Rosemount Quick Start Guide: Rosemount 975 Flame Detectors Certification Information Manuals & Guides

Rosemount™ 975 Series
Flame Detectors
Certification Information
00825-0500-4975, Rev AC
June 2021
Contents

1 Ex approvals

Manufacturer
Rosemount
6021 Innovation Blvd
Shakopee, MN 55379
WARNING
Electrical shock
Keep covers tight while circuits are alive.
WARNING
Attention
Garder le couvercle bien fermé tant que les circuits sont sous tension.
Or the equivalent.
WARNING
Install a shield within 18-in. (457.2 mm) of the enclosure.
WARNING
Attention
Un scellement doit être installé à moins de 18-in. (457.2 mm) du boîtier.
Table 1-1: ATEX/IECEx
Classification Standards
Rosemount 975 Legacy Series
II 2 G D
Ex db eb IIC T4 Gb Ex tb IIIC T100 °C Db (Ta -40 °C to +75 °C) IP66/68
Rosemount 975 Series
II 2G D
Ex db eb IIC T4 Gb Ex tb IIIC T110 °C Db (Ta –50 °C to +85 °C) IP66/68
ATEX
EN IEC 60079-0:2018 General Requirements
EN 60079-1:2014 Flameproof Enclosure
EN 60079-7:2015/ A1:2018 Increased Safety
EN 60079-31:2014 Dust Protection by Enclosure
IECEx
EN IEC 60079-0:2018 Ed.7 General Requirements
IEC 60079-1:2014 Ed.7 Flameproof Enclosure
IEC 60079-7:2015 Ed.5 Increased Safety
IEC 60079-31:2013 Ed.2 Dust Protection by Enclosure
Table 1-2: FM/FMC
Rosemount 975 Legacy Series Rosemount 975 Series
Class I, Division 1, Groups B, C, and D, T4A
Class II, III, Division 1, Groups E, F, and G, T4A
Class I, Division 2, Groups A, B, C, and D, T4
Ta = -40 °C to +75 °C Type 6P; IP 66/68 2 m for 45 minutes
Class I, Division 1, Groups B, C, and D, T4A
Class II, III, Division 1, Groups E, F, and G, T4A
Class I, Division 2, Groups A, B, C, and D, T4
Ta = -50 °C to +85 °C Type 6P; IP 66/68 2 m for 45 minutes
Table 1-3: United States and Canadian Standards
United States standards Canadian standards
Class number Date Class number Date
FM Class 3600 2018 CSA C22.2 No. 0.4 2013
FM Class 3615 2018 CSA C22.2 No. 0.5 R2012
FM Class 3616 2011 CSA C22.2 No. 25 R2009