Rosemount Quick Start Guide: Rosemount 644H and 644R Smart Temperature Transmitters Manuals & Guides

Quick Start Guide
00825-0100-4728, Rev DB
Rosemount™ 644H and 644R Smart Temperature Transmitters
Device Revision 7 or Previous
April 2019
Quick Start Guide April 2019
NOTICE
This guide provides basic guidelines for installing the Rosemount™ 644 Temperature Transmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installation. Refer to the Rosemount 644 Reference Manual for more instruction. The manual and this guide are also available electronically on Emerson.com/Rosemount.
Important
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this product. The United States has two toll-free assistance numbers and one international number. Customer Central: 1-800-999-9307 (7:00 a.m. to 7:00 p.m. Central Standard Time)
National Response Center: 1-800-654-7768 (24 hours a day). Equipment service needs
International: 1-(952)-906-8888
WARNING
Follow instructions
Failure to follow these installation guidelines could result in death or serious injury.
Ensure only qualified personnel perform the installation.
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of the transmitters in a hazardous environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the Product Certifications section for any restrictions associated with a safe installation.
Do not remove the connection head cover in explosive atmospheres when the circuit is live. Before connecting a handheld communicator in an explosive atmosphere, ensure the instruments
are installed in accordance with intrinsically safe or non-incendive field wiring practices.Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet explosion-proof requirements.
WARNING
Process leaks
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation. Install and tighten thermowells and sensors before applying pressure.
2 Rosemount 644H and 644R
April 2019 Quick Start Guide
WARNING
Electrical shock
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Contents
Configure (bench calibration)........................ 5
Verify configuration....................................... 7
Set switches.................................................12
Mount the transmitter................................. 13
Wire and apply power.................................. 19
Perform a loop test...................................... 25
Product Certifications.................................. 27
Quick Start Guide 3
Quick Start Guide April 2019
4 Rosemount 644H and 644R
B
A
April 2019 Quick Start Guide

1 Configure (bench calibration)

The Rosemount™ 644 communicates using the Field Communicator. Communication requires a loop resistance between 250 and 1100 ohms. Do not operate when power is below 12 Vdc at the transmitter terminal. Refer to the Rosemount 644 Reference Manual and the Field Communicator
Reference Manual for more information.

1.1 Update the field communicator software

The Field Communicator field device revision Dev v6, Device Dashboard (DD) v1 or higher is required for complete functionality. The device will communicate with all previous Rosemount™ 644 DD revisions.
Use this procedure to determine if a software upgrade is required.
Figure 1-1: Connecting a communicator to a bench loop
Rosemount 644 head mount and field mount
Rosemount 644 rail mount
A. 250Ω ≤ RL ≤ 1100Ω B. AMS™ Device Manager C. Power supply
D. Field Communicator
Procedure
1. Connect the sensor. See the wiring diagram on the inside of housing cover.
2. Connect the bench power supply to the power terminals (“+” or “–”).
3. Connect a Field Communicator to the loop across a loop resistor or at the power/signal terminals on the transmitter. The following message will appear if the communicator has a previous version of the device descriptors (DDs). Upgrade the
communicator software to access new XMTR functions. Continue with old description?
Quick Start Guide 5
Quick Start Guide April 2019
Need help?
If this notice does not appear, the latest DD is installed.
If the latest version is not available, the communicator will
communicate properly.
Note
When the transmitter is configured to use the advanced features of the transmitter (i.e., one of the added sensor input types), the user will experience trouble communicating and will be prompted to turn the communicator off. To prevent this from happening, upgrade to the latest DD or answer NO to the question and default to the generic transmitter functionality.
6 Rosemount 644H and 644R
April 2019 Quick Start Guide

2 Verify configuration

Use fast key sequences to verfiy transmitter configuration.
The traditional interface Fast Key sequences in Table 2-1 and Table 2-2 may be used for transmitter configuration and startup.

2.1 Field communicator traditional user interface

The traditional interface and fast key sequences.
Figure 2-1: Field Communicator Traditional Interface
Table 2-1: Traditional Interface Fast Key Sequences
Function Fast keys Function Fast Keys
Active Calibrator 1, 2, 2, 1, 3 Open Sensor
Holdoff
Alarm/Saturation 1, 3, 3, 2 Percent Range 1, 1, 5
AO Alarm Type 1, 3, 3, 2, 1 Poll Address 1, 3, 3, 3, 1
Burst Mode 1, 3, 3, 3, 3 Process
Temperature
Burst Option 1, 3, 3, 3, 4 Process Variables 1, 1
Calibration 1, 2, 2 PV Damping 1, 3, 3, 1, 3
Quick Start Guide 7
1, 3, 5, 3
1, 1
Quick Start Guide April 2019
Table 2-1: Traditional Interface Fast Key Sequences (continued)
Function Fast keys Function Fast Keys
Callendar-Van Dusen
Configuration 1, 3 Range Values 1, 3, 3, 1
D/A Trim 1, 2, 2, 2 Review 1, 4
Damping Values 1, 1, 10 Scaled D/A Trim 1, 2, 2, 3
Date 1, 3, 4, 2 Sensor Connection 1, 3, 2, 1, 1
Descriptor 1, 3, 4, 3 Sensor 1 Setup 1, 3, 2, 1, 2
Device Info 1, 3, 4 Sensor Serial
Device Output Configuration
Diagnostics and Service
Filter 50/60 Hz 1, 3, 5, 1 Sensor Type 1, 3, 2, 1, 1
Hardware Rev 1, 4, 1 Software Revision 1, 4, 1
HART Output 1, 3, 3, 3 Status 1, 2, 1, 4
Intermittent Detect
LCD Display Options
Loop Test 1, 2, 1, 1 Test Device 1, 2, 1
LRV (Lower Range Value)
LSL (Lower Sensor Limit)
Measurement Filtering
Message 1, 3, 4, 4 Variable Re-Map 1, 3, 1, 5
Meter Configuring 1, 3, 3, 4, 1 Write Protect 1, 2, 3
Meter Decimal Point
Num Req Preams 1, 3, 3, 3, 2
1, 3, 2, 1 PV Unit 1, 3, 3, 1, 4
Number
1, 3, 3 Sensor 1 Trim 1, 2, 2, 1
1, 2 Sensor 1 Trim-
Factory
1, 3, 5, 4 Tag 1, 3, 4, 1
1, 3, 3, 4 Terminal
Temperature
1, 1, 6 URV (Upper Range
Value)
1, 1, 8 USL (Upper Sensor
Limit)
1, 3, 5 Variable Mapping 1, 3, 1
1, 3, 3, 4, 2 2-Wire Offset 1, 3, 2, 1, 2, 1
1, 3, 2, 1, 4
1, 2, 2, 1, 2
1, 3, 2, 2
1, 1, 7
1, 1, 9
8 Rosemount 644H and 644R
April 2019 Quick Start Guide

2.2 Input/verify the Callendar Van-Dusen constants on the Field Communicator traditional user interface

If using sensor matching with this combination of a transmitter and sensor, verify the constants input.
Procedure
1. From the Home screen, select 1 Device Setup > 3 Configuration > 2 Sensor Config > 1 Sensor 1 > 3 Cal Van-Dusen.
2. Set the control loop to manual and select OK.
3. At the Enter Sensor Type prompt, select Cal Van-Dusen
4. At the Enter Sensor Connection prompt, select the appropriate number of wires.
5. Enter the R0, Alpha, Beta, and Delta values from the stainless steel tag attached to the special-order sensor.
6. Return the control loop to automatic control and select OK.

2.3 Field Communicator device dashboard

Figure 2-2: Device Dashboard
Quick Start Guide 9
Quick Start Guide April 2019
Table 2-2: Device Dashboard Fast Key Sequences
Function Fast keys Function Fast keys
Active Calibrator 2, 2, 4, 2 Num Req Preams 2, 2, 5, 2
Alarm/Saturation 2, 2, 2, 6 Open Sensor
Burst Mode 2, 2, 5, 3 Percent Range 2, 2, 2, 4
Burst Option 2, 2, 5, 4 Poll Address 2, 2, 5, 1
Calibration 2, 1, 2 PV Damping 2, 2, 1, 6
Callendar-Van Dusen
Configuration 2, 1, 1 Range Values 2, 2, 2, 5
D/A Trim 3, 4, 2 Scaled D/A Trim 3, 4, 3
Damping Values 2, 2, 1, 6 Sensor Connection 2, 2, 1, 3
Date 1, 7, 8 Sensor 1 Setup 2, 2, 1
Descriptor 1, 7, 6 Sensor Serial
Device Info 1, 7 Sensor 1 Trim 3, 4, 1
Device Output Configuration
Filter 50/60 Hz 1, 3, 3 Sensor Type 2, 2, 1, 2
Hardware Rev 1, 7, 9, 3 Software Revision 1, 7, 9, 4
HART Output 2, 2, 5 Tag 2, 2, 4, 1, 1
LCD Display Options
Loop Test 3, 5, 1 URV (Upper Range
LRV (Lower Range Value)
LSL (Lower Sensor Limit)
Message 1, 7, 7 Variable Re-Map 2, 2, 5, 5, 5
Meter Configuring 2, 2, 3, 1 Write Protect 2, 2, 4, 6
Meter Decimal Point
2, 2, 1, 10 PV Unit 2, 2, 1, 4
2, 2, 2 Sensor 1 Trim-
2, 2, 3 Terminal
2, 2, 2, 5, 3 USL (Upper Sensor
2, 2, 1, 9 Variable Mapping 2, 2, 5, 5
2, 2, 3, 2 2-Wire Offset 2, 2, 1, 5
Holdoff
Number
Factory
Temperature
Value)
Limit)
2, 2, 4, 4
2, 2, 1, 7
3, 4, 1, 2
3, 3, 2
2, 2, 2, 5, 2
2, 2, 1, 8
10 Rosemount 644H and 644R
April 2019 Quick Start Guide

2.4 Input/verify the Callendar Van-Dusen constants on the Field Communicator device dashboard

If using sensor matching with this combination of a transmitter and sensor, verify the constants input.
Procedure
1. From the Home screen, select 2 Configure > 2 Manual Setup > 1 Sensor.
2. Set the control loop to manual and select OK.
3. At the Enter Sensor Type prompt, select Cal Van-Dusen
4. At the Enter Sensor Connection prompt, select the appropriate number of wires.
5. Enter the R0, Alpha, Beta, and Delta values from the stainless steel tag attached to the special-order sensor.
6. Return the control loop to automatic control and select OK.
7. Disable the transmitter-sensor matching feature.
a) From the Home screen, select 2 Configure > 2 Manual Setup
> 1 Sensor > 10 SensorMatching-CVD.
b) At the Enter Sensor Type prompt, select the
appropriate sensor type.
Quick Start Guide 11
Quick Start Guide April 2019

3 Set switches

3.1 Set switches on the Rosemount™ 644H without LCD display

The switch is located on the bottom right of the electronics module.
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Set the switch to the desired position.
4. Replace the electronics housing cover.
5. Apply power and set the loop to automatic control.

3.2 Set switches on the Rosemount™ 644H withLCD display

The switch is located on the bottom right of the electronics module.
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Snap-off the LCD display straight off.
4. Set the switch to the desired position.
5. Reattach the LCD display and replace the electronics housing cover. Rotate the LCD display in 90° increments.
6. Apply power and set the loop to automatic control.
3.3
12 Rosemount 644H and 644R

Set switches on the Rosemount™ 644R

The switch is located on the middle of the front panel.
Procedure
1. Open the transmitter's front door.
2. Set the switch to the desired position.
April 2019 Quick Start Guide

4 Mount the transmitter

Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing.

4.1 Install connection head

Head mount transmitter with DIN plate style sensor.
Procedure
1. Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell before applying process pressure.
2. Assemble the transmitter to the sensor. Push the transmitter mounting screws through the sensor mounting plate and insert the snap rings (optional) into the transmitter mounting screw groove.
3. Wire the sensor to the transmitter.
4. Insert the transmitter-sensor assembly into the connection head. Thread the transmitter mounting screws into the connection head mounting holes. Assemble the extension to the connection head. Insert the assembly into the thermowell.
5. Slip the shielded cable though the cable gland.
6. Attach the cable gland into the shielded cable.
7. Insert the shielded cable leads into the connection head through the cable entry. Connect and tighten the cable gland.
8. Connect the shielded power cable leads to the transmitter power terminals.
Avoid contact with sensor leads and sensor connections.
9. Install and tighten the connection head cover.
WARNING
Enclosure covers must be fully engaged to meet explosion-proof requirements.
Quick Start Guide 13
D
A
E
B
F
C
Quick Start Guide April 2019
Example
A. Rosemount™ 644 Transmitter B. Connection head C. Thermowell
D. Transmitter mounting screws
E. Integral mount sensor with flying leads F. Extension

4.2 Install universal head

Head mount transmitter with threaded sensor.
Procedure
1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells before applying process pressure.
2. Attach necessary extension nipples and adapters to the thermowell. Seal the nipple and adapter threads with silicone tape.
3. Screw the sensor into the thermowell. Install drain seals if required for severe environments or to satisfy code requirements.
4. Verify the correct installation of Integral Transient Protection (option code T1).
a) Ensure the transient protector unit is firmly connected to the
transmitter puck assembly.
b) Ensure the transient protector power leads are adequately
secured under the transmitter power terminal screws.
c) Verify the transient protector’s ground wire is secured to the
internal ground screw found within the universal head.
Note
The transient protector requires the use of an enclosure of at least
3.5-in. (89 mm) in diameter.
14 Rosemount 644H and 644R
5. Pull the sensor wiring leads through the universal head and transmitter. Mount the transmitter in the universal head by
A
B
C
D
E
April 2019 Quick Start Guide
threading the transmitter mounting screws into the universal head mounting holes.
6. Mount the transmitter-sensor assembly into the thermowell. Seal adapter threads with silicone tape.
7. Install conduit for field wiring to the conduit entry of the universal head. Seal conduit threads with PTFE tape.
8. Pull the field wiring leads through the conduit into the universal head. Attach the sensor and power leads to the transmitter.
Avoid contact with other terminals.
9. Install and tighten the universal head cover. Enclosure covers must be fully engaged to meet explosion-proof
requirements.
Example
A. Threaded thermowell B. Standard extension C. Threaded style sensor
D. Universal head (transmitter and LCD inside)
E. Conduit entry
Quick Start Guide 15
Loading...
+ 33 hidden pages