Rosemount Quick Start Guide: Rosemount™ 326P Pressure Transmitter Manuals & Guides

Quick Start Guide
00825-0100-4327, Rev 02
August 2020
Rosemount™ 326P Pressure Transmitter
Quick Start Guide August 2020
Contents
Introduction.................................................................................................................................3
Installation................................................................................................................................. 10
Operation...................................................................................................................................14
Setting ranges............................................................................................................................35
Troubleshooting........................................................................................................................ 43
Product certifications................................................................................................................. 45
Factory settings..........................................................................................................................46
August 2020 Quick Start Guide

1 Introduction

The pressure transmitter measures and monitors pressure in a facility.

1.1 Pressure specifications

To ensure product performance and safety, adhere to the following specifications.

1.1.1 Measuring range

This table shows the range at which the pressure transmitter is able to measure pressure.
Pressure range Measuring range limits
inH2O mbar
1A -2.0 to 40 -5 to 99.5
2A -5.0 to 100 -12.4 to 248.8
psi bar
3A -14.5 to 14.5 -1 to 1
2B -0.73 to 14.5 -0.05 to 1
4A -1.45 to 20 -0.1 to 1.38
5A -1.8 to 36 -0.124 to 2.48
6A -14.5 to 55 -1 to 3.79
7A -14.5 to 85 -1 to 5.86
8A -14.5 to 145 -1 to 10
9A -14.5 to 230 -1 to 15.9
1B -14.5 to 360 -1 to 24.8
Note
The pressure transmitter is vacuum resistant. There are restrictions for nominal pressure ranges at or below 4.35 psi (300 mbar). Adhere to the specifications in the data sheet.
Quick Start Guide 3
Quick Start Guide August 2020

1.1.2 Overpressure limits

The table in this topic shows maximum allowable pressure for the pressure transmitter.
CAUTION
Take appropriate measures to avoid exceeding the specified overpressure limits.
Pressure range Overpressure limits
inH2O bar
1A 1606 4
2A 2400 6
psi bar
3A 145 10
2B 145 10
4A 215 15
5A 290 20
6A 435 30
7A 435 30
8A 725 50
9A 1085 75
1B 1450 100

1.1.3 Burst pressure limits

The burst pressure limit is the pressure at which the pressure transmitter will no longer function or be damaged.
CAUTION
Do not exceed the burst pressure limit. Exceeding the burst pressure limit can damage the pressure transmitter. Continuing to use the pressure transmitter after exceeding the burst pressure limit can cause damage and physical injury.
August 2020 Quick Start Guide
Pressure range Burst pressure limits
inH2O bar
1A 12044 30
2A 12044 30
psi bar
3A 435 30
2B 435 30
4A 580 40
5A 725 50
6A 1450 100
7A 1450 100
8A 2175 150
9A 3625 250
1B 5075 350

1.2 Operating modes

The wiring configuration sets the operating mode. After wiring the pressure transmitter, it automatically recognizes the connections and changes to the respective operating mode.
For more information, see Electrical connection.

1.2.1 Two-wire operation

OUT2 (pin 2)
The analog signal proportional to pressure (4-20 mA or 20-4 mA).

1.2.2 Three-wire operation

OUT1 (pin 4)
OUT2 (pin 2)
Switching signal for system pressure limit value
Switching signal used for system pressure limit value
Analog signal proportional to pressure (4-20 mA or 20-4
mA)
Quick Start Guide August 2020

1.3 Functions

The Rosemount 326P Pressure transmitter performs the functions described in this section.

1.3.1 Switching function

The switching function is available only for three-wire operations. OUT1 or OUT2 changes its switching status if the pressure is above or below the set switching limits (SPx, rPx). These switching functions are available:
Hysteresis function/normally open: OUx = Hno (Figure 1-1)
Hysteresis function/normally closed: OUx = Hnc (Figure 1-1)
First set the set point (SPx), then the reset point (rPx) with the requested difference.
Window function/normally open: OUx = Fno (Figure 1-2)
Window function/normally closed: OUx = Fnc (Figure 1-2)
Set the width of the window using the difference between SPx and rPx. SPx is the upper value and rPx is the lower value.
Figure 1-1: Hysteresis function
SP: Set point
rP: Reset point
P: Pressure
Hy: Hysteresis
Hno: Hysteresis function/normally
open
Hnc: Hysteresis function/normally
closed
Figure 1-2: Window function
FE: Window
Fno: Window function/normally
open
Fnc: Window function/normally
closed
August 2020 Quick Start Guide

1.3.2 Analog signal

The transmitter communicates measured pressure using an analog signal.
OU2 defines whether the set measuring range is provided as 4-20 mA (OU2 = I) or as 20-4 mA (OU2 = InEG).
Rerange the transmitter (set new values for ASP and AEP) by either manually entering range points or with an applied pressure source.
Applying a pressure source for the analog start point (tASP) or manually
setting the parameter (ASP) defines the measured value when the analog signal is 4 mA (20 mA at InEG).
Applying a pressure source for the analog end point (tASP) or manually
setting the parameter (ASP) defines the measured value when the output signal is 20 mA (4 mA at InEG).
Minimum distance between ASP and AEP is 25 percent of the upper range limit (maximum rangedown 4:1). For pressure range 3A, the minimum distance is 25 percent of the measuring span.
Figure 1-3: Factory setting
Figure 1-4: Transmitter reranged
P: system pressure
MAW: initial value of the measuring range (Lower range limit [LRL])
MEW: final value of the measuring range (Upper range limit [URL])
1: OU2 = I
2: OU2 = InEG
In the set measuring range the output signal is between 4 and 20 mA (OU2 = I) or between 20 and 4 mA (OU2 = InEG). When pressure is outside the set measuring range, the output signal is as follows:
Quick Start Guide August 2020
System pressure above the measuring range:Output signal > 20 mA if OU2 = I.
Output signal 4 to 3.8 mA if OU2 = InEG.
System pressure below the measuring range:Output signal 4 to 3.8 mA if OU2 = I.
Output signal > 20 mA if OU2 = InEG.

1.3.3 Customer-specific calibration (sensor trim)

A customer specific calibration (sensor trim) corrects the pressure offset and pressure range to match a pressure standard. This provides a slope correction to the transmitter's current characterization curve. An accurate pressure standard is required for a full calibration. For more information on performing a Sensor Trim, see Perform a sensor trim.
Sensor Trim is a two-point sensor calibration that applies two end-point
pressures (CP1, CP2) then linearizes the output between them. CP1 and CP2 must be within the scaled measuring range. For more information, see Analog signal.
Zero trim is a single-point offset adjustment. It compensates for
mounting position effects and is most effective when performed with the transmitter installed in its final mounting position. Since zero trim maintains the slope of the characterization curve, do not use it in place of a Sensor Trim over the full sensor range. For more information, see
Perform manual zero trim.
Reset the calibration by resetting all parameters to the factory default settings. For more information, see Resetting all parameters to factory
default settings.
P: measured pressure
P‘: modified measured value
CP1: calibration point 1
CP1‘: modified measured value for CP1
CP2: calibration point 2
1: curve of measured values at
factory setting
2: curve of measured values after
calibration
August 2020 Quick Start Guide
P: measured pressure
P‘: modified measured value
CP1: calibration point 1
CP2: calibration point 2 CP2‘: modified measured value for
CP2
1: curve of measured values at
factory setting
2: curve of measured values after
calibration
P: measured pressure
P‘: modified measured value
CP1: calibration point 1
CP1‘: modified measured value for CP1
CP2: calibration point 2
CP2‘: modified measured value for CP2
1: curve of measured values at
factory setting
2: curve of measured values after
calibration
Quick Start Guide August 2020

2 Installation

This section contains instructions for installing and wiring the Rosemount 326P Pressure Transmitter.
Note
Before installing or removing the unit, ensure no pressure is applied to the system. Note that when the pressure transmitter displays 0%, pressure might still be applied to the system.

2.1 Installation orientation (3-A® standards)

For optimized cleaning of the measuring element in hygienic areas according to the 3-A standards, follow these guidelines when installing the pressure transmitter.
To ensure the medium can run off the measuring element, do not install the unit at the lowest point of a pipe or container.
Note
This product is not suitable for use where the criteria for paragraph E1.2 / 63-03 of the 3-A® standard 63-03 must be met.

2.2 Installing with EHEDG standards

CAUTION
The unit is suited for CIP (cleaning in process) when installed correctly.
Observe the application limits (temperature and material resistance)
according to the data sheet.
Ensure the sensor is integrated into the system according to EHEDG:Use self-draining installation.
Only use process adapters permitted according to EHEDG with
special seals required by the EHEDG position paper.
August 2020 Quick Start Guide
CAUTION
The gasket of the system interface must not be in contact with the sealing point of the sensor.
In case of structures in a tank, the installation must be flush mount. If not
possible then direct water jet cleaning and cleaning of dead spaces must be possible.
Leakage ports must be clearly visible and must be installed facing
downwards for vertical pipes.
To avoid dead space, adhere to the dimensions: L < D.
A. Leakage port
2.3
2.4

Hygienic process connection adapter installation

Hygienic process connection adapters allow the transmitter to be installed according to application requirements. All connection adapters include an EPDM O-ring. More sealing rings are available to be ordered as accessories. See the Rosemount 326P Product Data Sheet for all available connectors and accessories. Hygienic process connection adapters include installation instructions with the packaging.

Electrical connection

This section provides instructions for wiring the pressure transmitter. A qualified electrician must wire the pressure transmitter. The electrical installation must adhere to national and international regulations.
Voltage supply according to EN 50178, SELV, PELV.
Quick Start Guide August 2020

2.4.1 Wiring for two-wire operation

Follow these steps to wire the pressure transmitter for two-wire operation.
Procedure
1. Disconnect the power.
2. Wire the pressure transmitter according to Figure 2-1.
Figure 2-1: Connection for two-wire operation
BN Brown
WH White
OUT Analog output (4-20 mA)
Colors to DIN EN 60947-5-2

2.4.2 Wiring for three-wire operation

Follow these steps to wire the pressure transmitter for three-wire operation.
Procedure
1. Disconnect the power.
2. Wire the pressure transmitter according to Figure 2-2.
Figure 2-2: Connection for three-wire operation
BK
BN Brown
BU Blue
WH White
Black
August 2020 Quick Start Guide
OUT1 Switching output
OUT2 Switching output or analog output
(4-20 mA)
Colors to DIN EN 60947-5-2
Wiring examples
2 x positive switching 2 x negative switching
1 x positive switching / 1 x analog 1 x negative switching / 1 x analog
Note
If the analog signal current (I) is selected in the menu under OU2 and the output is not connected (resistor = infinite), the pressure transmitter displays the error message W532 in intervals. This does not affect the measuring result. As an alternative, configure OU2 to a switching output.
Quick Start Guide August 2020

3 Operation

This section provides instructions for configuring parameter settings.

3.1 Display and function buttons

The pressure transmitter displays information using the display and can be controlled using the function buttons.
1 to 8: Indicator LEDs
LED 1 to LED 5 System pressure in the set unit of measurement.
LED 6 If OU2 is configured as an analog output, it indicates the
LED 7 Switching status of OUT2 (illuminates when output 2 is
LED 8 Switching status of OUT1 (illuminates if output 1 is switched).
9: Alphanumeric display, 4 digits
Current system pressure
Parameters and parameter values
system pressure in percent of the scaling of the analog output (range ASP to AEP). If OU2 is configured as a switching output, it indicates the system pressure in percent of the upper range limit (URL).
switched).
10: Set button
Selects a parameter from the menu and modifies the value by holding pressed for five seconds.
11: Mode/Enter button
Scrolls through the menu and acknowledges parameter values.
August 2020 Quick Start Guide

3.1.1 Read the set parameters

Follow these steps to view the set parameter values.
Procedure
1. Press Mode/Enter until the pressure transmitter displays the desired parameter.
2. Press Set. The pressure transmitter displays the value currently set for the selected parameter for 15 seconds then returns to run mode.

3.1.2 Change the display in run mode

Follow these steps to view the pressure measurement in different indicator types. During normal operation, the pressure transmitter displays the pressure measurement in the selected unit of measurement.
Procedure
Press Set.
The pressure transmitter displays the following information for 15 seconds:
System pressure in percent of the set scaling of the analog output if
OU2 is configured as analog output.
System pressure in percent of the upper range limit if OU2 is
configured as switching output.
Loading...
+ 33 hidden pages