Quick Start Guide April 2021
Safety Messages
NOTICE
This guide provides basic guidelines for the SmartPower family of products. It does not provide
instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or
installation of wireless devices. Refer to the wireless device's manuals and Quick Start Guides (QSG) for
more instruction. This guide is also available electronically on Emerson.com/Rosemount.
WARNING
Explosions could result in death or serious injury.
Installation of this power module in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Review the Product
Certifications section for any restrictions associated with a safe installation.
• Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments
are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock could cause death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
• The power module may be replaced in a hazardous area. The power module has surface resistivity
greater than one gigaohm and must be properly installed in the wireless device enclosure. Care
must be taken during transportation to and from the point of installation to prevent electrostatic
charge build-up.
CAUTION
Each Black Power Module contains two “C” size primary lithium-thionyl chloride battery. Primary
lithium batteries are regulated in transportation by the U. S. Department of Transportation, and are
also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation
Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility
of the shipper to ensure compliance with these or any other local requirements. Consult current
regulations and requirements before shipping.
Contents
Warning on product labels........................................................................................................... 3
Physical installation...................................................................................................................... 4
Verify operation........................................................................................................................... 6
Disposal/recycling of depleted power modules............................................................................ 9
Product Certifications.................................................................................................................10
2 Emerson.com/Rosemount

April 2021 Quick Start Guide
1 Warning on product labels
The Rosemount 701P power modules each have a warning printed on them.
In each case the warning text is the same. Below is a figure that shows each
label.
The text of the warning is: “WARNING Potential Static Hazard, Use Caution
when Handling. Risk of Fire, Explosion or Severe Burn Hazard. DO NOT
Recharge, Disassemble, Heat above 100 °C, Incinerate or Expose Contents to
Water. Li metal content approx 5g.”
Figure 1-1: Warning Label on 701PBK
Figure 1-2: Warning Label on 701PGN
Quick Start Guide 3

Quick Start Guide April 2021
2 Physical installation
There are two types of power modules that will be discussed in this
document. They are the black power module (701PBK) and the green power
module (701PGN).
2.1 Installing Black power module (701PBK)
Prerequisites
Install the HART® device according to standard installation practices and the
manufacturer’s instructions, being sure to use an approved thread sealant
on all connections.
Procedure
1. Unscrew the power module cover from the wireless device.
2. Connect the power module to the wireless device. The power
module has a keyed connection to prevent improper connection.
Note
Wireless devices should be powered up in order of proximity from
the Smart Wireless Gateway, beginning with the closest device to the
Gateway. This will result in a simpler and faster network installation.
3. Connect the power module to the wireless device. The power
module has a keyed connection to prevent improper connection.
Figure 2-1: Black Power Module Installation
2.2
4 Emerson.com/Rosemount
Installing Green power module (701PGN)
Prerequisites
Install the HART device according to standard installation practices and the
manufacturer’s instructions, being sure to use an approved thread sealant
on all connections.

April 2021 Quick Start Guide
Procedure
1. Unscrew the power module cover from the wireless device.
2. Connect the green power module to the wireless device. The green
power module has a keyed connection to prevent improper
connection. If the Green power module is placed into the housing the
wrong way, it will not fit entirely into the housing.
Note
Wireless devices should be powered up in order of proximity from
the Smart Wireless Gateway, beginning with the closest device to the
Gateway. This will result in a simpler and faster network installation.
3. Close the housing cover and tighten. Ensure the power module cover
is fully tightened to prevent moisture ingress. The lip of the polymer
power module cover should be in contact with the surface of the
polymer enclosure to ensure a proper seal. Do not over tighten.
Figure 2-2: Green Power Module Installation
Quick Start Guide 5

Quick Start Guide April 2021
3 Verify operation
Operation can be verified in four locations: by using the Field
Communicator, at the Gateway via the Wireless Gateway’s integrated web
server, via AMS Wireless Configurator, or with the wireless device’s LCD
display.
3.1 Verify operation using Field Communicator
If you are able to communicate to the wireless device via a Field
Communicator, the power module is powering the device and working
correctly. Figure 5 shows how to connect a Field Communicator to a wireless
device with either the black or green power module.
Figure 3-1: Connect to Device
A. Communication terminals
B. Handheld communicator
C. HART modem
6 Emerson.com/Rosemount