Rosemount TankMaster WinSetup Manuals & Guides

Page 1
Rosemount™ TankMaster™ WinSetup Configuration Software
Reference Manual
00809-0100-5110, Rev AA
December 2018
Page 2
Page 3
Reference Manual
00809-0100-5110, Rev AA

Contents

1Section 1: Introduction
2Section 2: The Main Window
Contents
December 2018
1.1 What is Rosemount TankMaster? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 TankMaster software package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Manual overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Technical documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.1 Reference manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.2 Product data sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Toolbar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3 Status bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4 Workspace - viewing tanks and devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4.1 Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4.2 Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.5 User management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.5.1 Logging on to TankMaster. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.5.2 Managing user accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5.3 Configuring a sub level description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.5.4 To set required access levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.5.5 To change protection level of separate windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.5.6 To change password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.5.7 To change inactivity timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.6 New connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.6.1 Connecting to another server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Content s
i
Page 4
Contents
December 2018
Reference Manual
00809-0100-5110, Rev AA
3Section 3: Basic Functions
3.1 Communication protocol setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.1.1 Master protocol channel configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.1.2 Slave protocol channel configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.1.3 Log file configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.1.4 Changing the current protocol channel configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.1.5 Protocol server configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.2 Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.2.1 Measurement units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.2.2 Ambient air temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.2.3 Inventory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.2.4 Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.2.5 Setting the name tag prefixes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.2.6 E-mail configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.2.7 Tank view layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.2.8 Tank visibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.3 Device installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.4 Tank installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.4.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.5 Level gauge calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.6 Tank capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.7 Tank Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4Section 4: Device Handling
4.1 To change device configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.2 To uninstall a device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
ii
Contents
Page 5
Reference Manual
00809-0100-5110, Rev AA
5Section 5: Service Functions
Contents
December 2018
5.1 Section overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
5.3 System status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
5.4 Customizing the Tools menu in WinSetup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
5.5 User defined temperature conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5.6 Viewing input and holding registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.7 To edit holding registers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.8 Viewing diagnostic registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.8.1 Configure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.8.2 Restore to default setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.9 Logging measurement data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.10Saving and loading database registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.10.1 To save device registers for a single device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.10.2 To save device registers for multiple devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5.10.3 To recover a device database . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.11Upgrading device firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
5.12Tank Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.12.1 Graph area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
5.12.2 Legend/Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.12.3 File storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.12.4 Action buttons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.12.5 Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5.13Viewing tank data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.13.1 Viewing data for all tanks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
5.13.2 Viewing data for a single tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.14Viewing alarm status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
5.15Protocol handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
5.15.1 Logging the channel communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
5.15.2 Saving the communication log to file . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
5.15.3 Searching for connected devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
5.15.4 Channel statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Content s
iii
Page 6
Contents
December 2018
Reference Manual
00809-0100-5110, Rev AA
5.16TankMaster Administrator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
5.16.1 Log on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
5.16.2 Changing the Administrator program password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
5.16.3 Autostart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
5.16.4 Backup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
5.16.5 Restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
5.16.6 File version information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
5.16.7 Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
5.17Proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
5.17.1 Proof test functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
iv
Contents
Page 7
Reference Manual
NOTICE
00809-0100-5110, Rev AA
Rosemount™ TankMaster™ WinSetup Configuration Software
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
For equipment service or support needs, contact your local Emerson Automation Solutions representative.
Title Page
December 2018
Title Page
v
Page 8
Title Page
December 2018
Reference Manual
00809-0100-5110, Rev AA
vi
Title Page
Page 9
Reference Manual
00809-0100-5110, Rev AA

Section 1 Introduction

What is Rosemount TankMaster? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1
TankMaster software package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2
Manual overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Technical documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Introduction
December 2018
Rosemount system. This manual describes the basic functions of the WinSetup configuration software, how to set up tank capacity tables (TCT), product parameters for inventory calculations, and various service functions. The manual includes a brief description of the recommended setup procedure for a Rosemount Tank Gauging system.
The Rosemount Tank Gauging product portfolio includes a wide range of components for small and large customized tank gauging systems. The system includes various field devices, such as radar level gauges, temperature transmitters, and pressure transmitters for complete inventory control. The TankMaster software suite provides you with the tools that you need to configure and operate the Rosemount Tank Gauging system. For detailed descriptions of how to setup various devices refer to the respective reference manuals. The Rosemount Tank Gauging System Configuration Manual comprehensive information on Rosemount Tank Gauging systems and how to use WinSetup for setting up Rosemount Tank Gauging systems. See “Technical documentation” on page 5 for a list of technical documentation.
TankMaste r™ WinSetup is the recommended tool for setting up a Rosemount Tank Gauging

1.1 What is Rosemount TankMaster?

Rosemount TankMaster is an Emerson Automation Solutions/Rosemount Tank Gauging inventory management software package for installation and configuration of level gauging equipment. It provides you with powerful and easy-to-use tools for installation and configuration of level gauging devices such as radar transmitter gauges (RTGs). Settings for protocols, devices and tanks can be changed in real time.
provides
Introduction
The graphical interface gives you a clear overview of installed devices and tanks. For each tank you can easily see the associated transmitters in the WinSetup application.
Key features
Monitoring of measured dataClear overview of installed tanks and devices (using WinSetup)Simple installation using wizards (using WinSetup)Open connectivityObject-oriented, user-friendly Graphical User Interface (GUI)
Rosemount TankMaster is designed to be used in a Microsoft access to measurement data from any PC in your network. Measurements and data are presented in realtime and you can customize views to suit your needs.
Rosemount TankMaster lets you connect via the TRL2, RS232, RS485, or Ethernet TCP/IP interfaces. Other communication interfaces, such as Enraf BPM, are also supported. Rosemount TankMaster is based on the open OPC standard, allowing you to import data into other systems such as DCS:s, PLC:s, Scada systems and Microsoft Office programs.
®
Windows environment, providing easy
1
Page 10
Introduction
WinOpi/WinSetup
Tank Server
Master Protocol Server Slave Protocol Server
COM1 COM2
December 2018

1.2 TankMaster software package

The TankMaster software package comprises several software modules such as:
WinOpiWinSetupWinViewTank ServerMaster Protocol serverSlave Protocol Server
Figure 1-1. Software Modules
Reference Manual
00809-0100-5110, Rev AA
WinOpi
WinOpi is the operator interface to the tank gauging system. It communicates with the Tank Server and various protocol servers to let the user monitor measured tank data. WinOpi also provides:
alarm handlingautomatic report distributionhistorical data samplinginventory calculations for volume, observed density and other parameters.
WinSetup
The WinSetup program is a graphical user interface (GUI) for installation, configuration and maintenance of level gauging devices.
WinView
WinView is the operator´s interface to the tank gauging system. It communicates with the Tank Ser ver and the different protocol servers to let the user monitor measured tank data. WinView also provides
2
alarm handling, automatic report handling as well as inventory calculations for volume and mass.
Introduction
Page 11
Reference Manual
00809-0100-5110, Rev AA
Tank Server
The Tan k Ser ver communicates with devices via the Master Protocol Server and handles configuration data for all installed tanks and devices. Parameters stored by the Tank Server include:
device namesconfiguration data, such as antenna typenumber of connected temperature sensorsnumber of connected analog inputs
The Tank Server collects data from connected devices and distributes this information to the WinOpi and WinSetup user interface.
Master protocol server
The Master Protocol Server transfers configuration data and measured data between the Tank Server and connected devices in the tank gauging system. The Master Protocol Server is able to communicate with various types of devices such as FCUs, the Rosemount 2410 Tank Hub, and the Rosemount 5900S Radar Level Gauge to collect measurements for, for example, level, temperature and pressure.
Slave protocol
Introduction
December 2018
The Slave Protocol Server is used to connect the Tan k Mas te r system to a host computer (DCS system). The Slave Protocol Server exchanges tank data between the Tank Ser ver and the host computer.
OPC Server with browser
Ta nk Ma st er uses OPC Data Access 2.0 (OLE for Process Control), an open industry standard, which eliminates the need for costly customized software integration.
With the OPC server and the browser it is easy to import all custody transfer and inventory data to other OPC clients such as different DCS:s, PLC:s, Scada systems, or Microsoft Office® programs.
See the web site for the OPC Foundation for more information: www.opcfoundation.org
Customized views
You can customize specific views and windows in Ta nk Ma ste r. Existing objects can be modified or new ones. You could, for example, create a window with an embedded image of your own plant, to give a realistic overview, and configure the window so that when you click on a specific tank in the image you can access the corresponding data for that tank.
Introduction
3
Page 12
Introduction
December 2018

1.3 Manual overview

The Rosemount TankMaster WinSetup Reference Manual includes the following sections:
Section 1: Introduction
A description of the various components in the Rosemount Tank Gauging system and an introduction to the TankMaster software package.
Section 2: The Main Window
An introduction to the basic features of the WinSetup configuration program. It describes the workspace, menus, and various toolbars.
Section 3: Basic Functions
A brief description of basic functions supported by the Rosemount TankMaster WinSetup configuration tool for setting up a Rosemount Tank Gauging system.
Section 4: Device Handling
This section describes basic functions for changing device configuration and uninstalling devices.
Section 5: Service Functions
Reference Manual
00809-0100-5110, Rev AA
A description of various functions supported by TankMaster WinSetup for service and maintenance of field devices.
4
Introduction
Page 13
Reference Manual
00809-0100-5110, Rev AA

1.4 Technical documentation

The Rosemount Tank Gauging System includes a wide portfolio of user documentation. For a complete list, see the Emerson™ Automation Solutions web page for Rosemount Tank Gauging
System and Rosemount Level Measurement products.

1.4.1 Reference manuals

Rosemount Tank Gauging System Configuration Manual (00809-0300-5100)Rosemount 2460 (00809-0100-2460)Rosemount 2410 (00809-0100-2410)Rosemount 5900S (00809-0100-5900)Rosemount 2240S (00809-0100-2240)Rosemount 2230 (00809-0100-2230)Rosemount 5900C (00809-0100-5901)Rosemount 5300 Series (00809-0100-4530)Rosemount 5400 Series (00809-0100-4026)Rosemount TankMaster Software Installation (00809-0400-5110)Rosemount TankMaster WinView (00809-0300-5110)Rosemount TankMaster WinOpi (00809-0200-5110)Rosemount TankMaster WinSetup (00809-0100-5110)Rosemount Wireless Tank Gauging System (300570)Rosemount TankMaster Floating Roof Monitoring Reference Manual (00809-0500-5100)
Introduction
December 2018

1.4.2 Product data sheets

Rosemount Tank Gauging System Data Sheet (00813-0100-5100)Rosemount 2460 System Hub Product Data Sheet (00813-0100-2460)Rosemount 2410 Product Data Sheet (00813-0100-2410)Rosemount 5900S Product Data Sheet (00813-0100-5900)Rosemount 5900C Product Data Sheet (00813-0100-5901)Rosemount 2240S Product Data Sheet (00813-0100-2240)Rosemount 2230 Product Data Sheet (00813-0100-2230)Rosemount 5300 Product Data Sheet (00813-0100-4530)Rosemount 5400 Product Data Sheet (00813-0100-4026)Rosemount Tank Gauging Installation Drawings
Introduction
5
Page 14
Introduction
Rosemount 2460 System Hub reference manual (Document No. 00809-0100-2460)
Rosemount 2410 Tank Hub reference manual (Document No. 00809-0100-2410)
Rosemount 5900S Radar Level Gauge reference manual (Document No. 00809-0100-5900)
Rosemount 2240S Multi-input Temperature Transmitter reference manual (Document No. 00809-0100-2240)
Rosemount 2230 Graphical Field Display reference manual (Document No. 00809-0100-2230)
Rosemount Tank Gauging system configuration manual
(Document No. 00809-0300-5100)
Rosemount TankMaster WinSetup reference manual
(Document No. 00809-0100-5110)
Rosemount TankMaster WinOpi reference manual
(Document No. 00809-0200-5110)
Rosemount TankMaster Software installation manual
(Document No. 00809-0400-5110
December 2018
Reference Manual
00809-0100-5110, Rev AA
Figure 1-2. System and Documentation Structure
6
Introduction
Page 15
Reference Manual
Minimize
Maximize
Close
Menubar
Toolbar
Work space
Status bar
00809-0100-5110, Rev AA

Section 2 The Main Window

Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10
Status bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Workspace - viewing tanks and devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
User management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
New connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24
The Main Window
December 2018
The Rosemount
TankMaste r ™main window includes the Workspace to display tanks and devices, a menu bar at the top of the screen, a status bar at the bottom of the screen and a number of buttons in the toolbar.
Figure 2-3. The WinSetup Main Window
The Main Window
7
Page 16
The Main Window
Right click in the Work space window and choose Allow Docking to place the Workspa ce window along the Main window side.
December 2018
The Workspace window can be moved anywhere on the Main window. It can be docked to either side, to the top, or to the bottom. It can also be left floating in the Main window.
Figure 2-4. The WinSetup workspace
Reference Manual
00809-0100-5110, Rev AA
8
The Main Window
Page 17
Reference Manual
00809-0100-5110, Rev AA

2.1 Menus

The menu bar at the top of the screen contains menus such as File, View, Service, Tools, and Help.
Figure 2-5. The WinSetup menu
Service menu options are also available by clicking the right mouse button. Different options are available depending on the type of object selected in the Workspace window. For example, clicking the right mouse button on the Devices folder will open the following menu:
Figure 2-6. Service menu
The Main Window
December 2018
The Main Window
Clicking the right mouse button on a device icon brings up a menu with different configuration and service options:
Figure 2-7. Right-click menu
9
Page 18
The Main Window
Hide/Show Toolbar
Toolbar
12 3456 78 9101112
December 2018

2.2 Toolbar

The toolbar provides buttons acting as shortcuts to certain menu options. Normally the Toolbar is visible. To hide it, open the View menu and deselect the Toolbar option:
Figure 2-8. The WinSetup Toolbar
Reference Manual
00809-0100-5110, Rev AA
Items included in the standard toolbar:
Figure 2-9. Toolbar items
1. Log off to View Only mode.
2. Log on to TankMaster as Operator, Supervisor or Administrator
3. Rename a tank
4. Search for a tank or a device in the workspace tree structure
5. Open the Properties dialog
6. Open the Tank View window
7. Install a new tank
8. Install a new device
9. Uninstall a tank
10. Uninstall a device
10
11. Turn the Workspace window On or Off
12. About WinSetup
The Main Window
Page 19
Reference Manual
A
B
C
D
E
00809-0100-5110, Rev AA

2.3 Status bar

The status bar is located at the bottom of the TankMaster main window. It provides general information about the current system state.
To hide the TankMaster status bar, open the View menu and deselect the Status bar option.
Figure 2-10. The WinSetup Status bar
The Main Window
December 2018
The Main Window
A. Status bar B. Connection status C. Current user D. Current protection level E. Indicator for normal operation
The status bar shows information about a device, tank or any other item that is selected in the WinSetup main window. Connection status, current user, current protection level (View Only, Operator etc.), and operation status are shown as well.
11
Page 20
The Main Window
Tab for the Logical View
Tab for the Physical View
December 2018

2.4 Workspace - viewing tanks and devices

The workspace displays an overview of all devices and tanks. You can switch between two different views: Logical and Physical view.
Figure 2-11. Logical and Physical Views in the WinSetup Workspace
Reference Manual
00809-0100-5110, Rev AA
12
In the workspace you can perform various tasks such as:
Install and configure tanks, devices, and protocolsRemove tanks and devicesChange the configuration of tanks and devicesView database and input registersSetup the tank view layoutSpecify tags for tank and device namesUpload new application software to a radar tank gaugeView communication log
The Main Window
Page 21
Reference Manual
00809-0100-5110, Rev AA

2.4.1 Workspace

The Workspace window shows the installed tanks and devices and available communication protocols. It also provides information about the configuration of installed devices.
The Main Window
December 2018
Example 1. In the Logical View all installed tanks and devices, as well as available communication protocols, are organized in separate folders to provide a clear overview of the system. A “+”-sign indicates that a device is connected to associated devices.
Example 2. The Tan k s folder showx an overview of the installed tanks. For each tank the associated devices are displayed. The Work space provides information that reflects the system configuration.
In this example, the symbols indicate that level gauge LT- 1 communicates with This
Workstation via Rosemount 2410 Tank Hub HUB-101 and Rosemount 2460 System Hub SYSHUB-201.
Example 3. Available communication protocols are displayed in the Protocols folder.
The Main Window
13
Page 22
The Main Window
December 2018

2.4.2 Icons

In the Workspace window the different tanks and devices are represented by the following icons:
Table 2-1. Device icons
Rosemount 5900S Radar Level Gauge (configured / not configured)
ATD (Auxiliary Tank Device; for example Rosemount 2240S, Rosemount 3051S).
Reference Manual
00809-0100-5110, Rev AA
Devices
Rosemount 2460 System Hub
Rosemount 2410 Tank Hub
Rosemount 2410 Tank Hub (Simulation Mode)
Rosemount 5900C Radar Level Gauge (configured)
Rosemount 5400 Series Radar Transmitter
Rosemount 5300 Series Radar Transmitter
Configured / not configured.
Emerson Wireless 1420 Gateway
Emerson Wireless 775 THUM Adapter
Rex Radar Tank Gauge (RTG)
Rosemount 2160/2165/2175 Field Communication Unit (FCU)
Slave Data Acquisition Unit (SDAU)
COM port status
COM port status for wireless system
Communication Protocol
Communication Protocol Channel
Communication Channel Modbus TCP
TRL PU
IOT 51XX
MCG32XX
MDPII
CIU
14
DS4
The Main Window
Page 23
Reference Manual
00809-0100-5110, Rev AA
Table 2-2. Tank icons
The Main Window
December 2018
Tan ks
Fixed Roof, HTG Fixed Roof
Floating Roof, HTG Floating Blanket
Sphere, LPG Sphere
Horizontal, LPG Horizontal
HTG Fixed Roof
HTG Floating Roof, HTG Floating Blanket
Servo Tank Fixed Roof
Servo Tank Floating Roof
Servo Tank Sphere, Servo Tank Sphere LPG
Servo Tank Horizontal, Servo Tank Horizontal LPG
Cryogenic Tank
The Main Window
15
Page 24
The Main Window
December 2018

2.5 User management

TankMaster provides several protection levels allowing you to prevent unauthorized changes. These protection levels are categorized as User Access Levels and User Access SubLevels.
Each user access level has five User Sub Access Levels providing a large number of unique access levels. In order to change tank and device configuration, install new tanks and devices, calibrate a level gauge,
change holding register values etc. you must be logged on to the appropriate TankMaster user access level. See “To set required access levels” on page 21 for more information.
You can be logged on as Chief Administrator, Administrator, Supervisor, Operator, or View Only mode. The default username and password for each user type is as follows:
Table 2-3. User Access Levels and Sub Levels
User Level Sub Level Default password
View VIEW ONLY * view Operator OPERATOR * oper Supervisor SUPERVISOR * super Administrator ADMINISTRATOR * admin ChiefAdmin ADMINISTRATOR ***** chief
Reference Manual
00809-0100-5110, Rev AA
16
The Main Window
Page 25
Reference Manual
Username User Access Level
00809-0100-5110, Rev AA

2.5.1 Logging on to TankMaster

1. From the File menu choose Log On or click the Log On button in the WinSetup toolbar.
2. Type your Username and Password. The password is case sensitive but the username is not.
Note
If logging on fails five consecutive times the user account is disabled. In this case the user account has to be enabled by an administrator.
The Main Window
December 2018
3. Click the OK button.
The currently logged on user and the corresponding protection level is displayed in the status bar.
The Main Window
17
Page 26
The Main Window
December 2018

2.5.2 Managing user accounts

TankMaster allows you to setup a number of users at different levels and sub levels. You must be logged on as an Administrator in order to add new user accounts or to change the existing user account settings.
To add a new user:
1. Log on as an Administrator.
2. Go to Tools>Administrative Tools>User Manager.
Reference Manual
00809-0100-5110, Rev AA
3. In the User Manager window, select a cell in an empty row and click the New button.
4. Type a user name and a password. If you like, you may enter a description in the Description field.
5. Choose the desired User Access Level and Sub Level and click the OK button. See “User
management” on page 16 for further information on the available User Access Levels and Sub Levels.
18
The Main Window
Page 27
Reference Manual
A new user account is added
Use first account with required access level as default
00809-0100-5110, Rev AA
The Main Window
December 2018
6. Verify that the new user appears in the User Manager window.
7. Select the “Use first account...” box if you want a default user name to appear in the Log On dialog
whenever it is opened. If this box is unmarked, the User Name field is empty when the Log On dialog opens.
8. Click OK to save the changes and close the User Manager window.
The Main Window
19
Page 28
The Main Window
December 2018

2.5.3 Configuring a sub level description

Ta nk Ma st er allows you to change Sub Level names to something more descriptive than the default settings. To configure the access sub level descriptions:
1. Go to Tools > Administrative Tools > User Manager.
2. In the User Manager window, click the Config Desc button.
3. In the Config Access Sub Levels Description window, enter new descriptions in the desired fields. In the
example above, the description of item number 5 of category Admin Sub Levels is changed from “*****” to “Sublevel 5”.
Reference Manual
00809-0100-5110, Rev AA
4. Click OK to close the window.
20
The Main Window
Page 29
Reference Manual
00809-0100-5110, Rev AA

2.5.4 To set required access levels

In TankMaster WinSetup, you can set the access level required for the following actions:
Tank/Device Install and UninstallTank/Device ConfigurationReplace, Restore and Restart DeviceProtocol ConfigurationExit WinSetupAdd Program (see “Customizing the Tools menu in WinSetup” on page 58)Start Program (in the Tools menu)
For example, if you are logged on as an Operator (* * * * *), you are not allowed to exit WinSetup if the required exit level for this action is set to Supervisor (*) or higher.
To set the required access levels:
1. From the Tools/Administrative Tools menu choose Set Required Access Levels.
The Main Window
December 2018
The Main Window
Note
You have to be logged on as an Administrator (* * * * *) to be able to set the required access levels. To create an Administrator (* * * * *) account, see “Managing user accounts” on page 18.
2. Set the required access levels for each type of action and click the OK button.
21
Page 30
The Main Window
December 2018

2.5.5 To change protection level of separate windows

In TankMaster it is possible to set a Protection Level for a specific window, e.g. the Properties window for a Rosemount 5900 Radar Level Gauge. This function is only available if you are logged on at the Administrator (* * * * *) level. To change the protection level do the following:
1. Put the cursor on the icon at the upper left corner and click the left mouse button.
Reference Manual
00809-0100-5110, Rev AA
2. Select the Protection Level... option.
Note
You have to be logged on as an Administrator (* * * * *) to be able to change the Protection Level. To create an Administrator (* * * * *) account, see “Managing user accounts” on page 18.
3. Select the desired protection level from the drop down menus and click the OK button. Now
changes in this window can only be performed if you are logged on at the specified protection level or higher.
22
The Main Window
Page 31
Reference Manual
00809-0100-5110, Rev AA

2.5.6 To change password

TankMaster allows you to change password at any time:
1. From the Tools/Administrative Tools menu choose the Set Password option.
2. Select the Tank Server on which your user account is valid. You can see the different servers in the
WinSetup workspace window. (If you are logged on, the current server is already selected in the Change User Password window).
3. Enter your username if the workspace is in View Only mode. If you are already logged on, your
username appears in the Username field.
The Main Window
December 2018
4. Enter the old password and the new password in the corresponding fields.
Note
The password is case sensitive.
5. Confirm the new password and click the OK button.

2.5.7 To change inactivity timeout

TankMaster WinSetup includes the option to set a timeout after which the current user is automatically logged off.
The timeout period is reset each time the user performs an activity that requires an access level check, for example changing the configuration of a device or logging on to WinSetup.
To set the inactivity timeout:
1. From the Tools/Administrative Tools menu choose the Set Inactivity Timeout option (you have to
be logged on as Administrator).
The Main Window
2. Type the desired value in the corresponding input field.
3. Click the OK button.
23
Page 32
The Main Window
December 2018

2.6 New connection

The New Connection window allows you to connect to another TankServer PC on a Local Area Network (LAN).
Before you can connect to another server on the network, a configuration of the DCOM be performed. See the Rosemount TankMaster Software Installation Manual (Document No. 00809-0400-5110).

2.6.1 Connecting to another server

1. Select the Logical View in the WinSetup workspace.
2. Select the Network Connections icon.
3. Open the File menu or click the right mouse button
4. Choose New Connection.
5. In the New Connection window press the Browse button and choose the computer with the desired
Tank Server.
6. Type a name in the Alias field. This name will be used in the WinSetup workspace for the new server.
Reference Manual
00809-0100-5110, Rev AA
(1)
settings has to
7. Press the OK button.
1. Distributed Component Object Model is a Microsoft® technology for communication between software components on computers in a network.
24
The Main Window
Page 33
Reference Manual
00809-0100-5110, Rev AA

Section 3 Basic Functions

Communication protocol setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 34
Device installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 44
Tank installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 45
Level gauge calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 46
Tank capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 47
Tank Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 48
Basic Functions
December 2018
This section describes functions supported by the Rosemount tool for installing a Rosemount
Tank Gauging system.
TankMaste r™ WinSetup configuration
The WinSetup configuration program lets you setup communication protocols, preferences for measurement units, inventory parameters, as well as device installation, and tank installation.
See the Rosemount System Configuration Manual
for detailed information on how to install and
configure supported devices. In brief, the installation procedure includes the following steps:
Communication protocol setup
(“Communication protocol setup” on page 26)
Preferences
(“Preferences” on page 34)
Installation and configuration of a Rosemount 2460 System Hub
(“Device installation” on page 44)
Installation and configuration of a Rosemount 2410 Tank Hub
(“Device installation” on page 44)
Installation and configuration of field devices
(“Device installation” on page 44)
Installation and configuration of tanks
(“Tank installation” on page 45)
Calibration
(“Level gauge calibration” on page 46)
Basic Functions
25
Page 34
Basic Functions
Rosemount 2410 Tan k H ub
Ta nk b us
MASTER PROTOCOL
Modbus RTU TRL2/RS232/RS485
Rosemount 2460 System Hub
SLAVE PROTOCOL
(PLC, SCADA, DCS)
Rosemount 5900S Radar Level Gauge
Rosemount 2230 Graphical Field Display
Rosemount 2240S Tem per atu re Tra nsm itter
Rosemount TankMaster
Host computer
Modbus TCP Ethernet
Modbus RTU RS232/RS485
Emerson Wireless 1420 Gateway
Emerson Wireless 775 THUM Adapter
To h ost com put er
Modbus TCP Ethernet
Modbus RTU TRL2/RS485
HART TCP Ethernet
OPC, Modbus RTU
December 2018

3.1 Communication protocol setup

The TankMaster work station can be connected to field devices and host computers via Master and Slave protocols. The Modbus Master protocol is available as default protocol when the Rosemount TankMaster software is installed on a TankMaster work station. Optional protocols, such as the Modbus Slave protocol for communication with host systems, can be obtained as well. Please contact Emerson Automations Solutions for more information on Rosemount Tank Gauging systems.
A Modbus protocol offers up to eight channels. Enraf and HART protocols support 16 channels. For each channel you can specify which PC communication port (USB/COM) to connect to, as well as standard communication parameters such as Baud Rate, Parity, and number of Stop Bits.
Figure 3-1. Communication with Various Rosemount Tank Gauging Devices
Reference Manual
00809-0100-5110, Rev AA
26
Basic Functions
Page 35
Reference Manual
Properties
00809-0100-5110, Rev AA

3.1.1 Master protocol channel configuration

The Modbus Master protocol channel can be configured for communication between field devices and a TankMaster work station. The procedure applies to other protocols and modems as well, but other parameter settings may be required.
To configure a protocol channel:
1. Open the Protocols folder in the Workspace window.
2. Select the icon that corresponds to the particular protocol to be configured (this example shows the
Modbus Master protocol).
Basic Functions
December 2018
Basic Functions
3. Click the right mouse button and select Properties, or choose Protocols/Properties from the
Service menu.
4. The Protocol Properties window lists the available protocol channels. For each channel the
corresponding icon indicates whether the channel is enabled or disabled.
5. Select the desired channel.
6. Click the Properties button to configure the protocol channel.
27
Page 36
Basic Functions
Modbus Master channel 1 is enabled
December 2018
Reference Manual
00809-0100-5110, Rev AA
Configuration
This window has two tabs:
The Communication tab allows you to configure parameters for communication between field devices
and a TankMaster work station.
The File Log tab lets you specify what type of information to be logged and saved to disk in (see also
“Saving the communication log to file” on page 94).
To enable a protocol channel
The Enable Channel check box lets you ac tivate the protocol channel. Once enabled, the Modbus Master Channel icon (channel no. 1 in this example) appears in the WinSetup workspace:
28
Basic Functions
Page 37
Reference Manual
1. Select the Modbus Slave protocol
2. Click Properties
Properties
00809-0100-5110, Rev AA

3.1.2 Slave protocol channel configuration

A Slave protocol allows you to collect data from a TankMaster workstation to a host computer.
Note
A hardware key must be installed in order to run a slave protocol server. Host communication needs to be enabled.
Modbus communication setup
To configure the Modbus Slave protocol channel do the following:
1. Open the Protocols folder in the Workspace window.
2. Select the ModbusSlave protocol icon.
Basic Functions
December 2018
Basic Functions
3. Click the right mouse button and select Properties, or choose Protocols>Properties from the
Service menu.
4. The Protocol Properties window lists enabled and disabled protocol channels.
5. Select the desired channel.
6. Click the Properties button to configure the protocol channel.
29
Page 38
Basic Functions
December 2018
Reference Manual
00809-0100-5110, Rev AA
7. The Enable Channel check box lets you activate the protocol channel.
8. This window has three tabs:
The Communication tab allows you to configure parameters for communication between field devices
and a TankMaster work station.
The File Log tab lets you specify what type of information to be logged and saved to disk in (see “Saving
the communication log to file” on page 94).
The Tank Mapping tab lets you specify from which tanks to collect data for the host system (see “Tank
mapping configuration” on page 31).
Note
If handshaking includes DSR, no query will be sent from the TankMaster Protocol Server if the communication is interrupted. This may result in a Query Timeout.
9. Click the OK button to store the current configuration and close the configuration window.
30
Basic Functions
Page 39
Reference Manual
00809-0100-5110, Rev AA
Tank mapping configuration
The slave protocol allows you to send data from a Rosemount Tank Gauging system to a host computer. In the Tank Mapping window you can specify from which tanks to collect data for the host system:
1. In the Slave Protocol Channel Configuration window, select the Tank Mapping tab:
Basic Functions
December 2018
2. From the list of tanks that appear in the Available Tanks pane, select the tanks that the host will
connect to.
3. Click the button to move the selected tanks to the list of Mapped Tanks.
Ensure that the tanks appear in the order required by the host system. When the host sends a query, TankMaster responds by sending tank data in the order as the tanks are listed in the Mapped Tanks column. You can easily change the position of mapped tanks by using the and buttons.
4. Click the OK button to save the current configuration and close the window.
Basic Functions
31
Page 40
Basic Functions
Protocols
Protocols subfolder
December 2018
Reference Manual
00809-0100-5110, Rev AA

3.1.3 Log file configuration

See chapter “Saving the communication log to file” on page 94 for information on how to store a communication log on disk.

3.1.4 Changing the current protocol channel configuration

The channel configuration can be changed at any time. Do the following:
1. In the WinSetup Workspace open the Protocols folder and the protocol subfolder with the enabled
channels.
32
2. Select the channel icon.
3. Click the right mouse button and choose Properties, or from the Service menu choose
Channels>Properties.
4. Choose the appropriate tab and change the protocol settings as described in the previous sections.
Basic Functions
Page 41
Reference Manual
00809-0100-5110, Rev AA

3.1.5 Protocol server configuration

You can specify which protocol servers that will be connected when starting TankMaster WinSetup. To change the current configuration do the following:
1. In the WinSetup workspace select the Protocols folder.
2. Click the right mouse button and choose Configure.
Basic Functions
December 2018
3. In the Connect column, select the check box of each protocol to be automatically connected when
WinSetup starts up.
You may disable a protocol server at any time by using the Disable command:
1. In the Winsetup workspace, open the Protocols folder.
2. Click the right mouse button on the desired protocol server icon and choose Disable.
Basic Functions
33
Page 42
Basic Functions
December 2018

3.2 Preferences

3.2.1 Measurement units

Specify units for inventory calculations and measured variables such as level and temperature. To change measurement units do the following:
1. Select the desired server (e.g. “This Workstation”) in the WinSetup workspace.
2. Click the right mouse button and choose Setup, or from the Service menu choose Servers>Setup.
3. In the Server Preferences window select the Units tab.
Reference Manual
00809-0100-5110, Rev AA
34
4. Choose the desired measurement units for level/ullage, temperature, pressure, volume, density, and
weight.
5. Click the OK button to save the current setting and close the window.
Note
Make sure that the desired measuring units are specified before installing new tanks and devices.
Note that these settings only affect installation of new tanks. Tanks which are already installed in the WinSetup Workspace will not be affected. In order to change measurement units for an existing tank you have to do the following:
1. Uninstall the tank.
2. Change measurement units in the Server Preferences/Units window (or in the TankMaster WinOpi
program choose menu option Setup>System and change units in the System Setup window).
3. Install the tank again.
Basic Functions
Page 43
Reference Manual
00809-0100-5110, Rev AA

3.2.2 Ambient air temperature

To change the Ambient Air Temperature preferences do the following:
1. Select the desired server (e.g. “This Workstation”) in the WinSetup workspace.
2. Click the right mouse button and choose Setup, or from the Service menu choose Servers>Setup.
3. In the Server Preferences window select the Ambient Air Temperature tab:
Basic Functions
December 2018
4. Choose Auto when there is a temperature sensor available that can be used for Ambient Air
Temperature measurements. Otherwise, select the Manual option and type a value for the Ambient Air temperature.
Device. Click the button and select the device to which a temperature sensor is connected.Ambient Air Temp Source. Select temperature source associated with the selected device. In a
Rosemount Tank Gauging system the associated temperature transmitter has to be configured in the tank database of the 2410 Tank Hub (see “Tank installation” on page 45 for more information).
Sensor. Choose a specific sensor to be used for Ambient Air Temperature.Value Range. The Value Range defines the minimum and maximum values when Ambient Air
Temperature is manually entered.
5. Click the OK button to save the current setting and close the window.
Basic Functions
35
Page 44
Basic Functions
December 2018

3.2.3 Inventory

Local Gravity and Ambient Air Density calculations are used for automatic density measurements. To change the Inventory settings do the following:
1. Select the desired server (e.g. “This Workstation”) in the WinSetup workspace.
2. Click the right mouse button and choose Setup, or from the Service menu choose Servers>Setup.
3. In the Sever Preferences window select the Inventory tab:
Reference Manual
00809-0100-5110, Rev AA
4. Local Gravity.
The Local Gravity is used for density and weight calculations when an optional pressure transmitter is installed.
Select Manual if you want to use a specific value for the Local Gravity.Choose Calculated if you want the local gravity to be calculated by TankMaster. In this case you need
to enter the Latitude and Elevation of the site.
5. Ambient Air Density.
The Ambient Air Density is used for calculating Observed Density and Weight in Air (WIA).
Select Manual if you want to use a specific Ambient Air Density value. Choose Calculated if you want the Ambient Air Density to be calculated by TankMaster. The calculated
value is based on the Base Density and the Ambient Air Temperature.
See the Rosemount TankMaster WinOpi Reference Manual
for more information on inventory
parameters and calculations.
6. Click the OK button to save the current settings and close the window.
36
Basic Functions
Page 45
Reference Manual
00809-0100-5110, Rev AA

3.2.4 Miscellaneous

To change parameters such as type of Tank Capacity Table, or Reference Temperature, do the following:
1. Select the desired server (e.g. “This Workstation”) in the WinSetup workspace.
2. Click the right mouse button and choose Setup, or from the Service menu choose Servers>Setup.
3. In the Server Preferences window select the Miscellaneous tab.
Basic Functions
December 2018
4. Choose the type of Tank Capacity Table (TCT) to be used as default setting when installing new tanks.
The default TCT type will automatically be chosen when strapping tables are created for new tanks. However, the TCT type can be changed when the strapping table is specified in the Tank Capacity
Setup window regardless of the settings in the Server Preferences window. You can choose between TCT type Raw, International, and Northern. See the Rosemount TankMaster WinOpi Reference Manual
5. Specify the maximum number of Digital Alarms that will be used.
6. Specify the Reference Temperature to be used for inventory calculations. Normally, the standard
value 15 °C is used.
7. Click the OK button to save the current settings and close the window.
for more information.
Basic Functions
37
Page 46
Basic Functions
December 2018

3.2.5 Setting the name tag prefixes

TankMaster WinSetup allows you to specify default name tag prefixes that will appear automatically when installing new tanks and devices. Note that Tank Tag must begin with a letter. These prefixes can be ignored if you want to use other prefixes instead.
To specify name tag prefixes do the following:
1. From the Service menu choose Preferences.
Reference Manual
00809-0100-5110, Rev AA
38
2. In the Preferences window select the Tag Prefixes tab.
3. Type the prefixes to be used for tank names and device names. and click the OK button. You can change the prefixes later at any time. Note that this will not affect names of existing tanks and
devices. The following characters should not be used when naming objects in TankMaster as this may cause
undesirable results:
Table 3-1. Illegal Characters
\ Reverse solidus % Percent symbol
/ Solidus < Less-than symbol
? Question mark > Greater-than symbol
* Asterisk { Left curly bracket
[ Left square bracket } Right curly bracket
] Right square bracket ' Apostrophe
| Vertical line Quotation mark
Basic Functions
Page 47
Reference Manual
00809-0100-5110, Rev AA

3.2.6 E-mail configuration

TankMaster WinSetup allows you to setup an e-mail client for alarm notifications and reports. To setup an e-mail client do the following:
1. From the Service menu choose Preferences.
Basic Functions
December 2018
2. In the Preferences window select the E-mail Configuration tab.
3. Enter the following information:
SMTP Server
Sender Address
SMTP Port
Authentication Configuration
Channel Security Configuration
Subject
Specify an SMTP server for outgoing messages. Contact your LAN administrator or Internet Service Provider (ISP) for details.
The e-mail account which will send e-mails from the current workstation must be located on the specified SMTP server.
Optional. Contact your LAN administrator or ISP for details.
Select this option and enter a Login name and Password if authentication is required on the mail server. Contact your LAN administrator or ISP for details.
Select this option if the e-mail client requires the use of channel security. Contact your LAN administrator or ISP for details.
Enter a title for an e-mail alarm notification. This subject is only used for Alarm notification and is optional. This subject will not be used for other e-mails sent from the built-in e-mail client.
Basic Functions
39
Page 48
Basic Functions
December 2018

3.2.7 Tank view layout

The Setup Tank View tab is used to specify variables to be presented in the Tank View window, see
“Viewing tank data” on page 87.
TankMaster WinSetup allows you to create a new tank view layout and store it on disk, or load an existing table layout from disk.
To create a Tank View layout do the following:
1. From the Service menu choose Preferences.
2. In the Preferences window select the Setup Tank View tab.
Reference Manual
00809-0100-5110, Rev AA
3. Click the Load Table button if you wish to edit an existing Table Layout.
4. In the Available Parameters pane on the left-hand side of the Preferences/Setup Tank View window,
select the parameter to be presented in the Tank View window (see “Viewing tank data” on page 87).
5. Click the Move button to move it to the Selected Parameters pane on the right-hand side of the
Preferences/Setup Tank View window.
6. Repeat steps 4 to 5 for each parameter you wish to include.
The Move All button allows you to move all variables at once to the Selected Parameters list box.
7. Ensure that all parameters to appear in the Tank V iew window are included in the Selected Parameters
list box as illustrated below:
40
Basic Functions
Page 49
Reference Manual
00809-0100-5110, Rev AA
8. Click the Save As button if you wish to store the current tank view table for future use.
Basic Functions
December 2018
9. Click the OK button to save the current Tank View settings and close the window.
Note
When clicking the Apply or the OK button, the parameter setup is stored in the table layout that is currently used by the Tank View window.
To view the resultspecified tank parameters click the right mouse button and choose the Open Tank View option:
Basic Functions
41
Page 50
Basic Functions
December 2018

3.2.8 Tank visibility

The Tanks Visibility tab lets you configure tanks on a remote tank server to make them visible on the current WinOpi client.
To specify tanks to be visible on the current WinOpi client:
1. From the Service menu choose Preferences and select the Tanks Visibility tab:
Reference Manual
00809-0100-5110, Rev AA
2. Select the Enable Tank Visibility function check box.
3. From the Select tank server drop-down list select the remote tank server on which the tanks are
installed.
4. In the Select tanks to be visible on this workstation pane, check the tanks you wish to make visible
on the current workstation. In the default setting all tanks are visible.
5. Choose the Visible on this workstation option to make new tanks visible on the current workstation.
6. Click the OK button to store the current configuration and close the Preferences window.
7. Figure 3-2 on page 43 illustrates the result in the WinSetup workspace when tank visiblity is enabled
and disabled, respectively.
42
Basic Functions
Page 51
Reference Manual
00809-0100-5110, Rev AA
Figure 3-2. Tanks Visiblity Enabled for All Tanks
Figure 3-3. One Tank Disabled from Visiblity (TK-X)
Basic Functions
December 2018
Basic Functions
43
Page 52
Basic Functions
December 2018

3.3 Device installation

The device installation wizard guides you step-by-step through the installation procedure. The wizard can be started in different ways as illustrated below.
Reference Manual
00809-0100-5110, Rev AA
See the respective device manuals and the Rosemount System Configuration Manual information on how to install various devices in a Rosemount Tank Gauging system.
1. Select the Devices folder.
2. Click the right mouse button and choose Install New from the popup menu, or from the Service>Devices menu
choose Install New.
As an alternative you can use the following method:
for detailed
1. Select the server where your system is installed.
2. From the File>Install New menu choose Device.
44
Basic Functions
Page 53
Reference Manual
00809-0100-5110, Rev AA

3.4 Tank installation

3.4.1 Overview

The purpose of the tank installation procedure is to associate various devices to the right tanks. It also includes mapping variables such as Free Water Level and Vapor Pressure to specific instrument outputs.
Basic Functions
December 2018
Installing a new tank is a simple and straightforward procedure when using the tank installation wizard.
Note
Make sure that measurement units are specified before installing a new tank. See also “Measurement
units” on page 34.
The specified measurement units only affect installation of new tanks. Changing measurement units has no effect on tanks which are already installed in WinSetup. This means that if you want to change measurement units for an installed tank, it has to be uninstalled first, and then installed again after changing the measurement units in the Server Preferences/Units window. See also “Measurement units”
on page 34.
A tank installation includes the following steps:
1. Specify tank type: Fixed Roof, Floating Roof, Sphere, Horizontal etc.
2. Select which devices to associate with the tank.
3. Configure the tank. For inventory calculations you will need to specify source signals for Free Water
Level (FWL), Vapor Temperature, Vapor Pressure and Liquid Pressure.
4. Specify input for the different tank variables: automatic (measured by a field device) or manual
values. See the Rosemount Tank Gauging System Configuration Manual
installation.
for more information on tank
Basic Functions
45
Page 54
Basic Functions
December 2018

3.5 Level gauge calibration

A minor level gauge adjustment may be needed in order to accurately match measured and actual product levels. For example, a deviation may result from minor errors in tank geometry parameters such as the tank height (R) or the position of the Gauge Reference Point (see the Rosemount 5900S Radar Level Gauge reference manual
The Rosemount 5900 can be calibrated by using the Calibration Distance parameter. It can be manually adjusted in the 5900 Properties/Geometry window.
For Still-pipe applications, you may use the Calibrate function to automatically calculate an optimized Correction Factor and Calibration Distance based on measurement data and hand dipping at different product levels.
1. To access the Calibrate function, select the level gauge icon in the WinSetup workspace, click the
right mouse button and choose Calibrate, or choose Calibrate from the Service/Devices menu:
, for more information on tank geometry).
Reference Manual
00809-0100-5110, Rev AA
46
See the Rosemount 5900S Radar Level Gauge reference manual Calibrate function.
for further information on using the
Basic Functions
Page 55
Reference Manual
00809-0100-5110, Rev AA

3.6 Tank capacity

The tank geometry can be defined in a strapping table; the Tank Capa city Tab le (TCT). The TCT is used to convert a product level to the corresponding volume. Different TCT types can be specified: Raw; International, and Northern.
To ope n the Tank Capa city Setu p window for a certain tank, select the tank icon in the workspace window, click the right mouse button and choose the Tank Capacity option:
Basic Functions
December 2018
Basic Functions
See the Rosemount TankMaster WinOpi Reference Manual Setup window and how to set up a tank capacity table.
for more information on the Tank Capacity
47
Page 56
Basic Functions
December 2018

3.7 Tank Entry

The Tank Entry window is used for specifying a number of product parameters to be used for inventory calculations. TankMaster can use measured data, or data that is manually entered. To open the Tank Entr y window:
1. In the WinSetup workspace select the tank to configure.
Reference Manual
00809-0100-5110, Rev AA
2. Click the right mouse button and choose the Tank Entry option:
3. To enter manual values select the check box and type the desired value in the input field. Manual
values are marked with yellow as illustrated above.
48
See the Rosemount TankMaster WinOpi Reference Manual Entry window.
for more information on how to use the Tan k
Basic Functions
Page 57
Reference Manual
Properties
00809-0100-5110, Rev AA

Section 4 Device Handling

To change device configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
To uninstall a device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51

4.1 To change device configuration

Once a device is installed and configured, you can modify the current settings at any time by opening the Properties dialog.
To op en the Properties dialog do the following:
1. In the Rosemount
2. Open the Devices folder and select the device icon.
WinSetup workspace window select the desired device.
Device Handling
December 2018
Device Handling
3. Click the right mouse button and choose the Properties option, or from the Service menu choose
the Devices/Properties option.
4. The device properties window (5900S RLG Properties window in this example, see the next page)
appears with various tabs allowing you to change the current device settings.
49
Page 58
Device Handling
December 2018
Reference Manual
00809-0100-5110, Rev AA
A number of tabs are available for configuration of communication parameters, tank geometry, device specific parameters and advanced configuration options.
Some of the tabs refer to the different steps in the device installation wizard. Similar dialogs are available for other device types as well, for example the Rosemount 2410 Tank Hub.
See Section 3: Basic Functions for detailed descriptions on how to configure various devices.
50
Device Handling
Page 59
Reference Manual
Uninstall
Properties
00809-0100-5110, Rev AA

4.2 To uninstall a device

A device can be uninstalled from the WinSetup workspace at any time. However, the associated tank must be uninstalled first. As an alternative you may keep the tank by disconnecting the device from the associated tank before the device is uninstalled.
To uninstall a device
1. Start by uninstalling the associated tank, see the Rosemount Tank Gauging System Configuration
Manual for more information.
2. In the WinSetup workspace, select the device and click the right mouse button.
Device Handling
December 2018
3. Choose the Uninstall option. Now the device is removed from the WinSetup workspace.
To uninstall a device without uninstalling the tank
If you prefer to keep the tank, you can disconnect it from the device and then uninstall the device:
1. In the WinSetup workspace, select the desired tank and click the right mouse button.
Device Handling
2. Choose the Properties option and select the Configuration tab.
51
Page 60
Device Handling
Change
Left arrow
December 2018
Reference Manual
00809-0100-5110, Rev AA
3. Click the Change button.
4. In the right-hand side of the Select Devices window, select the device and click the arrow button.
The device will be removed from the Selected Devices pane to the Available Devices pane on the
left-hand side.
5. Click the OK button.
6. Open the Tan ks folder:
52
Device Handling
Page 61
Reference Manual
The LT-TK-1 level gauge is not associated with tank TK-1,
but it is still available in the Devices folder.
Uninstall
00809-0100-5110, Rev AA
Device Handling
December 2018
7. Verify that the device (LT-TK-1 in this case) is no longer associated with the tank.
8. Open the Devices folder:
9. Select the device and click the right mouse button.
10.Choose the Uninstall option.
Now the device is removed. However, the tank is still available in the WinSetup workspace.
Device Handling
53
Page 62
Device Handling
December 2018
Reference Manual
00809-0100-5110, Rev AA
54
Device Handling
Page 63
Reference Manual
00809-0100-5110, Rev AA

Section 5 Service Functions

Section overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 56
System status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57
Customizing the Tools menu in WinSetup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 58
User defined temperature conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 60
Viewing input and holding registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 61
To edit holding registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 63
Viewing diagnostic registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 65
Logging measurement data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 68
Saving and loading database registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 69
Upgrading device firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 72
Tank Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 74
Viewing tank data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Viewing alarm status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 89
Protocol handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 91
TankMaster Administrator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 99
Proof test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 110
Service Functions
December 2018

5.1 Section overview

The information in this section covers a number of service functions that can be used for maintenance and troubleshooting devices supported by Rosemount
TankMaste r™.
Service Functions
55
Page 64
Service Functions
December 2018

5.2 Safety messages

Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Failure to follow safe installation and servicing guidelines could result in death or serious injury:
Make sure only qualified personnel perform the installation. Use the equipment only as specified in this manual. Failure to do so may impair the protection
provided by the equipment. Do not perform any service other than those contained in this manual unless you are qualified.
High voltage that may be present on leads could cause electrical shock:
Avoid contact with leads and terminals. Make sure the main power to the device is off and the lines to any other external power source are
disconnected or not powered while wiring the device.
Reference Manual
00809-0100-5110, Rev AA
56
Service Functions
Page 65
Reference Manual
00809-0100-5110, Rev AA

5.3 System status

The System Status Overview shows status and properties for the overall system, Tank Server, Protocol Servers, and devices.
To op en the System Status Overview do the following:
1. Select a workstation in the Workspace window.
2. Click the right mouse button and choose System Status Overview, or from the Service menu
choose Servers>System Status Overview.
Service Functions
December 2018
Service Functions
57
Page 66
Service Functions
Add
Menu Text
“Menu Text” will appear in Tools menu
December 2018

5.4 Customizing the Tools menu in WinSetup

To add custom options to the Tools menu do the following:
1. Choose the Tools>Applications menu option to open the Customize window:
Reference Manual
00809-0100-5110, Rev AA
2. Click the Add button to add a new menu option to the Tools menu.
3. In the Menu Text field type the text you would like to appear in the Tools menu.
58
Service Functions
Page 67
Reference Manual
Command
Browse button
00809-0100-5110, Rev AA
4. Press the button next to the Command field.
Service Functions
December 2018
Service Functions
5. Browse to the program file that will be associated with the new Tools menu option as given in the
Menu Text field.
6. Click the Open button and return to the Customize window.
7. In the Arguments field type any argument that you want to add to the command line. This line is
usually left blank.
8. Click the OK button.
9. In the Tools menu, choose the new menu option and verify that the associated application starts as
expected.
59
Page 68
Service Functions
Choose conversion method
Click to configure
Disable the Auto Sensor Configuration
December 2018

5.5 User defined temperature conversion

The Rosemount 2240S Multi-input Temperature Transmitter supports the use of non-standard spot temperature sensors. For these types of temperature elements you can specify the relation between temperature and electrical resistance with tables or mathematical formulas.
To enable and configure the different conversion methods:
1. In the WinSetup workspace, select the ATD device icon.
2. Click the right mouse button and choose the Properties option.
Reference Manual
00809-0100-5110, Rev AA
3. In the 22XX ATD window, select the 2240S MTT Temperature Sensor tab:
4. Disable Use Auto Sensor Configuration.
5. In the Conversion Method drop-down menu, choose the desired user defined conversion method;
User Defined Linearization Table, User Defined Formula, or User Defined Individual Formula.
6. Click the configuration button that corresponds to the selected user defined conversion method,
and configure the temperature sensor as described in the Rosemount 2240S reference manual.
7. Choose sensor type (Connection) and specify temperature range.
60
8. Click OK to store the configuration and close the 22XX ATD window.
Service Functions
Page 69
Reference Manual
00809-0100-5110, Rev AA

5.6 Viewing input and holding registers

In a Rosemount Tank Gauging system, measurement data is continuously stored in Input registers of devices such as the Rosemount 2410 Tank Hub, Rosemount 5900S Radar Level Gauge, and other devices. By viewing the input registers of a device, you can verify that the device is working properly.
Holding registers store various device parameters used to control measurement performance. To view Input or Holding registers of a certain device do the following:
1. In the WinSetup Workspace, select the device icon:
Service Functions
December 2018
2. Click the right mouse button, or open the Service>Devices menu, and choose the View Input
Registers or View Holding Registers option.
3. Registers Type:
Choose Predefined if you would like to see a commonly used selection of database registers. For advanced service the All option allows you to view a specific range of registers. Specify a
start value in the Start Register input field, and the total number of registers to be displayed in the Number of Registers field (1-500).
Service Functions
61
Page 70
Service Functions
December 2018
4. The Registers Scope drop-down list has three options:
Reference Manual
00809-0100-5110, Rev AA
Scope Description Access level
Basic Standard setting that includes the most
commonly used registers
Service Includes a wider range of registers for
advanced service and troubleshooting
Developer For advanced users only Administrator
View Only
Supervisor
5. In the Show Values in pane, choose the appropriate register format Decimal or Hexadecimal.
6. Click the Read button to upload the contents of the device database registers.
62
Service Functions
Page 71
Reference Manual
00809-0100-5110, Rev AA

5.7 To edit holding registers

Most Holding registers can be edited simply by typing a new value in the appropriate Valu e input field. Some holding registers (marked grey in the Value column) can be edited in a separate window. Then you can choose from a list of options or you can edit separate data bits.
To edit a holding register, do the following:
1. In the WinSetup Workspace, select the device icon:
2. Click the right mouse button, or open the Service>Devices menu, and choose the View Holding
Registers option.
Service Functions
December 2018
3. To change the contents of input fields with white background color in the Value column, put the
cursor in the field and type a new value.
To change input fields with grey background color, double click the field to open a new window for editing. Depending on the type of Holding register, an Expanded Enumerated or an Expanded Bitfield window is opened data bit (Expanded Bitfield) as illustrated below.
1. Contact Emerson Process Management/Rosemount Tank Gauging for more information about the different Holding register types.
Service Functions
(1)
. Select from the list of options (Expanded Enumerated) or change the appropriate
63
Page 72
Service Functions
December 2018
Reference Manual
00809-0100-5110, Rev AA
64
4. Click the Apply button to store the register data, or click the Close button to store and close the
window.
Service Functions
Page 73
Reference Manual
00809-0100-5110, Rev AA

5.8 Viewing diagnostic registers

The View Diagnostic Registers window shows a predefined set of diagnostic Input and Holding registers. Each device has a standard set of diagnostic registers which can be changed in the Configure Diagnostic Registers window.
To view and configure the diagnostic registers perform the following steps:
1. Select the device icon (for example a Rosemount 2410 or Rosemount 5900) in the Ta nk Ma s ter
WinSetup workspace.
Service Functions
December 2018
2. Click the right mouse button and choose View Diagnostic Registers.
Register values in this window are of read only type. They are loaded from the device as the window is opened.
Service Functions
Table cells with grey background color in the Value column represent registers of either Bitfield or ENUM type. An expanded Bitfield/ENUM window can be opened for these register types. Double-click a cell to open the Expanded Bitfield/ENUM window.
Registers of Bitfield and ENUM type can be presented in hexadecimal format by selecting the Show in Hex check box.
65
Page 74
Service Functions
Registers Type
Group Prefix
December 2018
It is possible to view diagnostic registers for devices of the same type without closing the window and opening it again for a new device. Press or buttons to step to the next or previous device.
Alternatively, another device can be selected from the drop down menu on the left-hand side of the View Diagnostic Registers window.
The Configure button lets you specify a default setting of diagnostic registers. See “Configure” on
page 66 for more information.
The Log Setup button provides easy access to the Register Log Scheduling window, which allows you to setup a log schedule for automatic start and stop of register logging. See “Logging measurement data”
on page 68 for more information.
The Print button lets you print the current register information.

5.8.1 Configure

The Configure button in the View Diagnostic Registers window opens the Configure Diagnostic Registers window which allows you to change the default selection of diagnostic registers. You can use this option to setup the View Diagnostic Registers window for the selected device type:
Reference Manual
00809-0100-5110, Rev AA
66
1. In the Registers Type pull down menu, choose Holding or Input registers. Input Registers are
displayed in blue, Holding Registers in black.
2. The Group Prefix drop down menu lets you filter the list in the left pane.
Note
The Group Prefix feature is not supported for all device types.
3. A standard selection appears automatically in the Selected Registers pane on the right-hand side of
the Configure... window. To add a register to the list, select it in the left pane and press the button. To remove a register from the right pane, select it and press the button.
4. The order in which registers are displayed in the View Diagnostic Registers window can be configured.
Select a register in the right pane and press to move it upwards, or to move it downwards in the list.
5. Press OK to store the current configuration.
Service Functions
Page 75
Reference Manual
00809-0100-5110, Rev AA

5.8.2 Restore to default setting

In case you wish to restore the View Diagnostic Registers window to the default setup, you need to remove the file that contains the current configuration data for the View Diagnostic Registers window.
To restore to the default setting do the following:
1. In Windows Explorer open the following folder:
C:\Rosemount\TankMaster\Setup\Data,
where C:\ is the drive letter associated with the hard disk on which TankMaster is installed.
2. Locate the configuration file for the device whose diagnostic register setup you wish to restore:
Device Configuration file
2410 Tank Hub R2410_diag.ini
5900S Radar Level Gauge R5900_diag.ini
Service Functions
December 2018
2240 Multi-Input Temperature Transmitter and Auxiliary Tank Devices (ATD)
3. Remove the *.ini file, or rename it in case you wish to store the file for future use (for example
R2410.old).
4. Start TankMaster WinSetup and open the View Diagnostic Registers window to verify that the View
Diagnostic Registers window shows the default setting of diagnostic registers.
R22XX_diag.ini
Service Functions
67
Page 76
Service Functions
December 2018

5.9 Logging measurement data

Logging of diagnostic registers can be a useful tool for verifying that a gauge works properly. The logging function can be accessed by using the TankMaster WinSetup program. To start logging do the following:
1. Start the TankMaster WinSetup program.
2. Select the device icon in the WinSetup workspace.
3. Click the right mouse button and choose Logging.
Reference Manual
00809-0100-5110, Rev AA
4. The Manual mode lets you start logging at any time. In Automatic mode you have to specify a Start
and Stop time.
5. The resulting log file(s) will not exceed the size specified by the Max File Size parameter.
In Automatic Mode logging will proceed until the Stop Date and Time is reached.In Manual Mode logging will proceed until the Stop button is pressed.Logging will stop automatically when the number of log files is equal to the number given by the Max
Log Files parameter.
6. The log file is stored as a plain text file and can be viewed in any word processing program. It is stored
in the following folder: C:\Rosemount\Tankmaster\Setup\Log, where C is the disk drive where the TankMaster software is installed. The log file contains the same input registers as the View Diagnostic Registers window. You can change which input registers to be included in the log file by configuring the View Diagnostic Registers window, see “Viewing diagnostic registers” on page 65 for more information.
68
Service Functions
Page 77
Reference Manual
Save
00809-0100-5110, Rev AA

5.10 Saving and loading database registers

Input and Holding Registers of the Rosemount 5900S and the 2410 can be stored on disk. This can be useful for backup purposes and troubleshooting. Input and Holding registers can be saved for a single device or several devices simultaneously.

5.10.1 To save device registers for a single device

To save configuration database registers (Holding or Input Registers) to file for a single device do the following:
1. Start the TankMaster WinSetup program.
2. In the TankMaster WinSetup workspace window, click the right mouse button on the device icon.
3. Choose the Save Database to File option, or from the Service menu choose Devices>Save
Database to File.
Service Functions
December 2018
Service Functions
4. Select Holding/Input registers (the Holding Register options is shown in the example above for
demonstration).
5. Choose the Predefined Registers or the User-Defined option.
The Predefined option stores the most frequently used registers. The User-defined option stores a specified range of Holding registers and should only be used
for advanced service.
6. For the Predefined option you may choose the desired Scope; "All Registers" or "Basic Registers".
Basic is a limited number of registers mostly related to configuration parameters for the device.
7. Click the Browse button, select a folder and type a file name.
8. Click the Save button to start saving the configuration database to file.
69
Page 78
Service Functions
December 2018

5.10.2 To save device registers for multiple devices

To save a backup copy of the current configuration for multiple devices, do the following:
1. In the TankMaster WinSetup workspace, select the Devices folder.
2. Click the right mouse button and choose the Save Database of All to Files option, or from the
Service menu choose Devices>Save Database of All to Files.
Reference Manual
00809-0100-5110, Rev AA
3. Select a device from the Available Devices pane and click the Add button in order to move it to the
Selected Devices pane. Repeat for all devices you would like to include.
4. Select register type: Holding or Input registers.
5. Choose the Predefined Registers or the User-Defined option.
The Predefined option stores the most frequently used registers.The User-defined option stores a specified range of Holding registers and should only be used
for advanced service.
6. Click the Browse button, select a folder and type a file name.
7. Click the Start button to save the database backup.
70
Service Functions
Page 79
Reference Manual
00809-0100-5110, Rev AA

5.10.3 To recover a device database

TankMaster WinSetup offers the option to replace the current holding register database with a backup database stored on disk. This can be useful, for example, when recovering configuration data.
To load a backup database to a device do the following:
1. Select the device icon in the WinSetup workspace.
2. Click the right mouse button and choose the Upload Database option, or from the Service menu
choose Devices>Upload Database.
3. Type a file path and file name, or click the Browse button and choose a backup database file to be
uploaded.
Service Functions
December 2018
4. Click the Upload button to start uploading the recovery database.
Service Functions
71
Page 80
Service Functions
December 2018

5.11 Upgrading device firmware

TankMaster WinSetup supports firmware upgrade for Rosemount Tank Gauging level gagues and temperature transmitters.
Note
In case the current program version is significantly older than the new one, it is recommended that you load the default configuration database once the device is reprogrammed. Contact Emerson Process Management/Rosemount Tank Gauging service department if you need further advice.
To upload new software do the following:
1. Make sure the devices are properly prepared for reprogramming (normal operation and no warnings
or errors).
2. In the WinSetup Workspace, select the Devices folder. (For a single device, select the device in the
Devices folder).
3. Click the right mouse button and choose the Program All option, or from the Service menu choose
Devices>Program All. (For a single device, choose the Program option, or from the Service menu, choose the
Devices>Program option).
Reference Manual
00809-0100-5110, Rev AA
72
4. Select the device to be programmed from the Available Devices pane and click the Move button.
Repeat for each device of the same type to be programmed. Note that if a single device was selected in the Workspace window, it will appear automatically in the Program These Devices pane. Use the Remove button if you would like to change the list of devices to be programmed.
5. Click the Browse button to locate the appropriate software file.
Service Functions
Page 81
Reference Manual
00809-0100-5110, Rev AA
6. Click the Start Programming button to open the Start Device Programming window:
Service Functions
December 2018
7. Click the Start Programming button to activate device programming.
See, for example, the Rosemount 5900S reference manual Rosemount 2410 reference manual programming devices in the Rosemount Tank Gauging system.
(Document No. 00809-0100-2410) for further information on
(Document No. 00809-0100-5900) or the
Service Functions
73
Page 82
Service Functions
Tank Sc an
December 2018

5.12 Tank Scan

The Tank Scan window allows you to view tank echoes. Then you may setup the most important parameters to enable separating surface echoes from disturbing echoes and noise.
To op en the Tank Scan window:
1. In the WinSetup workspace, select the gauge icon.
Reference Manual
00809-0100-5110, Rev AA
2. Click the right mouse button and choose the Properties option.
3. Select the Advanced Configuration tab.
4. Press the Tank Scan button
74
Service Functions
Page 83
Reference Manual
00809-0100-5110, Rev AA
Service Functions
December 2018
5. The Tank Scan window contains the Graph Area, Legend/Options area, File Storage buttons, and
various action buttons.
Service Functions
75
Page 84
Service Functions
Progress bar
Reread From Gauge
December 2018

5.12.1 Graph area

When the Tank Scan window opens, WinSetup reads tank data from the gauge. The process is indicated by a progress bar in the lower right corner of the Tank Sca n window.
Reference Manual
00809-0100-5110, Rev AA
Once the reading process is finished, a tank scan graph is displayed that shows a peak referring to the product surface. The Tank Scan graph may also contain other peaks. In addition to the surface echo, there might be echoes from agitators or other obstacles in the tank.
The Tank Scan function includes tools that allows you to configure the level gauge to distinguish between the surface peak and peaks from disturbing objects. See the following chapters for details.
The Tank Scan graph can be refreshed at any time with the Reread From Gauge button. The new echo curve will appear as a black line and the previous curve as a grey line. The graph may show up to two old echo curves. An old echo peak will be marked by a small cross symbol. This can be used to compare the existing tank signal with previous signals.
76
Service Functions
Page 85
Reference Manual
Previous Tank Echo curve
Tank Echo cu rv e
00809-0100-5110, Rev AA

5.12.2 Legend/Options

The following items can be shown in the graph area (check the appropriate box for each item to be shown):
Service Functions
December 2018
Tank Echo
Prev. Tank Echo (Previous Tank Echo)
General Threshold
The black line shows the latest Tank Echo curve, and the grey lines show previous Tank Echo curves (maximum two).
See Tank Echo.
The General Amplitude Threshold is shown in blue. Echoes with an amplitude below the General Amplitude Threshold will be filtered out by the level gauge.
Service Functions
False Echo Ar eas
The False Echo function is used to improve the performance of the gauge when the surface is close to a horizontal surface of a stationary object in the tank. The object causes an echo when it is above the surface. Added False Echo Areas are shown in grey:
77
Page 86
Service Functions
Amplitude Threshold Point
Disturbing Echo
December 2018
Reference Manual
00809-0100-5110, Rev AA
ATP (Amplitude Threshold Points)
Holdoff Distance
Gauge Ref. Point (Gauge Reference Point)
A weak disturbing echo can be filtered out by creating a curve of Amplitude Threshold Points.
The Holdoff Distance defines how close to the Gauge Reference Point a level value is accepted. The Holdoff Distance is shown in red.
The Gauge Reference Point is shown as a dashed (olive colored) line:
Zero Reference
The Zero Reference (zero level; dipping datum point) close to the bottom of the tank, is defined by the Tank Reference Height (R). It is shown as a dashed (sand colored) line:
78
Service Functions
Page 87
Reference Manual
Previous Peaks
00809-0100-5110, Rev AA
Service Functions
December 2018
Tank Bottom
Echo Peaks
Peak Labels
The Tank Bottom is shown in red:
Echo Peaks are shown in black for the Surface Echo and in green for unknown
echoes:
Peak Labels are shown for the Surface Echo and for unknown echoes:
Previous Peaks
Previous Peaks are shown for the Surface Echo and for unknown echoes:
Service Functions
79
Page 88
Service Functions
December 2018

5.12.3 File storage

To save Tank Scan data displayed in the Graph Area
1. In the Tank Scan window click the Save button.
2. Enter a name to identify the tank scan data. You may also type a comment in the Comment field (not
required). This can for example be used to describe any special circumstances under which the Tank scan data was obtained.
Reference Manual
00809-0100-5110, Rev AA
3. Press the OK button.
Note
The default data storage file is named StrTankScanII.dat. The file is stored in the following folder: C:\Rosemount\TankMaster\Lib\Data\.
80
Service Functions
Page 89
Reference Manual
00809-0100-5110, Rev AA
To export tank scan data to an external file
Tank scan data can be saved to file for viewing with the Tank Echo Viewer (Tools>Tank Echo Viewer):
1. In the Tank Scan window click the Save button to open the Save Tank Scan Data window:
2. Enter a name to identify the tank scan data. You may also type a comment to describe any special
circumstances when the Tank scan data was obtained.
3. Press the Advanced button.
Service Functions
December 2018
4. Select the Export tank scan data to external file check box.
5. Press the Browse button.
6. Browse to a destination folder and type a name in the File name input field. Press the Open button.
Service Functions
81
Page 90
Service Functions
December 2018
7. Press Yes to create the file.
8. Press OK.
Reference Manual
00809-0100-5110, Rev AA
82
9. Press OK to export tank scan data.
Service Functions
Page 91
Reference Manual
00809-0100-5110, Rev AA
To load data from a saved file into the Graph Area
1. In the Tank Scan window press the Stored Echoes button.
Service Functions
December 2018
2. Select the file to be loaded.
3. Press the Load button.
To delete a saved file
1. In the Tank Scan window press the Stored Echoes button.
Service Functions
2. Select the file you want to delete.
3. Press the Delete button.
83
Page 92
Service Functions
December 2018

5.12.4 Action buttons

The following buttons can be found in the Tank Scan window:
Reference Manual
00809-0100-5110, Rev AA
Save
Stored Echoes
Reread From Gauge
Print
Apply
OK
Cancel
Help
See “File storage” on page 80.
See “File storage” on page 80.
At any time, you can refresh tank echo and echo peaks with the Reread From Gauge button. The Tank Scan will display the new echo curve as a black line, and up to two previous echo curves in grey color. The previous echo peaks will appear with small crosses.
Opens the print dialogue and prints the Ta nk Scan window.
When changing a parameter that affects echo peak detection (e.g. General Amplitude Threshold), you will have to press the Apply button to write these settings to the internal memory of gauge. It takes a few seconds for the gauge to update the echo peak data (up to 30 seconds due to the echo peak filtering function in the gauge). Finally, press the Reread from Gauge button to update the echo peak information in the graph area.
Applies changes and closes the window.
Cancels all changes.
Opens the online help for the current window.
84
Service Functions
Page 93
Reference Manual
Handles for moving or right-click editing
Properties
00809-0100-5110, Rev AA

5.12.5 Editing

All the elements having handles can be edited. Each handle may be moved by using the mouse pointer.
Service Functions
December 2018
Clicking the right mouse button on a handle opens a dialog window. The Properties option allows you to review or change parameter values.
The following parameters can be edited via moving or right-clicking a handle:
General Amplitude ThresholdAmplitude Threshold PointFalse Echo AreaHold Off Distance
Service Functions
85
Page 94
Service Functions
December 2018
To add a False Echo Area or an Amplitude Threshold Point
1. Click the right mouse button in the graph area where you would like to add a False Echo Area or an
2. Select a menu item in the popup menu. In the example above, the New False Echo Area option was
Reference Manual
00809-0100-5110, Rev AA
Amplitude Threshold Point:
chosen:
3. Enter the new data and click the OK button.
To delete a False Echo Area or Amplitude Threshold Point
1. Right-click the handle of the False Echo Area or Amplitude Threshold Point to be deleted:
2. Select the Delete False Echo Area (or Delete Amplitude Threshold Point) option.
86
Service Functions
Page 95
Reference Manual
00809-0100-5110, Rev AA

5.13 Viewing tank data

WinSetup offers the option to view data from a single tank or a group of tanks. Various parameters such as Level, Level Rate, and Average Temperature can be displayed. The Setup Tank View window lets you specify the desired set of parameters. See “Tank view layout” on page 40 for more information.

5.13.1 Viewing data for all tanks

To view measurement data from all tanks, do the following:
1. In the WinSetup workspace, select the Tan k s folder.
Service Functions
December 2018
2. Click the right mouse button and choose Summary Tank View, or from the Service menu choose
Tanks/Summary Tank View.
3. Choose the All Tanks tab for a complete list of all tanks, or choose a view that includes a bar graph
for one tank at a time by selecting the appropriate tab.
Service Functions
87
Page 96
Service Functions
Open Tank View
December 2018

5.13.2 Viewing data for a single tank

To view measurement data for a single tank, do the following:
1. In the WinSetup workspace, select the desired tank icon.
Reference Manual
00809-0100-5110, Rev AA
2. Click the right mouse button and choose the Open Tank View option, or from the Service menu
choose Tanks/Open Tan k View:
Measurement data for the selected tank is displayed in the Tank View window.
88
Service Functions
Page 97
Reference Manual
00809-0100-5110, Rev AA

5.14 Viewing alarm status

WinSetup lets you view alarm status for all tanks, a certain tank group, or a single tank. To view the current alarm status for all tanks do the following:
1. In the WinSetup workspace, select the TankMaster workstation (or the Ta nk s folder) where the tanks
are installed:
Service Functions
December 2018
2. From the View menu choose Alarms. The Alarm Status window presents a list of alarms for all the
tanks connected to the selected TankMaster workstation:
Service Functions
89
Page 98
Service Functions
December 2018
To view the alarm status of a single tank:
1. Open the Tan ks folder and select the desired tank:
Reference Manual
00809-0100-5110, Rev AA
2. From the View menu choose Alarms. The Alarm Status window presents the current alarms for the
selected tank:
90
Service Functions
Page 99
Reference Manual
View Log
00809-0100-5110, Rev AA

5.15 Protocol handling

5.15.1 Logging the channel communication

WinSetup allows you to log communication on the various communication protocol channels. You can log specific devices, as well as filter out certain function codes and error types.
To log the communication of a particular protocol channel do the following:
1. In the WinSetup workspace, select the protocol channel icon:
Service Functions
December 2018
2. Click the right mouse button and choose the View Log option, or from the Service menu choose
Channels/View Log.
3. Specify a log profile. You can filter out certain function codes and devices as well as error types as
shown in Ta bl e 5 -1 below.
Service Functions
91
Page 100
Service Functions
December 2018
Table 5-1. Realtime log settings
Reference Manual
00809-0100-5110, Rev AA
Filter Setting Description
Function Code A Function Code defines a specific action or type of data. You can log all function codes or
a specific code.
Device Address You can log all devices or a device with a certain address by your own choice.
Note. The device address is automatically copied from the current settings in the File Log Settings window, see “Saving the communication log to file” on page 94. You can change
this address to any other address that you want to log.
Enable Filtering Mark this check box to enable filtering by function codes and addresses.
Errors Select the check box for the type of error you like to record: Time-out Errors, Check Sum
Errors, or Other Errors. You can select one or more check boxes.
Number of messages
Specify the number of messages that will be added each time the Communication Log window is updated. If the log is updated too quickly, you may increase the Number of messages value to reduce the update speed.
4. Click the OK button to open the Communication Log window.
92
The Channel Communication Log window is continuously updated with new data. To stop WinSetup from feeding new data click the right mouse button and choose Freeze.
Service Functions
Loading...