Rosemount Quick Start Guide: Rosemount™ 5408 and 5408:SIS Level Transmitters Parabolic Antenna Manuals & Guides

Quick Start Guide
00825-0300-4408, Rev BB
February 2020
Rosemount™ 5408 and 5408:SIS Level Transmitters
Parabolic Antenna
Quick Start Guide February 2020
About this guide...........................................................................................................................3
Confirm approval type..................................................................................................................5
Components of the parabolic antenna......................................................................................... 6
Mount the transmitter..................................................................................................................8
Adjust the inclination of the antenna..........................................................................................21
Connect the air purging..............................................................................................................24
Adjust display orientation (optional).......................................................................................... 25
Prepare the electrical connections..............................................................................................26
Connect wiring and power up.....................................................................................................33
Configure transmitter using Guided Setup................................................................................. 37
2 Rosemount 5408 and 5408:SIS Level Transmitters
February 2020 Quick Start Guide

1 About this guide

This Quick Start Guide provides basic guidelines for the Rosemount 5408 and 5408:SIS Level Transmitters. Refer to the Rosemount 5408 and 5408:SIS with HART® Reference Manual and Rosemount 5408 with FOUNDATION Fieldbus Reference Manual for more instructions. The manuals and this guide are also available electronically on Emerson.com/Rosemount.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure the transmitter is installed by qualified personnel and in
accordance with applicable code of practice.
Use the equipment only as specified in this manual. Failure to do so may
impair the protection provided by the equipment.
For installations in hazardous locations, the transmitter must be installed
according to the Rosemount 5408 and 5408:SIS Product Certifications document and System Control Drawing (D7000002-885).
Repair, e.g. substitution of components, etc. may jeopardize safety and
is under no circumstances allowed.
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent
with the appropriate hazardous locations certifications.
Before connecting a handheld communicator in an explosive
atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.
In Explosion-proof/Flameproof and Non-Incendive/Type n installations,
do not remove the transmitter covers when power is applied to the unit.
Both transmitter covers must be fully engaged to meet Explosion-proof/
Flameproof requirements.
Electrical shock could cause death or serious injury.
In Explosion-proof/Flameproof and Non-Incendive/Type n installations,
avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Ensure the mains power to the transmitter is off and the lines to any
other external power source are disconnected or not powered while wiring the transmitter.
Quick Start Guide 3
Quick Start Guide February 2020
WARNING
Process leaks could result in death or serious injury.
Ensure that the transmitter is handled carefully. If the process seal is
damaged, gas might escape from the tank.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
CAUTION
Hot surfaces The flange and process seal may be hot at high process temperatures. Allow to cool before servicing.
4 Rosemount 5408 and 5408:SIS Level Transmitters
February 2020 Quick Start Guide

2 Confirm approval type

For hazardous locations transmitters labeled with multiple approval types:
Procedure
Permanently mark the checkbox of the selected approval type(s).
Figure 2-1: Label with Multiple Approval Types
Quick Start Guide 5
2x
[
(
[
*
[
'
[
&
[
%
[
$
[
)
Quick Start Guide February 2020

3 Components of the parabolic antenna

3.1 Components of the threaded version

Figure 3-1: Components
A. Antenna B. Purge plug kit C. Threaded sleeve
D. M20 adapter
E. Lock nut BSPP (G) 3½-in. F. Antenna adapter with ball joint
G. O-ring
6 Rosemount 5408 and 5408:SIS Level Transmitters
[
(
[
.
[
)
[
*
[
/
[
,
[
-
[
'
[
&
[
%
[
$
[
+
February 2020 Quick Start Guide

3.2 Components of the welded version

Figure 3-2: Components
A. Antenna B. Purge plug kit C. Threaded sleeve
D. M20 adapter
E. Weld protection plate
F. Flange ball G. O-ring H. Clamp flange
I. Washer J. M8 screw
K. Weld protection bar
L. Ball joint
Quick Start Guide 7
Quick Start Guide February 2020

4 Mount the transmitter

4.1 Mount the flanged version

Procedure
1. Place a suitable gasket on the tank flange.
2. Lower the flange and antenna assembly into the nozzle.
3. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice.
Postrequisites
1. Adjust the inclination of the antenna (see Adjust the inclination of
the antenna).
8 Rosemount 5408 and 5408:SIS Level Transmitters
%
$
February 2020 Quick Start Guide
2. Connect the air purging system (see Connect the air purging).

4.2 Mount the threaded version

Procedure
1. Remove the lock nut.
2. Mount the O-ring.
3. Mount the antenna adapter on flange/manhole cover. Ensure the antenna adapter fits tightly to the flange/manhole cover.
A. Ø 3.98 ± 0.02 in. (Ø 101 ± 0.6 mm) or G 3½-in. B. Max. 0.59 in. (15 mm)
Quick Start Guide 9
27 mm
Torque 180 in-lb (20 N-m)
Quick Start Guide February 2020
4. Remove the M20 adapter and visually inspect the O-rings for damage and dirt.
5. Carefully insert the antenna.
6. Secure the antenna.
10 Rosemount 5408 and 5408:SIS Level Transmitters
H2 mm
Torque 5 in-lb (0.5 N-m)
February 2020 Quick Start Guide
7. Tighten the set screw.
8. Place a suitable gasket on the tank flange.
9. Lower the antenna assembly into the tank.
10. Tighten the bolts and nuts with sufficient torque for the flange and gasket choice.
Quick Start Guide 11
%
$
Quick Start Guide February 2020
Postrequisites
1. Adjust the inclination of the antenna (see Adjust the inclination of
the antenna).
2. Connect the air purging system (see Connect the air purging).

4.3 Mount the welded version

Procedure
1. Mount the protection plates to flange/manhole cover. These plates protect the internal surfaces of the flange ball from dust and sparks during welding.
A. Ø 3.94 ± 0.02 in. (Ø 100 ± 0.5 mm) B. Max. 1.18 in. (30 mm)
12 Rosemount 5408 and 5408:SIS Level Transmitters