Rosemount Supplemental Guide: Replacing a Rosemount 8712H Transmitter with a Rosemount 8782 Transmitter Manuals & Guides

Supplemental Guide
00825-1100-8782, Rev AB
December 2020
Replacing a Rosemount™ 8712H Transmitter with a Rosemount 8782 Transmitter
Supplemental Guide December 2020

1 Safety

WARNING
Failure to follow these installation guidelines could result in serious injury
or death.
Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the operating instructions, unless qualified.
Potential electrostatic charging hazard: Rosemount Magnetic flow
meters ordered with non-standard paint options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flow meter with a dry cloth or clean with solvents.
Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
To prevent ignition of flammable or combustible atmosphere,
disconnect power before servicing circuits.
Explosion hazard: Do not disconnect equipment when a flammable or
combustible atmosphere is present.
Do not connect a Rosemount 8782 Transmitter to a non-Rosemount
sensor.
Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the process reference ground.
Shock hazard: Shut off power before servicing. Do not operate without
power compartment cover.
2 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
December 2020 Supplemental Guide
CAUTION
The sensor liner is vulnerable to handling damage. Liner damage can
render the sensor useless. Failure to observe these instructions could result in severe damage to the sensor lining and possible sensor replacement.
To avoid possible damage to the sensor liner ends:Do not use metallic or spiral-wound gaskets. If spiral wound or
metallic gaskets are required for the application, lining protectors must be used.
If frequent removal is anticipated, attach short spool pieces to the
sensor ends.
Tighten bolts in the proper sequence to the specified torque limits.
Correct flange bolt tightening is crucial for proper sensor operation and life.
In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent stray voltage/current from passing through the meter. Failure to adequately protect the meter could result in damage to the transmitter and lead to meter failure.
Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
Supplemental Guide 3
Supplemental Guide December 2020

2 Introduction

This document provides specific instructions for replacing a Rosemount 8712H transmitter with a Rosemount 8782 Magnetic Slurry wall-mount transmitter, when used with a Rosemount 8707 sensor only.
For additional transmitter installation information, configuration,
maintenance, and troubleshooting, refer to the Rosemount™ 8782
Magnetic Slurry Flow Meter with HART Protocol Reference Manual
For sensor installation refer to the Rosemount™ 8700 Series Magnetic
Flowmeter Sensors Reference Manual
All user documentation can be found at www.emerson.com. For more contact information see Emerson Flow customer service.

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
4 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
Loading...
+ 8 hidden pages