Rosemount Analytical 6888 Specifications

Product Data Sheet
December 2017
CMB-PDS-6888
Rosemount™ 6888 In-Situ Oxygen Transmitter
The new standard for combustion flue gas analysis
The RosemountTM 6888 combustion ue gas transmitter provides a continuous, accurate measurement of the oxygen remaining
in ue gases coming from any combustion process. Accurate measurements of furnace exhaust excess oxygen are critical for combustion optimization, resulting in reduced energy costs, increased safety, and lower emissions. Reduction of overall downtime and maintenance can be achieved with the Rosemount 6888's robust oxygen sensor and autocalibration capabilities.
Overview
Proven performance and reliability
 Robust zirconia oxygen sensing cell with catalytic platinized beads increases cell
lifetime in presence of sulfur and other poisoning agents.
Outstanding accuracy: ±0.75% of reading or ±0.05% O2. Rugged explosion-proof design for hazardous area approvals satises ATEX/IECEX Ex d
and CSA Class 1, Division 1/Zone 1.
Advanced sensor diagnostics
Calibration recommended diagnostics. Plugged diffuser/lter diagnostics. Low oxygen diagnostics and O2 readings during reducing conditions.
Adaptability
 Completely eld repairable and adaptable to nearly any existing O2 probe installation
(Westinghouse World Class, Rosemount Oxymitter, and most competitive O2 probe installations).
 Variable probe insertion options.
Contents
RosemountTM 6888A In-Situ Oxygen Transmitter for general
purpose locations ........................................................................3
RosemountTM 6888C In-Situ Oxygen Transmitter for hazardous
locations .....................................................................................6
RosemountTM SPS 4001B and Rosemount IMPS 4000
Autocalibration Devices for general purpose locations ...............10
2 3
2
How to order: Complete Oxygen Analysis system ............... 12
Specications ..................................................................... 13
RosemountTM 6888 product certications...........................16
Dimensions ........................................................................19
Accessories......................................................................... 27
www.Emerson.com/RosemountGasAnalysis
December 2017 December 2017Rosemount 6888 Oxygen Transmitter Rosemount 6888 Oxygen Transmitter
RosemountTM 6888A In-Situ Oxygen Transmitter for general purpose locations
The RosemountTM 6888A combustion ue gas transmitter is a
solution for optimizing any industrial or large commercial boiler, red heater, or kiln. The Rosemount 6888A, as part of an oxygen trim system, improves plant energy efciency and lowers energy costs. It not only meets application requirements but also is simple to install, commission, and operate. The sensor, diffusers, and accessories for the Rosemount 6888A were developed to provide the greatest performance and longevity even in the harshest of process conditions.
 World-class performance and outstanding accuracy: ±0.75% of
reading or ±0.05% O
Digital communications: HART® 5 and Foundati onTM Fieldbus Resilient sensing cells provide protection to sulfur and other
poisoning agents present in ue gas
Specication and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 13 for more information on material selection.
2
Table 1. Rosemount 6888A In-Situ Oxygen Transmitter for General Purpose Locations
Model Sensor type
6888A In-Situ Oxygen Transmitter
Measurement
1
1OXY
2
2OXY
Probe length and type/shield
1 18 in. (457 mm) standard probe tube
3
2
3 18 in. (457 mm) abrasion-resistant probe tube
4 3 ft (0.91 m) standard probe tube
3
5
6 3 ft (0.91 m) abrasion-resistant probe tube
7 6 ft (1.83 m) standard tube
3
8
9 6 ft (1.83 m) abrasion-resistant probe tube
3
A
AA 9 ft (2.74 m) probe with abrasive shield accessory package (mounting hardware included)
3
B
BA 12 ft (3.66 m) probe with abrasive shield accessory package (mounting hardware included)
Oxygen - standard sensing cell
Oxygen - acid resistant sensing cell
18 in. (457 mm) probe with abrasive shield accessory package (mounting hardware included)
3 ft (0.91 m) probe with abrasive shield accessory package (mounting hardware included)
6 ft (1.83 m) probe with abrasive shield accessory package (mounting hardware included)
9 ft (2.74 m) probe with abrasion-resistant probe body
12 ft (3.66 m) probe with abrasion-resistant probe body
www.Emerson.com/RosemountGasAnalysis
3
Diffuser
1 Snubber diffuser for service to 400 °C (750 °F)
1A Snubber diffuser for service to 400 °C (750 °F) with dust seal for use with abrasive shield
1F Snubber diffuser for service to 400 °C (750 °F) with ashback arrestor
2 Ceramic diffuser for service to 825 °C (1517 °F)
2A Ceramic diffuser for service to 825 °C (1517 °F) with dust seal for use with absrasive shield
2F Ceramic diffuser for service to 825 °C (1517 °F) with ashback arrestor
3 Hastelloy diffuser for service to 705 °C (1300 °F)
3A Hastelloy diffuser for service to 705 °C (1300 °F) with dust seal for use with abrasive shield
Housing & electronics
1HT Standard housing, digital probe, HART protocol
2HT Integral autocalibration housing, digital probe, HART protocol
4FF Integral autocalibration housing, digital probe, Foundation Fieldbus protocol
5DR Standard housing, direct replacement probe, traditional architecture
6DRY Standard housing, direct replacement probe, with cold junction for YEW electronics
Mounting plate
00 No additional mounting hardware
04 New installation - square weld plate, ANSI: 6 x 6 in. (152.4 x 152.4 mm), 2.5 in. (63.5 mm) clearance hole, 4.75 in.
(120.65 mm) bolt circle, 5/8-11 studs
05 New installation - square weld plate, DIN 6 x 6 in. (152.4 x 152.4 mm), 2.5 in. (63.5 mm) clearance hole, 4.75 in.
(120.65 mm) bolt circle, 5/8-11 studs
06 New installation - variable insertion mount, abrasion-resistant probe only
07 New installation - variable insertion mount, mounted to existing OXT/WC abrasive shield mount; abrasion resistant probe only
08 Adapter plate for existing ANSI 3 in. (76.2 mm) 150# ange
09 Adapter plate for existing ANSI 4 in. (101.6 mm) 150# ange
10 Adapter plate for existing ANSI 6 in. (152.4 mm) 150# ange
11 Adapter plate for existing ANSI 3 in. (76.2 mm) 300# ange
12 Adapter plate for existing ANSI 4 in. (101.6 mm) 300# ange
99 Special adapter -provide existing ange dimensions, including thru-hole diameter
Manual calibration accessories
00 None
01 Calibration and reference gas owmeters and reference air lter regulator, provided loose
02 Calibration and reference gas owmeters and reference air lter regulator, mounted in a panel
Enable: Stochiometer indicator for reducing conditions
0 No
1 Yes
Enable: Programmable reference function
0 No
1 Yes
Enable: Extended temperature function
0 No
1 Yes
4
4
4
4 5
www.Emerson.com/RosemountGasAnalysis
December 2017 December 2017Rosemount 6888 Oxygen Transmitter Rosemount 6888 Oxygen Transmitter
Enable: Diffuser warning
4
0 No
1 Yes
1. Standard sensing cell includes catalytic protection beads which protect the sensor from sulfur and other poisoning agents.
2. Acid-resistant sensing cell includes additional catalytic protection beads compared to standard sensing to protect the sensor from sulfur and other poisoning agents.
3. Abrasive shield tube ordered separately.
4. Foundation Fieldbus versions only (for HART versions, order this feature with Rosemount Xi Electronics).
www.Emerson.com/RosemountGasAnalysis
RosemountTM 6888C In-Situ Oxygen Transmitter for hazardous locations
The RosemountTM 6888C combustion ue gas
transmitter is a solution for optimizing boilers or red heaters located in areas with hazardous requirements. The Rosemount 6888C's calibration equipment is simplied in hazardous areas with the approved integrated automatic calibration housing option. Maintenance costs are reduced with the redesigned modular diffuser and process ame arrestor assembly.
 Rugged explosion-proof design satises ATEX/
IECEx Ex d and CSA Class 1, Division/Zone 1 approval requirements.
 Digital communications: HART® 5 standard,
FoundationTM Fieldbus, and AMS/PlantWeb
 Resilient sensing cells provide protection to sulfur and
other poisoning agents present in ue gas.
Additional information
Specications can be found on page 13. Drawings are provided on page 19.
®
Specication and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 13 for more information on material selection.
Table 2. Rosemount 6888C In-Situ Oxygen Transmitter for Hazardous Locations
Model Product description
6888C In-Situ Oxygen Transmitter for hazardous locations
Measurement
1OXY Oxygen - standard sensing cell
2OXY Oxygen - acid resistant sensing cell
Probe length and mounting flange
1A 18 in. (457 mm) probe with ANSI ange: 7.5 in (190.5 mm). O.D., 6.00 in. (152.4 mm) bolt hole pattern diameter, 0.75 in.
1D 18 in. (457 mm) probe with DIN ange: 8.25 in. (209.55 mm) O.D., 6.69 in. (170 mm) bolt hole pattern diameter, .71 in. (18 mm)
2A 3 ft (0.91 m) probe with ANSI ange: 7.5 in (190.5 mm). O.D., 6.00 in. (152.4 mm) bolt hole pattern diameter, 0.75 in.
2D 3 ft (0.91 m) probe with DIN ange: 8.25 in. (209.55 mm) O.D., 6.69 in. (170 mm) bolt hole pattern diameter, .71 in. (18 mm) bolt
3A 6 ft (1.83 m) probe with ANSI ange: 7.5 in (190.5 mm). O.D., 6.00 in. (152.4 mm) bolt hole pattern diameter, 0.75 in.
3D 6 ft (1.83 m) probe with DIN ange: 8.25 in. (209.55 mm) O.D., 6.69 in. (170 mm) bolt hole pattern diameter, .71 in. (18 mm) bolt
1
(19.05 mm) bolt hole diameter
bolt hole diameter
(19.05 mm) bolt hole diameter
hole diameter
(19.05 mm) bolt hole diameter
hole diameter
6 7
www.Emerson.com/RosemountGasAnalysis
December 2017 December 2017Rosemount 6888 Oxygen Transmitter Rosemount 6888 Oxygen Transmitter
Diffuser
1 Snubber diffuser for service to 400 °C (750 °F)
2 Ceramic diffuser for service to 825 °C (1517 °F)
3 Hastelloy diffuser for service to 705 °C (1300 °F)
Housing and electronics
1HT Standard housing, digital probe, HART protocol
2HT Integral autocalibration housing, digital probe, HART protocol
4FF Integral autocalibration housing, digital probe, Foundation Fieldbus protocol
5DR Standard housing, direct replacement probe, traditional architecture
6DRY Standard housing, direct replacement probe, with cold junction for YEW electronics
Certifications
A ATEX/IECEx
C CSA
Mounting plate
00 No additional mounting hardware
04 New installation plate - 7.75 in. (196.85 mm) square diameter, 3.25 in. (82.55 mm) clearance hole, 6.00 in. (152.4 mm) bolt circle,
5/8-11 UNC studs
05 New installation plate - 8.46 in. (215 mm) square diameter, 3.25 in. (82.5) mm clearance hole, 6.7 in. (170 mm) bolt circle, M16 x
2 studs
09 Adapter plate for existing ANSI 4 in. (101.6 mm),150# ange
10 Adapter plate for existing ANSI 6 in. (152.4 mm), 150# ange
11 Adapter plate for exisiting ANSI 3 in. (76.2 mm), 300# ange
12 Adapter plate for existing ANSI 4 in. (101.6 mm), 300# ange
99 Special adapter - provide existing ange dimensions, including thru-hole diameters
Manual calibration accessories
00 None
01 Calibration and reference gas owmeters and reference air lter regulator, provided loose
02 Calibration and reference gas owmeters and reference air lter regulator, mounted in a panel
Enable: Stoichiometer indicator for reducing conditions
0 No
1 Yes
Enable: Programmable reference function
0 No
1 Yes
Enable: Extended temperature function
0 No
1 Yes
Enable: Diffuser warning
0 No
1 Yes
1. Foundation Fieldbus versions only (for HART versions, order this feature with Rosemount Xi Electronics).
1
1
1
1
www.Emerson.com/RosemountGasAnalysis
RosemountTM 6888 Xi Digital Transmitter for general purpose locations
The Rosemount 6888 Xi brings an at a glance view of pertinent information provided by an easy to use display and interface which effortlessly connects with a PLC or DCS via HART®/4-20 mA. It creates a centralized infrastructure for remote autocalibration devices, diagnostic tools, alarm relay(s), and advanced application features. The Roesmount 6888Xi is congurable to have up to two channels for digital inputs or one channel for supporting traditional architectures.
Easy to use operator interface and design Plugged diffuser diagnostic measures response time and
detects a plugged diffuser or empty gas bottle
 Stochiometer provides an oxygen reading during reducing
conditions, indicating extent of O2 deciency
Additional information
Specications can be found on page 13. Drawings are provided on page 19.
Specication and selection of product materials, options, or components must be made by the purchaser or the equipment. See page 13 for more information on material selection.
Table 3. Rosemount 6888 Xi Digital Transmitter for General Purpose Locations
Model Product description
6888Xi Digital Transmitter
Measurement
1OXY Single digital input (HART)
2OXY Single digital input (HART) and ame safety interlock for heater
3OXY Two digital inputs (HART)
1
4OXY
Mounting
00 No hardware
01 Panel mount kit with gasket
02 2 in. pipe/wall mount kit
2
Cable
00 No cable
10 20 ft (6 m) cable, use with traditional architecture probe only
11 40 ft (12 m) cable, use with traditional architecture probe only
12 60 ft (18 m) cable, use with traditional architecture probe only
13 80 ft (24 m ) cable, use with traditional architecture probe only
14 100 ft (30 m) cable, use with traditional architecture probe only
15 150 ft (45 m) cable, use with traditional architecture probe only
1
Single traditional architecture input
8 9
www.Emerson.com/RosemountGasAnalysis
December 2017 December 2017Rosemount 6888 Oxygen Transmitter Rosemount 6888 Oxygen Transmitter
Enable: Stochiometer indicator for reducing conditions
00 No
01 Single channel
02 Dual channel
Enable: Programmable reference function
00 No
01 Single channel
02 Dual channel
Enable: Extended temperature function
00 No
01 Single channel
02 Dual channel
Enable: Plugged diffuser diagnostics
00 No
01 Single channel
02 Dual channel
1. Compatible with oxygen probes utilizing a 120 V heater only.
2. Cables are not rated for use in hazardous locations and must be installed in accordance with local and national codes.
www.Emerson.com/RosemountGasAnalysis
RosemountTM SPS 4001B and Rosemount IMPS 4000 Autocalibration Devices for general purpose locations
The Rosemount SPS 4001B and Rosemount IMPS 4000 are cost-effective calibration systems which conveniently sequence calibration gases without any labor from an operator or maintenance technician. Calibration owmeter(s) and reference air owmeter(s)/regulator(s) are included with the autocalibration manifold. The calibration can be initiated by a contact relay or timer or automatically via calibration recommended diagnostic. The Rosemount SPS 4001B is designed to automatically calibrate one oxygen analysis system. The Rosemount IMPS 4000 is congurable to automatically calibrate one to four oxygen analysis systems. Both the Rosemount SPS 4001B and Rosemount IMPS 4000 require a Rosemount 6888 Xi Transmitter or Oxymitter electronics.
 Complete autocalibration assembly: includes calibration
owmeter and reference air owmeter/regulator and solenoids mounted on a single manifold
 Automatic calibrations reduce operator time to ensure
continuously accurate readings
 Rosemount IMPS 4000 enclosure designed to accept
a customer's z-purge system to meet hazardous area requirements
Additional information
Specications can be found on page 13. Drawings can be found on page 19.
Specication and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 13 for more information on material selection.
10 11