Quick Installation Guide
00825-0100-4830, Rev AA
January 2004
Rosemount 415 Fire Pump
Rosemount 415 Fire Pump
Step 1: Location and Orientation
Step 2: Drill Holes into Pipe
Step 3: Weld Mounting Hardware
Step 4: Insert the Annubar
¢00825-0100-4830e¤
www.rosemount.com

Quick Installation Guide
00825-0100-4830, Rev AA
January 2004
© 2004 Rosemount Inc. All rights reserved. All marks are the property of their owners.
Rosemount Inc.
8200 Market Boulevard
Chanhassen, MN USA 55317
T (US) (800) 999-9307
T (Intnl) (952) 906-8888
F (952) 949-7001
Emerson Process Management
Asia Pacific Private Limited
1 Pandan Crescent
Singapore 128461
T (65) 6777 8211
F (65) 6777 0947/65 6777 0743
Rosemount 415 Fire Pump
Emerson Process Management
GmbH & Co. OHG
Argelsrieder Feld 3
82234 Wessling
Germany
T 49 (8153) 9390
F49 (8153) 939172
Beijing Rosemount Far East
Instrument Co., Limited
No. 6 North Street,
Hepingli, Dong Cheng District
Beijing 100013, China
T (86) (10) 6428 2233
F (86) (10) 6422 8586
IMPORTANT NOTICE
This installation guide provides basic guidelines for Rosemount Eagle Eye
Fire Pump. It does not provide instructions for configuration, diagnostics,
maintenance, service, troubleshooting, Explosion-proof, Flame-Proof, or
instrinsically safe (I.S.) installations. Refer to the Rosemount Eagle Eye
Series Product Data Sheet (document number 00813-0100-4830) or the
Eagle Eye QIG (document number 00825-0100-4833) for more information.
These documents are also available electronically on www.rosemount.com.
WARNING
Process leaks may cause harm or result in death. To avoid process leaks,
only use gaskets designed to seal with the corresponding flange and o-rings
to seal process connections. Flowing medium may cause the 485 Annubar
assembly to become hot and could result in burns.

Quick Installation Guide
00825-0100-4830, Rev AA
January 2004
need
EXPLODED VIEW
Annubar Sensor
Pak-Lok Body
1
/8-in. NPT x 1/4-in. Reducer
1
/8-in. Ball Valve
1
/8-in. NPT x 1/4-in.
SAE Flare Adapter
Mounting U-Bolt
Rosemount 415 Fire Pump
Packing Rings (3)
Stud
Compression Plate
Washer
Nut
1
/4-in. O.D. Tube
Eagle Eye Indicator
31-490000-901A

Quick Installation Guide
00825-0100-4830, Rev AA
January 2004
Rosemount 415 Fire Pump
STEP 1: LOCATION AND ORIENTATION
Correct orientation and straight run requirements must be met for
accurate and repeatable flow measurements. Refer to Table 1 for
minimum pipe diameter distances from upstream disturbances.
Table 1. Straight Run Requirements
Upstream Dimensions
Without Vanes With Vanes
In
Out of
Plane A
Plane A
1
8
—
2
11
—
A’ C C’
10——8—4—44
16——8—4—44
Downstream
4
4
Dimensions
3
23
28——8—4—44
—
4