/6888C
This declaration is issued under the sole responsibility of the manufacturer: Rosemount Inc., 8200 Market Blvd., Chanhassen, MN 55317 USA The product,
6888 Oxygen Transmitter, Models 6888A and 6888C
to which this declaration relates, is in conformity with relevant Union harmonization legislation: (2014/30/EU) EMC Directive (2014/35/EU) Low Voltage Directive (2014/68/EU) Pressure Equipment Directive
This equipment has been designed and manufactured with sound engineering practices in accordance with Article 4, Paragraph 3 of the PED
(2014/34/EU) ATEX Directive (Model 6888C)
Provisions of the directive fulfilled by the equipment: Equipment Group II category 2 G Ex db
EC Type Examination Certificate: Sira14ATEX1031X
EC-Type Examination Certificate issued by Sira (0518), Rake Lane Eccleston Chester CH4 9JN, United Kingdom Product Quality Assessment Notification issued by SGS Baseefa (1180), Rockhead Business Park, Staden Lane, Buxton SK17 9RZ United Kingdom
IIB+H2 T3 Gb (-40°C ≤ Ta ≤ 70°C)
Assumption of conformity is based on the application of the harmonized standards: EN 61326-1:2013 Electrical equipment for measurement, control and laboratory use. EMC
requirements. General requirements
EN 61010-1:2010 Safety requirements for el ectri cal equipment for measurement, control,
and laboratory use. General requirements
EN 60079-0:2012+A11:2013 Explosive atmospheres. Equipment. General requirements. (Certified to
60079-0:2012, meets /A11:2013 which does not have any major technical change)
EN 60079-1:2014 Explosive atmospheres. Equipment protection by flameproof enclosures
"d"
_______________________ Vice President Global Quality, Engineering, & Approvals
(Signature) (Function name)
Chris LaPoint July 1, 2017
(Name printed) (Date of issue)
Page 39
Rosemount™ 6888C Product Certifications
32 6888C
Page 40
GLOBAL HEADQUARTERS Emerson Automation Solutions 6021 Innovation Blvd Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888 +1 952 949 7001
gas.csc@emerson.com www.Emerson.com/RosemountGasAnalysis NORTH AMERICA Rosemount 8200 Market Boulevard Chanhassen, MN 55317
Toll Free + 1 800 999 9307
F +1 952 949 7001
gas.csc@emerson.com www.Emerson.com/RosemountGasAnalysis
CMB-QSG-6888C
Rev B
2017
EUROPE
Emerson Automation Solutions Neuhofstrasse 19a P.O. Box 1046 CH-6340 Baar Switzerland
T + 41 (0) 41 768 6111
F + 41 (0) 41 768 6300
gas.csc@emerson.com www.Emerson.com/RosemountGasAnalysis
Linkedin.com/company/Emerson-Automation-Solutions
twitter.com/rosemount_news
Facebook.com/Rosemount
youtube.com/RosemountMeasurement
google.com/+RosemountMeasurement
AnalyticExpert.com
MIDDLE EAST AND AFRICA
Emerson Automation Solutions Emerson FZE Jebel Ali Free Zone Dubai, United Arab Emirates, P.O. Box 17033
T +971 4 811 8100 F +971 4 886 5465 gas.csc@emerson.com
www.Emerson.com/RosemountGasAnalysis
©
2017 Emerson. All rights reserved.
The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.
ASIA-PACIFIC
Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 Singapore
T +65 777 8211 F +65 777 0947 gas.csc@emerson.com
www.Emerson.com/RosemountGasAnalysis
Loading...