Read this manual before working with the product. For personal and system safety, and for optimum product performance,
ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
• United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
• Asia Pacific- 65 777 8211
North American Response Center
Equipment service needs.
• 1-800-654-7768 (24 hours a day — includes Canada)
• Outside of these areas, contact your local Emerson representative.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained personnel, in accordance with the
applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could
be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access
by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Hot surfaces
The transmitter and process seal may be hot at high process temperatures. Allow to cool before servicing.
The sections in this manual provide information on installing, operating, and maintaining
the Rosemount™ 1408A Level and Flow Transmitter – Non-Contacting Radar.
The sections are organized as follows:
Transmitter overview provides an introduction to theory of operation, a description of the
transmitter, information on typical applications, and process characteristics.
Configuration provides instructions on configuration of the transmitter.
Operation and maintenance contains operation and maintenance techniques.
Service and troubleshooting provides troubleshooting techniques for the most common
operating problems.
Specifications and reference data supplies reference and specification data.
Configuration parameters provides extended information about the configuration
parameters.
1.2Product certifications
See the Rosemount 1408A Product Certifications document for detailed information on
the existing approvals and certifications.
1.3Open source licenses
This device uses open source software. Further information can be found in the
License Information document available at Emerson.com/Rosemount.
1.4Product recycling/disposal
Recycling of equipment and packaging should be taken into consideration and disposed of
in accordance with local and national legislation or regulations.
Related information
Service support
Reference Manual5
IntroductionReference Manual
May 202200809-0200-4480
6Rosemount 1408A Level and Flow Transmitter
d
f
i
n
f
max
f
min
f
out
f
in
f
out
t
f
A
C
D
B
Reference ManualTransmitter overview
00809-0200-4480May 2022
2Transmitter overview
2.1Measurement principle
The Rosemount 1408A is a transmitter for continuous level measurements using fastsweep Frequency Modulated Continuous Wave (FMCW) technology.
The transmitter continuously emits signal sweeps with a constantly varying frequency
towards the product surface. Since the transmitter continuously changes the frequency of
the transmitted signal, there will be a difference in frequency between the transmitted
and the reflected signals (see Figure 2-1).
The frequency of the reflected signal is subtracted from the frequency of the signal
transmitted at that moment, resulting in a low frequency signal which is proportional to
the distance to the product surface. This signal is further processed to obtain fast, reliable,
and highly accurate level measurements.
Figure 2-1: FMCW-method
Δf∼d=distance
A. Frequency (GHz)
Time (s)
B.
C. Transmitted signal
D. Reflected signal
The Rosemount 1408A can also calculate the volume flow rate in an open channel.
2.2Process characteristics
2.2.1Dielectric constant
A key parameter for measurement performance is reflectivity. A high dielectric constant of
the media provides better reflection and enables a longer measuring range.
Reference Manual7
Transmitter overviewReference Manual
May 202200809-0200-4480
2.2.2Foam and turbulence
Foaming liquids or turbulence may cause weak and varying surface echo amplitudes.
Surface turbulence is not normally a problem unless it is excessive.
Measurement in foamy applications depends largely on the foam properties. When the
foam is light and airy, the actual product level is measured. For heavy and dense foam, the
transmitter may measure the level of the foam’s upper surface.
2.3Vessel characteristics
2.3.1In-tank obstructions
The transmitter should be mounted so that objects such as heating coils, ladders, and
agitators are not in the radar signal path. These objects may cause false echoes resulting in
reduced measurement performance. However, the transmitter has built-in functions
designed to reduce the influence from disturbing objects where such objects cannot be
totally avoided.
Vertical and inclined structures cause minimal effect since the radar signal is scattered
rather than directed back to the antenna.
2.4Non-contacting radar technology
Non-contacting radar technology is ideal for a wide range of applications as it is
maintenance-free, has a top-down installation that reduces the risk of leakages, and is
unaffected by process conditions such as density, viscosity, temperature, pressure, and
pH.
The Rosemount 1408A uses Frequency Modulated Continuous Wave (FMCW) technology
and smart algorithms to maximize measurement accuracy and reliability, even in small
tanks and challenging fast-filling vessels.
8Rosemount 1408A Level and Flow Transmitter
Reference ManualTransmitter overview
00809-0200-4480May 2022
2.4.1Application examples
Storage tanks
Gain insights into your tank and ensure production runs smoothly without interruption.
Plastic tanks
Monitor the inventory of your small and medium sized plastic tanks by measuring through
the plastic roof.
Open air applications
Get reliable level measurements of sumps or ponds, regardless of challenging surface and
weather conditions.
Reference Manual9
A
D
E
F
C
B
Transmitter overviewReference Manual
May 202200809-0200-4480
Open channel flow
Use the Rosemount 1408A for volume flow measurement of water and wastewater in
open channels.
2.5Components of the transmitter
Figure 2-2: Components
A. M12 connector (A-coded)
B. Transmitter housing (polished stainless steel)
C.
Wrench size: 39 mm
D. DIN 3869 profile ring
E. ISO 228/1-G1 thread
F. Antenna (PTFE sealing)
Related information
Dimensional drawings
10Rosemount 1408A Level and Flow Transmitter
C
A
D
E
B
Reference ManualTransmitter overview
00809-0200-4480May 2022
2.6Easy integration with IO-Link
The Rosemount 1408A provides both conventional 4-20 mA and digital switch outputs,
enabled by IO-Link connectivity. This supports easy integration into any automation
system.
Each IO-Link system consists of an IO-Link master and one or more IO-Link devices (sensors
and actuators). The connection between the master and the device is established via
unshielded standard cables using standard connectors such as M12. Process data, events
and parameters are transferred to the master via IO-Link. The IO-Link master then
transfers the data to the controller (PLC) and its fieldbus or industrial ethernet network.
Figure 2-3: Example of an IO-Link System
A. Industrial ethernet
Programmable logic controller (PLC)
B.
C.
Industrial Fieldbus
D. IO-Link master
E. IO-Link devices
Reference Manual11
Transmitter overviewReference Manual
May 202200809-0200-4480
12Rosemount 1408A Level and Flow Transmitter
Reference ManualMechanical installation
00809-0200-4480May 2022
3Mechanical installation
3.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
3.2Installation considerations
Before installing the transmitter, follow recommendations for mounting position,
sufficient free space, nozzle requirements, etc.
3.2.1Mounting position
When finding an appropriate location on the tank for the transmitter, the conditions of the
tank must be carefully considered.
Consider the following guidelines when mounting the transmitter:
• For optimal performance, the transmitter should be installed in locations with a clear
and unobstructed view of the product surface.
Reference Manual13
L
L
Mechanical installationReference Manual
May 202200809-0200-4480
• The transmitter should be mounted with as few internal structures as possible within
the signal beam.
• Do not mount close to or above the inlet stream.
• Do not mount the transmitter on a manway cover.
• Do not position the transmitter directly over a side manway door.
• Multiple Rosemount 1408A transmitters can be used in the same tank without
interfering with each other.
Figure 3-1: Recommended Mounting Position
3.2.2Free space requirements
If the transmitter is mounted close to a wall or other tank obstruction such as heating coils
and ladders, noise might appear in the measurement signal. See Table 3-1 for
recommended clearance.
Figure 3-2: Free Space Requirements
Table 3-1: Distance to Tank Wall (L)
MinimumRecommended
8 in. (200 mm)½ of tank radius
14Rosemount 1408A Level and Flow Transmitter
90°
Max. 3°
Reference ManualMechanical installation
00809-0200-4480May 2022
3.2.3Inclination
The transmitter should be mounted vertically to ensure a good echo from the product
surface. See Figure 3-3 for recommended maximum inclination.
Figure 3-3: Inclination
3.2.4Non-metallic tanks
Nearby objects outside the tank may cause disturbing radar echoes. Wherever possible,
the transmitter should be positioned so that objects close to the tank are kept outside the
signal beam.
Related information
Product certifications
Reference Manual15
D
W
Mechanical installationReference Manual
May 202200809-0200-4480
3.2.5Beam angle and beam width
The transmitter should be mounted with as few internal structures as possible within the
signal beam.
Figure 3-4: Beam Angle and Beam Width
Beam angle (α)
10° (8° with antenna extension)
Beam width
See Table 3-2 for beam width at different distances.
Table 3-2: Beam Width (W)
Distance (D)Beam angle (α)
8°10°
6.6 ft. (2 m)0.9 ft. (0.3 m)1.2 ft. (0.4 m)
13.1 ft. (4 m)1.8 ft. (0.6 m)2.3 ft. (0.7 m)
19.7 ft. (6 m)2.8 ft. (0.8 m)3.5 ft. (1.1 m)
26.2 ft. (8 m)3.7 ft. (1.1 m)4.6 ft. (1.4 m)
32.8 ft. (10 m)4.7 ft. (1.4 m)5.8 ft. (1.8 m)
16Rosemount 1408A Level and Flow Transmitter
D
H
Reference ManualMechanical installation
00809-0200-4480May 2022
3.2.6Nozzle requirements
To allow the microwaves to propagate undisturbed, the nozzle dimensions should be kept
within the specified limits as given in Table 3-3. The inside of the nozzle must be smooth
(i.e. avoid bad welding, rust, or deposit).
Figure 3-5: Mounting in Nozzles
Table 3-3: Nozzle Requirements
Nozzle diameter (D)Maximum nozzle height (H)
1 in. (25 mm)3.9 in. (100 mm)
1.5 in. (40 mm)5.9 in. (150 mm)
2 in. (50 mm)7.9 in. (200 mm)
3 in. (80 mm)11.8 in. (300 mm)
4 in. (100 mm)15.8 in. (400 mm)
6 in. (150 mm)23.6 in. (600 mm)
3.2.7Open air installations
The antenna extension must be fitted to the transmitter to comply with open air
requirements. The antenna extension is included in the bracket mount option.
Figure 3-6: Antenna Extension
Related information
Product certifications
Reference Manual17
AA
Mechanical installationReference Manual
May 202200809-0200-4480
3.2.8Thread engagement length
Refer to Figure 3-7 for the required thread engagement length at the customer G1 process
connection.
Figure 3-7: Thread Engagement Length
A. 0.35 to 0.63 in. (9 to 16 mm)
Related information
Dimensional drawings
3.3Mounting preparations
3.3.1Remove the protective cap
The protective cap protects the PTFE sealing from impacts during transport and storage.
Procedure
Before installing, carefully remove the protective cap.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
18Rosemount 1408A Level and Flow Transmitter
T30
90°
T30
Reference ManualMechanical installation
00809-0200-4480May 2022
3.3.2Cleaning the transmitter
Procedure
If needed, clean the wetted parts of the transmitter.
Use a damp cloth and a mild cleaning agent suitable for the media and wetted parts of the
transmitter.
Note
Be careful not to scratch any of the surfaces.
3.4Mount the bracket
Procedure
1. Mount the bracket on the wall/ceiling or other flat surface.
2. Ensure the adjustable holder is directed toward the ground.
Reference Manual19
AB
46 mm
36 mm
Mechanical installationReference Manual
May 202200809-0200-4480
3. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
4. Secure the transmitter to the bracket.
Mounting options:
• (A) Antenna extension for open air installations
• (B) Lock nut
3.5Installing on a tank
3.5.1Mount on a threaded flange connection
20Rosemount 1408A Level and Flow Transmitter
Related information
Bracket hole pattern
Procedure
1. Place a suitable soft gasket on the tank flange.
0.75 in. (19 mm)
39 mm
Torque 310 in-lb (35 N-m)
Reference ManualMechanical installation
00809-0200-4480May 2022
2. Place the flange over the gasket.
3. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice.
4. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
5. Mount the transmitter on the tank.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
Reference Manual21
41 mm
39 mm
Torque 310 in-lb (35 N-m)
Mechanical installationReference Manual
May 202200809-0200-4480
3.5.2Mount the threaded adapter version
Procedure
1. Apply anti-seize paste or PTFE tape on outer threads according to your site
procedures.
2. Mount the threaded adapter on the tank.
3. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
4. Mount the transmitter on the tank.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
22Rosemount 1408A Level and Flow Transmitter
39 mm
Torque 310 in-lb (35 N-m)
Reference ManualMechanical installation
00809-0200-4480May 2022
3.5.3Mount on a threaded connection
Procedure
1. Apply lubricating paste on the transmitter thread.
Note
The paste must be approved for the application and compatible with the
elastomers used.
2. Mount the transmitter on the tank.
Note
Be careful not to scratch or otherwise damage the PTFE sealing.
Reference Manual23
Mechanical installationReference Manual
May 202200809-0200-4480
24Rosemount 1408A Level and Flow Transmitter
Reference ManualElectrical installation
00809-0200-4480May 2022
4Electrical installation
4.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the
safety of the personnel performing the operations. Information that potentially raises
safety issues is indicated by a warning symbol (). Refer to the following safety messages
before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable
code of practice.
Inspection and maintenance of this equipment shall be carried out by suitably trained
personnel, in accordance with the applicable standards and code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no
circumstances allowed.
WARNING
Process leaks could result in death or serious injury.
Handle the transmitter carefully.
Install and tighten process connectors before applying pressure.
Do not attempt to loosen or remove process connectors while the transmitter is in service.
4.2Prepare the electrical connections
4.2.1Connector type
M12 (A-coded)
4.2.2Power supply
The transmitter operates on 18-30 Vdc at the transmitter terminals.
Related information
Load limitations
Reference Manual25
4
1
3
2BNW
H
BK
BU
1
4
2
3
OUT2
L+
L
OUT1/IO-Link
Electrical installationReference Manual
May 202200809-0200-4480
4.2.3Outputs
The transmitter provides two configurable outputs:
Output 1
Output 2
Digital output / IO-Link mode
Digital output or active 4-20 mA analog output
4.2.4Internal power consumption
< 2 W (normal operation at 24 Vdc, no outputs)
< 3.6 W (normal operation at 24 Vdc, digital and analog outputs active)
4.2.5Wiring diagram
Figure 4-1: Connection
Table 4-1: Pin Assignment
PinWire color
1BNBrownL+24 V
(1)
Signal
2WHWhiteOUT2Digital output or active 4-20 mA analog
output
3BUBlueL-0 V
4BKBlackOUT1/IO-LinkDigital output or IO-Link mode
(1) According to IEC 60947-5-2.
26Rosemount 1408A Level and Flow Transmitter
B
4
1
3
2
2: OUT2
4: OUT1
BN
W
H
BK
BU
L+
L
A
2: OUT2
4: OUT1
2: OUT2
4: OUT1
2: OUT2
4: OUT1
4
1
3
2BNWH
BK
BU
L+
L
C
4
1
3
2BNWH
BK
BU
L+
L
D
4
1
3
2BNWH
BK
BU
L+
L
Reference ManualElectrical installation
00809-0200-4480May 2022
Figure 4-2: Example Circuits
A. 2 x Digital output PnP
B. 2 x Digital output NpN
1 x Digital output PnP / 1 x Analog output
C.
D. 1 x Digital output NpN / 1 x Analog output
Related information
Outputs
Reference Manual27
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.