This guide provides basic guidelines for Rosemount Wireless Pressure Gauges. It does not provide
instructions for configuration, diagnostics, maintenance, service, troubleshooting, or intrinsically safe
(I.S.) installations. Refer to the Rosemount Wireless Pressure Gauge Reference Manual for more
instruction. The manual and this guide are also available electronically.
Shipping considerations
The device is shipped with the battery installed.
Each device contains one “D” size primary lithium-thionyl chloride battery. Primary lithium
batteries are regulated in transportation by the U.S. Department of Transportation, and are also
covered by IATA (International Air Transport Association), ICAO (International Civil Aviation
Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the
responsibility of the shipper to ensure compliance with these or any other local requirements.
Consult current regulations and requirements before shipping.
WARNING
Explosions could result in death or serious injury.
Installation of device in an explosive environment must be in accordance with appropriate local,
national, and international standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-incendive field practices.
Electrical shock could cause death or serious injury.
Care must be taken during transportation of device to prevent electrostatic charge build-up.
Device must be installed to ensure a minimum antenna separation distance of 8 in. (20 cm) from
all persons.
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Failure to follow these installation guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end
users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for
all systems used within the facility.
Declaration of conformity.......................................................................................................... 21
China RoHS................................................................................................................................ 24
Quick Start Guide3
Quick Start GuideFeburary 2021
4Emerson.com/Rosemount
AMS
Feburary 2021Quick Start Guide
1Required equipment
Anti-seize paste or PTFE tape (for
NPT threaded connection)
Standard tools, e.g. screwdriver,
wrench, pliers
AMS Wireless Configurator
version 12.0 or later, or Field
Communicator
Quick Start Guide5
Quick Start GuideFeburary 2021
2What's in the box?
Wireless Pressure GaugeQuick Start Guide
The following options are also available and will ship with the Rosemount
Wireless Pressure Gauge if ordered.
Rosemount 306 Integral Manifold (Model
code S5)
6Emerson.com/Rosemount
B4 Bracket (Model code B4)
Feburary 2021Quick Start Guide
Rosemount 1199 Seal (Model code S1)
Product Certification (Model Codes
Normal Range Indication (Model code LK)
below)
Q4: Calibration Cert
QG: Calibration Cert and GOST
Verification Cert
QP: Calibration Cert and Tamper Evident
Seal
Q8: Material Traceability cert per EN
102043.1
Q15: Cert of Compliance to NACE
MR0175/ISO 15156 for wetted materials
Q25: Cert of Compliance to NACE
MR00103 for wetted materials
Quick Start Guide7
Quick Start GuideFeburary 2021
3Optional: Power/device check
The device is designed to be installation-ready. To check device battery prior
to installation, perform the following:
Procedure
1. Perform Turn on device.
2. Slide the ON/OFF switch to the OFF position until ready for use.
8Emerson.com/Rosemount
Feburary 2021Quick Start Guide
4Optional: Normal range indication option
Procedure
1. Modify each of the stickers to desired size prior to proceeding to step
Step 2.
The stickers are intended to be installed on the dial only and should
not be applied on the inside or outside of the housing cover.
2. Remove housing cover.
3. Slide ON/OFF switch to the OFF position and wait for LED to stop
flashing.
4. Gently move the needle in the clockwise direction until it is pointing
at the Red X.
Note
Use caution as the electronics assembly is connected to the needle.
5. Remove any debris on the dial, so it does not become trapped under
the sticker.
6. Peel back the white paper backing of the sticker.
7. Slowly lower the sticker onto the surface of the dial in the desired
location and rub it in place firmly. Repeat steps 6 and 7 until desired
indication locations are set.
• Stickers should be applied in an environment where the ambient
temperature is above 50 °F (10 °C).
• Moving the sticker after initial contact is not recommended as
this decreases the amount of adhesive on the back of the sticker.
8. Slide ON/OFF switch to the ON position.
9. Replace housing cover.
Quick Start Guide9
OR
Quick Start GuideFeburary 2021
5Installation procedure
Figure 5-1: Seal and protect threads
Figure 5-2: Mount device
Note
Use wrench on flats, not on housing.
5.1
Mounting orientation
The low side pressure port (atmospheric reference) on the process pressure
gauge is located in the neck of the device behind the housing. The vent path
is between the housing and sensor.
CAUTION
Keep the vent path free of any obstruction, including but not limited to
paint, dust, and lubrication by mounting the device so the process can drain
away.
10Emerson.com/Rosemount
A
Feburary 2021Quick Start Guide
Figure 5-3: Low Side Pressure Port
A. Low side pressure port (atmospheric reference)
5.2Turn on device
Check to ensure the device and battery are working properly.
Procedure
1. Twist the cover counterclockwise to remove it.
2. Slide the OFF/ON switch to the ON position to initiate the power
sequence.
Note
During the power sequence, the dial tests full range of motion and
LED flashes amber.
3. Once the power sequence ends, verify the LED flashes green.
Quick Start Guide11
1 2 3
64 5
8 709
A
B
C
Quick Start GuideFeburary 2021
Note
The LED may display several colors; see Table 6-1in Troubleshooting
for device statuses.
5.3Connect to device
A. Field Communicator
B. HART® Modem
C. AMS Wireless Configurator
5.4Field Communicator
Procedure
1. Turn on the Field Communicator.
2. From the Main menu, select the HART® symbol.
5.5
5.6
12Emerson.com/Rosemount
AMS Wireless Configurator
Procedure
1. Start AMS Wireless Configurator.
2. From the View menu, select Device Connection View.
3. Double click the device under the HART® modem.
Eliminate mounting effects
Devices are factory-calibrated. Once installed, it is recommended to perform
this step to eliminate potential error caused by mounting position or static
pressure. Instructions for using a Field Communicator are listed below.
Feburary 2021Quick Start Guide
Note
See the Rosemount Wireless Pressure Gauge Reference Manual for the
following:
• Using AMS Wireless Configurator
• Sensor trim function on absolute gauge
Procedure
1. Vent the device.
2. Connect the Field Communicator.
3. From the HOME screen, enter the HART® Fast Key sequence.
Device dashboard Fast
Keys
4. Follow the commands to perform the procedure.
5.7Activate wireless
Do not activate wireless until Smart Wireless Gateway is installed and
functioning properly; toggling off and on reduces battery life.
Note
If Network ID and Join Key is specified at order entry, then the device will
automatically search and connect to the wireless network when powered
on.
5.8
Join device to network
Procedure
1. Obtain Network ID and Join Key for the wireless network (available in
wireless gateway).
2. From the HOME screen, enter the HART® Fast Key sequence.
Device dashboard Fast
Keys
3. Follow the commands to perform the procedure.
4. Select Overview>Status.
5. Verify the communication status displays Connected.
2, 1, 1
2, 1, 2
Note
Joining the device to the network could take several minutes.
Quick Start Guide13
Quick Start GuideFeburary 2021
6Troubleshooting
This section provides information for basic troubleshooting. See Wireless
Pressure Gauge Reference Manual for advanced troubleshooting.
Device status
The flashing LED indicates device status using the colors descibed.
Table 6-1: Status Descriptions
LED colorDevice status
GreenFunctioning properly
Amber Battery is low, battery replacement recommended
RedBattery replacement required OR Device is
No
color
malfunctioning
No power, verify ON/OFF switch is in “on” position
6.1Pressure measurement
If the mounting effects have not been eliminated after completing Eliminate
mounting effects, perform this alternative procedure for verifying the
pressure value.
Procedure
1. From the HOME screen, eter the HART® Fast Key sequence.
Device dashboard Fast
Keys
2. Follow the commands to perform the procedure.
6.2
Wireless connectivity
If the device has not joined to the network after power up, verify the
following:
• Active Advertising has been enabled on the Smart Wireless Gateway
2, 2, 1, 1, 1
14Emerson.com/Rosemount
Feburary 2021Quick Start Guide
• Network ID and Join Key in the device match the Network ID and Join Key
of the Gateway
The Network ID and Join Key may be obtained from the Smart Wireless
Gateway on the Setup > Network > Settings page on the web interface.
Quick Start Guide15
Quick Start GuideFeburary 2021
7Product Certifications
Rev: 4.0
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EC Declaration of
Conformity can be found at www.rosemount.com.
Telecommunication compliance
All wireless devices require certification to ensure that they adhere to
regulations regarding the use of the RF spectrum. Nearly every country
requires this type of product certification. Emerson™ is working with
governmental agencies around the world to supply fully compliant products
and remove the risk of violating country directives or laws governing
wireless device usage.
FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following conditions: This devices may not cause harmful interference,
this devices must accept any interference received, including interference
that may cause undesired operation. This device must be installed to ensure
a minimum antenna separation distance of 20 cm from all persons.
This device complies with Industry Canada license-exempt RSS-247.
Operation is subject to the following two conditions: (1) this device may not
cause interference, and (2) this device must accept any interference,
including interference that may cause undesired operation of the device.
Changes or modification to the equipment not expressly approved by
Rosemount Inc. could void the user's authority to operate the equipment.
Cet appareil est conforme à la Partie 15 de la réglementation FCC. Son
fonctionnement est soumis aux conditions suivantes: Cet appareil ne doit
pas causer d'interférences nuisibles. Cet appareil doit accepter toute
interférence reçue, incluant toute interférence pouvant causer un
fonctionnement indésirable. Cet appareil doit être installé pour assurer une
distance minimum de l'antenne de séparation de 20 cm de toute personne.
Cet appareil est conforme à la norme RSS-247 Industrie Canada exempt de
licence. Son fonctionnement est soumis aux deux conditions suivantes: (1)
cet appareil ne doit pas provoquer d'interférences et (2) cet appareil doit
accepter toute interférence, y compris les interférences pouvant causer un
mauvais fonctionnement du dispositif.
Les changements ou les modifications apportés à l'équipement qui n'est pas
expressément approuvé par Rosemount Inc pourraient annuler l'autorité de
l'utilisateur à utiliser cet équipement.
16Emerson.com/Rosemount
Feburary 2021Quick Start Guide
Ordinary Location Certification from CSA
The product has been examined and tested to determine that the design
meets the basic electrical, mechanical, and fire protection requirements by
CSA, a nationally recognized test laboratory (NRTL) as accredited by the
Federal Occupational Safety and Health Administration (OSHA).
Installing in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone
marked equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined
in the respective codes.
7.1USA
I5 U.S.A. Intrinsically Safe (IS)
7.2
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. Do not replace battery when explosive atmosphere is present.
2. Use only 00G45-9000-0001 batteries.
3. The surface resistivity of the housing is greater than 1G Ω. To avoid
4. Substitution of components may impair intrinsic safety.
[CSA] 70047656
FM 3600 – 2011, FM 3610 – 2010, UL Standard 50 – Eleventh
IS CL I, DIV 1, GP A, B, C, D T4; Class 1, Zone 0, AEx ia IIC T4
Ga; T4 (-40 °C ≤ Ta ≤ +70 °C) when installed per Rosemount
drawing 00G45-1020; Type 4X; IP66/67
electrostatic charge build-up, it must not be rubbed or cleaned with
solvents or a dry cloth.
1. Do not replace battery when explosive atmosphere is present.
2. Use only 00G45-9000-0001 batteries. Utiliser uniquement des
3. The surface resistivity of the housing is greater than 1G Ω. To avoid
4. Substitution of components may impair intrinsic safety.
7.3Europe
I1 ATEX Intrinsic Safety
Intrinsically Safe for Class I, Division 1, Groups A, B, C, D T4; Ex
ia IIC T4 Ga T4 (-40 °C ≤ Ta ≤ +70 °C) when installed per
Rosemount drawing 00G45-1020; Type 4X; IP66/67
Ne pas remplacer les accumulateurs si une atmosphère explosive
peut être présente.
accumulateurs 00G45-9000-0001.
electrostatic charge build-up, it must not be rubbed or cleaned with
solvents or a dry cloth.
La résistivité de surface du boÎtier est supérieure à un gigaohm. Pour
éviter l’accumulation de charge électrostatique, ne pas frotter ou
nettoyer avec des produits solvants ou un chiffon sec.
La substitution de composants peut compromettre la sécurité
intrinsèque.
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The plastic enclosure may constitute a potential electrostatic ignition
risk and must not be rubbed or cleaned with a dry cloth.
2. The measured capacitance between the equipment enclosure and
metallic inline sensor module is 4.7 ㎊. This must be considered only
when the WPG is integrated into a system where the process
connection is not grounded.
3. Do not change the battery when an explosive atmosphere is present.
4. Only replace battery with Rosemount Part No. 00G45-9000-0001.
18Emerson.com/Rosemount
Baseefa16ATEX0005X
EN 60079-0: 2012 + A11: 2013, EN 60079-11: 2012
II 1 G Ex ia IIC T4 Ga, T4 (-40 °C ≤ Ta ≤ +70 °C) IP66/67
Feburary 2021Quick Start Guide
7.4International
I7 IECEx Intrinsic Safety
Certificate:
Standards:
Markings:
Special Conditions for Safe Use (X):
1. The plastic may constitute a potential electrostatic ignition risk and
2. The measured capacitance between the equipment enclosure and
3. Do not change the battery when an explosive atmosphere is present.
4. Only replace battery with Rosemount Part No. 00G45-9000-0001.
7.5Brazil
I2 INMETRO Intrinsic Safety
Certificate:
Standards:
Markings:
IECEx BAS 16.0012X
IEC 60079-0: 2011, IEC 60079-11: 2011
Ex ia IIC T4 Ga, T4 (-40 °C ≤ Ta ≤ +70 °C) IP66/67
must not be rubbed or cleaned with a dry cloth.
metallic inline sensor module is 4.7pF. This must be considered only
when the WPG is integrated into a system where the process
connection is not grounded.
Emerson Terms and Conditions of Sale are
available upon request. The Emerson logo
is a trademark and service mark of
Emerson Electric Co. Rosemount is a mark
of one of the Emerson family of
companies. All other marks are the
property of their respective owners.
www.emerson.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.