Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end
users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your
system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for
all systems used within the facility.
The Rosemount 975 Flame Detectors are electro-optical devices designed to
identify fire events, enabling alarm activation. The detectors are intended
for indoor or outdoor use and can be used stand alone or connected to an
alarm/automatic extinguishing system.
The Rosemount 975 series comprises the following detectors:
Rosemount 975MR
The Rosemount 975MR, an ultra-fast multispectrum triple infrared (IR3)
flame detector, provides superior, longest distance detection of
hydrocarbon fires at up to 295 ft. (90 m), exceptional ultra-fast detection in
under 50 msec, and unparalleled reliability. The Rosemount 975 is based on
proven IR3 technology, ensuring highest sensitivity with best immunity to
false alarms.
Rosemount 975HR
The Rosemount 975HR is a multispectrum IR flame detector that provides
superior, longest distance detection of hydrogen (at up to 165 ft. [50 m])
and hydrocarbon fires (at up to 295 ft. [90 m]), exceptional ultra-fast
detection in under 50 msec, and unparalleled reliability. The Rosemount
975HR is designed to deal with the challenges of invisible fires based on
proven triple IR (IR3) technology, ensuring highest sensitivity with best
immunity to false alarms.
Rosemount 975UF
The Rosemount 975UF is an ultra-fast ultraviolet (UV)/IR flame detector,
which is able to detect in under 20 msec and features a unique dual sensor
with selectable UV and IR channels that can be used separately or combined.
The detector is designed to detect a range of fires, such as hydrocarbonbased fuel and gas, hydroxyl, hydrogen, metal, and inorganic.
Rosemount 975UR
The Rosemount 975UR is an ultra-fast UV/IR flame detector that is able to
detect in under 20 msec, and features a unique dual sensor with selectable
UV and IR channels that can be used separately or combined. The detector is
designed to detect hydrocarbon-based fuel and gas fires.
Table 1-1: Rosemount 975 Series General Technical Specifications
Spectral responseInfrared and ultraviolet bands
Response timeVaries according to model, typically under
Field of viewVaries according to model, up to 100 degrees
Quick Start Guide3
5 seconds
Quick Start GuideMay 2021
Table 1-1: Rosemount 975 Series General Technical Specifications
(continued)
Output4-20 mA, relays, communication
EnclosureStainless steel 316 or aluminum polyurethane
Operating voltage18-32 Vdc
Maximum power rating9.6 W
Relay contacts2A/30 Vdc
Over voltage category2
Relative humidityNon-condensing relative humidity up to 100%
painted
CAUTION
If the product is used outside of specified limits, this voids the product
certification, and our company is not responsible for any incurred warranty
expense.
Do not open this product, except for the terminal compartment as listed in
this document, under any circumstances.
The detector is not field-repairable. Any attempt to modify or repair the
internal circuits or change their settings, as this will impair the system’s
performance and void the product warranty.
Opening the attachment screws to dismantle the front part of the detector
from remaining parts is restricted and voids the product warranty.
4Emerson.com/Rosemount
May 2021Quick Start Guide
2Installing the detector
Table 2-1: Required Tools
ToolFunction
Hex key 1.5 mmFasten back cover security screw
Hex key 6 mmAdjust the tilt mount
Hex key 10 mmAffix the detector to the tilt mount
Hex key 3/16-in.Attach protective cover to detector
Flat screwdriver 6 mmConnect ground terminal
Flat screwdriver 2.5 mmConnect wires to the terminal blocks
Hex key 5/16-in.Stop plug 3/4 national pipe thread (NPT)
Open wrench 28 mmStop plug M25 only
Note
These are standard tools and are not supplied with the detector.
2.1Mounting accessories
2.1.1Tilt mount
The tilt mount (PN 00975-9000-0022) enables the detector to be mounted
on flat wall surfaces.
For more information, see Attach detector to tilt mount.
Quick Start Guide5
Quick Start GuideMay 2021
2.1.2Pole mount
Use the pole mount to mount the detector on poles with the following
diameters:
Table 2-2: Pole Mount Options
Pole diameterPart number
2 in. (50.8 mm)00975-9000-0007
3 in. (76.2 mm)00975-9000-0008
For more instructions, refer to the Pole Mount Reference Manual.
2.2Attach detector to tilt mount
Procedure
1. Unpack the detector.
2. Insert location pins on the tilt mount into the openings on detector
housing.
3. Thread the holding screw and tighten it.
Note
To change the detector field of view, release the horizontal and
vertical locking screws.
4. Point the detector toward the protected area and ensure the view of
the area is unobstructed.
5. Secure the detector in that position by tightening the locking screws
on the tilt mount.
The detector is now correctly located, aligned, and ready to be
connected to the system.