Rosemount Quick Start Guide: Rosemount™ Hygienic Process Connection Adapters (FB-1041) Manuals & Guides

00825-0100-4104, Rev 02
Rosemount™ Hygienic Process Connection Adapter
Weld-in Adapter
Quick Start Guide
August 2020
This guide provides instructions for installing the Rosemount 326, 327, and 1408 transmitters with G1 process connectors using a weld-in adapter (part number FB-1041).

1.1 Safety instructions

Follow these guidelines to ensure safe use and extend the life of the product.
CAUTION
Read this document before using the product and keep it during
the entire service life.
The product must be suitable for the corresponding applications
and environmental conditions without any restrictions.
Only use the product for its intended purpose.
If the operating instructions or the technical data are not adhered
to, personal injury and/or damage to property might occur.
The manufacturer assumes no liability or warranty for any
consequences caused by tampering with the product or incorrect use by the operator.
Installation, electrical connection, set-up, operation and
maintenance of the product must be carried out by qualified personnel.

1.2 Hygienic adapter O-ring

The adapter comes with an EPDM O-ring. More O-rings are available as accessories. See each product's Product Data Sheet for more information.
2

2 Install the weld-in adapter

Use the weld-in adapter to install transmitters with G1 process connections to containers or pipes.
Prerequisites
After welding, allow the adapter to cool before installing. Do not weld the adapter to the container or pipe with the transmitter connected.
Procedure
Bore a hole that has the outside diameter of the adapter in the
1. pipe or container wall.
Maximum oversize: 0.008 in (0.2 mm)
Weld the adapter.
2.
Note
While welding, prevent the adapter from warping.
a) Turn the marking (1) (marking may vary) to the
position shown below for the display of the screwed transmitter.
3