Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option5
ContentsReference Manual
October 202100809-1100-4004
6Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualSafety messages
00809-1100-4004October 2021
1Safety messages
WARNING
Explosion hazards. Failure to follow these instructions could cause an explosion,
resulting in death or serious injury.
• Verify the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
• Installation of this transmitter in an explosive environment must be in accordance
with the appropriate local, national, and international standards, codes, and
practices. Review the approvals documents for any restrictions associated with a safe
installation.
• Do not remove transmitter covers or thermocouple (if equipped) in explosive
atmospheres when the circuit is live. Both transmitter covers must be fully engaged
to meet explosion-proof requirements.
• Before connecting a hand-held communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
WARNING
Electrical shock hazard. Failure to follow this instruction could result in death or serious
injury. Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
WARNING
General hazard. Failure to follow these instructions could result in death or serious
injury.
• This product is intended to be used as a flowmeter for liquid, gas, or steam
applications. Do not use for any other purpose.
• Make sure only qualified personnel perform the installation.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option7
Safety messagesReference Manual
October 202100809-1100-4004
8Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualIntroduction
00809-1100-4004October 2021
2Introduction
2.1Overview
System description
The Vortex Flow Meter consists of a meter body and transmitter, and measures volumetric
flow rate by detecting the vortices created by a fluid passing by the shedder bar.
The meter body is installed in-line with process piping. A sensor is located at the end of the
shedder bar which creates a sine wave signal due to the passing vortices. The transmitter
measures the frequency of the sine wave and converts it into a flow rate.
Safety messages
Procedures and instructions in this manual may require special precautions to ensure the
safety of the personnel performing the operations. Refer to the safety messages listed at
the beginning of this document, before performing any operations.
Chapters
SectionWho usesDescription
Pre-installationPlanners and
installers
Basic installationPlanners and
installers
Basic
configuration
Advanced
installation
Advanced
configuration
OperationOperations
TroubleshootingInstallers and
MaintenanceOperations
Operations
technicians
InstallersInstallation procedures required after initial setup for
Operations
technicians
technicians
operations
technicians
technicians
Reference information to help you verify compatibility
between the meter and its application and installation
location
Mechanical and electrical installation instructions typically
required as initial setup in all applications
Configuration parameters typically required as initial setup
in all applications
some applications
Configuration procedures required after initial setup for
some applications
Information on advanced configuration parameters and
functions that can aid in maintaining the flow meter
Troubleshooting techniques, diagnostic information, and
transmitter verification procedures
Information on maintaining the flow meter
Appendixes
Appendixes include supplementary information that may be useful in some situations.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option9
IntroductionReference Manual
October 202100809-1100-4004
10Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualPre-installation
00809-1100-4004October 2021
3Pre-installation
3.1Planning
3.1.1Sizing
To determine the correct meter size for optimal flow meter performance:
• Determine the limits of measuring flow.
• Determine the process conditions so that they are within the stated requirements for
Reynolds number and velocity.
For sizing details, see Product Specifications.
Sizing calculations are required to select the proper flow meter size. These calculations
provide pressure loss, accuracy, and minimum and maximum flow rate data to guide in
proper selection. Vortex sizing software can be found using the Selection and Sizing tool.
The Selection and Sizing tool can be accessed online or downloaded for offline use using
this link: www.Emerson.com/FlowSizing.
3.1.2
3.1.3
Wetted material selection
Ensure that the process fluid is compatible with the meter body wetted materials when
specifying the Rosemount 8800D. Corrosion will shorten the life of the meter body.
Consult recognized sources of corrosion data or contact technical support for more
information.
Note
If Positive Material Identification (PMI) is required, perform test on a machined surface.
Orientation
The best orientation for the meter depends on the process fluid, environmental factors,
and any other nearby equipment.
Vertical installation
Vertical, upward, installation allows upward process liquid flow and is generally preferred.
Upward flow ensures that the meter body always remains full and that any solids in the
fluid are evenly distributed.
The meter can be mounted in the vertical down position when measuring gas or steam
flows. This type of application is strongly discouraged for liquid flows, although it can be
done with proper piping design.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option11
Pre-installationReference Manual
October 202100809-1100-4004
Figure 3-1: Vertical installation
AB
A. Liquid or gas flow
B. Gas flow
Note
To ensure the meter body remains full, avoid downward vertical liquid flows where back
pressure is inadequate.
Horizontal installation
For horizontal installation, the preferred orientation is to have the electronics installed to
the side of the pipe. In liquid applications, this helps prevent any entrained air or solids
from striking the shedder bar and disrupting the shedding frequency. In gas or steam
applications, this helps prevent any entrained liquid (such as condensate) or solids from
striking the shedder bar and disrupting the shedding frequency.
Figure 3-2: Horizontal installation
B
A
A. Preferred installation—meter body installed with electronics to side of pipe
B. Acceptable installation—meter body installed with electronics above pipe
High-temperature installations
The maximum process temperature for integral electronics is dependent on the ambient
temperature where the meter is installed. The electronics must not exceed 185 °F (85 °C).
Figure 3-3 shows combinations of ambient and process temperatures needed to maintain
a housing temperature of less than 185 °F (85 °C).
12Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualPre-installation
00809-1100-4004October 2021
Figure 3-3: Ambient/Process temperature limits
200 (93)
180(82)
160 (71)
600 (316)
700 (371)
C
800 (427)
900 (482)
1000 (538)
A
140 (60)
120 (49)
100 (38)
80 (27)
60 (16)
0
100 (38)
200 (93)
300 (149)
400 (204)
500 (260)
B
A. Ambient temperature °F (°C)
B. Process temperature °F (°C)
C. 185 °F (85 °C) Housing temperature limit.
Note
The indicated limits are for horizontal pipe and vertical meter position, with meter and
pipe insulated with 3 in. (77 mm) of ceramic fiber insulation.
Install the meter body so the electronics are positioned to the side of the pipe or below the
pipe as shown in Figure 3-4. Insulation may also be required around the pipe to maintain
an electronics temperature below 185 °F (85 °C). See Figure 4-2 for special insulation
considerations.
Figure 3-4: Examples of high-temperature installations
B
A
A. Preferred installation—The meter body installed with the electronics to the side of the
pipe.
B. Acceptable installation—The meter body installed with the electronics below the pipe.
3.1.4
Location
Hazardous area
The transmitter has an explosion-proof housing and circuitry suitable for intrinsically safe
and non-incendive operation. Individual transmitters are clearly marked with a tag
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option13
Pre-installationReference Manual
October 202100809-1100-4004
indicating the certifications they carry. For hazardous location installation, including
Explosion-proof, Flameproof,or Intrinsic Safety (I.S.), please consult the Emerson 8800
Approval Document 00825-VA00-0001.
Environmental considerations
Avoid excessive heat and vibration to ensure maximum flow meter life. Typical problem
areas include high-vibration lines with integrally mounted electronics, warm-climate
installations in direct sunlight, and outdoor installations in cold climates.
Although the signal conditioning functions reduce susceptibility to extraneous noise,
some environments are more suitable than others. Avoid placing the flow meter or its
wiring close to devices that produce high intensity electromagnetic and electrostatic
fields. Such devices include electric welding equipment, large electric motors and
transformers, and communication transmitters.
Upstream and downstream piping
The meter may be installed with a minimum of ten diameters (D) of straight pipe length
upstream and five diameters (D) of straight pipe length downstream.
To achieve reference accuracy, straight pipe lengths of 35D upstream and 5D downstream
are required. The value of the K-factor may shift up to 0.5% when the upstream straight
pipe length is between 10D and 35D. For optional K-factor corrections, see Rosemount
™
8800 Vortex Installation Effects Technical Data Sheet. To correct this effect, see Meter factor.
Steam piping
For steam applications, avoid installations such as the one shown in the following figure.
Such installations may cause a water-hammer condition at start-up due to trapped
condensation. The high force from the water hammer can stress the sensing mechanism
and cause permanent damage to the sensor.
Figure 3-5: Wrong steam pipe installation
Pressure and temperature transmitter location
When using pressure and temperature transmitters in conjunction with the vortex flow
meter for compensated mass flows, install the transmitter(s) downstream of the vortex
flow meter.
14Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualPre-installation
00809-1100-4004October 2021
Figure 3-6: Pressure and temperature transmitter location
C
A
B
D
A. Pressure transmitter
B. Four straight pipe diameters downstream
C. Temperature transmitter
D. Six straight pipe diameters downstream
3.1.5
Power supply
Analog 4–20 mA Power supply
External power supply required. Each transmitter operates on 10.8 VDC to 42 VDC
terminal voltage.
Power consumption
One watt maximum per transmitter.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option15
5വ
9SV
Pre-installationReference Manual
October 202100809-1100-4004
HART communication
Figure 3-7: HART communication voltage/resistance requirement
Maximum loop resistance is determined by the voltage level of the external power supply,
as described in the graph.
Note that HART Communication requires a minimum loop resistance of 250 ohms up to a
maximum of 1100 ohms.
R(Ω)
V
ps
Load resistor value.
Minimum power supply voltage required
R(Ω)max = 41.7 (Vps – 10.8 V).
Additional wiring information
• The DC power supply should provide power with less than two percent ripple. The total
resistance load is the sum of the resistance of the signal wiring and the load resistance
of the controller, indicator, and related pieces. Note that the resistance of intrinsic
safety barriers, if used, must be included.
• If a Smart Wireless THUM™ Adapter is being used with the flow meter to exchange
information via IEC 62591 (WirelessHART® Protocol) technology, a minimum loop
resistance of 250 ohms is required. In addition, a minimum power supply voltage (Vps)
of 19.3 volts will be required to output 24 mA.
• If a single power supply is used to power more than one transmitter, the power supply
used and circuitry common to the transmitters should not have more than 20 ohms of
impedance at 1200 Hz. See Table 3-1.
• Loop resistance must be considered in determining the minimum power supply
voltage.
16Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualPre-installation
00809-1100-4004October 2021
Table 3-1: Resistance based on wire gauge
Gauge numberOhms per 1,000 ft (305 m) at 68 °F (20 °C)
equivalent
14 AWG (2 mm2)2.5
16 AWG (1 mm2)4.0
18 AWG (0.8mm2)6.4
20 AWG (0.5 mm2)10
22 AWG (0.3 mm2)16
24 AWG (0.2 mm2)26
3.2Commissioning
For proper configuration and operation, commission the meter before putting it into
operation. Bench commissioning also enables you to check hardware settings, test the
flowmeter electronics, verify flowmeter configuration data, and check output variables.
Any problems can be corrected—or configuration settings changed—before going out into
the installation environment. To commission on the bench, connect a configuration
device to the signal loop in accordance the device instructions.
3.2.1
Alarm and security jumper configuration
Two jumpers on the transmitter specify the alarm and security modes. Set these jumpers
during the commissioning stage to avoid exposing the electronics to the plant
environment. The two jumpers can be found on the electronics board stack or on the LCD
display.
Alarm
Security
To access the jumpers, remove the transmitter electronics housing or the LCD cover (if
equipped) opposite of the terminal block, See Figure 3-8 and Figure 3-9.
As part of normal operations, the transmitter continuously runs a selfdiagnostic routine. If the routine detects an internal failure in the electronics,
flow meter output is driven to a low or high alarm level, depending on the
position of the failure mode jumper. The factory sets the jumper according to
the Configuration Data Sheet, if applicable, or HI by default.
You can protect the configuration data with the security lockout jumper. With
the security lockout jumper ON, any configuration changes attempted on the
electronics are disallowed. You can still access and review any of the operating
parameters and scroll through the available parameters, but no changes can
be made. The factory sets the jumper according to the Configuration Data
Sheet, if applicable, or OFF by default.
Note
If you will be changing configuration variables frequently, it may be useful to
leave the security lockout jumper in the OFF position to avoid exposing the
flow meter electronics to the plant environment.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option17
Pre-installationReference Manual
October 202100809-1100-4004
Figure 3-8: Alarm and security jumpers (no LCD option)
VORTEX
4-20mA
HART
TP1
TEST FREQ
IN
Figure 3-9: Alarm and security jumpers (with LCD option)
HILO
HILO
ALARM
ALARM
FLOW
SECURITY
SECURITY
ONOFF
ONOFF
Failure mode vs. saturation output values
The failure mode alarm output levels differ from the output values that occur when the
operating flow is outside the range points. When the operating flow is outside the range
points, the analog output continues to track the operating flow until reaching the
saturation value listed below; the output does not exceed the listed saturation value
regardless of the operating flow. For example, with standard alarm and saturation levels
and flows outside the 4–20 mA range points, the output saturates at 3.9 mA or 20.8 mA.
When the transmitter diagnostics detect a failure, the analog output is set to a specific
alarm value that differs from the saturation value to allow for proper troubleshooting. The
saturation and alarm levels are software selectable between Rosemount Standard and
NAMUR levels.
18Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualPre-installation
00809-1100-4004October 2021
Table 3-2: Analog output: standard alarm values vs. saturation values
Level4–20 mA saturation value4–20 mA alarm value
Low3.9 mA≤ 3.75 mA
High20.8 mA≥ 21.75 mA
Table 3-3: Analog output: NAMUR-compliant alarm values vs. saturation values
Level4–20 mA saturation value4–20 mA alarm value
Low3.8 mA≤ 3.6 mA
High20.5 mA≥ 22.6 mA
3.2.2Calibration
The flow meter is wet-calibrated at the factory and needs no further calibration during
installation. The calibration factor (K-factor) is indicated on each meter body and is
entered into the electronics. Verification can be accomplished with a configuration device.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option19
Pre-installationReference Manual
October 202100809-1100-4004
20Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualBasic installation
00809-1100-4004October 2021
4Basic installation
4.1Handling
Handle all parts carefully to prevent damage. Whenever possible, transport the system to
the installation site in the original shipping containers. Keep the shipping plugs in the
conduit connections until you are ready to connect and seal them.
NOTICE
To avoid damage to the meter, do not lift the flow meter by the transmitter. Lift the meter
by the meter body. Lifting supports can be tied around the meter body as shown.
Figure 4-1: Lifting supports
4.2Flow direction
The meter can only measure flow in the direction indicated on the meter body. Be sure to
mount the meter body so the FORWARD end of the flow arrow points in the direction of
the flow in the pipe.
4.3Gaskets
The flow meter requires gaskets supplied by the user. Be sure to select gasket material
that is compatible with the process fluid and pressure ratings of the specific installation.
Note
Ensure the inside diameter of the gasket is larger than the inside diameter of the flow
meter and adjacent piping. If gasket material extends into the flow stream, it will disturb
the flow and cause inaccurate measurements.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option21
Basic installationReference Manual
October 202100809-1100-4004
4.4Insulation
Insulation should extend to the end of the bolt on the bottom of the meter body and
should leave at least 1-in. (25 mm) of clearance around the electronics bracket. The
electronics bracket and electronics housing should not be insulated. See Figure 4-2.
Figure 4-2: Insulation best practice to prevent electronics overheating
A. Support tube
CAUTION
In high temperature installations, to avoid damage to the electronics on integral units or
to the remote cable on remote units, only insulate the meter body as shown. Do not
insulate the support tube. See also Orientation.
4.5Flanged-style flow meter mounting
Most vortex flow meters use a flanged-style process connection. Physical mounting of a
flanged-style flow meter is similar to installing a typical section of pipe. Conventional
tools, equipment, and accessories (such as bolts and gaskets) are required. Tighten the
nuts following the sequence shown in Figure 4-4.
Note
The required bolt load for sealing the gasket joint is affected by several factors, including
operating pressure and gasket material, width, and condition. A number of factors also
affect the actual bolt load resulting from a measured torque, including condition of bolt
threads, friction between the nut head and the flange, and parallelism of the flanges. Due
to these application-dependent factors, the required torque for each application may be
different. Follow the guidelines outlined in ASME PCC-1 for proper bolt tightening. Make
sure the flow meter is centered between flanges of the same nominal size and rating as
the flow meter.
22Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualBasic installation
00809-1100-4004October 2021
Figure 4-3: Flanged-style flow meter installation
A. Installation studs and nuts (supplied by customer)
B. Gaskets (supplied by customer)
C. Flow
Figure 4-4: Flange bolt torquing sequence
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option23
Basic installationReference Manual
October 202100809-1100-4004
4.6Wafer-style flow meter alignment and
mounting
Center the wafer-style meter body inside diameter with respect to the inside diameter of
the adjoining upstream and downstream piping. This will ensure the flow meter achieves
its specified accuracy. Alignment rings are provided with each wafer-style meter body for
centering purposes. Follow these steps to align the meter body for installation. Refer to
Figure 4-5.
1. Place the alignment rings over each end of the meter body.
2. Insert the studs for the bottom side of the meter body between the pipe flanges.
3. Place the meter body (with alignment rings) between the flanges.
• Make sure the alignment rings are properly placed onto the studs.
• Align the studs with the markings on the ring that correspond to the flange you
are using.
• If a spacer is used, see Spacers.
Note
Be sure to align the flow meter so the electronics are accessible, the conduits drain,
and the flow meter is not subject to direct heat.
4. Place the remaining studs between the pipe flanges.
5. Tighten the nuts in the sequence shown in Figure 4-4.
6. Check for leaks at the flanges after tightening the flange bolts.
Note
The required bolt load for sealing the gasket joint is affected by several factors,
including operating pressure and gasket material, width, and condition. A number
of factors also affect the actual bolt load resulting from a measured torque,
including condition of bolt threads, friction between the nut head and the flange,
and parallelism of the flanges. Due to these application-dependent factors, the
required torque for each application may be different. Follow the guidelines
outlined in ASME PCC-1 for proper bolt tightening. Make sure the flow meter is
centered between flanges of the same nominal size and rating as the flow meter.
24Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualBasic installation
00809-1100-4004October 2021
Figure 4-5: Wafer-style flow meter installation with alignment rings
B
B
A
4.6.1
C
D
A. Installation studs and nuts (supplied by customer)
B. Alignment rings
C. Spacer (for Rosemount 8800D to maintain Rosemount 8800A dimensions)
D. Flow
Note
See Spacers for instructions on retrofitting 8800D to 8800A installations.
Stud bolts for wafer-style flow meters
The following tables list the recommended minimum stud bolt lengths for wafer-style
meter body size and different flange ratings.
Table 4-1: Stud bolt length for wafer-style flow meters with ASME B16.5 flanges
Line sizeMinimum recommended stud bolt lengths (in inches) for each flange
rating
Class 150Class 300Class 600
½-inch6.006.256.25
1-inch6.257.007.50
1½-inch7.258.509.00
2-inch8.508.759.50
3-inch9.0010.0010.50
4-inch9.5010.7512.25
6-inch10.7511.5014.00
8-inch12.7514.5016.75
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option25
Basic installationReference Manual
October 202100809-1100-4004
Table 4-2: Stud bolt length for wafer-style flow meters with EN 1092 flanges
Line sizeMinimum recommended stud bolt lengths (in mm) for each flange rating
PN 16PN 40PN 63PN 100
DN 15160160170170
DN 25160160200200
DN 40200200230230
DN 50220220250270
DN 80230230260280
DN 100240260290310
DN 150270300330350
DN 200320360400420
Line sizeMinimum recommended stud bolt lengths (in mm) for each flange
rating
JIS 10kJIS 16k and 20kJIS 40k
15mm150155185
25mm175175190
40mm195195225
50mm210215230
80mm220245265
100mm235260295
150mm270290355
200mm310335410
4.7Cable glands
If you are using cable glands instead of conduit, follow the cable gland manufacturer’s
instructions for preparation and make the connections in a conventional manner in
accordance with local or plant electrical codes. Be sure to properly seal unused ports to
prevent moisture or other contamination from entering the terminal block compartment
of the electronics housing.
4.8Flow meter grounding
Grounding is not required in typical vortex applications; however, a proper ground will
eliminate possible noise pickup by the electronics. Grounding straps may be used to
ensure that the meter is grounded to the process piping. If you are using the transient
protection option (T1), grounding straps are required to provide a proper low impedance
ground.
26Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference ManualBasic installation
00809-1100-4004October 2021
Note
Properly ground flow meter body and transmitter per the local code.
To use grounding straps, secure one end of the grounding strap to the bolt extending from
the side of the meter body and attach the other end of each grounding strap to a suitable
ground. See Figure 4-6.
Figure 4-6: Grounding connections
A. Internal ground connection
B. External ground assembly
4.9Grounding the transmitter case
The transmitter case should always be grounded in accordance with national and local
electrical codes. The most effective transmitter case grounding method is direct
connection to earth ground with minimal impedance. Methods for grounding the
transmitter case include:
Internal
Ground
Connection
External
Ground
Assembly
Note
Grounding the transmitter case using the threaded conduit connection may not provide a
sufficient ground. The transient protection terminal block (Option Code T1) does not
provide transient protection unless the transmitter case is properly grounded. For
transient terminal block grounding, see Transient protection. Use the above guidelines to
The Internal Ground Connection screw is inside the FIELD TERMINALS
side of the electronics housing. This screw is identified by a ground
symbol ( ), and is standard on all Rosemount 8800D transmitters.
This assembly is located on the outside of the electronics housing and
is included with the optional transient protection terminal block
(Option Code T1). The External Ground Assembly can also be ordered
with the transmitter (Option Code V5) and is automatically included
with certain hazardous area approvals. See Figure 4-6 for the location
of the external ground assembly.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option27
Basic installationReference Manual
October 202100809-1100-4004
ground the transmitter case. Do not run the transient protection ground wire with signal
wiring as the ground wire may carry excessive electric current if a lightning strike occurs.
4.10Conduit installation
Prevent condensation in any conduit from flowing into the housing by mounting the
flowmeter at a high point in the conduit run. If the flowmeter is mounted at a low point in
the conduit run, the terminal compartment could fill with fluid.
If the conduit originates above the flowmeter, route conduit below the flowmeter to form
a drip loop before entry. In some cases a drain seal may need to be installed.
Figure 4-7: Proper conduit installation
AA
A. Conduit line
4.11Wiring
The signal terminals are located in a compartment of the electronics housing separate
from the flow meter electronics. Connections for a configuration tool and an electric
current test connection are above the signal terminals.
Note
A power disconnect is required to remove power from the transmitter for maintenance,
removal, and replacement.
Common wiring practices
Twisted pairs are required to minimize noise pickup in the 4–20 mA signal and digital
communication signal. For high EMI/RFI environments, shielded signal wire is required and
recommended in all other installations. To ensure communication, wiring should be 24
AWG (0.205 mm²) or larger, and not exceed 5,000 ft (1500 m).
4.11.1
Analog output
The flow meter provides a 4–20 mA dc isolated electric current output, linear with the flow
rate or optionally the Process Temperature with the MCA option. To make connections,
remove the FIELD TERMINALS side cover of the electronics housing. All power to the
electronics is supplied over the 4–20 mA signal wiring. Connect the wires as shown.
28Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
A
Reference ManualBasic installation
00809-1100-4004October 2021
Figure 4-8: 4–20 mA wiring
A. Power supply. See Power supply.
4.12Remote installation
4.12.1
If a remote electronics option (Rxx or Axx) was ordered, the flow meter assembly will be
shipped in two parts:
• The meter body with an adapter installed in the support tube and an interconnecting
coaxial cable attached to it.
• The electronics housing installed on a mounting bracket.
If an armored remote electronics option (Axx) was ordered, follow the same instructions as
for the standard remote cable connection with the exception that the cable may not need
to be run through conduit. Both standard and armored cable include cable glands.
Information on remote installation can be found in Cable connections.
Mounting
Mount the meter body in the process flow line as described earlier in this section. Mount
the bracket and electronics housing in the desired location. The housing can be
repositioned on the bracket to facilitate field wiring and conduit routing.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option29
Basic installationReference Manual
October 202100809-1100-4004
4.12.2Cable connections
Complete these steps for connecting the loose end of the coaxial cable to the electronics
housing. If connecting/disconnecting the meter adapter to the meter body, see Remote
electronics procedures.
Figure 4-9: Remote installation
A
B
C
D
E
F
G
H
P
O
N
J
K
I
M
L
A. ½ NPT conduit adapter or cable gland (supplied by customer for Rxx options)
B. Coaxial cable
C. Meter adapter
D. Union
E. Washer
F. Nut
G. Sensor cable nut
H. Support tube
I. Meter body
J. Electronics housing
K. Coaxial cable SMA nut
L. ½ NPT conduit adapter or cable gland (supplied by customer for Rxx options)
M. Housing adapter screws
N. Housing adapter
O. Housing base screw (one of four)
P. Ground connection
30Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Loading...
+ 114 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.