Rosemount Safety Manual: Rosemount 3051S Series of Instrumentation Manuals & Guides

Safety Manual
00809-0700-4801, Rev CA
March 2021
Rosemount™ 3051S Series of Instrumentation
Pressure, Flow, and Level Measurement
Safety messages
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
See listed technical assistance contacts.
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 211
Europe/ Middle East/Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson representative.
The content of this document is based on the English language version. Any differences in non-English versions should be resolved in favor of the most current English version.
2
Safety Manual
00809-0700-4801

Contents

March 2021
Contents
Chapter 1 Introduction.............................................................................................................. 5
1.1 Using this manual........................................................................................................................ 5
Chapter 2 Installation and commissioning..................................................................................7
2.1 Installation wiring considerations................................................................................................ 7
2.2 IEC 61508 relevant requirements.................................................................................................7
2.3 Failure rates according to IEC 61508 in FIT................................................................................... 7
2.4 SIS-certified firmware versions...................................................................................................10
2.5 Safety precautions.....................................................................................................................10
2.6 Installation in SIS applications....................................................................................................11
2.7 Configuring in SIS applications...................................................................................................11
Chapter 3 Proof tests................................................................................................................15
3.1 Partial proof test........................................................................................................................ 16
3.2 Comprehensive proof test......................................................................................................... 17
3.3 Partial proof test – PATC Diagnostics enabled............................................................................18
Chapter 4 Operating considerations.........................................................................................21
4.1 Reliability data........................................................................................................................... 21
4.2 Failure reporting........................................................................................................................ 22
4.3 Equipment replacement or disposal...........................................................................................22
Appendix A Terms and definitions...............................................................................................23
3
March 2021
Safety ManualContents
00809-0700-4801
4 www.Emerson.com
Safety Manual
00809-0700-4801

1 Introduction

1.1 Using this manual

This document provides information about how to install, commission, and proof test a Rosemount 3051S, Rosemount 3051S Advanced Diagnostics, Rosemount 3051S MultiVariable™, and Rosemount 3051S Electronic Remote Sensor (ERS™) System to comply with safety instrumented systems (SIS) requirements.
This manual assumes that the following conditions apply:
transmitter has been installed correctly and completely according to the instructions in
the transmitter Reference Manual and Quick Start Guide
installation complies with all applicable safety requirements
operator is trained in local and corporate safety standards
Introduction
March 2021
Related documents
All product documentation is available at Emerson.com.
For more information, reference the following documents:
Transmitter Document
Rosemount 3051S Rosemount 3051S with Advanced Diagnostics
Rosemount 3051S Quick Start Guide
Rosemount 3051S with Advanced Diagnostics Quick Start Guide
Rosemount 3051SMV MultiVariable Transmitter Reference Manual
Rosemount 3051S Electronic Remote Sensor (ERS) System Reference Manual
Reference Manual
Quick Start Guide
Quick Start Guide
5
March 2021
Safety ManualIntroduction
00809-0700-4801
6 www.Emerson.com
Safety Manual
Installation and commissioning
00809-0700-4801

2 Installation and commissioning

Use this section to install and commission a Rosemount 3051S Pressure, Flow, and Level Transmitter with SIS features.

2.1 Installation wiring considerations

Refer to the product reference manual for specifications and recommendations for proper installation.

2.2 IEC 61508 relevant requirements

The Rosemount 3051S Pressure Transmitter, Rosemount 3051S Advanced Diagnostics, Rosemount 3051S MultiVariable™ Transmitter, and Rosemount 3051S Electronic Remote Sensor (ERS™) System are all certified per the relevant requirements of IEC 61508 or the Route 2H approach.
March 2021
Systematic capability Random capability
SIL 3 capable Type B Element
Route 1H: SIL 2@HFT=0 SIL 3@HFT=1 (SFF ≥ 90%) Route 2H (low demand): SIL 2@HFT=0 SIL 3@HFT=1 (SFF < 90%) Route 2H (high demand): SIL 2@HFT=0 SIL 3@HFT=1 (SFF < 90%)
(1) Rosemount 3051S MultiVariable Transmitter not available with Route 1H. (2) Only available with the Rosemount 3051S Advanced Diagnostics Transmitter (DA2 option).
(1)

2.3 Failure rates according to IEC 61508 in FIT

FIT = 1 failure/109 hours
Table 2-1: Failure Rates for Rosemount 3051S Pressure Transmitter (Software Rev.
7.0 and Above)
Transmitter Λ
Rosemount 3051S Coplanar DP and Gage 0 82 274 40
Rosemount 3051S Coplanar Absolute, In-line Gage and Absolute
Rosemount 3051S Flow Meter based on 1195, 405, or 485 primaries
Rosemount 3051S Level Transmitter (w/o additional seal)
SD
0 80 260 37
0 90 274 51
0 82 274 74
Λ
SU
Λ
DD
(2)
Λ
DU
7
March 2021
Safety ManualInstallation and commissioning
00809-0700-4801
Table 2-2: Failure Rates for Rosemount 3051S Pressure Transmitter, Option Code DA2 (Software Rev. 7.0 and Above)
Transmitter Λ
SD
Λ
SU
Λ
DD
Λ
Rosemount 3051S Coplanar DP and Gage 0 6 685 34
Rosemount 3051S Coplanar DP and Gage with PATC
0 6 699 20
enabled
Rosemount 3051S Coplanar Absolute, In-line Gage
0 6 681 34
and Absolute
Rosemount 3051S Coplanar Absolute, In-line Gage
0 6 695 20
and Absolute with PATC enabled
Rosemount 3051S Flow Meter based on 1195, 405, or
0 14 685 45
485 primaries
Rosemount 3051S Level Transmitter (w/o additional
0 6 702 51
seal)
Table 2-3: Failure Rates for Rosemount 3051SMV MultiVariable Transmitter (Software Rev. 3.0 and Above)
Transmitter Λ
SD
Rosemount 3051SMV_P1 0 74 902 104
Rosemount 3051SMV_P2 0 74 642 73
Rosemount 3051SMV_P3, 3051SMV_P5,
0 74 880 81
3051SMV_P6
Λ
SU
Λ
DD
Λ
DU
DU
Rosemount 3051SMV_P4, 3051SMV_P7,
0 74 620 50
3051SMV_P8
Rosemount 3051SMV_M1 0 74 987 150
Rosemount 3051SMV_M2 0 74 727 119
Rosemount 3051SMV_M3 0 74 831 127
Rosemount 3051SMV_M4 0 74 705 95
Rosemount 3051SFA1, 3051SFC1, 3051SFP1 – High
0 82 987 161
Trip (normal conditions)
Rosemount 3051SFA1, 3051SFC1, 3051SFP1 – Low
0 84 987 159
Trip (normal conditions)
Rosemount 3051SFA2, 3051SFC2, 3051SFP2 – High
0 82 727 130
Trip (normal conditions)
Rosemount 3051SFA2, 3051SFC2, 3051SFP2 – Low
0 84 727 128
Trip (normal conditions)
Rosemount 3051SFA3, 3051SFC3, 3051SFP3 – High
0 82 831 138
Trip (normal conditions)
Rosemount 3051SFA3, 3051SFC3, 3051SFP3 – Low
0 84 831 136
Trip (normal conditions)
Rosemount 3051SFA4, 3051SFC4, 3051SFP4 – High
0 82 705 106
Trip (normal conditions)
8 www.Emerson.com