Rosemount Quick Start Guide: Rosemount™ 8712EM Transmitter with FOUNDATION™ Fieldbus Manuals & Guides

Quick Start Guide
00825-0500-4445, Rev AA
May 2019
Rosemount™ 8712EM Transmitter with FOUNDATION™ Fieldbus
Quick Start Guide May 2019

1 Safety

WARNING
Failure to follow these installation guidelines could result in serious injury
or death.
Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the operating instructions, unless qualified.
Rosemount Magnetic Flowmeters ordered with non-standard paint
options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flowmeter with a dry cloth or clean with solvents.
Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
To prevent ignition of flammable or combustible atmosphere,
disconnect power before servicing circuits.
Explosion hazard—Do not disconnect equipment when a flammable or
combustible atmosphere is present.
Do not connect a Rosemount Transmitter to a non-Rosemount sensor
when installed in an “Ex” environment, explosive atmosphere, hazardous area, or classified area.
Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the process reference ground.
CAUTION
In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent stray voltage/current from passing through the meter. Failure to adequately protect the meter could result in damage to the transmitter and lead to meter failure.
Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
2 Rosemount™ 8712EM Transmitter with Foundation™ Fieldbus
May 2019 Quick Start Guide

2 Introduction

This document provides basic installation guidelines for the Rosemount 8712EM wall-mount transmitter.
For sensor installation refer to the Rosemount™ 8700 Magnetic Flow Meter
Sensor Quick Installation Guide
All user documentation can be found at www.emerson.com. For more contact information see Emerson Flow customer service.

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
Quick Start Guide 3
Quick Start Guide May 2019

2.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240
Canada +1 303 527
5200
Mexico +41 (0) 41
7686 111
Argentina +54 11 4837
7000
Brazil +55 15 3413
8000
Venezuela +58 26 1731
3446
The Netherlands
France 0800 917 901 India 800 440 1468
Germany 0800 182
Italy 8008 77334 China +86 21 2892
Central & Eastern
Russia/CIS +7 495 981
Egypt 0800 000
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444
1978
+31 (0) 704 136 666
5347
+41 (0) 41 7686 111
9811
0015
0684
Australia 800 158 727
New Zealand 099 128 804
Pakistan 888 550 2682
9000
Japan +81 3 5769
6803
South Korea +82 2 3438
4600
Singapore +65 6 777
8211
6426
4 Rosemount™ 8712EM Transmitter with Foundation™ Fieldbus
May 2019 Quick Start Guide

3 Pre-Installation

Before installing the transmitter, there are several pre-installation steps that should be completed to make the installation process easier:
Set the hardware switches if necessary
Consider mechanical, electrical, and environmental requirements
Note
Refer to the product reference manual for more detailed requirements.
Hardware switches
The electronics board is equipped with two user-selectable hardware switches. These switches set the Simulate Enable and Transmitter Security. The standard configuration for these switches when shipped from the factory are as follows:
Table 3-1: Hardware switch default settings
Setting Factory configuration
Simulate enable Off
Transmitter security Off
In most cases, it is not necessary to change the setting of the hardware switches. If the switch settings need to be changed, refer to the product reference manual.
Be sure to identify any additional options and configurations that apply to the installation. Keep a list of these options for consideration during the installation and configuration procedures.
Mechanical considerations
The mounting site for the transmitter should provide enough room for secure mounting, easy access to conduit entries, full opening of the transmitter covers, and easy readability of the Display screen (if equipped).
Quick Start Guide 5
Quick Start Guide May 2019
Figure 3-1: Rosemount 8712EM Dimensional Drawing
9.0
2.81 [71]
[229]
3.12 [79]
3.51 [89]
11.15 [283]
A
B
12.03 [306]
3.90
[99]
17.68 [449]
D
C
A. Conduit entry, 1/2-14 NPT (4 places) B. Ground lug C. Lower cover opens for electrical connections
D. Standard electronics cover
1.94 [49]
1.70 [43]
1.94 [49]
1.59 [40]
7.80
[198]
11.36 [289]
Note
Dimensions are in inches [Millimeters]
Electrical considerations
Before making any electrical connections to the transmitter, consider national, local, and plant electrical installation requirements. Be sure to have the proper power supply, conduit, and other accessories necessary to comply with these standards.
6 Rosemount™ 8712EM Transmitter with Foundation™ Fieldbus
May 2019 Quick Start Guide
The transmitter requires external power. Ensure access to a suitable power source.
Table 3-2: Electrical data
Rosemount 8712E flow transmitter with FOUNDATION fieldbus
Power input AC power:
90–250VAC, 0.45A, 40VA
Standard DC power: 12–42VDC, 1.2A, 15W
Fieldbus Fieldbus segment requires a separate
9VDC to 32VDC power supply with a power conditioner to decouple the power supply output from the fieldbus wiring segment.
Environmental considerations
To ensure maximum transmitter life, avoid extreme temperatures and excessive vibration. Typical problem areas include the following:
Tropical or desert installations in direct sunlight
Outdoor installations in arctic climates
Remote mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and to provide easy access for configuration or service.
Quick Start Guide 7
Quick Start Guide May 2019

4 Mounting

Wall mount transmitters are shipped with mounting hardware for use on a 2-in. pipe or flat surface.
Figure 4-1: Mounting bracket
A
B
C
A. U-bolt B. Saddle clamp C. Fasteners
4.1
4.2
8 Rosemount™ 8712EM Transmitter with Foundation™ Fieldbus

Pipe mounting

1. Attach the saddle clamp to the pipe using the U-bolt mounting hardware.
2. Attach the transmitter to the saddle clamp assembly with appropriate fasteners.

Surface mounting

Attach the transmitter to the mounting location using customer supplied mounting screws. The installation of the transmitter shall be rated for four (4) times the weight of the transmitter or 44lbs ( 20kgs).
May 2019 Quick Start Guide

5 Wiring

5.1 Conduit entries and connections

Transmitter conduit entries ports are ½"-14NPT as standard, M20 conduit connections will use an adapter. Conduit connections should be made in accordance with national, local, and plant electrical codes. Unused conduit entries should be sealed with the appropriate certified plugs. The plastic shipping plugs do not provide ingress protection.

5.2 Conduit requirements

For installations with an intrinsically safe electrode circuit, a separate
conduit for the coil cable and the electrode cable may be required. Refer to the product reference manual.
For installations with non-intrinsically safe electrode circuit, or when
using the combination cable, a single dedicated conduit run for the coil drive and electrode cable between the sensor and the remote transmitter may be acceptable. Removal of the barriers for intrinsic safety isolation is permitted for non-intrinsically safe electrode installations.
Bundled cables from other equipment in a single conduit are likely to
create interference and noise in the system. See Figure 5-1.
Electrode cables should not be run together in the same cable tray with
power cables.
Output cables should not be run together with power cables.
Select conduit size appropriate to feed cables through to the flowmeter.
Quick Start Guide 9
Quick Start Guide May 2019
Figure 5-1: Best practice conduit preparation
5.3
A
B
A. Safety ground B. Power C. Coil
D. Output
E. Electrode
C D E
A
A

Sensor to transmitter wiring

Cable kits are available as individual component cables or as a combination coil/electrode cable. Remote cables can be ordered directly using the kit numbers shown in Table 5-1, Table 5-2, and Table 5-3. Equivalent Alpha cable part numbers are also provided as an alternative. To order cable, specify length as quantity desired. Equal length of component cables is required.
Examples:
25 feet = Qty (25) 08732-0065-0001
25 meters = Qty (25) 08732-0065-0002
10 Rosemount™ 8712EM Transmitter with Foundation™ Fieldbus
Loading...
+ 22 hidden pages