with 4-20 mA HART® Revision 5 and 7 Selectable Protocol
July 2020
Safety messages
NOTICE
Read this manual before working with the product. For personal and system safety and for optimum product performance, ensure
you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central (Technical support, quoting, and order-related questions.)
• United States: 1-800-999-9307 (7:00 am to 7:00 pm Central Time)
• Asia Pacific: 65 777 8211
• Europe/Middle East/Africa: 49 (8153) 9390
North American Response Center (Equipment service needs.): 1-800-654-7768 (24 hours - includes Canada)
Outside of these areas, contact your local Emerson representative.
WARNING
Explosions
Explosions could result in death or serious injury.
In an explosion-proof/flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international
standards, codes, and practices. Review the Product Certifications section of the Rosemount 3051 Product Data Sheet for any
restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments are installed in accordance
with intrinsically safe or non-incendive field wiring practices.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Replacement equipment
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining
capabilities of the transmitter and may render the instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not
contact sensor module housing.
Severe changes in the electrical loop may inhibit HART Communication or the ability to reach alarm values. Therefore,
Rosemount absolutely cannot warrant or guarantee that the correct Failure alarm level (High or Low) can be read by the host
system at the time of annunciation.
2
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Nuclear applications
The products described in this document are not designed for nuclear-qualified applications. Using non-nuclear qualified products
in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
C.1 LOI menu tree..........................................................................................................................127
C.2 LOI menu tree - extended menu.............................................................................................. 128
C.3 Enter numbers in the LOI......................................................................................................... 129
C.4 Enter text in the LOI................................................................................................................. 130
6Rosemount 3051
Reference Manual
00809-0100-4007July 2020
Introduction
1Introduction
1.1Using this manual
The sections in this manual provide information on installing, operating, and maintaining
the Rosemount 3051 Pressure Transmitter. The sections are organized as follows:
Configuration provides instruction on commissioning and operating the transmitters. It
also includes information on software functions, configuration parameters, and online
variables.
Hardware installation contains mechanical installation instructions and field upgrade
options.
Electrical installation contains electrical installation instructions and field upgrade options.
Operation and maintenance provides detailed information on calibrating and changing
HART revisions.
Troubleshooting provides troubleshooting techniques for the most common operating
problems.
Safety Instrumented Systems (SIS) requirements provides identification, installation,
configuration, operation and maintenance, and inspection information for Safety
Instrumented Systems.
Reference data provides information on how to access specifications, ordering
information,and dimensional drawings.
Field Communicator menu trees and fast keys provides full menu trees and abbreviated
Fast Key sequences for commissioning tasks.
Local Operator Interface (LOI) provides detailed LOI menu trees.
1.2Models covered
The following Rosemount 3051 Transmitters are covered by this manual:
• Rosemount 3051C Coplanar™ Pressure Transmitter
— Measures differential and gage pressure up to 2000 psi (137.9 bar).
— Measures absolute pressure up to 4000 psia (275.8 bar).
• Rosemount 3051T In-Line Pressure Transmitter
— Measures absolute pressure up to 20000 psi (1378.95 bar).
• Rosemount 3051L Liquid Level Transmitter
— Measures level and specific gravity up to 300 psi (20.7 bar).
• Rosemount 3051CF Series Flowmeter
— Measures flow in line sizes from ½-in. (15 mm) to 96-in. (2400 mm).
Note
For transmitter with FOUNDATION Fieldbus, see Rosemount 3051 Reference Manual.
Reference Manual7
IntroductionReference Manual
July 202000809-0100-4007
For transmitter with PROFIBUS® PA, see Rosemount 3051 Reference Manual.
1.3Product recycling/disposal
Consider recycling equipment. Dispose of packaging in accordance with local and national
legislations/regulations.
8Rosemount 3051
Reference ManualConfiguration
00809-0100-4007July 2020
2Configuration
2.1Overview
This section contains information on commissioning and tasks that should be performed
on the bench prior to installation, as well as tasks performed after installation as described
in Configuring transmitter diagnostics.
This section also provides instructions on configuring with Field Communicator, AMS
Device Manager, and Local Operator Interface (LOI). For convenience, Field Communicator
Fast Key sequences are labeled Fast Keys, and abbreviated LOI menus are provided for each
function below.
Full Field Communicator menu trees and Fast Key sequences are available in Field
Communicator menu trees and fast keys. LOI menu trees are available in Local Operator
Interface (LOI).
2.2Safety messages
Procedures and instructions in this section may require special precautions to ensure the
safety of the personnel performing the operations.
WARNING
Explosions
Explosions could result in death or serious injury.
Before connecting a handheld communicator in an explosive atmosphere, ensure that
the instruments in the loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
In an explosion-proof/flameproof installation, do not remove the transmitter covers
when power is applied to the unit.
Process leaks
Process leaks may cause harm or result in death.
Install and tighten process connectors before applying pressure.
Electrical shock
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads
can cause electrical shock.
Static electricity
Observe safe handling precautions for static-sensitive components.
Reference Manual9
ConfigurationReference Manual
July 202000809-0100-4007
WARNING
Conduit/cable entries
Unless marked, the conduit/cable entries in the transmitter housing use a ½–14 NPT
thread form. Entries marked “M20” are M20 × 1.5 thread form. On devices with multiple
conduit entries, all entries will have the same thread form. Only use plugs, adapters,
glands, or conduit with a compatible thread form when closing these entries.
When installing in a hazardous location, use only appropriately listed or Ex certified plugs,
glands, or adapters in cable/conduit entries.
Replacement parts
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
Improper assembly
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of
flange web (i.e., bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART® communication or the ability
to reach alarm values. Therefore, Rosemount cannot absolutely warrant or guarantee
that the correct Failure alarm level (High or Low) can be read by the host system at the
time of annunciation.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or unintentional and
needs to be protected against.
Physical security is an important part of any security program and fundamental to
protecting your system. Restrict physical access by unauthorized personnel to protect end
users’ assets. This is true for all systems used within the facility.
2.3System readiness
• If using HART®-based control or asset management systems, confirm the HART
capability of such systems prior to commissioning and installation. Not all systems can
communicate with HART Revision 7 devices.
• For instructions on how to change the HART revision of your transmitter, see Switching
HART® revision.
2.3.1
10Rosemount 3051
Confirm correct device driver
• Verify the latest Device Driver (DD/DTM™) is loaded on your systems to ensure proper
communications.
Reference ManualConfiguration
00809-0100-4007July 2020
• Download the latest DD at Emerson.com or FieldCommGroup.org
• In the Browse by Member dropdown menu, select Rosemount business unit of
Emerson.
• Select desired product.
• Use the device revision numbers to find the correct Device Driver.
Table 2-1: Rosemount 3051 Device Revisions and Files
Release
date
April 20121.0xx1.0xx0171000809-0100
January
1998
(1) NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signfied above by xx,
represent minor product changes as defined per NE53. Compatibility and functionality are preserved, and you can use
the product interchangeably.
(2) You can read the HART software revision with a HART capable configuration tool. Value shown is minimum revision
that could correspond to NAMUR Revisions.
(3) Device Driver file names use Device and DD Revision, e.g., 10_01. HART Protocol is designed to enable legacy device
driver revisions to continue to communicate with new HART devices. To access new functionality, you must download
the new Device Driver. Emerson recommends downloading new Device Driver files to ensure full functionality.
(4) HART Revision 5 and 7 selectable, power diagnostics, safety certified, LOI, process alerts, scaled variable, configurable
alarms, expanded engineering units.
Device identificationDevice driver
identification
NAMUR
software
revision
N/AN/A1785300809-0100
(1)
HART
hardware
revision
(1)
HART
software
revision
HART
universal
(2)
revision
59
Device
revision
(3)
Review
instructions
Manual
document
number
-4007
-4001
Review
functionality
Change
description
(4)
N/A
2.4Configuration basics
CAUTION
Transmitter hardware adjustments
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
You can configure the transmitter either before or after installation. To ensure all
transmitter components are in working order prior to installation, configure the
transmitter on the bench using a Field Communicator, AMS Device Manager, or LOI. Verify
the Security switch is set in the Unlock position in order to proceed with configuration.
See Figure 4-2 for switch location.
2.4.1
Reference Manual11
Configuring on the bench
To configure on the bench, you need a power supply and a Field Communicator, AMS
Device Manager, or LOI (option M4). Wire equipment as shown in Figure 2-1 below. To
ensure successful HART® Communication, verify the resistance between the transmitter
A.
B.
ConfigurationReference Manual
July 202000809-0100-4007
and the power supply is at least 250 Ω. See Power supply for a 4-20 mA HART for more
details. Connect the Field Communicator to the terminals labeled COMM on the terminal
block.
Figure 2-1: Wiring the Transmitter
A. Vdc supply
B. RL ≥ 250 (necessary for HART Communication only)
2.4.2
Configuration tools
Configure with a Field Communicator
There are two interfaces available with the Field Communicator: Traditional and
Dashboard. All steps using a Field Communicator are described using Dashboard
interfaces.
Figure 2-2 shows the Device Dashboard interface. As stated in System readiness, it is
critical that the latest DD's are loaded into the Field Communicator. Visit Emerson.com or
FieldCommGroup.org to download latest DD library.
Field Communicator menu trees and Fast Keys are available in Field Communicator menu
trees and fast keys.
12Rosemount 3051
SAVE
1. Overview
2. Configure
3. Service Tools
3051 FT 45B
Online
Reference ManualConfiguration
00809-0100-4007July 2020
Figure 2-2: Device Dashboard
Configure with AMS Device Manager
Full configuration capability with AMS Device Manager requires loading the most current
Device Descriptor (DD) for this device.
Download the latest DD at Emerson.com or FieldCommGroup.org.
Note
This manual describes all AMS Device Manager steps using version 11.5.
Configure with the LOI
To order the Rosemount 3051 Transmitter with the LOI, select option code M4 when
ordering.
To activate the LOI, push either configuration button. Configuration buttons are located
on the LCD display (must remove housing cover to access) or underneath the top tag of
the transmitter. See Table 2-2 for configuration button functionality and Figure 2-3 for
configuration button location. When using the LOI for configuration, several features
require multiple screens for a successful configuration. Data entered is saved on a screenby-screen basis; the LOI indicates this by flashing SAVED on the LCD display each time.
LOI menu trees are available in Local Operator Interface (LOI).
Reference Manual13
ConfigurationReference Manual
July 202000809-0100-4007
Figure 2-3: LOI Configuration Buttons
A. Internal configuration buttons
B. External configuration buttons
Table 2-2: LOI Button Operation
Button
LeftNoScroll
RightYesEnter
2.5Setting the loop to manual
Whenever sending or requesting data that would disrupt the loop or change the output of
the transmitter, set the process application loop to manual control.
WARNING
Explosions
Explosions could result in death or serious injury.
Before connecting a handheld communicator in an explosive atmosphere, ensure the
instruments are installed in accordance with intrinsically safe or non-incendive field wiring
practices.
The Field Communicator, AMS Device Manager, or LOI will prompt you to set the loop to
manual when necessary. The prompt is only a reminder; acknowledging this prompt does
not set the loop to manual. You must set the loop to manual control as a separate
operation.
14Rosemount 3051
Reference ManualConfiguration
00809-0100-4007July 2020
2.6Verify configuration
Emerson recommends that you verify various configuration parameters prior to
installation into the process.
The following sections detail the various parameters for each configuration tool.
Depending on what configuration tool(s) are available, follow the steps listed relevant to
each tool.
2.6.1Verify configuration with Field Communicator
Review configuration parameters listed in Table 2-3 prior to transmitter installation. Field
Communicator menu trees and fast keys provides a full list of configuration parameters
that can be reviewed or configured using a Field Communicator.
Table 2-3 shows Fast Key sequences for the latest DD. For Fast Key sequences for legacy
DDs, contact your local Emerson representative.
From the HOME screen, enter the Fast Key sequences listed.
Table 2-3: Device Dashboard Fast Key Sequence
FunctionFast Key sequence
HART® 7HART 5
Alarm and saturation levels2, 2, 2, 52, 2, 2, 5
Damping2, 2, 1, 1, 52, 2, 1, 1, 5
Primary variable2, 1, 1, 4, 12, 1, 1, 4, 1
Range values2, 1, 1, 42, 1, 1, 4
Tag2, 2, 7, 1, 12, 2, 7, 1, 1
Transfer function2, 2, 1, 1, 62, 2, 1, 1, 6
Units2, 2, 1, 1, 42, 2, 1, 1, 4
2.6.2Verify configuration with AMS Device Manager
Complete the following steps to verify the configuration parameters with the AMS Device
Manager.
Procedure
1. Right-click the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.6.3
Reference Manual15
Verify configuration with LOI
Complete the following steps to verify configuration parameters with the LOI.
Procedure
1. Press any configuration button to activate the LOI.
ConfigurationReference Manual
July 202000809-0100-4007
2. Select VIEW CONFIG to review the below parameters.
3. Use the configuration buttons to navigate through the menu.
The parameters you need to review prior to installation include:
• Tag
• Units
• Transfer Function
• Alarm and Saturation Levels
• Primary Variable
• Range Values
• Damping
2.6.4
Verifying process variables configuration
This section describes how to verify that you selected the correct process variables.
Verify process variables with a Field Communicator
From the HOME screen, enter the Fast Key sequence:
Device Dashboard Fast Keys
3, 2, 1
Verify process variables with AMS Device Manager
Complete the following steps to verify process variables with AMS Device Manager.
Procedure
1. Right-click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary, and
quaternary variables.
2.7Basic setup of the transmitter
This section goes through the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to Configuring scaled variable for
setup instructions.
16Rosemount 3051
Reference ManualConfiguration
00809-0100-4007July 2020
2.7.1Setting pressure units
WARNING
Spare parts
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
The pressure unit command sets the unit of measure for the reported pressure.
Set pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 1, 1, 4
Set pressure units with AMS Device Manager
Complete the following steps to set pressure units with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select Manual Setup and select desired units from the Pressure Units dropdown
menu.
3. Select Send when complete.
Set pressure units with the LOI
Complete the following steps to select pressure units with the LOI.
Procedure
1. Follow Figure 2-4 to select desired pressure and temperature units. Go to UNITS →
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
2.7.2
Setting transmitter output (transfer function)
The transmitter has two output settings: Linear and Square root.
As shown in Figure 2-6, activating the square root options makes analog output
proportional to flow and includes a fixed Low Flow Cutoff at five percent.
However, Emerson recommends using scaled variable for Differential Pressure (DP) Flow
and DP Level applications. Refer to Configuring scaled variable for setup instructions.
Set transmitter output with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Set transmitter output with AMS Device Manager
Complete the following steps to set transmitter output with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select Manual Setup, select output type from Analog Output Transfer Function,
and click Send.
3. Carefully read the warning and select Yes if it is safe to apply the changes.
2, 2, 1, 1, 6
18Rosemount 3051
Set transmitter output with the LOI
Reference Figure 2-5 to select either linear or square root transfer function using the LOI.
Go to EXTENDED MENU → TRANSFER FUNCT.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT
VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
TRANSFER FUNCT
LINEAR TRANSFER
FUNCTION
SQR ROOT TRANSFER
FUNCTION
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
A
B
C
0.51
% Pressure Input
0
010 20 30 40 50 60 70 80 90 100
4 mA
20mA
% Pressure Input
B
A
4 mA
Reference ManualConfiguration
00809-0100-4007July 2020
Figure 2-5: Set Transmitter Output with LOI
Figure 2-6: 4-20 mA HART® Square Root Output Transition Point
2.7.3
Reference Manual19
A. Square root curve
B. 5% transition point
C. 4% transition point
Rerange the transmitter
The range values command sets each of the lower and upper range analog values (4 and
20 mA points) to a pressure. The lower range represents zero percent of range, and the
upper range point represents 100 percent of range.
In practice, you can change the transmitter range values as often as necessary to reflect
changing process requirements. For a complete listing of range and sensor limits, refer to
the Specifications section of the Rosemount 3051 Product Data Sheet.
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
July 202000809-0100-4007
• Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or LOI.
• Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local Zero and Span buttons.
Manually rerange the transmitter by entering range points
Enter range points with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys2, 2, 2, 1
Enter range points with AMS Device Manager
Complete the following steps to manually enter range points with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and select Send.
4. Carefully read the warning and select Yes if it is safe to apply the changes.
Enter range points with LOI
Reference Figure 2-7 to rerange the transmitter using the LOI. Go to RERANGE → ENTER
VALUES. Enter values using the SCROLL and ENTER buttons.
Figure 2-7: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 2, 2
20Rosemount 3051
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
APPLY VALUES
LRV
URV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
A
Reference ManualConfiguration
00809-0100-4007July 2020
Rerange with an applied pressure source using AMS Device Manager
Complete the following steps to use an applied pressure source to rerange the transmitter
with AMS Device Manager.
Procedure
1. Right-click the device; select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts to range
the transmitter.
Rerange with an applied pressure source using the LOI
Use Figure 2-8 to manually rerange the device using an applied pressure source with the
LOI. Go to RERANGE → APPLY VALUES.
Figure 2-8: Rerange with Applied Pressure Using LOI
Reference Manual21
Rerange with an applied pressure source using local Zero and Span
buttons
If you order them to, you can use local Zero and Span buttons (option code D4) to rerange
the transmitter with applied pressure.
Refer to Figure 2-9 for analog Zero and Span button location.
Figure 2-9: Analog Zero and Span Buttons
A. Zero and Span buttons
ConfigurationReference Manual
July 202000809-0100-4007
To rerange the transmitter using the Zero and Span buttons:
Procedure
1. Loosen the screw holding the top tag of the transmitter housing. Rotate the label to
expose the Zero and Span buttons.
2. Confirm device has local Zero and Span buttons by verifying blue retainer under the
tag.
3. Apply transmitter pressure.
4. Rerange the transmitter.
a) To change the zero (4 mA point) while maintaining the span, press and hold
the Zero button for at least two seconds; then release.
b) To change the span (20 mA) point while maintaining the zero point, press
and hold the Span button for at least two seconds and then release.
Note
4 and 20 mA points must maintain the minimum span defined in the Specifications
section of the Rosemount 3051 Product Data Sheet.
2.7.4
• If the transmitter security is on, you cannot adjust the zero and span. Refer to
Configuring transmitter security for security information.
• The span is maintained when you set the 4 mA point. The span changes when
you set the 20 mA point. If you set the lower range point to a value that causes
the upper range point to exceed the sensor limit, the transmitter automatically
sets the upper range point to the sensor limit and adjusts the span accordingly.
• Regardless of the range points, the Rosemount 3051 measures and reports all
readings within the digital limits of the sensor. For example, if you set the 4 and
20 mA points to 0 and 10 inH2O, and the transmitter detects a pressure of 25
inH2O, it digitally outputs the 25 inH2O reading and a 250 percent of range
reading.
Damping
The damping command changes the response time of the transmitter; higher values can
smooth variations in output readings caused by rapid input changes.
CAUTION
Improper assembly
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of
flange web (i.e., bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART® communication or the ability
to reach alarm values. Therefore, Rosemount cannot absolutely warrant or guarantee
that the correct Failure alarm level (High or Low) can be read by the host system at the
time of annunciation.
22Rosemount 3051
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Reference ManualConfiguration
00809-0100-4007July 2020
Determine the appropriate damping setting based on the necessary response time, signal
stability, and other requirements of the loop dynamics within your system. The damping
command uses floating point configuration, allowing you to input any damping value
within 0 - 60 seconds.
Damping with a Field Communicator
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys2, 2, 1, 1, 5
2. Enter desired damping value and select APPLY.
Damping with AMS Device Manager
Complete the following steps to set the damping value with AMS Device Manager.
Procedure
1. Right-click the device, and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully click the warning and click Yes if it is safe to apply the changes.
2.8Configuring the LCD display
Reference Manual23
Damping with the LOI
Reference Figure 2-10 to enter damping values using the LOI. Go to EXTENDED MENU →
DAMPING.
Figure 2-10: Damping with LOI
Use the LCD display configuration command to customize of the LCD display to suit
application requirements. The LCD display will alternate between the selected items.
• Pressure units
DISPLAY
PRESS (on/off)
SCALED (on/off)
TEMP (on/off)
%RANGE (on/off)
ANALOG (on/off)
STRTUP (on/off)
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
July 202000809-0100-4007
• % of range
• Scaled variable
• Sensor temperature
• mA output
Using the following instructions, you can configure the LCD display to display
configuration information during the device setup. Select Review Parameters at Startup to
enable or disable this functionality.
2.8.1Configure LCD display with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
2, 2, 4
2.8.2Configure LCD display with AMS Device Manager
Complete the following steps to configure the LCD display with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Click Manual Setup and select the Display tab.
3. Select desired display options and select Send.
2.8.3
Configure LCD display with the LOI
Refer to Figure 2-11 for LCD display configuration using the LOI. Go to DISPLAY.
Figure 2-11: Display with LOI
2.9Detailed transmitter setup
2.9.1Configuring alarm and saturation levels
24Rosemount 3051
In normal operation, the transmitter drives the output in response to pressure from the
lower and upper saturation points. If the pressure goes outside of the sensor limits, or if
Reference ManualConfiguration
00809-0100-4007July 2020
the output would be beyond the saturation points, the output will be limited to the
associated saturation point.
The Rosemount 3051 Transmitter automatically and continuously performs selfdiagnostic routines. If the self-diagnostic routines detect a failure, the transmitter drives
the output to configured alarm and value based on the position of the alarm switch. See
Set transmitter alarm.
Table 2-4: Rosemount Alarm and Saturation Values
Level4-20 mA saturation4-20 mA alarm
Low3.9 mA≤ 3.75 mA
High20.8 mA≥ 21.75 mA
Table 2-5: NAMUR-Compliant Alarm and Saturation Values
Level4-20 mA saturation4-20 mA alarm
Low3.8 mA≤ 3.6 mA
High20.5 mA≥ 22.5 mA
Table 2-6: Custom Alarm and Saturation Values
Level4-20 mA saturation4-20 mA alarm
Low3.7 - 3.9 mA3.6 - 3.8 mA
High20.1 - 22.9 mA20.2 - 23.0 mA
You can configure failure mode alarm and saturation levels using a Field Communicator,
AMS Device Manager, or the LOI. The following limitations exist for custom levels:
• Low alarm level must be less than the low saturation level.
• High alarm level must be higher than the high saturation level.
• Alarm and saturation levels must be separated by at least 0.1 mA.
The configuration tool provides an error message if the configuration rule is violated.
Note
Transmitters set to HART® multidrop mode send all saturation and alarm information
digitally; saturation and alarm conditions will not affect the analog output. See also
Establishing multidrop communication.
Configure alarm and saturation levels using a Field
Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Reference Manual25
2, 2, 2, 5, 6
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
ALARM SAT VALUES
ROSEMOUNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
July 202000809-0100-4007
Configure alarm and saturation levels with AMS Device
Manager
Complete the following steps to configure alarm and saturation levels with AMS Device
Manager.
Procedure
1. Right-click the device and select Configure.
2. Select the Configure Alarm and Saturation Levels button.
3. Follow screen prompts to configure alarm and saturation levels.
Configure alarm and saturation levels using the LOI
Refer to Figure 2-12 for instructions to configure alarm and saturation levels. Go to
EXTENDED MENU → ALARM SAT VALUES.
Figure 2-12: Configuring Alarm and Saturation with LOI
2.9.2
26Rosemount 3051
Configuring process alerts
The transmitter uses process alerts to indicate when it exceeds the configured data point.
You can set process alerts for pressure, temperature, or both. An alert is displayed on a
Field Communicator or AMS Device Manager status screen or in the error section of the
LOI/LCD display. The alert will reset once the value returns within range.
Note
HI alert value must be higher than LO alert value. Both alert values must be within the
pressure or temperature sensor limits.
Configure process alerts using a Field Communicator
Complete the following steps to configure process alerts with a Field Communicator.
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Reference ManualConfiguration
00809-0100-4007July 2020
Device Dashboard Fast Keys2, 3
2. Select either Pressure Alert or Temperature Alert and press ENTER.
3. Select Configure Alert.
4. Follow screen prompts to configure process alerts.
Configure process alarts using AMS Device Manager
Complete the following steps to configure process alerts with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select Guided Setup.
3. Select the Process Alerts button.
4. Follow screen prompts to configure process alerts.
2.9.3
Configuring scaled variable
With the scaled variable configuration, you can create a relationship/conversion between
the pressure units and user-defined/custom units. There are two use cases for a scaled
variable. The first is to allow custom units to be displayed on the transmitter's LOI/LCD
display. The second is to allow custom units to drive the transmitter's 4-20 mA output.
If you desire custom units to drive the 4-20 mA output, you must remap scaled variable as
the primary variable. Refer to Re-mapping device variables.
The scaled variable configuration defines the following items:
• Scaled variable units: Custom units to be displayed.
• Scaled data options: Defines the transfer function for the application.
— Linear
— Square root
• Pressure value position 1: Lower known value point with consideration of linear offset.
• Scaled variable value position 1: Custom unit equivalent to the lower known value
point.
• Pressure value position 2: Upper known value point.
• Scaled variable value position 2: Custom unit equivalent to the upper known value
point.
• Linear offset: The value required to zero out pressures effecting the desired pressure
reading.
• Low flow cutoff: Point at which output is driven to zero to prevent problems cause by
process noise. Emerson highly recommends using the low flow cut off function in order
to have a stable output and avoid problems due to process noise at a low flow or no
flow condition. Enter a low flow cutoff value that is practical for the flow element in the
application.
Reference Manual27
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
SCALED VARIAB
VIEW SCALED
CONFIG SCALED
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
ConfigurationReference Manual
July 202000809-0100-4007
Configure scaled variable using a Field Communicator
Complete the following steps to configure a scaled variable with a Field Communicator.
Procedure
1. From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys2, 1, 5, 7
2. Follow the screen prompts to configure scaled variable.
• When configuring for level, select Linear under Select Scaled data options.
• When configuring for flow, select Square Root under Select Scaled data options.
Configure scaled variable using AMS Device Manager
Complete the following steps to configure the scaled variable with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure the scaled variable.
• When configuring for level applications, select Linear under Select Scaled data
options.
• When configuring the flow applications, select Square Root under Select Scaled
data options.
Configure scaled variable using the LOI
Refer to Figure 2-13 for instructions on configuring scaled variable using the LOI. Go to
EXTENDED MENU → SCALED VARIAB → CONFIG SCALED.
Figure 2-13: Configuring Scaled Variable Using the LOI
28Rosemount 3051
H
L
230-in.
200-in.
12-in.
0.94 sg
Reference ManualConfiguration
00809-0100-4007July 2020
DP Level example
Figure 2-14: Example Tank
Us a differential transmitter in a level application. Once installed on an empty tank with the
taps vented, the process variable reading is -209.4 inH2O. The process variable reading is
the head pressure created by fill fluid in the capillary. Based on Table 2-7, the scaled
variable configuration would be as follows:
Table 2-7: Scaled Variable Configuration for Tank Application
Scaled variable unitsinch
Scaled data optionslinear
Pressure value position 10 inH2O
Scaled variable position 112-in.
Pressure value position 2188 inH2O
Reference Manual29
ConfigurationReference Manual
July 202000809-0100-4007
Table 2-7: Scaled Variable Configuration for Tank Application (continued)
Scaled variable position 2212-in.
Linear offset-209.4 inH2O
DP Flow example
Use a differential pressure transmitter in conjunction with an orifice plate in a flow
application where the differential pressure at full scale flow is 125 inH2O.
Emerson highly recommends using the low flow cutoff function in order to have a stable
output and avoid problems due to process noise at a low flow or no flow condition. Enter a
low flow cutoff value that is practical for the flow element in the application. In this
particular example, the low flow cutoff value is 1000 gallons of water per hour. Based on
this information, the scaled variable configuration would be as follows:
Table 2-8: Scaled Variable Configuration for Flow Application
Scaled variable unitsgal/h
Scaled data optionssquare root
2.9.4
Pressure value position 2125 inH2O
Scaled variable position 220,000 gal/h
Low flow cutoff1000 gal/h
Note
Pressure value position 1 and scaled variable position 1 are always set to zero for a flow
application. You don't have to configure these values.
Re-mapping device variables
Use the re-mapping function to configure the transmitter primary, secondary, tertiary,
and quaternary variables (PV, 2V, 3V, and 4V). You can map the PV with a Field
Communicator, AMS Device Manager, or the LOI. You can only re-map variables (2V, 3V,
and 4V) via Field Communicator or AMS Device Manager.
Note
The variable assigned to the primary variable drives the 4-20 mA output. You can select
this value as Pressure or Scaled Variable. The 2, 3, and 4 variables only apply if you are
using HART® burst mode.
Re-map using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Fast Keys
30Rosemount 3051
2, 1, 1, 3
Loading...
+ 102 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.