Rosemount Rosemount™ 327T Temperature Transmitter Quick Start Guide Manuals & Guides

00825-0100-4329, Rev 02
Rosemount™ 327T Temperature Transmitter
Quick Start Guide
August 2020
Contents
2 Quick Start Guide

1 Introduction

The Rosemount 327T Temperature Transmitter detects media temperature and converts it into an analog output signal (4 - 20 mA). The temperature transmitter includes an IO-Link interface for configuring parameter settings or viewing process and diagnostic data.

1.1 Getting started

Follow these steps to configure the temperature transmitter for normal operation.
Procedure
1. Connect the temperature transmitter to a PC to set parameters using IO-Link.
2. Set the standard unit of measurement in °F or °C (Uni). (See
Adjustable parameters)
3. Set the analog signal. (See Analog function)
OU2: I = 4-20 mA or Ineg = 20-4 mA
ASP and AEP: scaling of the measuring range.
4. Configure Drift Monitoring. (See Setting range for drW and drA)
drW: drift threshold at which the temperature transmitter signals
"warning".
drA: drift threshold at which the temperature transmitter signals
"alarm".
ddr: Drift Monitoring Diagnostic delay.
5. Set which diagnostic cases the temperature transmitter signals using drEd. (See Diagnostic cases)
ON: only failure diagnostic cases
ONdr: alarm and failure diagnostic cases
OFF: warning, alarm, and failure diagnostic cases
6. Configure analog signal for diagnostic cases (FOU2). (See Adjustable
parameters)
ON: 21.5 mA
OFF: 3.5 mA
7. Configure switching signal for diagnostic cases in three-wire operation (dOU1). (See Diagnostic function (three-wire))
Quick Start Guide 3
dOU1: Output opens, closes, or pulsates; according to
configuration.
8. Configure output logic for diagnostic output in three-wire operation (P-n). (See Adjustable parameters)
pnp
npn
9. Complete all other necessary parameter settings.
Postrequisites
Perform these tasks to complete setting up the transmitter:
Mounting the transmitter
Wire the Transmitter
Operation

1.2 Functions and features

The temperature transmitter detects process temperature and converts it into an analog output signal.
The temperature transmitter includes an IO-Link interface for configuring parameter settings or viewing process and diagnostic data.
The transmitter operates in two-wire or three-wire operation modes. The modes produce these output signals:
Operating mode
Two-wire Analog signal for temperature measurement and diagnostics
Three-wire OUT1: switching signal for diagnostics and IO-Link
Output signals
communication
OUT2: analog signal for temperature measurement and
diagnostics

1.2.1 Analog function

The temperature transmitter converts the measured temperature value into an analog signal proportional to the temperature.
The temperature transmitter also uses the analog output to send diagnostic messages (see Diagnostic function). Diagnostic messages interrupt the transfer of the measured temperature value depending on the operating mode and drEd. The transmitter modifies the analog output to the following values according to NE43: 3.5 mA (FOU2 = On) or 21.5 mA (FOU2 = OFF).
4 Quick Start Guide
Depending on the OU2 setting, the analog signal is between these measuring ranges in normal operation:
I: 4-20 mA
Ineg: 20-4 mA
The measuring range is scalable using these parameters:
ASP: the analog start point and the measured temperature when the
analog signal is 4 mA (OU2 = I) or 20 mA (OU2 = Ineg)
AEP: the analog end point and the measured temperature when the
analog signal is 20 mA (OU2 = I) or 4 mA (OU2 = Ineg).
Note
The minimum difference between ASP and AEP is 9°F (5°C).
If the measured temperature value is outside the scaled measuring range, the analog signal is 20-20.5 mA or 3.8-4 mA (see Figure 1-1). When the measured temperature value continues to increase or decrease, diagnostic case 5 occurs. For more information, see Diagnostic cases.
Figure 1-1: Analog output with factory settings
1: Setting OU2 = I
2: Setting OU2 = Ineg
MAW: initial value of the measuring range
MEW: final value of the measuring range
ASP: analog start point
AEP: analog end point
Quick Start Guide 5

1.2.2 Diagnostic function

The temperature transmitter uses two different, thermally coupled sensor elements (NTC, PT 1000) to automatically detect drifts and errors during temperature measurement.
The temperature transmitter forms an average value using the individual NTC and Pt 1000 measured values. That value determines the measured temperature value and is the basis for Drift Monitoring Diagnostic (see Drift
Monitoring).
The temperature transmitter can detect other errors. Use the parameter drEd to set which diagnostic cases the temperature transmitter signals. For more information, see Diagnostic cases.
The analog signal provides diagnostic case messages in two-wire operations. In three-wire operations, the switching signal provides diagnostic case messages in addition to the analog signal.
Drift Monitoring
For Drift Monitoring Diagnostic, the temperature transmitter compares the temperature deviation of sensor element 1 (NTC) and sensor element 2 (Pt
1000) to the average temperature value. The parameters drW (warning threshold) and drA (alarm threshold) define the permissible temperature deviation.
When values exceed these thresholds, the temperature transmitter triggers drift monitoring and identifies a fault (see Diagnostic cases).
Figure 1-2: Drift monitoring example
Example: NTC sensor element (1) measures 149 °F and Pt 1000 sensor element (2) measures 140 °F. The average value (3) is 144.5 °F, i.e. both elements deviate by 4.5 °F. With setting drW = 4 °F and drA = 9 °F, the temperature transmitter provides a warning message if drEd = OFF. In this case, the temperature transmitter would not send an alarm message.
6 Quick Start Guide
For more information about configuring drW and drA, see Setting range for
drW and drA.
Note
Temperature difference of at most 0.18 °F (0.1 °C) can occur with sensor elements because of standard manufacturing tolerances. This does not affect the drift monitoring diagnostic.
Note
Large temperature changes in the medium might cause short-term differences between the measured temperature values of both sensor elements. To avoid short-term drift warnings, increase the drift warning delay time (ddr).
Sensor backup
If one of the two sensors in the transmitter fails, the temperature transmitter can use the remaining sensor for temperature measurement.
For more information on operating the temperature transmitter in backup mode, see Troubleshooting.
Note
Drift monitoring is not possible if a sensor fails and sensor backup is active.
Diagnostic cases
The temperature transmitter identifies error scenarios with these diagnostic cases.
For more information on parameters relating to diagnostic cases, see
Adjustable parameters or Drift Monitoring.
Table 1-1: Warnings
Diagnostic number
1 The temperature deviation exceeded the drift warning
2 The temperature of the internal electronics exceeded the limit
Description
threshold (drW).
of 257 °F (125 °C).
Table 1-2: Alarms
Case number Description
3 The temperature deviation exceeded the drift alarm threshold
4 One of the two sensor elements failed.
Quick Start Guide 7
(drA).
Table 1-2: Alarms (continued)
Case number Description
5 The measured temperature value is outside the allowable
6 The supply voltage is outside the operating range.
(1) For 2-wire operation, no diagnostic message is provided in case of low voltage
(see Diagnostic function (two-wire)).
measuring range.
(1)
Table 1-3: Failures
Case number Description
7 The temperature deviation exceeded the drift failure threshold
8 An error occurred while setting parameters using IO-Link.
9 Both sensor elements failed or general electronics problems.
(drF).
Diagnostic function (two-wire)
In two-wire operation, the temperature transmitter uses the analog output for temperature measurement and diagnostics.
drEd configures the diagnostic cases that the temperature transmitter signals using the analog output:
ON: Limits the diagnostic messages to only failure messages. The
temperature transmitter will signal only diagnostic cases 7-9.
ONdr: Limits the diagnostic messages to alarm and failure messages. The
temperature transmitter will signal only diagnostic cases 3-9.
OFF: Allows all diagnostic messages. The temperature transmitter will
signal all diagnostic cases.
For more information, see Diagnostic cases.
To signal a diagnostic case, the temperature transmitter interrupts the transfer of temperature measurements and provides these analog outputs using FOU2:
ON: 21.5 mA
OFF: 3.5 mA
Note
In a two-wire operation, the temperature transmitter does not provide diagnostic messages in the event of low voltage.
8 Quick Start Guide
Loading...
+ 16 hidden pages