Rosemount Quick Start Guide: Vortex Flow Meter - 8600D Series | Rosemount Manuals & Guides

00825-0100-4860, Rev EC
Rosemount® 8600 Series Vortex Flowmeter
Quick Start Guide
April 2019
Quick Start Guide April 2019

1 About this guide

This guide provides basic guidelines for the Rosemount™ 8600D Series Vortex Flowmeter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (I.S.) installations. Refer to the reference manual for more instruction. The manuals and this quick start guide are also available electronically on EmersonProcess.com/Rosemount.
WARNING
Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of thereference manual for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive
atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the flowmeter is consistent with the
appropriate product certifications.
In an Explosion-proof/Flameproof installation, do not remove the
flowmeter covers when power is applied to the unit. Electrical shock can result in death or serious injury.
WARNING
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
1.1
2 Rosemount 8600 Series Vortex Flowmeter

Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
April 2019 Quick Start Guide

1.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240
Canada +1 303 527
5200
Mexico +41 (0) 41
7686 111
Argentina +54 11 4837
7000
Brazil +55 15 3413
8000
Venezuela +58 26 1731
3446
The Netherlands
France 0800 917 901 India 800 440 1468
Germany 0800 182
Italy 8008 77334 China +86 21 2892
Central & Eastern
Russia/CIS +7 495 981
Egypt 0800 000
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444
1978
+31 (0) 704 136 666
5347
+41 (0) 41 7686 111
9811
0015
0684
Australia 800 158 727
New Zealand 099 128 804
Pakistan 888 550 2682
9000
Japan +81 3 5769
6803
South Korea +82 2 3438
4600
Singapore +65 6 777
8211
6426
Quick Start Guide 3
Quick Start Guide April 2019

2 Installation

2.1 Mount the flowmeter

Design process piping so the meter body will remain full, with no entrapped air. The vortex flowmeter can be installed in any orientation without affecting accuracy. However, the following are guidelines for certain installations.

2.1.1 Vertical mounting

If the vortex flowmeter will be installed in a vertical orientation:
Install upward or downward flow for gas or steam.
Install upward flow for liquids.
Figure 2-1: Vertical installation
BA
A. Gas flow B. Liquid or gas flow
4 Rosemount 8600 Series Vortex Flowmeter
April 2019 Quick Start Guide

2.1.2 Horizontal mounting

Figure 2-2: Horizontal installation
B
A
A. Preferred installation—meter body installed with electronics to side of
pipe
B. Acceptable installation—meter body installed with electronics above pipe
For steam and fluids with small solids content, it is recommended to have the flowmeter installed with the electronics to the side of the pipe. This will minimize potential measurement errors by allowing the condensate or solids to flow under the shedder bar without interrupting the vortex shedding.

2.1.3 High temperature mounting

The maximum temperature for integral electronics is dependent on the ambient temperature where the flowmeter is installed. The electronics must not exceed 185 °F (85 °C).
Figure 2-3 shows combinations of ambient and process temperatures
needed to maintain a housing temperature of less than 185 °F (85 °C).
Quick Start Guide 5
Quick Start Guide April 2019
Figure 2-3: Ambient/Process temperature limits
C
A
B
A. Ambient temperature °F (°C) B. Process temperature °F (°C) C. 185 °F (85 °C) Housing temperature limit.
Note
The indicated limits are for horizontal pipe and vertical meter position, with meter and pipe insulated with 3 in. (77 mm) of ceramic fiber insulation.
The following orientations are recommended for applications with high process temperatures.
Install with electronics head beside or below process pipe.
Insulation around pipe may be necessary to maintain ambient
temperature below 185 °F (85 °C).
Note
Insulate pipe and meter body only. Do not insulate support tube bracket or transmitter so heat can be dissipated.

2.1.4 Steam installations

Avoid installation shown in Figure 2-4. Such conditions may cause a water­hammer condition at start-up due to trapped condensation.
6 Rosemount 8600 Series Vortex Flowmeter
April 2019 Quick Start Guide
Figure 2-4: Improper installation

2.1.5 Upstream/downstream requirements

The flowmeter may be installed with a minimum of ten straight pipe diameters (D) upstream and five straight pipe diameters (D) downstream by following the K-factor corrections as described in the 8800 Installation Effects Technical Data Sheet (00816-0100-3250). No K-factor correction is required if 35 straight pipe diameters upstream (35D) and 10 straight pipe diameters downstream (10D) are present.

2.1.6 External pressure/temperature transmitters

When using pressure and temperature transmitters in conjunction with the flowmeter for compensated mass flows, install the transmitters downstream of the flowmeter as shown in Figure 2-5.
Figure 2-5: Upstream/Downstream piping
A
B
D
A. Pressure transmitter B. Four straight pipe diameters downstream C. Temperature transmitter
D. Six straight pipe diameters downstream
Quick Start Guide 7
C
Quick Start Guide April 2019

2.1.7 Flanged style installation

Figure 2-6: Flanged style installation
A
B
A. Installation bolts and nuts (supplied by customer) B. Gaskets (supplied by customer) C. Flow direction
Note
The required bolt load for sealing the gasket joint is affected by several factors, including operating pressure, gasket material, width, and condition. A number of factors also affect the actual bolt load resulting from a measured torque, including condition of bolt threads, friction between the nut head and the flange, and parallelism of the flanges. Due to these application-dependent factors, the required torque for each application may be different. Follow the guidelines outlined in ASME PCC-1 for proper bolt tightening. Make sure the flowmeter is centered between flanges of the same nominal size as the flowmeter.
C
2.2
8 Rosemount 8600 Series Vortex Flowmeter

Install remote electronics

If you order one of the remote electronics options (options R10, R20, R30, or RXX), the flowmeter assembly ships in two parts:
1. The meter body with an adapter installed in the support tube and an interconnecting coaxial cable attached to it.
2. The electronics housing installed on a mounting bracket.
1. Mount the meter body in the process flow line as described in Mount
the flowmeter.
2. Mount the bracket and electronics housing in the desired location. The housing can be repositioned on the bracket to facilitate field wiring and conduit routing.
Loading...
+ 16 hidden pages