Rosemount Reference Manual: Rosemount 8800D Series Vortex Flow Meter with MPA and MCA option Manuals & Guides

00809-1100-4004, Rev AC
Rosemount™ 8800D Vortex Flow Meter
For Meters with Pressure Compensation (MPA) or Pressure+Temperature Compensation (MCA)
Reference Manual
October 2021
Reference Manual Contents
00809-1100-4004 October 2021

Contents

Rosemount™ 8800D Vortex Flowmeter................................................................................. 0
Chapter 1 Safety messages.........................................................................................................7
Chapter 2 Introduction.............................................................................................................. 9
2.1 Overview..................................................................................................................................... 9
Chapter 3 Pre-installation........................................................................................................ 11
3.1 Planning.................................................................................................................................... 11
3.2 Commissioning..........................................................................................................................17
Chapter 4 Basic installation...................................................................................................... 21
4.1 Handling....................................................................................................................................21
4.2 Flow direction............................................................................................................................21
4.3 Gaskets......................................................................................................................................21
4.4 Insulation...................................................................................................................................22
4.5 Flanged-style flow meter mounting...........................................................................................22
4.6 Wafer-style flow meter alignment and mounting...................................................................... 24
4.7 Cable glands.............................................................................................................................. 26
4.8 Flow meter grounding............................................................................................................... 26
4.9 Grounding the transmitter case.................................................................................................27
4.10 Conduit installation................................................................................................................. 28
4.11 Wiring......................................................................................................................................28
4.12 Remote installation................................................................................................................. 29
Chapter 5 Basic configuration.................................................................................................. 37
5.1 About basic configuration..........................................................................................................37
5.2 Process variables........................................................................................................................37
5.3 Tag............................................................................................................................................ 39
5.4 Long Tag....................................................................................................................................39
5.5 Process configuration................................................................................................................ 39
5.6 Reference K-factor.....................................................................................................................40
5.7 Flange type................................................................................................................................41
5.8 Pipe I.D...................................................................................................................................... 41
5.9 Upper and lower range values....................................................................................................42
5.10 Damping................................................................................................................................. 42
5.11 Optimize Digital Signal Processing (DSP)................................................................................. 43
Chapter 6 Advanced installation...............................................................................................45
6.1 Insert integral temperature sensor.............................................................................................45
6.2 Pulse output.............................................................................................................................. 46
6.3 Transient protection.................................................................................................................. 47
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 3
Contents Reference Manual
October 2021 00809-1100-4004
6.4 Wire a HART pressure transmitter for pressure compensation................................................... 50
Chapter 7 Advanced configuration...........................................................................................53
7.1 LCD display................................................................................................................................ 53
7.2 Compensated K-factor...............................................................................................................53
7.3 Meter body................................................................................................................................54
7.4 Meter factor...............................................................................................................................54
7.5 Variable mapping...................................................................................................................... 54
7.6 Alarm/saturation levels..............................................................................................................55
7.7 Pulse output.............................................................................................................................. 56
7.8 Mass compensation...................................................................................................................57
7.9 Configure HART pressure transmitter........................................................................................ 62
7.10 SMART fluid diagnostic............................................................................................................ 62
7.11 HART multidrop communication............................................................................................. 64
7.12 Burst mode..............................................................................................................................65
7.13 Optimizing HART systems for pressure compensation.............................................................66
7.14 Signal processing.....................................................................................................................66
7.15 Device information.................................................................................................................. 68
7.16 Change HART revisions............................................................................................................69
7.17 Special process variable units...................................................................................................69
7.18 Elapsed Time Meter................................................................................................................. 70
7.19 Flow totalizer...........................................................................................................................70
7.20 Locate device...........................................................................................................................71
Chapter 8 Troubleshooting...................................................................................................... 73
8.1 Communication problem with HART-based communicator.......................................................73
8.2 Incorrect 4–20 mA output......................................................................................................... 73
8.3 Incorrect pulse output............................................................................................................... 74
8.4 Error messages on a HART-based communicator.......................................................................74
8.5 Flow in Pipe, No Output............................................................................................................. 74
8.6 No flow, output......................................................................................................................... 75
8.7 Diagnostic messages................................................................................................................. 76
8.8 Temperature and pressure compensation troubleshooting....................................................... 81
8.9 Electronics test points................................................................................................................82
Chapter 9 Maintenance............................................................................................................85
9.1 Transient protection.................................................................................................................. 85
9.2 Installing the LCD indicator........................................................................................................86
9.3 Hardware replacement.............................................................................................................. 88
9.4 Return of material....................................................................................................................102
Appendix A Product Specifications............................................................................................105
A.1 Physical specifications............................................................................................................. 105
A.2 Performance specifications......................................................................................................109
4 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Contents
00809-1100-4004 October 2021
A.3 Typical flow rates.....................................................................................................................114
A.4 HART specifications.................................................................................................................122
A.5 LCD indicator functional specifications.................................................................................... 126
Appendix B Spacers.................................................................................................................. 127
Appendix C Electronics verification........................................................................................... 129
C.1 Electronics verification using flow simulation mode.................................................................129
C.2 Fixed flow rate simulation........................................................................................................130
C.3 Varying flow rate simulation....................................................................................................130
C.4 Verify electronics using an external frequency generator.........................................................130
C.5 Output variable calculations with known input frequency........................................................132
C.6 Unit conversion table...............................................................................................................133
C.7 Example calculations............................................................................................................... 133
Appendix D Dual and Single Analog Wiring Configuration with the HART Communication
Bridge............................................................................................................... 139
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 5
Contents Reference Manual
October 2021 00809-1100-4004
6 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Safety messages
00809-1100-4004 October 2021

1 Safety messages

WARNING
Explosion hazards. Failure to follow these instructions could cause an explosion, resulting in death or serious injury.
Verify the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Installation of this transmitter in an explosive environment must be in accordance
with the appropriate local, national, and international standards, codes, and practices. Review the approvals documents for any restrictions associated with a safe installation.
Do not remove transmitter covers or thermocouple (if equipped) in explosive
atmospheres when the circuit is live. Both transmitter covers must be fully engaged to meet explosion-proof requirements.
Before connecting a hand-held communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
WARNING
Electrical shock hazard. Failure to follow this instruction could result in death or serious injury. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
WARNING
General hazard. Failure to follow these instructions could result in death or serious injury.
This product is intended to be used as a flowmeter for liquid, gas, or steam
applications. Do not use for any other purpose.
Make sure only qualified personnel perform the installation.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 7
Safety messages Reference Manual
October 2021 00809-1100-4004
8 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Introduction
00809-1100-4004 October 2021

2 Introduction

2.1 Overview

System description
The Vortex Flow Meter consists of a meter body and transmitter, and measures volumetric flow rate by detecting the vortices created by a fluid passing by the shedder bar.
The meter body is installed in-line with process piping. A sensor is located at the end of the shedder bar which creates a sine wave signal due to the passing vortices. The transmitter measures the frequency of the sine wave and converts it into a flow rate.
Safety messages
Procedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Refer to the safety messages listed at the beginning of this document, before performing any operations.
Chapters
Section Who uses Description
Pre-installation Planners and
installers
Basic installation Planners and
installers
Basic configuration
Advanced installation
Advanced configuration
Operation Operations
Troubleshooting Installers and
Maintenance Operations
Operations technicians
Installers Installation procedures required after initial setup for
Operations technicians
technicians
operations technicians
technicians
Reference information to help you verify compatibility between the meter and its application and installation location
Mechanical and electrical installation instructions typically required as initial setup in all applications
Configuration parameters typically required as initial setup in all applications
some applications
Configuration procedures required after initial setup for some applications
Information on advanced configuration parameters and functions that can aid in maintaining the flow meter
Troubleshooting techniques, diagnostic information, and transmitter verification procedures
Information on maintaining the flow meter
Appendixes
Appendixes include supplementary information that may be useful in some situations.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 9
Introduction Reference Manual
October 2021 00809-1100-4004
10 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Pre-installation
00809-1100-4004 October 2021

3 Pre-installation

3.1 Planning

3.1.1 Sizing

To determine the correct meter size for optimal flow meter performance:
Determine the limits of measuring flow.
Determine the process conditions so that they are within the stated requirements for
Reynolds number and velocity.
For sizing details, see Product Specifications.
Sizing calculations are required to select the proper flow meter size. These calculations provide pressure loss, accuracy, and minimum and maximum flow rate data to guide in proper selection. Vortex sizing software can be found using the Selection and Sizing tool. The Selection and Sizing tool can be accessed online or downloaded for offline use using this link: www.Emerson.com/FlowSizing.
3.1.2
3.1.3

Wetted material selection

Ensure that the process fluid is compatible with the meter body wetted materials when specifying the Rosemount 8800D. Corrosion will shorten the life of the meter body. Consult recognized sources of corrosion data or contact technical support for more information.
Note
If Positive Material Identification (PMI) is required, perform test on a machined surface.

Orientation

The best orientation for the meter depends on the process fluid, environmental factors, and any other nearby equipment.
Vertical installation
Vertical, upward, installation allows upward process liquid flow and is generally preferred. Upward flow ensures that the meter body always remains full and that any solids in the fluid are evenly distributed.
The meter can be mounted in the vertical down position when measuring gas or steam flows. This type of application is strongly discouraged for liquid flows, although it can be done with proper piping design.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 11
Pre-installation Reference Manual
October 2021 00809-1100-4004
Figure 3-1: Vertical installation
A B
A. Liquid or gas flow
B. Gas flow
Note
To ensure the meter body remains full, avoid downward vertical liquid flows where back pressure is inadequate.
Horizontal installation
For horizontal installation, the preferred orientation is to have the electronics installed to the side of the pipe. In liquid applications, this helps prevent any entrained air or solids from striking the shedder bar and disrupting the shedding frequency. In gas or steam applications, this helps prevent any entrained liquid (such as condensate) or solids from striking the shedder bar and disrupting the shedding frequency.
Figure 3-2: Horizontal installation
B
A
A. Preferred installation—meter body installed with electronics to side of pipe
B. Acceptable installation—meter body installed with electronics above pipe
High-temperature installations
The maximum process temperature for integral electronics is dependent on the ambient temperature where the meter is installed. The electronics must not exceed 185 °F (85 °C).
Figure 3-3 shows combinations of ambient and process temperatures needed to maintain
a housing temperature of less than 185 °F (85 °C).
12 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Pre-installation
00809-1100-4004 October 2021
Figure 3-3: Ambient/Process temperature limits
200 (93)
180(82)
160 (71)
600 (316)
700 (371)
C
800 (427)
900 (482)
1000 (538)
A
140 (60)
120 (49)
100 (38)
80 (27)
60 (16)
0
100 (38)
200 (93)
300 (149)
400 (204)
500 (260)
B
A. Ambient temperature °F (°C)
B. Process temperature °F (°C)
C. 185 °F (85 °C) Housing temperature limit.
Note
The indicated limits are for horizontal pipe and vertical meter position, with meter and pipe insulated with 3 in. (77 mm) of ceramic fiber insulation.
Install the meter body so the electronics are positioned to the side of the pipe or below the pipe as shown in Figure 3-4. Insulation may also be required around the pipe to maintain an electronics temperature below 185 °F (85 °C). See Figure 4-2 for special insulation considerations.
Figure 3-4: Examples of high-temperature installations
B
A
A. Preferred installation—The meter body installed with the electronics to the side of the
pipe.
B. Acceptable installation—The meter body installed with the electronics below the pipe.
3.1.4

Location

Hazardous area
The transmitter has an explosion-proof housing and circuitry suitable for intrinsically safe and non-incendive operation. Individual transmitters are clearly marked with a tag
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 13
Pre-installation Reference Manual
October 2021 00809-1100-4004
indicating the certifications they carry. For hazardous location installation, including Explosion-proof, Flameproof,or Intrinsic Safety (I.S.), please consult the Emerson 8800 Approval Document 00825-VA00-0001.
Environmental considerations
Avoid excessive heat and vibration to ensure maximum flow meter life. Typical problem areas include high-vibration lines with integrally mounted electronics, warm-climate installations in direct sunlight, and outdoor installations in cold climates.
Although the signal conditioning functions reduce susceptibility to extraneous noise, some environments are more suitable than others. Avoid placing the flow meter or its wiring close to devices that produce high intensity electromagnetic and electrostatic fields. Such devices include electric welding equipment, large electric motors and transformers, and communication transmitters.
Upstream and downstream piping
The meter may be installed with a minimum of ten diameters (D) of straight pipe length upstream and five diameters (D) of straight pipe length downstream.
To achieve reference accuracy, straight pipe lengths of 35D upstream and 5D downstream are required. The value of the K-factor may shift up to 0.5% when the upstream straight pipe length is between 10D and 35D. For optional K-factor corrections, see Rosemount
8800 Vortex Installation Effects Technical Data Sheet. To correct this effect, see Meter factor.
Steam piping
For steam applications, avoid installations such as the one shown in the following figure. Such installations may cause a water-hammer condition at start-up due to trapped condensation. The high force from the water hammer can stress the sensing mechanism and cause permanent damage to the sensor.
Figure 3-5: Wrong steam pipe installation
Pressure and temperature transmitter location
When using pressure and temperature transmitters in conjunction with the vortex flow meter for compensated mass flows, install the transmitter(s) downstream of the vortex flow meter.
14 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Pre-installation
00809-1100-4004 October 2021
Figure 3-6: Pressure and temperature transmitter location
C
A
B
D
A. Pressure transmitter
B. Four straight pipe diameters downstream C. Temperature transmitter D. Six straight pipe diameters downstream
3.1.5

Power supply

Analog 4–20 mA Power supply
External power supply required. Each transmitter operates on 10.8 VDC to 42 VDC terminal voltage.
Power consumption
One watt maximum per transmitter.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 15



5വ
9SV


Pre-installation Reference Manual
October 2021 00809-1100-4004
HART communication
Figure 3-7: HART communication voltage/resistance requirement
Maximum loop resistance is determined by the voltage level of the external power supply, as described in the graph.
Note that HART Communication requires a minimum loop resistance of 250 ohms up to a maximum of 1100 ohms.
R(Ω)
V
ps
Load resistor value.
Minimum power supply voltage required
R(Ω)max = 41.7 (Vps – 10.8 V).
Additional wiring information
The DC power supply should provide power with less than two percent ripple. The total
resistance load is the sum of the resistance of the signal wiring and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.
If a Smart Wireless THUM™ Adapter is being used with the flow meter to exchange
information via IEC 62591 (WirelessHART® Protocol) technology, a minimum loop resistance of 250 ohms is required. In addition, a minimum power supply voltage (Vps) of 19.3 volts will be required to output 24 mA.
If a single power supply is used to power more than one transmitter, the power supply
used and circuitry common to the transmitters should not have more than 20 ohms of impedance at 1200 Hz. See Table 3-1.
Loop resistance must be considered in determining the minimum power supply
voltage.
16 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Pre-installation
00809-1100-4004 October 2021
Table 3-1: Resistance based on wire gauge
Gauge number Ohms per 1,000 ft (305 m) at 68 °F (20 °C)
equivalent
14 AWG (2 mm2) 2.5
16 AWG (1 mm2) 4.0
18 AWG (0.8mm2) 6.4
20 AWG (0.5 mm2) 10
22 AWG (0.3 mm2) 16
24 AWG (0.2 mm2) 26

3.2 Commissioning

For proper configuration and operation, commission the meter before putting it into operation. Bench commissioning also enables you to check hardware settings, test the flowmeter electronics, verify flowmeter configuration data, and check output variables. Any problems can be corrected—or configuration settings changed—before going out into the installation environment. To commission on the bench, connect a configuration device to the signal loop in accordance the device instructions.
3.2.1

Alarm and security jumper configuration

Two jumpers on the transmitter specify the alarm and security modes. Set these jumpers during the commissioning stage to avoid exposing the electronics to the plant environment. The two jumpers can be found on the electronics board stack or on the LCD display.
Alarm
Security
To access the jumpers, remove the transmitter electronics housing or the LCD cover (if equipped) opposite of the terminal block, See Figure 3-8 and Figure 3-9.
As part of normal operations, the transmitter continuously runs a self­diagnostic routine. If the routine detects an internal failure in the electronics, flow meter output is driven to a low or high alarm level, depending on the position of the failure mode jumper. The factory sets the jumper according to the Configuration Data Sheet, if applicable, or HI by default.
You can protect the configuration data with the security lockout jumper. With the security lockout jumper ON, any configuration changes attempted on the electronics are disallowed. You can still access and review any of the operating parameters and scroll through the available parameters, but no changes can be made. The factory sets the jumper according to the Configuration Data Sheet, if applicable, or OFF by default.
Note
If you will be changing configuration variables frequently, it may be useful to leave the security lockout jumper in the OFF position to avoid exposing the flow meter electronics to the plant environment.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 17
Pre-installation Reference Manual
October 2021 00809-1100-4004
Figure 3-8: Alarm and security jumpers (no LCD option)
VORTEX
4-20mA HART
TP1
TEST FREQ
IN
Figure 3-9: Alarm and security jumpers (with LCD option)
HI LO
HI LO
ALARM
ALARM
FLOW
SECURITY
SECURITY
ON OFF
ON OFF
Failure mode vs. saturation output values
The failure mode alarm output levels differ from the output values that occur when the operating flow is outside the range points. When the operating flow is outside the range points, the analog output continues to track the operating flow until reaching the saturation value listed below; the output does not exceed the listed saturation value regardless of the operating flow. For example, with standard alarm and saturation levels and flows outside the 4–20 mA range points, the output saturates at 3.9 mA or 20.8 mA. When the transmitter diagnostics detect a failure, the analog output is set to a specific alarm value that differs from the saturation value to allow for proper troubleshooting. The saturation and alarm levels are software selectable between Rosemount Standard and NAMUR levels.
18 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Pre-installation
00809-1100-4004 October 2021
Table 3-2: Analog output: standard alarm values vs. saturation values
Level 4–20 mA saturation value 4–20 mA alarm value
Low 3.9 mA ≤ 3.75 mA
High 20.8 mA ≥ 21.75 mA
Table 3-3: Analog output: NAMUR-compliant alarm values vs. saturation values
Level 4–20 mA saturation value 4–20 mA alarm value
Low 3.8 mA ≤ 3.6 mA
High 20.5 mA ≥ 22.6 mA

3.2.2 Calibration

The flow meter is wet-calibrated at the factory and needs no further calibration during installation. The calibration factor (K-factor) is indicated on each meter body and is entered into the electronics. Verification can be accomplished with a configuration device.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 19
Pre-installation Reference Manual
October 2021 00809-1100-4004
20 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Basic installation
00809-1100-4004 October 2021

4 Basic installation

4.1 Handling

Handle all parts carefully to prevent damage. Whenever possible, transport the system to the installation site in the original shipping containers. Keep the shipping plugs in the conduit connections until you are ready to connect and seal them.
NOTICE
To avoid damage to the meter, do not lift the flow meter by the transmitter. Lift the meter by the meter body. Lifting supports can be tied around the meter body as shown.
Figure 4-1: Lifting supports

4.2 Flow direction

The meter can only measure flow in the direction indicated on the meter body. Be sure to mount the meter body so the FORWARD end of the flow arrow points in the direction of the flow in the pipe.

4.3 Gaskets

The flow meter requires gaskets supplied by the user. Be sure to select gasket material that is compatible with the process fluid and pressure ratings of the specific installation.
Note
Ensure the inside diameter of the gasket is larger than the inside diameter of the flow meter and adjacent piping. If gasket material extends into the flow stream, it will disturb the flow and cause inaccurate measurements.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 21
Basic installation Reference Manual
October 2021 00809-1100-4004

4.4 Insulation

Insulation should extend to the end of the bolt on the bottom of the meter body and should leave at least 1-in. (25 mm) of clearance around the electronics bracket. The electronics bracket and electronics housing should not be insulated. See Figure 4-2.
Figure 4-2: Insulation best practice to prevent electronics overheating
A. Support tube
CAUTION
In high temperature installations, to avoid damage to the electronics on integral units or to the remote cable on remote units, only insulate the meter body as shown. Do not insulate the support tube. See also Orientation.

4.5 Flanged-style flow meter mounting

Most vortex flow meters use a flanged-style process connection. Physical mounting of a flanged-style flow meter is similar to installing a typical section of pipe. Conventional tools, equipment, and accessories (such as bolts and gaskets) are required. Tighten the nuts following the sequence shown in Figure 4-4.
Note
The required bolt load for sealing the gasket joint is affected by several factors, including operating pressure and gasket material, width, and condition. A number of factors also affect the actual bolt load resulting from a measured torque, including condition of bolt threads, friction between the nut head and the flange, and parallelism of the flanges. Due to these application-dependent factors, the required torque for each application may be different. Follow the guidelines outlined in ASME PCC-1 for proper bolt tightening. Make sure the flow meter is centered between flanges of the same nominal size and rating as the flow meter.
22 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Basic installation
00809-1100-4004 October 2021
Figure 4-3: Flanged-style flow meter installation
A. Installation studs and nuts (supplied by customer)
B. Gaskets (supplied by customer)
C. Flow
Figure 4-4: Flange bolt torquing sequence
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 23
Basic installation Reference Manual
October 2021 00809-1100-4004

4.6 Wafer-style flow meter alignment and mounting

Center the wafer-style meter body inside diameter with respect to the inside diameter of the adjoining upstream and downstream piping. This will ensure the flow meter achieves its specified accuracy. Alignment rings are provided with each wafer-style meter body for centering purposes. Follow these steps to align the meter body for installation. Refer to
Figure 4-5.
1. Place the alignment rings over each end of the meter body.
2. Insert the studs for the bottom side of the meter body between the pipe flanges.
3. Place the meter body (with alignment rings) between the flanges.
Make sure the alignment rings are properly placed onto the studs.
Align the studs with the markings on the ring that correspond to the flange you
are using.
If a spacer is used, see Spacers.
Note
Be sure to align the flow meter so the electronics are accessible, the conduits drain, and the flow meter is not subject to direct heat.
4. Place the remaining studs between the pipe flanges.
5. Tighten the nuts in the sequence shown in Figure 4-4.
6. Check for leaks at the flanges after tightening the flange bolts.
Note
The required bolt load for sealing the gasket joint is affected by several factors, including operating pressure and gasket material, width, and condition. A number of factors also affect the actual bolt load resulting from a measured torque, including condition of bolt threads, friction between the nut head and the flange, and parallelism of the flanges. Due to these application-dependent factors, the required torque for each application may be different. Follow the guidelines outlined in ASME PCC-1 for proper bolt tightening. Make sure the flow meter is centered between flanges of the same nominal size and rating as the flow meter.
24 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Basic installation
00809-1100-4004 October 2021
Figure 4-5: Wafer-style flow meter installation with alignment rings
B
B
A
4.6.1
C
D
A. Installation studs and nuts (supplied by customer)
B. Alignment rings C. Spacer (for Rosemount 8800D to maintain Rosemount 8800A dimensions) D. Flow
Note
See Spacers for instructions on retrofitting 8800D to 8800A installations.

Stud bolts for wafer-style flow meters

The following tables list the recommended minimum stud bolt lengths for wafer-style meter body size and different flange ratings.
Table 4-1: Stud bolt length for wafer-style flow meters with ASME B16.5 flanges
Line size Minimum recommended stud bolt lengths (in inches) for each flange
rating
Class 150 Class 300 Class 600
½-inch 6.00 6.25 6.25
1-inch 6.25 7.00 7.50
1½-inch 7.25 8.50 9.00
2-inch 8.50 8.75 9.50
3-inch 9.00 10.00 10.50
4-inch 9.50 10.75 12.25
6-inch 10.75 11.50 14.00
8-inch 12.75 14.50 16.75
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 25
Basic installation Reference Manual
October 2021 00809-1100-4004
Table 4-2: Stud bolt length for wafer-style flow meters with EN 1092 flanges
Line size Minimum recommended stud bolt lengths (in mm) for each flange rating
PN 16 PN 40 PN 63 PN 100
DN 15 160 160 170 170
DN 25 160 160 200 200
DN 40 200 200 230 230
DN 50 220 220 250 270
DN 80 230 230 260 280
DN 100 240 260 290 310
DN 150 270 300 330 350
DN 200 320 360 400 420
Line size Minimum recommended stud bolt lengths (in mm) for each flange
rating
JIS 10k JIS 16k and 20k JIS 40k
15mm 150 155 185
25mm 175 175 190
40mm 195 195 225
50mm 210 215 230
80mm 220 245 265
100mm 235 260 295
150mm 270 290 355
200mm 310 335 410

4.7 Cable glands

If you are using cable glands instead of conduit, follow the cable gland manufacturer’s instructions for preparation and make the connections in a conventional manner in accordance with local or plant electrical codes. Be sure to properly seal unused ports to prevent moisture or other contamination from entering the terminal block compartment of the electronics housing.

4.8 Flow meter grounding

Grounding is not required in typical vortex applications; however, a proper ground will eliminate possible noise pickup by the electronics. Grounding straps may be used to ensure that the meter is grounded to the process piping. If you are using the transient protection option (T1), grounding straps are required to provide a proper low impedance ground.
26 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Reference Manual Basic installation
00809-1100-4004 October 2021
Note
Properly ground flow meter body and transmitter per the local code.
To use grounding straps, secure one end of the grounding strap to the bolt extending from the side of the meter body and attach the other end of each grounding strap to a suitable ground. See Figure 4-6.
Figure 4-6: Grounding connections
A. Internal ground connection
B. External ground assembly

4.9 Grounding the transmitter case

The transmitter case should always be grounded in accordance with national and local electrical codes. The most effective transmitter case grounding method is direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case include:
Internal Ground Connection
External Ground Assembly
Note
Grounding the transmitter case using the threaded conduit connection may not provide a sufficient ground. The transient protection terminal block (Option Code T1) does not provide transient protection unless the transmitter case is properly grounded. For transient terminal block grounding, see Transient protection. Use the above guidelines to
The Internal Ground Connection screw is inside the FIELD TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( ), and is standard on all Rosemount 8800D transmitters.
This assembly is located on the outside of the electronics housing and is included with the optional transient protection terminal block (Option Code T1). The External Ground Assembly can also be ordered with the transmitter (Option Code V5) and is automatically included with certain hazardous area approvals. See Figure 4-6 for the location of the external ground assembly.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 27
Basic installation Reference Manual
October 2021 00809-1100-4004
ground the transmitter case. Do not run the transient protection ground wire with signal wiring as the ground wire may carry excessive electric current if a lightning strike occurs.

4.10 Conduit installation

Prevent condensation in any conduit from flowing into the housing by mounting the flowmeter at a high point in the conduit run. If the flowmeter is mounted at a low point in the conduit run, the terminal compartment could fill with fluid.
If the conduit originates above the flowmeter, route conduit below the flowmeter to form a drip loop before entry. In some cases a drain seal may need to be installed.
Figure 4-7: Proper conduit installation
A A
A. Conduit line

4.11 Wiring

The signal terminals are located in a compartment of the electronics housing separate from the flow meter electronics. Connections for a configuration tool and an electric current test connection are above the signal terminals.
Note
A power disconnect is required to remove power from the transmitter for maintenance, removal, and replacement.
Common wiring practices
Twisted pairs are required to minimize noise pickup in the 4–20 mA signal and digital communication signal. For high EMI/RFI environments, shielded signal wire is required and recommended in all other installations. To ensure communication, wiring should be 24 AWG (0.205 mm²) or larger, and not exceed 5,000 ft (1500 m).
4.11.1

Analog output

The flow meter provides a 4–20 mA dc isolated electric current output, linear with the flow rate or optionally the Process Temperature with the MCA option. To make connections, remove the FIELD TERMINALS side cover of the electronics housing. All power to the electronics is supplied over the 4–20 mA signal wiring. Connect the wires as shown.
28 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
A
Reference Manual Basic installation
00809-1100-4004 October 2021
Figure 4-8: 4–20 mA wiring
A. Power supply. See Power supply.

4.12 Remote installation

4.12.1
If a remote electronics option (Rxx or Axx) was ordered, the flow meter assembly will be shipped in two parts:
The meter body with an adapter installed in the support tube and an interconnecting
coaxial cable attached to it.
The electronics housing installed on a mounting bracket.
If an armored remote electronics option (Axx) was ordered, follow the same instructions as for the standard remote cable connection with the exception that the cable may not need to be run through conduit. Both standard and armored cable include cable glands. Information on remote installation can be found in Cable connections.

Mounting

Mount the meter body in the process flow line as described earlier in this section. Mount the bracket and electronics housing in the desired location. The housing can be repositioned on the bracket to facilitate field wiring and conduit routing.
Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option 29
Basic installation Reference Manual
October 2021 00809-1100-4004

4.12.2 Cable connections

Complete these steps for connecting the loose end of the coaxial cable to the electronics housing. If connecting/disconnecting the meter adapter to the meter body, see Remote
electronics procedures.
Figure 4-9: Remote installation
A
B C D
E F
G
H
P
O
N
J
K
I
M
L
A. ½ NPT conduit adapter or cable gland (supplied by customer for Rxx options)
B. Coaxial cable C. Meter adapter D. Union
E. Washer
F. Nut G. Sensor cable nut H. Support tube
I. Meter body J. Electronics housing
K. Coaxial cable SMA nut
L. ½ NPT conduit adapter or cable gland (supplied by customer for Rxx options)
M. Housing adapter screws
N. Housing adapter
O. Housing base screw (one of four)
P. Ground connection
30 Rosemount™ 8800D Vortex Flow Meter with MPA or MCA option
Loading...
+ 114 hidden pages