This Rosemount product complies with all applicable European directives when properly installed in accordance with the
instructions in this manual. Refer to the EU declaration of conformity for directives that apply to this product. The EU declaration
of conformity, with all applicable European directives, and the complete ATEX Installation Drawings and Instructions are available
on the internet at www.emerson.com or through your local Emerson support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found on the internet at http://
www.emerson.com.
For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Full product specifications can be found in the product data sheet. Troubleshooting information can be found in the user manual.
Product data sheets and manuals are available from the Emerson website at http://www.emerson.com.
Return policy
Follow Emerson procedures when returning equipment. These procedures ensure legal compliance with government
transportation agencies and help provide a safe working environment for Emerson employees. Emerson will not accept your
returned equipment if you fail to follow Emerson procedures. Return procedures and forms are available on our web support site
at www.emerson.com, or by phoning the Emerson Customer Service department.
Emerson Flow customer service
Email:
• Worldwide: http://flow.support@emerson.com
• Asia-Pacific: http://APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
United States800 522 6277U.K.0870 240 1978Australia800 158 727
HART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810
10
1.Introduction
1. Introduction
April 2022
1.1
1.2
1.3
1.4
Scope
The scope of this document is to define the HART revision 7 functional requirements, device
specific commands and all Universal and the supported Common Practice commands
supported by the HART interface for Rosemount 3810 Series Liquid Ultrasonic Flow Meters,
Purpose
The purpose of this document is to list the functional requirements for developing the 3810
Series Liquid Ultrasonic Flow Meters HART rev 7 firmware. This document complies with HART
Protocol Revision 7 and Field Device Specification HCF_LIT-18, Revision 11.0 in preparation and
development of engineering regression tests of functionality not covered by the HCF-Kit-192.
Who should use this document?
This specification is designed to be a technical reference for HART capable Host Application
Developers, System Integrators, and knowledgeable End Users. It also provides functional
specifications (e.g., commands, enumerations and performance requirements) used during
Field Device Development, maintenance and testing. This document assumes the reader is
familiar with HART Protocol requirements and terminology.
Definitions, abbreviations, acronyms and
references
The following is a list of commonly used definitions used throughout this document.
Scope 1
1. Introduction HART Field Device Specification 3810 Series Ultrasonic Meter
April 202200825-0300-3810
1.4.1 Definitions
Table 1-1 Definitions
NameDefinition
Emerson Field Communicator375 or 475 field communicator - handheld device
HART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810
1.4.4References
The documents referenced within the text of this document are listed in the table below:
Table 1-4 Reference documentation
TitleDocument number, revision, date
1. Introduction
April 2022
American Petroleum Institute (API) Manual of Petroleum Measurement Standards (MPMS) Chapter 21 - Flow Measurement Using
Electronic Metering Systems
Section 1 - Electronic Gas Measurement
HART SMART Communications Protocol Specification (also includes
the specifications listed below)
1. Introduction HART Field Device Specification 3810 Series Ultrasonic Meter
April 202200825-0300-3810
4References
2. Device identificationHART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810April 2022
21
2.Device identification
This section details the Rosemount 3810 Series Liquid Ultrasonic Flow Meter identification
and physical description.
2.1
Rosemount 3810 Series Liquid Ultrasonic Flow
Meter identification
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter Field Device Identification
summary is shown in Table 2-1 below.
Table 2-1 3810 Series Liquid Ultrasonic Flow Meter device identification
Rosemount 3810
Series Liquid
Manufacturer Name:
Manufacture ID Code:13 (D Hex)Device Type Code:41 (29 Hex)
HART Protocol Revision:7Device Revision:6
Number of Device Variables:3
Physical Layers Supported:Bell 202 FSKNote:
Physical Device Category:
Emerson
Rosemount Series 3810
Liquid Ultrasonic F
low Meter
Model Name(s):
HART Hardware Revision4
HART Software Revision:26
Ultrasonic Flow
Meter
Rosemount 3810 Series Liquid Ultrasonic Flow Meter identification
5
HART Field Device Specification 3810 Series Ultrasonic Meter2. Device identification
April 202200825-0300-3810
2.2Physical description
The Series 3810 Liquid Ultrasonic Meter electronics enables the meter to easily communicate
with other field devices, and ultimately, communicate key diagnostic information through
PlantWeb architecture. Any programmable device, such as the FPGA, is programmed via the
CPU Module. The CPU Module part number is P/N 1-360-03-001).
Figure 2-1 3810 Series Liquid Ultrasonic Flow Meter Electronics - CPU Module
6Physical description
3. Product overviewHART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810April 2022
3. Product overview
This section specifies the purpose and application of the Rosemount 3810 Series Liquid
Ultrasonic Flow Meter for HART communications.
3.1
3.2
3.3
Device function, purpose and features
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter enables communication with other
field devices, and ultimately, communicates key diagnostic information through the
PlantWeb® architecture.
All analog inputs and outputs are isolated from each other and isolated from the system with a
minimum isolation of 500 V.
Process connections
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter’s electronics (the firmware, CPU
module and the Acquisition module) allows communications with other field devices.
External interfaces (electrical and non-electrical)
Any pressure and/or temperature input read via the Rosemount 3810 Series Liquid Ultrasonic
Flow Meter is configured using a hand-held communicator (e.g., Emerson's 375 Field
Communicator) and not via the meter such as for device address, device tag, limits, and units.
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter is compliant with Asset Management
Solutions, AMSTM Device Manager, software applications that provides operator interface
between a HART enabled field device and a remote PC.
3.4
Device function, purpose and features 7
Other required equipment
An RS-232C/RS-485 (half duplex) serial communication port for Modbus communication is
provided on Port A, Port B and Port C.
Any programmable device on the Rosemount 3810 Series Liquid Ultrasonic Flow Meter (such
as a FPGA) is programmed via the CPU Module.
HART Field Device Specification 3810 Series Ultrasonic Meter3. Product overview
April 202200825-0300-3810
8Other required equipment
00825-0300-3810
4
4.Product interfaces
This section discusses the Rosemount 3810 Series Liquid Ultrasonic Flow Meter for
HART communications, electrical interface, and input and output requirements.
4. Product interfacesHART Field Device Specification 3810 Series Ultrasonic Meter
April 2022
4.1
4.1.1
Process interfaces
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter is capable of communicating with a
flow computer or other interface devices (e.g. (AMSTM Device Manager or an Emerson Field
Communicator, etc.) via HART and enables PlantWeb connectivity.
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter provides an RS-232C/RS-485 halfduplex serial communications port (Port A) connected via the CPU Module. Two independent
analog input circuits and 16-bit, 4-20mA analog output circuits are supported.
LED status indicators show 24V power, 24V current limit, TX and RX serial communication ports,
and HART slave communication via Analog Output 1.
Sensor input channels
Rosemount 3810 Series Liquid Ultrasonic Flow Meters supports analog and discrete inputs as
shown below.
Name
Analog Input 14 mA- 20 mA Input for temperature device
Analog Input 24 mA- 20 mA Input for pressure device
Functional description
Note: AI-1 and AI-2 are electronically isolated and operate in sink
mode. The input contains a series resistance so HART Communicators can be connected to configure sensors.
A 24 Volt DC power supply is available to provide power to the
sensors.
Digital Input
(Selectable)
Ethernet PortOne Ethernet Port (TCP/IP)
Frequency/Digital Output(s)Maximum frequency for the frequency outputs
Serial PortOne serial RS-232/RS-485 port
Process interfaces 9
(1) Single polarity (for flow calibration gating - contact closure)
•Single input for starting and stopping
•Four pulse configurations available
•Up to 100 Mbps
•Modbus TCP
•1000Hz
•5000Hz
Mode options:
•Open Collector (requires external excitation supply voltage
and pull-up resistor)
TTL (internally powered by the meter 0-5 VDC signal)
(115 kbps baud rate) (Modbus RTU/ASCII)
HART Field Device Specification 3810 Series Ultrasonic Meter4. Product interfaces
April 202200825-0300-3810
Name
Tra n sd uc er s•LT- 01
Functional description
•LT-03
•LT-04
•LT-05
•LT-06
•LT-07
•LT-08
•LT-09
•LT-10
•LT-11
•LT-14
•LT-15
•LT-16
•LT-17
Note: The process temperature must not exceed the operating tem-
perature range of the transducers.
4.1.2Sensor analog output channels
The firmware supports two independently-configurable analog output channels (AO1 and AO2).
For conventional operation, the analog output channels provide identical but separate
configuration parameters including, but not limited to, the currently available AO1
configuration parameters (for content and scaling configuration). These configuration
parameters follow the same naming convention as the AO1related configuration parameters
(which retain their current names). The Boolean data point, IsAO1Avail indicates the presence
of Analog Output 1 (AO1). NOTE: HART communication is available over AO1 only.
10Sensor analog output channels
4. Product interfacesHART Field Device Specification 3810 Series Ultrasonic Meter
Configuration via the HART slave port, requires device-specific commands.
00825-0300-3810
Table 4-1 Analog output configuration parameters
Val ues
Direction
Linear over-rangeDown greater than-3.125%3.5 mA
Up less than+106.25%21 mA
Maximum current+106.25%21 mA
Multi-drop current draw
Lift-off voltage7 V@ full scale
(percent of range)
4 mA (Available in sink mode only)
Choose the HART selectable output Primary or Secondary Variable (via any serial, Ethernet, or
HART slave port):
•uncorrected volumetric flow rate
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter output Third and Fourth Variables
(via any serial, Ethernet, or HART slave port) from among the choices available for the Primary
Variable and additionally the following choices (if applicable):
Values
(e.g., in mA)
April 2022
•live pressure value
•live temperature value
•for each frequency output: maximum frequency, content, relationship to flow
direction, B channel action upon error, A and B channel phase relationship, and output
scaling
•for each digital output: content, and polarity
•for each analog output (conventional 4-20 mA operation): content, relationship to flow
direction, and output scaling
Sensor analog output channels 11
HART Field Device Specification 3810 Series Ultrasonic Meter4. Product interfaces
•The HART slave supports the HART Rev. 7 commands listed in Section 8 through
Section 10.
•The HART slave does not support transfer functions.
Each analog output has individually configurable alarm selections. The selections includes:
•Very Low (3.5 mA)
•Low (4.0 mA), High (20 mA)
•Very High (20.5 mA)
•Hold Last Value
•None
Trim the analog outputs via Trim the analog outputs via HART, serial or Ethernet interfaces. The
AOXActionUponInvalidContent data point specifies the action for Analog Output 1 current
when the content is invalid. No special action is taken when set to none.
Each analog output is considered saturated if the "pre-trimmed" value is (strictly) outside the
range (3.5, 20.5) mA. Note that a value less than 4 mA should only occur if the output is invalid
and the invalid content is selected to be represented by a fixed 3.5 mA output. The database
point AOXIsSaturated shall be used to indicate the saturation status.
For each analog output, after the saturation determination is made, then the DAC -limits of (3.5,
21) mA is applied to the pre-trimmed value. The resulting value is written to the appropriate
AOXOutput database point (so that the point's meaning is consistent with the pre-HART
firmware).
The analog output trim zero and gain values (stored in database points AOXCurrentTrimZero
and AOXCurrentTrimGain, respectively) are always applied to the analog output's pretrimmed, DAC -limited value (i.e., the value stored in the database point AOXOutput) as shown
in Equation 1 (all values in milliamps except the dimensionless gain). The DAC - limits (3.5, 21)
mA is applied to the resultant trim value (AOXTRIM) and DAC -limited result shall be stored in the
database point AOXOutputTrimmed and output to the DAC.
Equation 4-1 AOXOutput Trim
The user shall be able to zero the meter (i.e., perform zero-flow calibration) via any serial,
Ethernet, or HART slave port.
12Sensor analog output channels
4. Product interfacesHART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810
4.1.3Time Stamp
A time stamp shall be calculated for each of the HART device variables when the device variable
is updated and the status is good. The time stamps shall be associated with the corresponding
data points shown in Table 4-2
Table 4-2 Device variables time stamp
Device variable Associated time stamp data point name
Uncorrected flow rate (QFlow) HARTQFlowUpdateTime
Pressure (FlowPressure)HARTPressureUpdateTime
Temperature (FlowTemperature)HARTTemperatureUpdateTime
Time stamps shall be calculated for additional device variables that indicate percent of range
and loop current.
Table 4-3 Time stamp calculations for additional device variables
.
April 2022
Device variable Associated time stamp data point name
Percent rangeHARTPercentRangeUpdateTime
Analog output 1HARTAO1OutputUpdateTime
Time stamps shall:
•be unsigned 32 bit integer with least significant bit of time value representing 1/32 of
milliseconds.
•indicate time since midnight and shall rollover after 24 hours
•have units of milliseconds
Time Stamp 13
HART Field Device Specification 3810 Series Ultrasonic Meter4. Product interfaces
April 202200825-0300-3810
14Time Stamp
5. Device variablesHART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810April 2022
51
5. Device variables
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter does not use Device Family
commands.
The flow-condition volumetric flow rate is the result of applying expansion correction and flowprofile correction to the raw volumetric flow rate derived as subject to the low-flow cut-off. If the resulting value is below the low-flow cut-off value, it is set to zero. The low-flow cut-off
volumetric flow rate (QCutOff) is the specified low-flow velocity threshold (ZeroCut) converted
to a volumetric flow rate.
0
66
Volumetric Flow
Name
Unit Codes
5.2Device variable 6 - pressure
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter samples the input analog signal(s)
and updates the corresponding data point (LiveFlowPressure) once per second regardless of
the input selection (disabled, live, or fixed).
Every five seconds, the meter updates the “in-use” flow-condition pressure and temperature
values (FlowPressure and AbsFlowPressure) depending upon the input selection, validity of the
input data, and the selected data source upon alarm.
Uncorrected Flow Rate
(Table 11- 5 )
The flow-condition pressure is configurable (via the EnablePressureInput data point) to be:
•disabled (0)
•live (1) (4-20 mA input signal) or
•fixed (2)
Table 5-2 Device variable 6 - pressure
Device Variable
Number:
Classification:
If an input is live, then the values corresponding to the minimum and maximum input (4 and
20 mA, respectively) are specified via data points MinInputPressure and MaxInputPressure.
To configure the live pressure, plus associated alarms, configure the data points in Section
11.15.
Device variable 0 - uncorrected flow rate 15
6
65
Pressure
Name
Unit Codes
Pressure
(Table 11- 4 )
HART Field Device Specification 3810 Series Ultrasonic Meter5. Device variables
April 202200825-0300-3810
5.3Device variable 7 - temperature
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter samples the input analog signal(s)
and updates the corresponding data point (LiveFlowTemperature) once per second regardless
of the input selection (disabled, live, or fixed).
Every five seconds, the meter updates the “in-use” flow-condition pressure and temperature
values (FlowTemperature) depending upon the input selection, validity of the input data and the
selected data source upon alarm.
The flow-condition temperature is configurable (via the EnableTemperatureInput data point) to
be:
•disabled (0)
•live (1) (4-20 mA input) or
•fixed (2)
Table 5-3 Device variable 7 - temperature
Device Variable
Number:
Classification:
7
64
If an input is live, then the values corresponding to the minimum and maximum input (4 and
20 mA, respectively) are specified via data points MinInputTemperature and MaxInputTemperature.
To configure the live temperature, plus associated alarms, configure the data points in Section
11.15.
Name
Unit Codes
Temperature
(Table 5-3)
5.4HART slave device variables good status
indicators
Refer to the following table for HART Slave Device Variables database points indicating the
response status is good.
Table 5-4 Device variable good indicators
Device variable
Code - content
0 - Uncorrected flow rate66QFlowValidity
6 - Pressure (3rd and 4th variable only)65HARTIsPressureGood
7- Temperature (3rd and 4th variable only)64HARTIsTemperatureGood
Device variable
Classification code
Device variable
Good indicators
16Device variable 7 - temperature
6. Dynamic variablesHART Field Device Specification 3810 Series Ultrasonic Meter
00825-0300-3810April 2022
61
6.Dynamic variables
This section documents the HART primary, secondary, tertiary, and quaternary variables.
6.1
6.2
Table 6-1 Dynamic variables configurable mapping
Dynamic VariableDevice Variable NumberName
PV
SV
TV
QV
Fixed dynamic variables
There are no fixed Dynamic Variables for this device.
Dynamic variables with configurable mapping
The Rosemount 3810 Series Liquid Ultrasonic Flow Meter allows the following userconfigurable Dynamic Variables mapped to the Device Variables:
•0•0 Uncorrected Flow Rate
•0•0 Uncorrected Flow Rate
•0, 6 or 7•0, 6, 7: PV + Pressure, Temperature
•0, 6 or 7•0, 6, 7: PV + Pressure, Temperature
The default primary Dynamic Variable is Uncorrected Flow Rate for all meters.
Fixed dynamic variables 17
Loading...
+ 171 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.